and the shaped aperture in the disc. The increase in flow as the valve is
The need for multiple pipe reduction is usually eliminated.
opened is very slow and controlled.
Better control prevents “hunting” of the control loop, increasing This produces better part-load behavior and improved stability of
life span of actuator and valve. control while also optimizing energy consumption.
FEATURES
1
Feature / Benefits
Characterized Control Valves™ (CCV)
B2 Series Two-way ½” to 3”
B3 Series Three-way ½” to 2”
Mixing*/Diverting
2
Sizing/Selection
Characterized Control Valves™ (CCV)
2-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
240 2” 50 B254* 240 339 416 480 537 588 635 679 720 759
60 2½” 65 B261 60 85 104 120 134 147 159 170 180 190
75 2½” 65 B262 75 106 130 150 168 194 198 212 225 237
110 2½” 65 B263 110 156 191 220 246 269 291 311 330 348
150 2½” 65 B264 150 212 260 300 335 367 397 424 450 474
210 2½” 65 B265* 210 297 364 420 470 514 556 594 630 664
70 3” 80 B277 70 99 121 140 157 172 185 198 210 221
130 3” 80 B278 130 194 225 260 290 318 344 368 390 411
170 3” 80 B280* 170 240 294 340 380 416 450 481 510 538
70 2½” 65 B6250S-070 70 99 121 140 157 171 185 198 210 221
110 2½” 65 B6250S-110 110 156 191 220 244 266 282 296 312 320
110 3” 80 B6300S-110 110 156 191 220 244 266 282 296 312 320
186 4" 100 B6400S-186 186 263 322 372 416 456 492 526 558 588
290 5" 125 B6500S-290 290 410 502 580 648 710 767 820 870 917
400 6" 150 B6600S-400 400 566 693 800 894 980 1058 1131 1200 1265
GPM = Cv x ∆p
*Models with no characterizing disc.
The influence of the pipe geometry due to reduced flow is negligible for all valves 57 Cv and below with characterizing discs.
3
Sizing/Selection
Characterized Control Valves™ (CCV)
3-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
4
Set-up and Wiring Instructions
Characterized Control Valves™ (CCV)
SET-UP
2-WAY VALVE 3-WAY VALVE
SPECIFY UPON ORDERING SPECIFY UPON ORDERING
TR24-SR-T US NC: Closed A to AB, will NO: Open A to AB, will close NC: Closed A to AB, will NO: Open A to AB, will close
TR24-SR US open as voltage increases. as voltage increases. open as voltage increases. as voltage increases.
Proportional (Can be chosen with (Can be chosen with
Type Actuators switch inside terminal switch inside terminal
block of actuator.) block of actuator.)
LRB24 (-3), MFT, SR Power to pin 2 will drive NO: Open A to AB, will close Power to pin 2 will drive NO: Open A to AB, will close
LRX24 (-3), MFT, SR valve CW. Power to pin 3 as voltage increases or valve CW. Power to pin 3 as voltage increases or
ARB24 (-3), MFT, SR will drive valve CCW. The power applied. (Can be will drive valve CCW. The power applied. (Can be
ARX24 (-3), MFT, SR above will function when chosen with CW/CCW above will function when chosen with CW/CCW
Floating Point or the directional switch is in switch.) the directional switch is in switch.)
Proportional Type Actuators the “1” position, to reverse the “1” position, to reverse
select the “0” position. select the “0” position.
TFRB24 NO/FO Valve: Open A to AB NC/FC Valve: Closed A to AB NO/FO Valve: Open A to AB NC/FC Valve: Closed A to AB
LF24 US will drive closed. will drive open. will drive closed. will drive open.
AFRB24 Spring Action: Spring Action: Spring Action: Spring Action:
Will spring open A to AB Will spring closed A to AB Will spring open A to AB Will spring closed A to AB
upon power loss. upon power loss. upon power loss. upon power loss.
TF (-3), MFT, SR NC/FO Valve: Closed A to AB NC/FC or NO/FC NC/FO Valve: Closed A to AB NC/FC or NO/FC
SPRING RETURN
Note Fail Position
LF (-3), MFT, SR will drive open. Valve: Closed A to AB or will drive open Valve: Closed A to AB
AF SR Spring Action: Open A to AB. Spring Action: or Open A to AB.
AFR, MFT Will spring open A to AB (Can be chosen with Will spring open A to AB (Can be chosen with
Floating Point or upon power loss. CW/CCW switch.) upon power loss. CW/CCW switch.)
Proportional Type Actuators Spring Action: Spring Action:
Will spring closed A to AB Will spring closed A to AB
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
5
Flow, Operation and Installation
Characterized Control Valves™ (CCV)
FLOW PATTERNS
2-way Characterized Control Valves™ (Belimo B2 Series) (Belimo B6 Series) Flow Direction
Two-way valves
should be installed
with the disc
upstream.
Upstream A
Downstream AB
INCORRECT PIPING
The A-port must be piped to the coil to maintain proper control.
Three-
Wa y D ivertingValve PipingD iagram WARNING! Do Not Pipe in this manner!
Three-
Wa
W a y MixingValve PipingD iagram
(2 npu
I ts,1 O ut
utput) (1 n
np
Iput, 2O utputs) Note Valve Porting!
A
A The A-port must be piped to the coil! Not the B-port!
Return
B
B Return
Return Return Flow is not possible from A to B. If AB-port is not piped as
AB Coil Coil the common port, the valve must be re-piped. It is good
Coil Coil
AB A
A practice to install a balancing valve in the bypass line.
SupplySupply SupplySupply
B These valves are intended for closed loop systems. Do not
B
AB
AB install in an open loop system or in an application that is
open to atmospheric pressure.
3-WAY VALVES MUST BE PIPED CORRECTLY. They can be mixing or diverting. Mixing is the preferred piping arrangement.
The BELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the A-port. It is similar to the globe valve in that
the middle port is the B or bypass port. The common port AB is on the main opposite the A-port. These diagrams are for typical applications only. Consult engineering
specification and drawings for particular circumstances.
REDUCED B-PORT FLOW
Note: The B-port flow of the 3-way CCV is lower than that of the A-port. In most applications this is beneficial since the reduced flow compensates for the inexistent
pressure drop across the coil in the bypass mode. Therefore, proper sizing is important to avoid flow noise in particular when the system is designed with constant
speed pumps. Please refer to our valve sizing and selection guidelines.
The flow velocity in the pipe upstream and downstream of the valve should be considered as well. The typical HVAC design maximum flow is 4 to 8 ft/s to avoid noise
issues.
Also, the pipe reduction factor must be considered and can be found on pages 3 and 4. Pipe reducers decrease the Cv value of a valve and consequently increase the
pressure drop across the valve, a situation that could lead to noise or a lower than designed flow.
6
Nomenclature
Characterized Control Valve™ (CCV)
B2 09 +LRX 24 -MFT
Valve Valve Size Trim Material Actuator Type Power Supply Control
B2 = 2-way 07-80 = ½” to 3” B = Chrome Plated Non Fail-Safe 24 = 24 VAC/DC Blank = On/Off -S = Built-in
B3 = 3-way Brass Ball, TR 120 = 120 VAC* -3 = On/Off, Floating Point Auxiliary
Nickel Plated LRB, LRX 230 = 230 VAC -SR = 2-10 VDC Switch
Stem LRQX UP = 24 to 240 VAC -MFT = Multi-Function -T = Terminal
Blank = Stainless NRB, NRX Technology Strip
Steel Ball NRQX -MFT95 = 0-135 Ω N4 = NEMA
and Stem ARB, ARX 4/4X
-IP = Internet Protocol
ARQX
Fail-Safe
Spring Return
TFR, TFRX
LF
AFR, AFRX
Electronic
GKR
Ordering Example
4
2 Specify preference or configuration.
Does order
require
Set-Up tagging?
7
Nomenclature
Characterized Control Valve™ (CCV)
Ordering Example
8
B2 Series, 2-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
TR Series
LR Series
TF Series
LF Series
Ball chrome plated brass 7.4 ½ 15 B214B
Stem nickel plated brass 10 ½ 15 B215B
Seats PTFE 16 ½ 15 B216B
Characterizing disc Tefzel® 4.7 ¾ 20 B217B
Packing 2 EPDM O-rings, lubricated 7.4 ¾ 20 B218B
Body pressure rating 600 psi 10 ¾ 20 B219B
Media temp. range 0°F to 250°F [-18°C to 120°C] 14 ¾ 20 B220B
Close off pressure 200 psi
24 ¾ 20 B221B*
Maximum differential 50 psi for typical applications *Models without characterizing disc
pressure (∆P)
( P)
Leakage 0% for A to AB
External leakage according to EN 12266-1:2003
Cv rating A-port: see product chart for values
Tefzel® is a registered trademark of DuPont
Dimensions
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2WayValve-B207-B220
Flow Patterns
9
B3 Series, 3-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
TR Series
LR Series
TF Series
LF Series
B-port modified for constant common port flow 4.7 ½ 15 B313B
Controllable Flow Range 75° 10 ½ 15 B315B
Sizes ½”, ¾” 16 ½ 15 B316B
Type of end fitting NPT female ends 4.7 ¾ 20 B317B
Materials: 7.4 ¾ 20 B318B
Body forged brass, nickel plated 14 ¾ 20 B320B
Ball chrome plated brass 24 ¾ 20 B321B
Stem nickel plated brass *Models without characterizing disc
Seats PTFE
Characterizing disc Tefzel®
Packing 2 EPDM O-rings, lubricated
Body pressure rating 600 psi
Media temp. range 0°F to 250°F [-18°C to 120°C]
Close off pressure 200 psi
Maximum differential 50 psi for typical applications
pressure (∆P)
( P)
Leakage 0% for A to AB
<2.0% for B to AB
External leakage according to EN 12266-1:2003
Cv rating A-port: see product chart for values
B-port: 70% of A to AB Cv
Dimensions
3WayValve-B307-B320
Flow Patterns
“B” Port must
be piped to the
bypass leg.
10
B2 Series, 2-Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
TR Series
TF Series
Service chilled or hot water, 60% glycol 4.7 ½ 15 B213
Flow characteristic A-port equal percentage 7.4 ½ 15 B214
Controllable Flow Range 75° 10 ½ 15 B215
NR...N4 Series
16 ½ 15 B216
LR Series
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3”
LF Series
Type of end fitting NPT female ends 4.7 ¾ 20 B217
Materials: 7.4 ¾ 20 B218
Body forged brass, nickel plated 10 ¾ 20 B219
Ball stainless steel 14 ¾ 20 B220
Stem stainless steel 24 ¾ 20 B221*
Seats PTFE 7.4 1 25 B222
Characterizing disc Tefzel® 10 1 25 B223
Packing 2 EPDM O-rings, lubricated 19 1 25 B224
Body pressure rating 30 1 25 B225*
600 psi ½” - 1¼” (B230) 10 1¼ 32 B229
400 psi 1¼” (B231) - 3” 19 1¼ 32 B230*
Media temp. range 0°F to 250°F [-18°C to 120°C] 25 1¼ 32 B231
Close off pressure 37 1¼ 32 B232*
200 psi ½” - 2” (B254)
19 1½ 40 B238
100 psi 2½” (B261) - 3”
29 1½ 40 B239
Maximum differential 50 psi for typical applications
37 1½ 40 B240*
pressure (∆P)
( P)
29 2 50 B248
Leakage 0% for A to AB
46 2 50 B249
External leakage according to EN 12266-1:2003
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
57 2 50 B250*
Cv rating A-port: see product chart for values
AR...N4 Series
65 2 50 B251
AR Series
AF Series
Tefzel® is a registered trademark of DuPont
85 2 50 B252
Dimensions 120 2 50 B253
240 2 50 B254*
2WayValve-B207-B220
60 2½ 65 B261
75 2½ 65 B262
110 2½ 65 B263
150 2½ 65 B264
210 2½ 65 B265*
70 3 80 B277
130 3 80 B278
170 3 80 B280*
*Models without characterizing disc
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2] Flow Patterns
B212-B216 ½” 15 2.38” [60.4] 1.78” [45.2]
B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
11
B3 Series, Three Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
TR Series
TF Series
3 ½ 15 B312
Technical Data
NR...N4 Series
4.7 ½ 15 B313
Service chilled or hot water, 60% glycol
LR Series
LF Series
10 ½ 15 B315
Flow characteristic A-port equal percentage
16 ½ 15 B316
B-port modified for constant common port flow
4.7 ¾ 20 B317
Controllable Flow Range 75°
7.4 ¾ 20 B318
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”
14 ¾ 20 B320
Type of end fitting NPT female ends
24 ¾ 20 B321
Materials:
7.4 1 25 B322
Body forged brass, nickel plated
Ball stainless steel 10 1 25 B323
Stem stainless steel 30 1 25 B325*
Seats PTFE 10 1¼ 32 B329
Characterizing disc Tefzel® 19 1¼ 32 B330
Packing 2 EPDM O-rings, lubricated 25 1¼ 32 B331
Body pressure rating 19 1½ 40 B338
29 1½ 40 B339
AR...N4 Series
600 psi ½” - 1”
AR Series
37 1½ 40 B340
AF Series
400 psi 1¼” - 2”
Media temp. range 0°F to 250°F [-18°C to 120°C] 46 1½ 40 B341
Close off pressure 29 2 50 B347
200 psi ½” - 2” 37 2 50 B348
Maximum differential 50 psi for typical applications 46 2 50 B349
pressure (∆P)
( P) 57 2 50 B350
Leakage 0% for A to AB 68 2 50 B351
<2.0% for B to AB 83 2 50 B352
12
Characterized Control Valve Product Range Overview
B2.., B3.., 2-way, 3-way, Stainless Steel Ball and Stem
TFR Series
Characteristic
TR Series
4.7 ½ 15 B213(B) B313(B)
7.4 ½ 15 B214(B) Mode of Operation
10 ½ 15 B215(B) B315(B) The Characterized Control Valve is operated by a rotary
actuator. The actuators are controlled by a standard voltage
14 ½ 15 B216(B)* B316(B)* for on/off control or a proportional signal or 3-point control
system which move the ball of the valve to the position
NR Series
LR Series
LF Series
4.7 ¾ 20 B217(B) B317(B) dictated by the control system.
7.4 ¾ 20 B218(B) B318(B) Product Features
The equal-percentage characteristic of the flow is ensured
10 ¾ 20 B219(B) by the integral characterizing disc. This characteristic
provides linear heating or cooling output from the coil
14 ¾ 20 B220(B)*
improving energy efficiency and comfort.
14 ¾ 20 B320(B)
Actuator Specifications
24 ¾ 20 B221(B)* B321(B)* Control type on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
7.4 1 25 B222 B322 Manual override TR, LR, AR, NR, AFR series
10 1 25 B223 B323 Electrical connection 3 ft [1m] cable with ½”
conduit fitting or covered screw
19 1 25 B224 terminal strip
30 1 25 B225* B325* Valve Specifications
10 1¼ 32 B229 Service chilled or hot water, 60% glycol
Flow characteristic A-port equal percentage
19 1¼ 32 B230* B-port modified for constant
common port flow
10 1¼ 32 B329
Controllable flow range 75°
19 1¼ 32 B330 Sizes ½” - 2”
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AR Series
* Models without characterizing discs. (B) Models with chrome plated brass ball and brass stem
* 3-Way Valves not for use in change over applications
13
Characterized Control Valve Product Range Overview
B6.., 2-way, Stainless Steel Ball and Stem
Valve Nominal
2-way Flanged Suitable Actuators
Size
DN Non
NEMA Fail- NEMA
Cv Inches [mm] ANSI 125 ANSI 250 Fail- Internet Protocol
4X Safe 4X
Safe
70 2½ 65 B6250S-070 B6250S-070-250
AKR..-IP
AFR..-IP
AR..-IP
AFR
AFR
110 2½ 65 B6250S-110 B6250S-110-250
AR
AR
110 3 80 B6300S-110 B6300S-110-250 CCV
186 4 100 B6400S-186 B6400S-186-250 Equal Percentage
GR / GKR
Characteristic
GKR
290 5 125 B6500S-290 B6500S-290-250
GR Mode of Operation
400 6 150 B6600S-400 B6600S-400-250
The Characterized Control Valve is operated by a rotary
actuator. The actuators are controlled by a standard voltage
for on/off control, a modulating signal, or floating point control
system which move the ball of the valve to the position dictated
by the control system.
Product Features
The equal-percentage characteristic of the flow is ensured by
the integral characterizing disc. This characteristic provides
linear heating or cooling output from the coil improving energy
efficiency and comfort.
Actuator Specifications
Control type on/off, floating point, 2...10 V,
multi-function technology (MFT)
Manual override AR, GR, AFR and GKR series
Electrical connection 3 ft. [1 m] cable with ½”
conduit fitting or covered screw
terminal strip
Valve Specifications
Fluid chilled or hot water, up to
60% glycol max.
Flow characteristic A-port equal percentage
Controllable flow range 75°
Sizes 2½”, 3”, 4”, 5”, 6”
End fitting ANSI Class 125 flange, flat face*,
*125 psi flanges have a plain flat face and should not be bolted
to a raised face flange.
Tefzel® and Teflon® are registered trademarks of DuPont™.
14
TR24-3 Actuators, On-Off, Floating Point
D1349
D
C
E F B
A TR
D1350
Nominal voltage 24 VAC 50/60 Hz
Nominal voltage range 19.2…28.8 VAC
Power consumption 1W
Transformer sizing 1VA (class 2 power source)
Electrical connection screw terminals accessible after removal of D C
small cover (3 ft, 10 ft, 16 ft cables optional)
Input impedance 0.36 kΩ
Angle of rotation 90°
Position indication integrated into handle
Manual override push down handle
Running time 90 seconds @ 60 hz, 108 seconds @ 50 hz
Humidity 5 to 95% non-condensing E F B
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
15
TR24-3 Actuators, On-Off, Floating Point
W187
connected to the Hot connection of the controller.
Actuators with plenum rated cable do not have numbers on wires;
3 use color codes instead.
4 The actuator Hot must be connected to the control board Hot.
W186
electrical components could result in death or serious injury.
On/Off Control
You may not use one wire control.
16
TR24-SR Actuators, Proportional
D1349
D
C
E F B
A TR
Technical Data
Control proportional Dimensions with 3-Way Valve
Nominal voltage 24 VAC 50/60 Hz, 24 VDC
D1350
Nominal voltage range 19.2…28.8 VAC, 21.6…28.8 VDC
Power consumption 0.5 W
Transformer sizing 1VA (class 2 power source)
Electrical connection screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional) D C
Input impedance 100 kΩ
Angle of rotation 90°
Direction of rotation reversible with switch under cover
Position indication integrated into handle
Manual override push down handle
Running time 90 seconds
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
17
TR24-SR Actuators, Proportional
Wiring Diagrams
W190
Actuators with color coded wires are optional.
2 Wire numbers are provided for reference.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
2 to 10 VDC Control of TR24-SR(-T) US
WARNING Live Electrical Components!
W191
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
4 to 20 mA Control of TR24-SR(-T) US
18
LR...24-3 Actuators, On/Off, Floating Point
D1351
D C
H1 H2
E F B
A
LRB, LRX -3, -SR
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 1.39” [35.2] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 1.78” [45.2] 1.78” [45.2]
LRB24-3-T LRX24-3-T w/Terminal Block B217(B)-B221(B) ¾” 20 1.87” [47.4] 1.87” [47.4]
LRB24-3 LRX24-3 w/3 ft. cable B222-B225 1” 25 1.87” [47.4] 1.87” [47.4]
LRB24-3-S LRX24-3-S w/built-in Aux. Switch B229-B231 1¼” 32 1.87” [47.4] 1.87” [47.4]
D1352
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 1.5 W
holding 0.2 W
Transformer sizing 2 VA (class 2 power source) D
Electrical connection ½” conduit connector C
18 GA, plenum rated cable H2
H1
LRB24-3 3 ft [1m]
LRX24-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
Direction of rotation reversible with protected switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LR...24-3-T
Electrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2, IP20)
LR...24-3-S
Auxiliary switch 1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
19
LR...24-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W193-LR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires.
3 Wire numbers are provided for reference.
4 Actuators may also be powered by 24 VDC.
On/Off control
W123-LR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
W169-08
Auxiliary switch
20
LR...24-SR Actuators, Proportional
D1351
D C
H1 H2
E F B
A
LRB, LRX -3, -SR
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB24-SR-T LRX24-SR-T w/Terminal Block B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRB24-SR LRX24-SR w/3ft. cable B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B231 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve
24 VDC ± 10%
D1352
Power consumption running 1.5 W
holding 0.4 W
Transformer sizing 3 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRB24-SR 3 ft [1m] C
LRX24-SR 3 ft [1m], 10 ft [3m], 16 ft [5m] H2
Overload protection electronic throughout 0° to 95° rotation H1
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA
Input impedance 100 kΩ (0.1 mA), 500 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
Direction of rotation reversible with protected switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRB, LRX
Position indication handle Valve Nominal Size Dimensions (Inches [mm])
Manual override external push button Valve Body Inches DN [mm] A B C
Running time constant independent of load B307(B)-B311(B) ½” 15 2.06” [52.2] 1.39” [35.2] 1.20” [30.6]
LRB24-SR 90 seconds
B312(B)-B315(B) ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
LRX24-SR 150, 95, 60, 45, 35 seconds
B317(B)-B321(B) ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Humidity 5 to 95% RH non-condensing
B322-B325 1” 25 3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
(EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <35 dB(A)
Quality standard ISO 9001
LR...24-SR-T
Electrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2/IP20)
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
21
LR...24-SR Actuators, Proportional
Wiring Diagrams
W265-LR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
2 to 10 VDC control
W265-LR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2
to 10 VDC, up to 2 actuators may be connected in parallel.
22
LR...120-3 Actuators, On/Off, Floating Point
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB120-3 B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRX120-3
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control On/Off, Floating Point
Power supply 100 to 240 VAC, 50/60 Hz (nominal) Dimensions with 3-Way Valve
85 to 265 VAC, 50/60 Hz (tolerance)
D1354
Power consumption running 2 W
holding 0.5 W
Transformer sizing 4 VA (class 2 power source)
Electrical connection ½” conduit connector D
18 GA, plenum rated cable C
LRB120-3 3 ft [1m]
H1 H2
LRX120-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop E F B
Direction of rotation reversible with protected switch
A
Position indication handle
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
23
LR...120-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W405
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W406
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
24
LR...120-SR Actuators, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB120-SR B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRX120-SR B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 100 to 240 VAC, 50/60 Hz (nominal) Dimensions with 3-Way Valve
85 to 265 VAC, 50/60 Hz (tolerance)
D1354
Power consumption running 2.5 W
holding 1 W
Transformer sizing 4.5 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRB120-SR 3 ft [1m] C
LRX120-SR 3 ft [1m], 10 ft [3m], 16 ft [5m] H2
H1
Overload protection electronic throughout 0° to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA
Input impedance 100 kΩ (0.1 mA), 500 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
Direction of rotation reversible with protected switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
25
WARNING APPLI
LR...120-SR Actuators, Proportional Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
Meets cU
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components electrical
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
7 A 500 Ω
Wiring Diagrams signal to
W365
100 to 240 VAC
15 2 19
1 Neutral
CAUTION Equipment damage! N L1
Cable 2
2
Actuators may be connected in parallel. H L2 2 Hot +
Cable 1
(–)
Control Signal
15 LRB(X) can be supplied with both 120 VAC and 230 VAC. VDC/mA (+) 3 Y Input, 2 to 10V
2 to 10 VDC (–)
Feedback Signal (+) 5 U Output, 2 to 10V
19 All 120 VAC and 230 VAC actuators use appliance rated cables.
1 0
LR...120-SR
26
LR...24-MFT Actuators, Multi-Function Technology
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-MFT Flexible Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 6 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m] C
Overload protection electronic throughout 0° to 95° rotation
H1 H2
Operating range Y 2 to 10 VDC (default)
4 to 20 mA
variable (VDC, PWM, floating point, on/off)
Feedback output U 2 to 10 VDC, 0.5mA max E F B
VDC variable A
Input impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off) LRB, LRX
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Angle of rotation 90° electronically variable Valve Nominal Size Dimensions (Inches [mm])
adjustable with mechanical stop Valve Body Inches DN [mm] A B C
Direction of rotation reversible with protected switch B307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
Position indication handle B312-B315 ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Manual override external push button B317-B321 ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Running time 150 seconds (default) B322-B325 1” 25 3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
Variable (35 to 150 secs)
Humidity 5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <35 dB(A)
Quality standard ISO 9001
† Rated impulse voltage 800V, Control pollution degree 3,
Type of action 1 (1.B for -S models)
27
LR...24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
6 or the Common (sink) 24 VAC line. On/Off control
Contact closures A & B also can be triacs.
W538
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
W538
electrical components could result in death or serious injury.
VDC/4-20 mA
W538
28
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-PC B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 5 VA (Class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable
D
3 ft [1m], 10 ft [3m], 16 ft [5m] C
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 0 to 20V phasecut H1 H2
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 8 kΩ (50 mW)
Angle of rotation 90°, adjustable with mechanical stop
E F B
electronically variable
Direction of rotation reversible with switch A
Position indication handle LRB, LRX
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Manual override external push button Valve Nominal Size Dimensions (Inches [mm])
Running time 150 seconds (default) Valve Body Inches DN [mm] A B C
Humidity 5 to 95% RH non-condensing B307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
(EN 60730-1) B312-B315 ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Ambient temperature -22°F to 122°F [-30°C to 50°C] B317-B321 ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Storage temperature -40°F to 176°F [-40°C to 80°C] B322-B325 1” 25 3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <35 dB(A)
Quality standard ISO 9001
29
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
Wiring Diagrams
W185
1
24 VAC Transformer
30
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-MFT95 B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 5 VA (Class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m] D
C
Overload protection electronic throughout 0 to 95° rotation
Operating range WRB 0 to 135 Ω Honeywell Electronic H1 H2
Series 90, 0 to 135 Ω input
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 100 kΩ (0.1 mW)
Angle of rotation 90°, adjustable with mechanical stop E F B
electronically variable A
Direction of rotation reversible with switch LRB, LRX
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
31
24 Resistor value depends on the type of 23 Volts
22 Actuators and controller must have 22
controller and the number of
Wht (3) W Wiring Multiple Actuators to a Series 9
separate transformers. actuators.
W No resistor is used for one 24 22
24 VAC Transformer
Series 90 actuator.
R Honeywell® resistor
Wht kits
(4) may
R 21
B R W
Controller
also be used.
23 Consult controller instruction data for B R W B Wht (5) B Line H205 Blk (1) Co
reversing
Series 90 high switch.
limit control - 280 Ω -MFT95 US
24 Resistor value depends on the type of Shunting
W Wht (3) W
Wht (4) R
controller and the number of Override
Resistor 22 R
Wiring Multiple Actuators to a Series 90 Controller B W Wht (5) B
Wiring Diagrams actuators. No resistor is used for one Switch A Switch B Damper Position 24 Shunting
Resistor Wht (6) ‘U5
W_new60408_5
Series 90
24 VAC Transformer
actuator. Honeywell® resistor kits may ControllerB
W018
21 Damper Open -MFT
also be used. Line Blk (1)Closed
Damper Common
21
Y
Line Blk (1) Co
Volts Red (2) GMX24-MFT95
+ Hot
To reverse control rotation, use the Actuators: AF24-MFT95
is set so that the failUS AMX24-MFT95 (2) +N
Provide overload protection and disconnect25
The direction of rotation switch safe position and the Volts R R RedW
23
21 as required. position of the damper is closed with no signal at wire R.
24
reversing switch. W973, W7100
W
21 24 VAC Transformer Wht (3) W 25actuators
No. of Controller
Resistance
Wht (3) W
Actuators and controller must have separate transformers. Shunting Wht (4) R
W015
R Wht (4) R 2 140 Ω
22 Override
Resistor
Line Blk (1) Common 3 71.5 Ω Wht (5) B
Volts B Red (2)Wht (5) B
+ Hot High45 Limit47.5 Ω
Control Wht (6) ‘U5
21
37.5 Ω
Consult controller instruction data for more detailed
Switch A Switch B Damper Position 24
INSTALLATION
Series 90 A NOTES
Wht (6) 23 Output 2 to 10 VDC6
‘U5’ 28 Ω To other
-MFT
23 information. Controller Wht (3) W 24
Line actuators
Resistor Kit No. ZG-R03
24 VAC Transformer
Damper Open 135 Ω Wht (4) R
-MFT95 US 21 Volts
2121 Provide overload B Wiring Multiple Actuators to a Series 9
protection
Wht (5) Band using
Line a Minimum Position Potentiomet Blk (1)
Resistor value depends on the type of controller and the Damper Closed
Line disconnect as required.
Wht (6)Blk‘U5’(1)
Output 2 toCommon
10 VDC Volts Red (2)
24 number of actuators. No resistor is used for one actuator. 24 VAC Transformer
S963A
Minimum Position
The direction of rotation switch is set so that the fail safe position and the Volts 24 VAC Transformer Red (2)US + Hot
-MFT95 No. of Potentiometer
22
21 Actuators and controller must have 21
23 22 W actuators Resistance Wht (3)
Honeywell® resistor kits may also be used.
position of the damper is closed with no signal at wire R.
separate transformers. Line 2 1300 Ω Blk (1) C
Line Blk (1) Common Series 90 3 910 Ω Wht (4)
Volts R
21 24 VAC Transformer No. of
Volts Red (2)Wht (3) W
+ Hot 25Controller 4 768 Ω Red (2) +
To reverse control rotation, use the reversing 23 Consult controller instruction
actuators Resistance data
Wht (4) R 23for Series 90 B R W B Wht (5)
W015
Controller Resistor Kit No. ZG-R06
140 Ω
25 2
more detailed information.
A (6)To
Wht(3)
switch.2524232221
R B W Wht W
Line Blk (1) Common 3 71.5 Ω W Wht (3)Wht
W (5) B 24
B ac
Line
4 47.5 Ω R SeriesR 90 high limit control - 280 Ω Wht (4)-MF
R
Volts Red (2) + Hot 24
Volts
5 Resistor
37.5 Ω value dependsB
Wht onWht
(4) the(6)type
R
‘U5’ of
Output 2 to 10 VDC 22
Wht (5) B
23 6 controller
28 Ω B and the number Wht (5) of
B Shunting W Used with t
WARNING Live Electrical Components!
Resistor
A 22 Kitactuators.
To other Wiring Multiple Actuators to a Series
Wht (6) ‘U9
Wht (3) W Resistor No. ZG-R03 No
Controller resistorWht
actuators is(6)
used for
-MFT95
‘U5’ Output 2 toone
10 VDC US
24 23
During installation, testing, servicing and troubleshooting of Override
24 actuator. Honeywell® resistor -MFT95kits US may 21B
24 VAC Transformer
R W
-MFT
135 Ω Wht (4) R also be used.
Wiring Multiple Actuators to a Series 90 Controller
this product, it may be necessary to work with live electrical compo- B Line
H205 Change- Occupied Blk (1) C
nents. Have a qualified licensed electrician or other individual who Wht (5) B using a Minimum
Low Limit Control Position Potentiometer over Controller Contact
Volts Red (2) +
25 To reverse control rotation, use the 21 24 VAC Transformer
has been properly trained in handling live electrical components Wht (6) ‘U5’ Output 2 to 10 VDC S963A
reversing switch. Minimum Position
W016
W019
perform these tasks. Failure to follow all electrical safety precau- -MFT95 US 24
24 VAC Transformer
VAC Transformer Potentiometer Line
W Wht (3) W
24 VAC Transformer 2121 Shunting
tions when exposed to live electrical components could result 21 in 21
Resistor R Wht (4) R
Override
Line
Line Blk (1)BlkCommon Volts
death or serious injury. Line Blk (1) Common
(1) Common Line B Wht (5) B
Blk (1) C
Volts Red (2) + Hot 24
VoltsSwitch A Switch B Damper Position
Red (2) + Hot Volts 23
Series 90 22 Wht (6) ‘
Red (2) +
Volts Red (2) + Hot 23
Series 90 25 Controller
R B W -MFT
23 22 W
Controller
Damper Open
Wht (3) W 22 24
W
A
W R B 24 21 Wht (3) W
SeriesB90 R B W (4)Wht
WhtDamperR (3) W R R W
Wht (3) W R Closed
Line
W 24 Controller Line Wht
Blk (4)
(1) RC
B Wht (5)Wht B (4) R B
Wht (4) R R Volts Wht
Red (5) B+
Volts
R The direction 22 switch is set so that the fail
of rotation safe position and the Shunting
Resistor
(2)
B position of the damper is closed with no signal atWht
WSeries 90 low limit control Wht
wire(6)
R. (5)
‘U5’ Output 2 B
to 10 VDC ‘U Wht (6)
B Wht (5) B Shunting
Resistor 135 Ω for 0 to 50% control
W973, W7100 Honeywell
T775 To other
T675A Morning
24280 Ω forTransformer
VAC 0 to 100% control Wht (6)US‘U5’ Output 2 to 10 VDC
-MFT95 No. of Wht (3)
actuatorsWarmup -MFT W
22 Controller Wht (6) ‘U5’ Output 2 to 10 VDC 21 23 actuators Resistance
24 Wht (4) R
W015
-MFT95 US 2 140 Ω
Line Blk (1) Common
-MFT95 US B R W
3 71.5 Ω Wht (5) B
Volts 4 47.5 Ω
Red (2) + Hot 5 37.5 Ω Wht (6) ‘
H205 Change- Occupied 23 6 28 Ω
A
over Controller Contact To other
Low Limit Control Wht (3) W 24
Resistor Kit No. ZG-R03 actuators -MFT
B
Wht (5) B using a Minimum Position Potentiome
24 VAC Transformer
21 Wht (6) ‘U5’ Output 2 to 10 VDC
21 S963A
Minimum Position
21 -MFT95 US 24 VAC Transformer Potentiometer
Line Blk (1) Common 21 24 VAC Transformer 21 Line
Line Blk (1) Common
Volts Red (2) + Hot Line Blk (1) Common
Line Volts Blk (1) C
Volts Red (2) + Hot
24 VAC Transformer
21
21
Line Blk (1) Common
Line Blk (1) C
Volts Red (2) + Hot
23 Volts Red (2) +
22 W W R B Wht (3) W 24 22
Wht (3) W
Series 90 Wht (4) R
R
Controller Wht (4) R
Actuators: AF24-MFT95 US GMX24-MFT95 B AMX24-MFT95
Wht (5) NMX24-MFT95
B LMX24-MFT95
Wht (5) B
Series 90 low limit control Wht (6) ‘U5’ Output 2 to 10 VDC Wht (6) ‘
135 Ω for 0 to 50% control To other
280 Ω for 0 to 100% control -MFT95 US actuators -MF
Low Limit ControlHigh Limit Control Typical wiring diagrams for multiple a
INSTALLATION NOTES used with the W973, W7100 and T775
W017
Occupied
21 Contact
also be used. Line Blk (1) Common Y
800-543-9038 USA 866-805-7089 CANADA Volts
203-791-8396 LATIN AMERICA / CARIBBEAN
Red (2) + Hot
Honeywell T6
Morning War
25 To reverse control rotation, use the 23 R R W
24
32 reversing switch.
W Wht (3) W 25 W973, W7100
Controller
Shunting
Resistor R Wht (4) R
LRQ...24-1 Quick Running Actuators, On/Off
D1355
D C
H1 H2
E F B
A
LRQB, LRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRQB24-1 Basic Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
LRQX24-1 Flexible Version B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control on/off Dimensions with 3-Way Valve
Power supply 24 VAC ± 20% 50/60 Hz
D1356
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source)
20A @ 5ms max D
Electrical connection ½” conduit connector C
18 GA plenum rated cable H2
H1
LRQB24-1 3 ft [1m]
LRQX24-1 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Input impedance 600 Ω E F B
Angle of rotation max 95°, adjustable with mechanical stop A
Direction of rotation reversible with switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
33
LRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
W403-LRQ-08
1 Provide overload protection and disconnect as required.
34
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1371
D C
H1 H2
E F B
A
LRQB, LRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRQB24-MFT Basic Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
LRQX24-MFT Flexible Version B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve
24 VDC ± 10%
D1372
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source)
20A @ 5ms max
Electrical connection ½” conduit connector D
18 GA plenum rated cable C
LRQB24-MFT 3 ft [1m] H1 H2
LRQX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off) E F B
Feedback output U 2 to 10 VDC, 0.5mA max A
VDC variable
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
35
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
36
NRQ...24-1 Quick Running Actuators, On/Off
D1357
D C
H1 H2
E F B
A
NRQB, NRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
NRQB24-1 Basic Version
B248-B250 2” 50 4.21” [107] 2.27” [57.7]
NRQX24-1 Flexible Version
D1358
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
D
Transformer sizing 18 VA (Class 2 power source) C
Electrical connection ½” conduit connector,
18 GA plenum rated cable H1 H2
NRQB24-1 3 ft [1m]
NRQX24-1 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Input impedance 600 Ω E F B
Angle of rotation max 95°, adjustable with mechanical stop A
Direction of rotation reversible with switch NRQB, NRQX
Position indication reflective visual indicator (snap-on) Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
37
NRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
W403-NRQ-08
1 Provide overload protection and disconnect as required.
38
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1357
D C
H1 H2
E F B
A
NRQB, NRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
NRQB24-MFT Basic Version B248-B250 2” 50 4.21” [107] 2.27” [57.7]
NRQX24-MFT Flexible Version
D1358
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source) D
C
Electrical connection ½” conduit connector,
18 GA plenum rated cable H1 H2
NRQB24-MFT 3 ft [1m]
NRQX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default) E F B
variable (VDC, on/off) A
Feedback output U 2 to 10 VDC, 0.5mA max
NRQB, NRQX
VDC variable Valve Nominal Size Dimensions (Inches [mm])
Input impedance 100 kΩ (0.1 mA), 500 Ω, 1500 Ω Valve Body Inches DN [mm] A B C
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
39
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
40
NRB24-3-T N4, NRX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
NRB24-3-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRB24-3-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
NRX24-3-T N4 B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
NRX24-3-T N4H w/built in heater B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Dimensions with 3-Way Valve
Control on/off, floating point
D1364
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.0 W / heater 24 W
holding 0.2 W
Transformer sizing 4 VA (class 2 power source) / heater 19 VA
Electrical connection screw terminal (for 26 to 14 GA wire) D C
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer E F B
Manual override external push button A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
41
NRB24-3-T N4, NRX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
Wiring Diagrams
W193-NR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel. N L L N
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires. 1 2 3
3 Wire numbers are provided for reference.
4 Actuators may also be powered by 24 VDC.
On/Off control
W123-NR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection. M
1 2 3
Floating Point control
T H
(°C)
M
m with actuator types ..-3
Legend:
1
N L L N L M = actuator
2 T (°C) = Thermostat
1 2 3 H = Heating
M
N L L N L
T H
1 2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
1 <x <x
>x >x
2 1 2 3 5
T H x = 0 ... 100%
(°C)
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
42
NRB24-SR-T N4, NRX24-SR-T N4 NEMA 4X Actuators, Proportional
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models
NRB24-SR-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRB24-SR-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
NRX24-SR-T N4 B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
NRX24-SR-T N4H w/built in heater B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
D1364
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W / heater 24 W
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) / heater 20 VA D C
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100 kΩ (0.1mA), 500Ω
500
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch E F B
Position indication visual pointer A
Manual override external push button
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
43
NRB24-SR-T N4, NRX24-SR-T N4 NEMA 4X Actuators, Proportional
Wiring Diagrams
W265-NR-08
2 CAUTION Equipment damage! N L L N L
Actuators may be connected in parallel.
Power consumption and input impedance must be observed. 1 2 3
3 Actuators may also be powered by 24 VDC.
2 to 10 VDC control
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2
M
to 10 VDC, up to 2 actuators may be connected in parallel. 1
W265-NR-08
2
L L N WARNING
L Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
2 3 be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
Wiring Diagrams (°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L T H x = 0 ... 100%
M = actuator 4 to 20 mA control
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
1
2
L L N L
T H
2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
N L N L
1 <x <x
>x >x
2 1 2 3 5 1 2
T H x = 0 ... 100%
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
44
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
NRX24-MFT-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRX24-MFT-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control 2 to 10 VDC, 4 to 20 mA (default) vari-
able (VDC, PWM, floating point, on/off) Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC ± 10%
Power consumption running 3.5 W (1.25 W) / heater 24 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) / heater 21 VA
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Input impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off)
Angle of rotation 95°, adjustable with mechanical stop
electronically variable
Direction of rotation reversible with switch E F B
Position indication visual pointer A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
45
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source) N L L N L
6 On/Off control
or the Common (sink) 24 VAC line.
1 2 3
Contact closures A & B also can be triacs.
W538
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
T H
(°C)
W538
N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
(°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L M = actuator T H x = 0 ... 100%
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
VDC/4-20 mA 1
2
W538
L N L
T H
2 3 (°C) S1 S2 S3 S4 S5 S6
Note
M
1 The ffollowing points must be taken into account
N L L N L T H
with independent, external wiring:
2 PWM (°C)
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient 1
<x
numbers of wires, e.g. so that the heating and the <x 2
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
46 M
1
2
AR...24-3 Actuators, On/Off, Floating Point
D1359
D C
H1 H2
E F B
A
ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Models B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
ARB24-3 B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
ARB24-3-S w/built-in Aux. Switch B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
ARX24-3 Flexible B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
ARX24-3-S Flexible w/built-in Aux. Switch
ARB24-3-5-14
ARX24-3-5-14 Dimensions with 3-Way Valve
D1360
Technical Data
Control on/off, floating point
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% D C
Power consumption running 2.5 W
H1 H2
holding 0.2 W
Transformer sizing 5.5 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable E F B
ARB24-3... 3 ft. [1m] A
ARX24-3... 3 ft. [1m] 10 ft. [3m] 16 ft. [5m]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
ARB, ARX
Overload protection electronic throughout 0° to 95° rotation Valve Nominal Size Dimensions (Inches [mm])
Input impedance 600 Ω Valve Body Inches DN [mm] A B C
Angle of rotation 90°, adjustable with mechanical stop B329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
Direction of rotation reversible with protected switch B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
Position indication handle B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
Manual override external push button
Running time
ARB24-3... 90 seconds
ARX24-3... 300, 150, 90 seconds,
constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <45 dB(A)
Quality standard ISO 9001
AR...24-3-S
Auxiliary switch (-S models) 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0 to 90°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
47
AR...24-3 Actuators, On/Off, Floating Point
D1373
2 CAUTION Equipment damage!
D Actuators may be connected in parallel.
I Power consumption and input impedance must be observed.
C For end position indication, interlock control, etc.,
3 ARB24-3-S incorporates one built-in auxiliary switches:
1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
4 Actuators may also be powered by 24 VDC.
G
B
Meets cULus or UL and CSA requirements without the
E F A
need of an
O n-off electrical
cont ground connection.
rolofARB24-3
ARB, ARX
WARNING Live Electrical Components!
Nominal Top During installation, testing, servicing and troubleshooting of this product, it may
Valve Flange Face-to-Face be necessary to work with live electrical components. Have a qualified licensed electrician
Pipe Flange Height
Body Diameter Length or other individual who has been properly trained in handling live electrical components
Size Design
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
A B C electrical components could result in death or serious injury.
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
WAR NING
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1] Live Electrical Components!
D uring installation,testing, ser vicing and troubleshooti
ng ofthi s product,itmaybe
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9] necessar
or t
y to w ork withlive electricalcom ponents.H ave aqualified licensed electrician
oherindivi dualwho has been properly trained in handling live electricalcom ponents
Floating pointoron- off cont r ol
performthese tasks.Failureto foofARB24-3
ll
ow allelectrical safe
ty precauti ons when exposed
to live electricalcom ponents could res ultin death or serious injury.
W409
24 VAC Transformer 2
4
Line Blk (1) mon –
Com
Volts Red (2) +
a open a
Wht (3) +
a closed
TheNING
WAR indicati
on ofdirecti
on 1 0
is valid forwit
sch positi
on 1.
Live Electrical Components!
D uring install
ation,testing, servici
ng and troubleshooting ofthi s product ARB24-3
,itmaybe
necessar y to w ork withliv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividualwho has been properly trained in handli ng live electricalcom ponents
On/Off control performthese tasks.Fail ureto fo ll
ow allelectrical safe
ty precauti ons when exposed
W411
24 VAC Transformer 2
4
Notes:
Wht (3) +
1 Provide overload protecti
on and disconnect as re
quired.
is validforwitch
s positi on 1.
Auxiliarywitchs ofARB24-3-S ARB24-3
M eets cULus re quirements with outthe
4 need of anlect e ricalground connecti on.
Floating Point or On/Off control
W410
Notes:
WAR NING
1 Provid e overload protecti on and disconnect as re quired.
Live ElectricalC om ponents!
D uringins talla
tion, e
tsting,servicing and S1 3
2 ootAct
troublesh ing ouat
fh
tisors
productma
,iytmaalybe
so be pow ered by NC
24 VD C .
necessar y tow ork with li
ve elec trical
com ponents.H ave a qualified licensed S2
M eet s cULus requi rement
s withoutth e need of an
elec 4 ro otherindi
trician vidual who hasbeen
properly r elect
tained ricalgro
inhandling veund
li elec trical on. S3
connecti 0° to 95
°
NO
com ponents perform htese atsks.Failure to
foll
ow allelectrical
safety precau tions when
exposed tolive electrical
com ponents could ARB24-3-S W 409
resultindeath orserious injury.
Auxiliary switch
N otes:
D1359
D C
H1 H2
E F B
A
ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
Models
ARB24-SR Dimensions with 3-Way Valve
ARX24-SR Flexible Version
D1360
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W D C
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) H1 H2
Electrical connection ½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
E F B
Overload protection electronic throughout 0° to 95° rotation
A
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA ARB, ARX
Input impedance 100 kΩ (0.1 mA), 500 Ω Valve Nominal Size Dimensions (Inches [mm])
Angle of rotation 90°, adjustable with mechanical stop Valve Body Inches DN [mm] A B C
Torque 180 in-lb [20 Nm] B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Direction of rotation reversible with protected switch B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
Position indication handle B347-B352 2” 50 4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
Manual override external push button
Running time
ARB24-SR... 90 seconds
ARX24-SR... 300, 150, 90 seconds,
constant independent of load
Humidity 5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <45 dB(A)
Quality standard ISO 9001
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
49
AR...24-SR Actuators, Proportional WAR NING
LiveElectrical
C om ponents ! LiveElectrical
C om pone
WAR NING
D urin
g installation
, testin
g, servicin
g and trou
bleshooting of h
tis product , it
m aybe D urin
g installation
, tes
necessary tow ork w it
h live electrical
m ponents.
co H ave a quali fied licensed electrician necessary tow ork w it
h
or ot
her individual
w ho has been properl
y trainedhandlin
in g live electrical m ponents
co or ot
her individual
w ho h
perform h
tese tasks.Failure follo
to w all electrical
fety precautions
sa w hen exposed perform h
tese tasks.Fa
to live electrical
m ponents
co could resultdeathinor serious jury.
in to live electrical
m pon
Wiring Diagrams
W408
24 VAC Transform er 2 24 VAC Tr
Line
2 CAUTION Equipment damage! Line
Volts
Blk (1) Com
mon –
Volts
Red (2) Hot +3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed. Wht (3) Input,
Y 2 to 10V
4 to 20A m (–
Control
Signal (–)
Org (5) Output,
U 2 to 10V Control
Signal (
3 Actuators may also be powered by 24 VDC. 2 to 10DCV (+)
1 0
2 to 10
DCV (–)
WAR circuits.
NING WAR NING
5 Only connect common to neg. (–) leg of control Feedback Signal (+)
LiveElectrical
C om ponents !
ARB2 4-SR
LiveElectrical
C om ponents !
D urin
g installation
, testin
g, servicin
g and trou
bleshooting of h
tis product , it
m aybe D urin
g installation
, testin
g, servicin
g and trou
bles
hooting of h
tis product , it
m aybe 5
necessary tow ork w it
h live electrical
m ponents.
co H ave a quali fied licensed electrician necessary tow ork w it
h live electrical
m ponents.
co H ave a qualified licensed electrician
or ot
her individual
perform h
tese tas
w ho has been properl
ks.Failure follo
y trainedhandlin
to w all electrical
fety precautions
sa 2 to 10 VDC control
in g live electrical m ponents
w hen exposed
co or ot
her individual
perform h
tese tas
w ho has been properl
ks.Failure follo
y trainedhandlin
in g live electrical
to w all electrical
fety precautions
sa
m ponents
w hen exposed
co
to live electrical
m ponents
co could resultdeathinor serious jury.
in to live electrical
m ponents
co could result hinordeatseriousjury.
in
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
W408
2 to 10 VDC, up to 2 actuators may be connected
24 VACinTrans
parallel.
form er 2 24 VAC Transform er 2
Notes:
W408
50
AR...120-3 Actuators, On/Off, Floating Point
D1361
D C
H1 H2
E F B
A
D1362
Power supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 3 W
holding 0.6 W D C
Transformer sizing 7 VA (class 2 power source)
Electrical connection ½” conduit connector H1 H2
18 GA appliance rated cable
ARB120-3 3 ft [1m]
ARX120-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation E F B
A
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
ARB, ARX
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Direction of rotation reversible with protected switch Valve Nominal Size Dimensions (Inches [mm])
Position indication handle Valve Body Inches DN [mm] A B C
Manual override external push button B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Running time B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
ARB120-3 90 seconds B347-B352 2” 50 4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
ARX120-3 300, 150, 90 seconds,
constant independent of load
Humidity 5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <45 dB(A)
Servicing maintenance free
Quality standard ISO 9001
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
51
AR...120-3 Actuators, On/Off, Floating Point
D1373
1 Provide overload protection and disconnect as required.
D
I
2 CAUTION Equipment damage!
C Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W414
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
On/Off control
W415
52
AR...120-SR Actuators
D1361
D C
H1 H2
E F B
A
Models
ARB120-SR Dimensions with 3-Way Valve
ARX120-SR Flexible Version
D1362
Technical Data
Control on/off, floating point
Power supply 100 to 240 VAC, 50/60 Hz (nominal) D C
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 3 W H1 H2
holding 0.6 W
Transformer sizing 7.5 VA (class 2 power source)
Electrical connection ½” conduit connector E F B
18 GA plenum rated cable A
ARB120-SR 3 ft [1m]
ARX120-SR 3 ft [1m], 10 ft [3m], 16 ft [5m] ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Overload protection electronic throughout 0° to 95° rotation
Valve Body Inches DN [mm] A B C
Feedback output U 1 to 10 VDC, max 0.5 mA
B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Input impedance 600 Ω
B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
53
WARNING APPLI
AR...120-SR Actuators Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
Meets cU
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components electrica
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
7 A 500 Ω
Wiring Diagrams signal to
W365
100 to 240 VAC
15 2 19
1 Neutral
CAUTION Equipment damage! N L1
Cable 2
2
Actuators may be connected in parallel. H L2 2 Hot +
Cable 1
(–)
Control Signal
15 ARB(X) can be supplied with both 120 VAC and 230 VAC. VDC/mA (+) 3 Y Input, 2 to 10V
2 to 10 VDC (–)
Feedback Signal (+) 5 U Output, 2 to 10V
19 All 120 VAC and 230 VAC actuators use appliance rated cables.
1 0
54
AR...24-MFT Actuators, Multi-Function Technology
D1361
D C
H1 H2
E F B
A
D1362
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) D C
Electrical connection ½” conduit connector
18 GA plenum rated cable H1 H2
ARX24-MFT 3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default) E F B
variable (VDC, PWM, floating point, on/off) A
Feedback output U 2 to 10 VDC, 0.5 mA max
VDC variable ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
55
AR...24-MFT Actuators, Multi-Function Technology
Dimensions
W538
D1374
D
I
C
G On/Off control
W538
B
E F A
ARB, ARX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
A B C
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
Floating Point
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
W538
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
Wiring Diagrams
W538
Position feedback cannot be used with Triac sink controller.
4
The actuator internal common reference is not compatible.
PWM
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
56
ARX24-PC Actuators, Phasecut
D1361
D C
H1 H2
E F B
A
D1362
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 5.5 VA (Class 2 power source)
Electrical connection ½” conduit connector D C
18 GA plenum rated cable
3 ft. [1m], 10 ft. [3m], 16 ft. [5m] H1 H2
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 0 to 20V phasecut
Feedback output U 2 to 10 VDC, 0.5mA max E F B
VDC variable A
Input impedance 8 kΩ (50 mW)
Angle of rotation 90°, adjustable with mechanical stop ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
57
ARX24-PC Actuators, Phasecut
Wiring Diagrams
W185
1
24 VAC Transformer
58
ARX24-MFT95 Actuators, 0 to 135 Ω
D1361
D C
H1 H2
E F B
A
D1362
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 6 VA (Class 2 power source) D C
Electrical connection ½” conduit connector
18 GA plenum rated cable H1 H2
3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range WRB 0 to 135 Ω Honeywell Electronic E F B
Series 90, 0 to 135 Ω input A
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 100 kΩ (0.1 mW) ARB, ARX
Angle of rotation 90°, adjustable with mechanical stop Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
59
ARX24-MFT95 Actuators, 0 to 135 Ω
S963A
24 VAC Minimum Position
Transformer Potentiometer
1
Wiring Diagrams Switch A Switch B Damper Position
1 Common
Line
Damper Open
Volts 2 + Hot
Damper Closed Series 90
Controller
The direction of rotation switch is set so that the fail safe position and the
B R B W 3 W
position of the damper is closed with no signal at wire R.
24 VAC Transformer W 5 B
1 Shunting
3 information.
135 B
4 R
5 B
Resistor value depends on the type of controller and the number of 6 ‘U5’ Output 2-10 VDC
During installation, testing, servicing and troubleshooting of this product, it may 2 Controller 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-1
To other
be necessary to work with live electrical components. Have a qualified licensed electrician …MFT95 actuators …MFT95
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live Override Wiring multiple actuators to a
electrical components could result in death or serious injury. Series 90 controller using a
minimum position potentiometer.
S963A
24 VAC Minimum Position
Transformer Potentiometer
1 24 VAC Transformer
1
Switch A Switch B Damper Position
Line
Notes: 1 Common 1 Commo
Line
Damper Open
Volts 2 + Hot Volts 2 + Hot
Damper Closed Series 90
1 Provide overload protection and
5
disconnect as required. 4 Re
Controller
The direction of rotation switch is set so that the fail safe position and the
B R B W 3 W
2
W W B R 3 W
the
position of the damper is closed with no signal at wire R.
R
2 Actuators and controller
4 R must have separate transformers. 4 R ac
Series 90 R
2
24 VAC Transformer 5 B Controller 5 B
W B
1 Shunting
Resistor
6 ‘U5’ Output 2-10 VDC
1 Common 3 Series 90 low limit control To
6 ‘U5’ Outp
3 Consult controller instruction data for more135detailed 5
Line
4 for 0 to 50% control
Volts 2 + Hot 3 …MFT95 280 for 0 to 100% control …MFT
B R Winstallation information.
A 4
H205 Change- Occupied
3 W
over Controller Contact Low Limit Control
135 4 R
B
5 B
6 ‘U5’ Output 2-10 VDC
24 VAC Transformer
1 1
24 VAC Transformer …MFT95
1 Line 1 Common Line 1 Commo
3
Line 1 Common Volts 2 + Hot Volts 2 + Hot
Volts 2 + Hot 3 5
2
4 2
A 3 W W 3 W
W 3 W
Line 4 R R 4 R
R 4 R Series 90
Volts B 5 B Controller R W B 5 B
B 5 B B
Notes:
S963A
24 VAC Minimum Position
Potentiometer
1
Transformer
1 Provide overload protection and disconnect
1
24 VACas required.
Transformer 4 Resistor value depends on the type of contro
Switch A Switch B Damper Position
Line 1 Common 1 Common
the number of actuators. No resistor is used
Line
Damper Open
Volts 2 Actuators and controller
2 + Hot must have Volts
separate transformers. 2 + Hot actuator.
3 Honeywell resistor kits may also b
Damper Closed Series 90 5
Controller 5
R B W 2
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
B
Consult controller
3 W
instruction data for more Rdetailed
W W B R 3 W
5 To reverse control rotation, use the reversing
R 3 4 R
Series 90
4 R
2
24 VAC Transformer W
installation information.
5 B Controller
B 5 B
1 Shunting
Resistor
6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC
Line 1 Common 3 Series 90 low limit control
4 135 for 0 to 50% control
Volts 2 + Hot 3 …MFT95 280 for 0 to 100% control …MFT95
B R W
A 4
H205 Change- Occupied
3 W
over Controller Contact Low Limit Control
135 4 R
B
5 B
6 ‘U5’ Output 2-10 VDC
24 VAC Transformer
1 1
24 VAC Transformer …MFT95
1 Line 1 Common Line 1 Common
3
Line 1 Common Volts 2 + Hot Volts 2 + Hot 3
Volts 2 + Hot 3 5
2 5
4 2
A 3 W W 3 W
W 3 W
Line 4 R R 4 R
R 4 R Series 90
Volts B 5 B Controller R W B 5 B
B 5 B B
2 Controller 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC
To other Series 90 high limit control - 280
…MFT95 actuators …MFT95 …MFT95
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
ARB24-3-T N4 B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARB24-3-T N4H w/built in heater B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
ARX24-3-T N4 B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
ARX24-3-T N4H w/built in heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Control on/off, floating point Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC ± 10%
Power consumption running 2.5 W / heater 23 W
holding 0.5 W
Transformer sizing 5.5 VA (class 2 power source) / heater 20.5 VA
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer
Manual override external push button E F B
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
61
ARB24-3-T N4, ARX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
WAR NING
Live Electrical Components!
D uring installation,testing, ser vicing and troubleshooti
ng ofthi s product,itmaybe
necessar y to w ork withlive electricalcom ponents.H ave aqualified licensed electrician
or t oherindivi dualwho has been properly trained in handling live electricalcom ponents
performthese tasks.Failureto fo ll
ow allelectrical safe
ty precauti ons when exposed
Floating pointoron- offcontrolofARB24-3
to live electricalcom ponents could res ultin death or serious injury.
Wiring Diagrams
W409
24 VAC Transformer 2
4
Line Blk (1) mon –
Com
W411
Meets cULus or UL and CSA requirements without the 24 VAC Transformer 2
4
need of an electrical ground connection.
Line Blk (1) mon –
Com M
WARNING Live Electrical Components! Volts Red (2) +
During installation, testing, servicing and troubleshooting of this product, it may N L L N L Notes:
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components 1 1 Provide overload protecti
on andWht
disconnect
(3) as+ re
quired.
2 3
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. 2 Act uators
The ma
indic
a yonalso
ti bere
ofdi pow
cti
onered by1 240 VD C .
is validforwitch
s positi on 1.
N L L N
M eets cULus re quirements with outthe ARB24-3
4 need of anlect e ricalground connecti on. 1 2 3
T H
Floating Point or On/Off
(°C) control
M
m with
ith actuator types ..-3
Notes: Legend:
1
N L L N L M = actuator
1 Provid
e overload protecti
on and disconnect as re
quired.
2 T (°C) = Thermostat
1 2 3 2 y also be pow ered byH 2
Actuators ma =4 Heating
VD C .
M
T
1 <x <x
>x >x
2 1 2 3 5
Note
M
1 The ffollowing points must be taken into account
N L L N L
with independent, external wiring:
2
• All contact between the cables or wires that
1 2 3 S1 S2 isS3 W 411
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient
<x
T numbers of wires, e.g. so that the heating and the <x
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
62
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
ARB24-SR-T N4 B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARB24-SR-T N4H w/built in heater B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
ARX24-SR-T N4 B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
ARX24-SR-T N4H w/built in heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve1363
24 VDC ± 10%
D1364
Power consumption running 2.5 W / heater 23 W
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) / heater 20 VA
Electrical connection screw terminal (for 26 tp 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Operating range Y 2 to 10 VDC, 4 to 20 mA
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer E F B
Manual override external push button A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
63
N L L N L
1 2 3
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
N L L N
1 2 3
Wiring Diagrams Wiring Diagrams(°C)T H
M
m with actuator types ..-3
Legend:
2 CAUTION Equipment damage! N L
1
L N L M = actuator
Actuators may be connected in parallel. 2 T (°C) = Thermostat
Power consumption and input impedance must be observed. 1 2 3 H = Heating
M
3 Actuators may also be powered by 24 VDC.
W408-SR-T
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
W408-SR-T
(°C)
M
1
2
4 to 20 mA control
64
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARX24-MFT-T N4
B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
ARX24-MFT-T N4H w/built in heater
B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
Technical Data B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Control 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve1363
24 VDC ± 10%
D1364
Power consumption running 3.5 W / heater 24 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) / heater 21 VA
Electrical connection screw terminal (for 26 tp 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation
D C
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and
on/off control
Angle of rotation 95°, adjustable with mechanical stop
E F B
electronically variable
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
A
Direction of rotation reversible with switch
Position indication visual pointer NRB N4, NRX N4
Manual override external push button Valve Nominal Size Dimensions (Inches [mm])
Running time 150 seconds (default) Valve Body Inches DN [mm] A B C
constant independent of load B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
variable (75 to 350 seconds) B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
Humidity 100% RH B347-B352 2” 50 4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing type UL Type 4X/NEMA 4X/IP66 & IP67
Housing material Polypropelene
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1, CSA C22.2 No. 24-93, CE ac-
cording to 89/336/EEC.
Quality standard ISO 9001
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
*Cannot be used with the CCV-EXT-KIT
65
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source) N L L N L
6 On/Off control
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs. 1 2 3
W538
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
T H
(°C)
L N WARNING
L Live Electrical Components! 2
During installation, testing, servicing and troubleshooting of this product, it may
2 3 be necessary to work with live electrical components. Have a qualified licensed electrician Floating Point
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
W538
N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
(°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L M = actuator T H x = 0 ... 100%
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
VDC/4-20 mA 1
2
W538
L N L
T H
2 3 (°C) S1 S2 S3 S4 S5 S6
Note
M
1 The ffollowing points must be taken into account
N L L N L T H
with independent, external wiring:
2 PWM (°C)
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient 1
<x
numbers of wires, e.g. so that the heating and the <x 2
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
66 M
1
ARQX24-1 Quick Running Actuators, On/Off
D1375
D C
H1 H2
E F B
A
ARQB, ARQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B248-B280 2” 50 4.21” [107] 2.27” [57.7]
Models
ARQX24-1 Flexible Version Dimensions with 3-Way Valve
D1376
Technical Data
Control on/off
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% D
C
Power consumption running 15 W
holding 1.5 W H1 H2
Transformer sizing 26 VA (Class 2 power source)
Electrical connection ½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m] E F B
Overload protection electronic throughout 0 to 95° rotation A
Input impedance 100 Ω
ARQB, ARQX
Angle of rotation max 95°, adjustable with mechanical stop Valve Nominal Size Dimensions (Inches [mm])
Direction of rotation reversible with switch Valve Body Inches DN [mm] A B C
Position indication reflective visual indicator (snap-on) B330-B332 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Manual override external push button
B338-B340 1½” 40 4.39” [111.6] 2.51” [63.7] 2.90” [61.1]
Running time constant of independent load
B348-B352 2” 50 4.95” [124.5] 2.73” [69.5] 2.74” [69.7]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
10 or 15 seconds
Humidity 5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <52 dB(A)
Quality standard ISO 9001
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
67
ARQ...24-1
Wiring Diagrams
W403-ARQ-08
1 Provide overload protection and disconnect as required.
ARQ...24-1
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
ARQX24-1
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W403-ARQ-08
68
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
D149-2A
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARQX24-MFT Flexible Version B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Technical Data B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 15 W Dimensions with 3-Way Valve
holding 1.5 W
D149A
Transformer sizing 26 VA (Class 2 power source)
Electrical connection ½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off)
Feedback output U 2 to 10 VDC, 0.5mA max
VDC variable
Input impedance 100 kΩ (0.1 mA), 500 Ω, 1500 Ω
(on/off)
Angle of rotation max 95°, adjustable with mechanical stop
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
electronically variable
Direction of rotation reversible with switch
Position indication reflective visual indicator (snap-on) Valve Nominal Size Dimensions (Inches [mm])
Manual override external push button Valve Body Inches DN [mm] A B C
Running time constant of independent load B330-B332 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
10 or 15 seconds B338-B340 1½” 40 4.39” [111.6] 2.51” [63.7] 2.90” [61.1]
Humidity 5 to 95% RH non-condensing B348-B352 2” 50 4.95” [124.5] 2.73” [69.5] 2.74” [69.7]
(EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or
–S versions
Noise level <52 dB(A)
Quality standard ISO 9001
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
69
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
70
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GRB24-3-5-14
GRX24-3-5-14 A B C
B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
F05
Technical Data B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control on/off, floating point
Power supply 24 VAC ± 20% 50/60 Hz
Power consumption running 4 W
holding 2 W
Transformer sizing 6 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
GRX 3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation max. 95°, adjustable with mechanical stop
Direction of rotation reversible with switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
71
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W254_08
1 Provide overload protection and disconnect as required.
W255_08
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
72
GRB120-3, GRX120-3
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GRB120-3
GRX120-3 A B C
B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
F05
Technical Data B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Power Supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 4 W
holding 2 W
Transformer sizing 7 VA (Class 2 power source)
Electrical connection 18 GA appliance rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Control on/off, floating point
Input impedance 600 Ω
Angle of rotation max. 95°, adjustable with mechanical stop
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
73
GRB120-3, GRX120-3
Wiring Diagrams
W375_08
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel.
2 Power consumption and input impedance must be observed.
W376_08
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
74
GRX24-MFT Actuators, Multi-Function Technology
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
Models A B C
GRX24-MFT-5-14 B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control 2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4.5 W
holding 1.5 W
Transformer sizing 7 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC, 0.5 mA max, VDC variable
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
75
GRX24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
W399_08
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W399_08
76
TFRB(X) Actuators, On/Off
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24 TFRB(X)120
TFRB(X)24-S TFRB(X)120-S w/built-in Aux. Switch Dimensions with 3-Way Valve
D1366
Technical Data
Control on/off
Power supply
TFRB(X)24(-S) 24VAC ± 20%, 50/60Hz
24VDC ± 10%
D
TFRB(X)120(-S) (nominal) 100 to 240 VAC, 50/60 Hz
(tolerance) 85 to 265 VAC, 50/60 Hz C
Power consumption running 2.5 W
holding 1.3 W
Transformer sizing
TFRB(X)24(-S) 5 VA (class 2 power source) E F
TFRB(X)120(-S) 5 VA (class 2 power source) B
A
Electrical connection ½” conduit connector
TFRB, TFRX
(-S models have 2 cables) 18 GA appliance cable
Valve Nominal Size Dimensions (Inches [mm])
TFRB(X)24... 3 ft [1m]
Valve Body Inches DN [mm] A B C
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
TFRB(X)120 10 ft [3m]
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
16 ft [5m]
B312(B)-B315(B) ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Overload protection electronic throughout 0° to 95° rotation
B317(B)-B321(B) ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Angle of rotation 95°
Direction of rotation reversible with protected mounting
Position indication visual indicator, 0° to 95°
Running time motor <75 seconds (0 to 18 in-lb)
spring <75 sec @ -22°F to 122°F [-20°C to 50°C]
Humidity 5 to 95% RH non-condensing
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA type 2/IP42
Housing material UL94 - 5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
Noise level (max) running <40 db (A)
spring return <40 dB (A)
Quality standard ISO 9001
TFRB(X)...-S
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
77
TFRB(X) Actuators, On/Off WAR NING
Live Electrical Components!
D uring installation,testi ng, servici
ng and troubleshooting ofthis product ,itmaybe
necessar y to w ork w it
h liv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividu alw ho has been properly trained in handli ng live electricalcom ponents
performthese tasks.Failu reto fo ll
ow allelectrical safe
ty precauti ons w hen exposed
to live electricalcom ponents could res ultin death or serious injury.
W237
24 VAC Transformer
1 Common
3
2 CAUTION Equipment damage! 2 + Hot
W217
100 to240 VAC
Meets cULus or UL and CSA requirements without the N L1 1 Neutral
need of an electrical ground connection. 1 2 Hotas re
H eL2overload protecti
Provid on and disconnect quired.
W248
WAR NING
t1
Live Elec CPr
rical omovide
ponents! overl oad protection and disc
onnectas required.
D uringins
talla
tion, etsting,servicing and S1
ootingAct
troublesh tuato
of h rsm,i
is product ay
tmabe
ybeconnected inparallel.
Pow er
necessary2tow ork with live electrical NC
consum ption m ustbe observed. S2
com ponents.H ave a qualifiedlicensed
electricianro ot
herindi
M eetsvidual
cULuswho hasbeen
require m ents w itS3
hout he
t need ofan
properly r
tained
3 elecinhandling li
ve elec
trical 0° to 95
°
com ponents perform t
hrical
t tgr
ese a ound connec
sks.Failure
to tion. NO
foll
ow allelectrical
safety precau tions when
exposed tolive electrical
com ponents could TFX… -S US 2
resultindeath orserious injury.
Auxiliary Switch
W 237
W 248
78
TFRB(X)24-3 Actuators, Floating Point
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24-3
TFRB(X)24-3-S w/built-in Aux. Switch Dimensions with 3-Way Valve
D1366
Technical Data
Control floating point
Power supply 24VAC ± 20%, 50/60Hz
Power consumption running 2.5 W
holding 1.0 W D
Transformer sizing 4 VA (class 2 power source) C
Electrical connection ½” conduit connector
(-S models have 2 cables) 18 GA plenum rated cable
TFRB(X)24-3... 3 ft [1m]
10 ft [3m]
E F
16 ft [5m] B
A
Overload protection electronic throughout 0° to 95° rotation
TFRB, TFRX
Input impedance 1000 Ω (0.6w) control inputs
Angle of rotation 95° Valve Nominal Size Dimensions (Inches [mm])
Direction of rotation spring reversible with CW/CCW mounting Valve Body Inches DN [mm] A B C
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
motor reversible with built-in switch B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
Position indication visual indicator, 0° to 95° B312(B)-B315(B) ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Running time motor 95 sec constant, independent of load B317(B)-B321(B) ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
spring <25 sec @ -4°F to 122°F [-20°C to 50°C]
<60 sec @ -22°F [-30°C]
Humidity 5 to 95% RH non-condensing
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA type 2/IP42
Housing material UL94 - 5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
Noise level (max) running <35 db (A)
spring return 62 dB (A)
Quality standard ISO 9001
TFRB(X)24-3-S US
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
79
Floatin
g pointcontrol f
oTF24-3(-S)US
W240
24 VA C Transfor
m er 7
xx
xx
xx
xx
xx
~
xx xx
Or (W4)
xx xx
b
xx xx
xx xx
xx xx
x x
3
CCW CW
The actuator Hot must be connected to the control board common. TF24-3(-S)US
4 stop stop stop stop
For end position indication, interlock control, fan startup, etc., The indication of direction is valid
for switch position CW.
5 TF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A) @250 VAC, UL listed, adjustable 0° to 95°. Floating point control
Actuators with plenum rated cable do not have numbers on wires; use
7
W242
color coded instead. Actuators with appliance rated cable use numbers.
24 VA C Transfor
m er
WAR NING Line
LiveElectricalm ponents
Co ! Volts
D urin
g installation
, testing,
Meets cULus or UL and CSA requirements without the servicin
g and tro
of this uctprod
ubleshootin
, it
m aybe
g
2 7
need of an electrical ground connection. necessary to wor
electrical
k with live
co N otes
m ponents. H ave:
H ot Com
a qualified licensed electrician
Blk (1) Common
WARNING Live Electrical Components! or other individ
been properl
ual who has
y trained1in Provide overload protection and disconnect quired.Red 2)
(
as re Hot ~
During installation, testing, servicing and troubleshooting of this product, it may handling live electrical
Tr iac si
n k Wh t W3
( ) ~
be necessary to work with live electrical components. Have a qualified licensed electrician com ponents perform these
tasks.Fail
ure to follow
or other individual who has been properly trained in handling live electrical components electrical ysafet 2 all Actuatorsm ay be connected in parallel.
Power consum ption
Or m Wust
4)be observed.
( ~
preca utions
perform these tasks. Failure to follow all electrical safety precautions when exposed to comliveponents co
when exposed to live electrical
uld res ult in
jury. 7 Act uators with um plen
rated ble
ca do not have
um bers
n on wires
;use color codes instead.
TF24-3(-S)
US
electrical components could result in death or serious injury. death or serio
us in
Triac source
W243
24 VA C Transfor
m er
WAR NING Line
LiveElectricalm ponents
Co Volts
!
D urin
g installation
, testing,
servicin
g and troubleshootin g
2 7
of this uct
necessar
prod
, it
y to wor
m aybe
k with live
W 240
electrical m ponents.
co H ave
H ot Com
a qualified licensed electrician
Blk (1) Common
or other individ
ual who has
been properly trained in
Red 2)
( ~ Hot 3
handling live electrical
com ponents perfor m these () ~
Wh t W3 4
tasks.Fail
ure to follow all
N otes:
electrical ysafet
preca utions
Or (W 4) ~
W241
WAR NING
Live Electrical C om ponents!
D uringins talla
tion, etsting,servicing and S1 5
troubleshooting of h tis product,itma ybe
NC
necessar y tow ork with li ve elec trical
com ponents.H ave a qualified licensed S2
electricianr o ot
herindi vidual who hasbeen
S3
properly rtained inhandling live elec trical
NO W0°242
to 5°
9
N otes: com ponents perf orm htese a tsks.Failure to
foll
ow allelec trical safety precau tions when
exposed toli ve elec tricalcom ponents could TF24-3-S US
resultindeath orseri ous injury.
1 Provide overload protection and disconnect
quired. as re
Auxiliary switch
Actuatorsm ay be connected in parallel.
Power cons
um ption
2 m ustbe observed.
W 243
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
80
TFRB(X)24-SR Actuators, Proportional
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24-SR
TFRB(X)24-SR-S w/built-in Aux. Switch Dimensions with 3-Way Valve
D1366
Technical Data
Control proportional
Power supply 24 VAC ± 20%, 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W D
holding 1.0 W C
Transformer sizing 4 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 18 GA plenum rated cable
TFRB(X)24-SR... 3 ft [1m]
10 ft [3m] E F B
16 ft [5m] A
Electrical protection actuators are double insulated TFRB, TFRX
Overload protection electronic throughout 0° to 95° rotation Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
TFRB(X)24-SR-S
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
81
TFRB(X)24-SR Actuators, Proportional WAR NING
Live Electrical Components!
D uring installation,testi ng, servici
ng and troubleshooting ofthis product ,itmaybe
necessar y to w ork w it
h liv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividu alw ho has been properly trained in handli ng live electricalcom ponents
performthese tasks.Failu reto fo ll
ow allelectrical safe
ty precauti ons w hen exposed
to live electricalcom ponents could res ultin death or serious injury.
Wiring Diagrams
W245
24 VAC Transformer 6
4 to one 500 Ω resistor, a +2% shift of control signal may be required. WAR NING 2
Power consumption must be observed. LiveElectrical
C om ponents! TF24-SR US
D urin
g installation
, testin
g, servicin
g and trou
bleshooting of h
tis product, it
m aybe
W246
24 VAC Transform er 6
Actuators with plenum rated cable do not have numbers on wires;
6 use color codes instead. Notes:
Line Blk (1)Common
3
For end position indication, interlock control, fan startup, etc., Volts Red (2) + Hot
1 Provid
e overloadΩprotecti
on and disconnect as re
quired.
7 TF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
500Ω
(0.5A ) @250 VAC, UL listed, adjustable 0° to 95°. 4 to 20A m (–)
Actuators ma
y be connected iWht
n para
llel. Pow
2rolSignal (+)
Cont (3) Y 2er
1 Input,
consum pti
to 10V
on
and inputim pedance mustbe observed.
4
Auxiliaryswitchesof TF24-SR-S US
3 Actuator may also be pow ered by 24 VD C .
Meets cULus or UL and CSA requirements without the 5 To other
2
Actuatorsw ithactuators
plenum rated cable do nothave num bers on
need of an electrical ground connection. 6 w ires;use colorcodes instead. TF24-SR US
W246
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live WAR NING
electrical components could result in death or serious injury. Live Elec
trical
C om ponents!
N otesD:uringinstalla
tion, e
tsting,servicing
and S1 7
troubleshooting of h
tis product,itma ybe
necessary tow ork with live elec trical NC
1 Provide
com overload
ponents.H ave a qualified protection and
licensed S2 disconnect as required.
electricianro ot
herindi vidual who hasbeen
S3
properl
U p yto r
tained inhandling
4 actuators
com ponents perform h tese a
mli
ve elec
ay be trical
tsks.Failure
connected
to
W 0°
h to
in Nparallel.
O it 95
°
2 4 owactuators
foll allelec wsafe
trical ired
ty precautotionsone
500Ω
when resistor
, a+2% shift f o
control
exposed vegnal
toli sitrical
elec m ay combeponentrequired.
s could w er
PoTF24-SR-S
consum ptionUS
resultindeath orseri
m ustbe observed. ous injury. W 245
Auxiliary switch3 Actuator
m ay also
be pow eredby 24 VDC .
A 500Ω resistor converts
he 4… t20m A control
4 signal to
2 to10 VDC . (ZG-R01)
Forend position indication,interlock control,fanstartup,etc.,
5 O nly connect mm
co on toS ne
7 TF24-SR-SU g.(
inc–)
o le
g to
rpora f control
es one buil circuits.
t-inauxiliar
y switch: 1 x SPDT,
W 247
W 246
82
TFRX24-MFT Actuators, Multi-Function Technology
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRX24-MFT
Dimensions with 3-Way Valve
Technical Data
D1366
Control MFT
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W
holding 1.0 W D
Transformer sizing 4 VA (class 2 power source) C
Electrical connection ½” conduit connector
3 ft [1m], 18 GA plenum rated cable
Overload protection electronic throughout 0° to 95° rotation
Operating range Y* 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off) E F B
Feedback output U* 2 to 10 VDC, 0.5 mA max A
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA) TFRB, TFRX
500 Ω for 4 to 20 mA Valve Nominal Size Dimensions (Inches [mm])
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1500 Ω for PWM, floating point and Valve Body Inches DN [mm] A B C
on/off control B307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
Mechanical angle of rotation* 95° B312-B315 ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Angle of rotation adaptation* Off (Default) B317-B321 ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch
Position indication visual indicator, 0° to 95°
Override control* Min. (Min Position) = 0%
- ZS (Mid. Position) = 50%
- Max. (Max. Position) = 100%
Running time motor* 95 seconds constant independent of load
spring <25 seconds @-4°F to 122°F [-20°C to 50°C]
<60 seconds @-22°F [-30°C]
Humidity 5 to 95% RH, non-condensing
Ambient temperature -22 to 122° F (-30 to 50° C)
Storage temperature -40 to 176° F (-40 to 80° C)
Housing NEMA 2/IP42
Housing material UL 94-5VA
Agency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
Noise level (max) running <35 dB (A)
spring return <65 dB (A)
Quality standard ISO 9001
* Variable when configured with MFT options
† Rated impulse voltage 0.8 kV, Control pollution degree 3, Type of action 1.AA.
83
TFRX24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W024
1 Provide overload protection and disconnect as required.
W025
84
LF Actuators, On/Off
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24 US
B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LF24-S US w/built-in Aux. Switch
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
LF120 US
LF120-S US w/built-in Aux. Switch B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
D1368
Power supply
LF24(-S) US 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
LF120(-S) US 120 VAC ± 10% 50/60 Hz
Power consumption
LF24(-S) US running 5W D C
holding 2.5 W
LF120(-S) US running 5.5 W
holding 3.5 W
Transformer sizing
LF24(-S) US 7 VA, class 2 power source
E F B
LF120(-S) US 7.5 VA, class 2 power source
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
A
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable LF
Electrical protection 120V actuators double insulated Valve Nominal Size Dimensions (Inches [mm])
Overload protection electronic throughout rotation Valve Body Inches DN [mm] A B C
Angle of rotation 95° B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
Spring return direction reversible with CW/CCW mounting B312(B)-B315(B) ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
Position indication visual indicator 0° to 90° B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Running time motor <40 to 75 seconds (on/off) B322-B325 1” 25 3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
spring <25 sec. @-4°F to 122°F [-20°C to 50°C]
<60 sec. @-22°F [-30°C]
Ambient temperature -22° F to 122° F [-30° C to 50° C]
Housing NEMA 2
Agency listings† cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93
Noise level (max) running <30 db(A)
spring return 62 dB(A)
Quality standard ISO 9001
LF...-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
85
LF Actuators, On/Off WAR NING
Live Electrical Components!
D uring installation,testi ng, servici
ng and troubleshooting ofthis product ,itmaybe
necessar y to w ork w it
h liv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividu alw ho has been properly trained in handli ng live electricalcom ponents
performthese tasks.Failu reto fo ll
ow allelectrical safe
ty precauti ons w hen exposed
to live electricalcom ponents could res ultin death or serious injury.
Wiring Diagrams
W047
24 VAC Transformer
Line 1 Common
Volts 2 + Hot 3
1 Provide overload protection and disconnect as required.
W049-LF-08
For end position indication, interlock control, fan startup, etc.,
4 LF24-S US and LF120-S US incorporates a built-in auxiliary switch:
1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
1 Provid
e overload protecti
on and disconnect as re
quired.
Meets cULus or UL and CSA requirements without the Actuators may be connected in parall
el.Pow erconsum pti
on
need of an electrical ground connection. 2 m ustbe observed.
WARNING Live Electrical Components! 3 Actuator may also be pow ered by 24VD C .
During installation, testing, servicing and troubleshooting of this product, it may On/Off wiring for 120 VDC
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
W048-AUX
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Auxiliary Switch
W0 47
86
LF24-3 Actuators, Floating Point
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
LF24-3 US B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-3-S US w/built-in Aux. Switch B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2.5 W
D1368
holding 1W
Transformer sizing 5 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotation
Input impedance 1000 Ω (0.6w) control inputs D C
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch
Position indication visual indicator 0° to 90°
Running time motor 150 seconds constant independent of load
spring <25 seconds @ -4°F to 122°F [-20°C to 50°C] E F B
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24-3-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
87
LF24-3 Actuators, Floating Point
Wiring Diagrams
W054
24 VA C Transfor
m er
Line
Volts
The common connection from the actuator must be connected to the orotherindividualwho has Grn 4)( +
4
been properly trained in
Hot connection of the controller. handling liveelectrical
com ponentsperfor m these
CW CCW
W055
Actuators with plenum rated cable do not have numbers on wires; 24 VA C Transfor
m er
use color coded instead. Actuators with appliance rated cable use Line
8 Volts
numbers. WAR NING 2 8
LiveElectrical Com ponents !
D urin
g installation
,testing, H ot Com
Triac singkand
servicin wtro
ith separgate transform ers
ubleshootin Blk (1)Common 4
ofthisproduct,itm aybe
Meets cULus or UL and CSA requirements without the necessar y towork withlive
electrical N otHes:
com ponents. ave
Red 2) ( + Hot
5
need
n-Offcontrolof of an(-S)
LF24-3 electrical
US ground connection. a qualifiedlicensed electrician Wh t 3)( +
orotherindivid ualwho has
been properl y trained in Actuatorsm ay be connected inparallel. Powercons
Grn (4)um+ption
WARNING Live Electrical Components! handling liveelectrical
com ponentsperfor
2
m these
m ustbe observed.
CW CCW
During installation, testing, servicing and troubleshooting of this product, it may tasks.Failuretofollow all
electricalsafety preca 8 Actuatorswithplen
utions um ratedcabledo nothavenum berson wires
LF24-3(-S) ;use color
US codesinstead.
be necessary to work with live electrical components. Have a qualified licensed electrician when exposedtolive Actuators
electrical Cowith appliance
ntroller ratedcableuse num bers.
or other individual who has been properly trained in handling live electrical components com ponentscouldresultin
The indication
ofdirection
isvalid
forswitch
position
CW.
deathorserio us injury.
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. Triac sink
W056
24 VA C Transfor
m er 24 VA C Transfor
m er
W061
24 VA C Transfor
m er 8
WAR NING 8 Actuatorswithplen
um ratedcabledo nothavenum berson wires
;use color
codesinstead.
LiveElectricalm ponents
Co ! Blk (1) Common Actuatorswithappliance
ratedcableuse num bers.
During installation
, testing,
Line
servicin
g and tro
ubleshootin g Volts Red (2) +
of this uctprod
, it
m aybe N otes:
necessary to wor
k with live a Wht (3) +
otes: electricalm ponents.
co H ave Instala
ltionSide
a qualified licensed electrician Actuatorsm ay be connected
inparallel.
Powerconsum ption
2
xx
xx
m ustbe observed.
xx
xx
xx
xx xx
or other individ
ual who has
xx
xx
xx
xx xx
Grn (4) +
xx xx
b
xx xx
xx xx
x x
2 Actbeen
uatorsproperl
handlin
y trained in
may be connected
g live electrical
i
Sw it
n para
ch
ll
CC W
D irection
el. Pow CW
erconsum pti
tion foR otationSw it
ch
on mustbe observed.
Positions
ositions
com ponents perfor
m these
tasks.Fail
ure to follow Auxiliary
a
all (3) (4)
b
switchof
CW CC W C WLF24-3CC W (-S) US CW CCW 5 The actuatorH otm ustbe connected
tothecontrol
board Comm on.
3 M ay also be pow
electrical ysafet
ere
preca
d by
utions
24 VD C . LF24-3(-S)US
when exposed to live electrical
com ponents co
uld res ult in
stop stop stop stop
8 Actuatorswithplen W055
um ratedcabledo nothavenum berson wires
;use color
codesinstead.
8 Actuat ors with plenum ra
ted cabl e do no thave n
um bers on
wires;use col or codes instead. Actuatorswithappliance
ratedcableuse num bers.
death or serio
us injury. The indication of direction
Actuatorswithappliance ra
ted cable use n
um bers.
is valid for switch position CW.
WAR NING
Live Electrical C om ponents!
N otes: D uringins talla
tion, e
tsting,servicing and S1 6
troubleshooting of h tis product,itma ybe NC
necessar y tow ork with live elec trical
S2
2 Actuatorsm ay com
betponent
elec ricianr
s.H ave a qualified
connected
o ot
herindi
inwlicensed
vidual
parallel.
Power cons
ho hasbeen
um ptionm ustbe observed.
properly rtained inhandling live electrical
S3 0° to 95
°
NO
com ponents perf orm h
tese a tsks.Failure to
3 M ay also
be powered
foll
ow all bytrical
elec 24safe
VDtyC.
precautions when
LF24-3-S US
exposed toli
resul
ve elec
tindeath orseri
tricalcom ponents could
ous injury. W051 W056
8 Actuators with um
plen
rated ble
ca do not haveum bers
n on wires
;use color codes instead.
Auxiliary switch
Actuators with appliance rated
bleuse ca
n
um bers.
800-543-9038
Forend positiUSA
on indica
tion,interl 866-805-7089
ock control,fanstartup,et
c., CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
6 LF24-3(-S )US incorporates one buil
t-inauxiliar
y switch: 1 x SPDT,
88 3A (0.5A)@2 50 VAC ,UL listed,adjustable 0° to 95
°.
LF24-SR Actuators, Proportional
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-SR US
B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LF24-SR-S US w/built-in Aux. Switch
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control proportional
Control signal 2 to 10 VDC Dimensions with 3-Way Valve
4 to 20 mA (with 500 Ω resistor)
D1368
Power consumption running 2.5 W
holding 1W
Transformer sizing 5 VA, class 2 power
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
D C
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC
Input impedance 100 kΩ
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch E F B
Position indication visual indicator
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
A
Running time motor 150 sec. independent of load (proportional)
LF
spring <25 seconds @ -4°F to 122°F [-20°C to 50°C]
<60 seconds @ -22°F [-30°C] Valve Nominal Size Dimensions (Inches [mm])
Ambient temperature -22° F to 122° F [-30° C to 50° C] Valve Body Inches DN [mm] A B C
Housing NEMA 2 B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
Agency listings cULus according to UL 873 and CAN/CSA B312(B)-B315(B) ½” 15 2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
C22.2 No. 24-93 B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Noise level (max) running <30 db(A) B322-B325 1” 25 3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
spring return 62 dB(A)
Quality standard ISO 9001
LF24-SR-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
89
LF24-SR
WAR NING
Actuators, Proportional
Live Electrical Components!
D uring installation,testing, servici
ng and troubleshooting ofthis product ,itmaybe
necessar y to w ork wit
h liv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividu alw ho has been properlytrained in handling live electricalcom ponents
performthese tasks.Failu reto fo ll
ow allelectrical safe
typrecauti ons w hen exposed
to live electricalcom ponents could res ultin death or ser
ious injury.
Wiring Diagrams
W057
4 to20 mA co
ntro
24 l oTra
VAC fLF24-SR (-S)US with2 to
nsformer 410 VDC feedback out
put
W059
5 Only connect common to neg. (–) leg of control circuits. 24 VAC Transformer 4
For end position indication, interlock control, fan startup, etc.,
Line Blk (1)Common
6 LF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A 3
Volts Red (2)
+ Hot
(1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°. Ω
Notes: 500Ω
7 The LF24-SR-S US wire 5 is white. 4 to 20A m (–)
Signal (+)
Control 1 Wht (3)Input,
Y 2 to 10V
Actuators ma
y be connected in parall
el.Pow erconsum pti
on
2
2 to and
10DCiVnputi
(–) m pedance mustbe observed.
Feedback Signal(+) Grn (5) U Output,
2 to 10V
3 Actuator may also be pow ered by 24 VD C .
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 5 To other CW CC W
actuators 2
2 to 10 VDC, up to 2 actuators may be connected in parallel. Auxiliary
Actuatorswit
switchesof
h plenum rated cable do LF24-SR
LF24-SR-S US
nothave US
num bers on
4 wires;use colorcodes instead.
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection. 4 to 20 mA control 7 The LF24-SR-SUS wire5 is w hit
e.
W058
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician WAR NING
Live ElectricalC om ponents!
or other individual who has been properly trained in handling live electrical components D uringins talla
tion, e
tsting,servicing and S1 6
perform these tasks. Failure to follow all electrical safety precautions when exposed to live N otes :
troublesh
necessar
ooting of htis product,itma ybe
y tow ork with live elec trical NC
electrical components could result in death or serious injury. com ponents.H ave a qualified licensed S2
Up
elec to ro 4otherindi
trician actuators
vidual may be connected in parallel.
who hasbeen With
2 properl
4 actuators
y rtained inhandlingwired
live elec to one
trical 500 ,S3
Ω resistora+2%
NO
shi
ft0°f
oto 95
°
comcontrol
ponents perf gnal
sihtese
orm may
a be quired.
tsks.Failure reto Power consumption
foll
ow allelec
musttoli
trical
be
safety precau
observed.
tions when
LF24-SR-S US
W 057
exposed ve elec tricalcom ponents could
resultindeath orseri ous injury.
3 Actuator may also be powered
24 VDC
by.
Auxiliary switch
Actuators with plenum rated cablevedonumbers
not ha
4 on wires
; use color codes instead.
W 059
W058
90
LF24-MFT Actuators, Multi-Function Technology
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-MFT US
B217-B220 ¾” 20 2.73” [69.3] 1.87” [47.4]
LF24-MFT-S US w/built-in Aux. Switch
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control MFT
Control signal 2 to 10 VDC Dimensions with 3-Way Valve
Power consumption running 2.5 W
D1368
holding 1W
Transformer sizing 5 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC, 0.5 mA max D C
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA
750 Ω for PWM
500 Ω for on/off and floating point
Angle of rotation 95°
E F B
Direction of rotation spring reversible with CW/CCW mounting
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24-MFT-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
91
LF24-MFT Actuators, Multi-Function Technology W irin g – PWM, t
WAR NING
Liv riac source and sin
e Electrical Components! k
D uring install
ation,testing, servici
ng and troubleshooting ofthi s product, itmaybe
necessar y to w ork withliv
e electricalcom ponents.H ave aquali fied lic
ensed electrici
an
or t oherindividu alwho has been properlytrained in handli ng live electricalcom ponents
performthese tasks.Failu reto fo ll
ow allelectrical safe
typrecauti ons when exposed
to liv
e electricalcom ponents could res ultin death or ser
ious injury.
Wiring Diagrams
W043
24 VAC/DC Transformer
W041
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or
6 Common (Sink) 24 VAC line. Line (1) Common
Volts 6
Position feedback cannot be used with Triac sink controller. (2) + Hot
7 The actuators internal common reference is not compatible. (3) Y Input
7 Position (–)
Feedback VDC (+) (5) U Output
W302
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W0
W303
92
AFRB24(-S),
AFRB24(-S), AFRX24(-S)
AFRX24(-S) Actuators,
Actuators,On/Off
On/Off
Dimensions
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRB24
Valve Nominal Size Dimensions (Inches [mm])
AFRB24-S
Valve Body Inches DN [mm] A B
AFRX24
B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
AFRX24-S
B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
Technical Data B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC ± 20% 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption running 5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 2.5 W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing 7.5 VA (class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
AFRB24... 3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
AFRX24... 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
Dimensions
1/2” conduit connector
D1370
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
Overload protection electronic throughout 0 to 95° rotation
Inc.
Control on/off
(USA),Inc.
D C
Direction of rotation spring reversible with CW/CCW mounting
Aircontrols (USA),
A
(0° is full spring return position)
Manual override 5 mm hex crank (3/16" Allen), supplied AFRB, AFRX
change. ©
to change.
Ambient temperature -22°F to 122°F [-30°C to 50°C] Valve Nominal Size Dimensions (Inches [mm])
Storage temperature -40°F to 176°F [-40°C to 80°C] Valve Body Inches DN [mm] A B C
Housing NEMA 2, IP54, Enclosure Type2
Subject to
Agency listings † cULus according. to UL60730-1A/-2-14, B317-B321 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
CAN/CSA E60730-1:02, CE according. to B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
2004/108/EC & 2006/95/EC B329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
P10419 -- 09/13
Noise level <50dB(A) motor @ 75 seconds B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
<62dB(A) spring return B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
O50905
AFRB24-S, AFRX24-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038
800-543-9038 USA
USA 866-805-7089
866-805-7089 CANADA
CANADA 203-791-8396 LATIN AMERICA
203-791-8396 / CARIBBEAN
LATIN AMERICA
93
97
AFRB24(-S), AFRX24(-S) Actuators, On/Off
Wiring Diagrams
W063_AFB(X)
1 24 VAC Transformer
W064_AFB(X)_-S
+10°, one is adjustable 10° to 90°.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFB24-S
AFX24-S
03/12 --Subject
P10419 -- 09/13
O50905 change.©
Subjecttotochange. Aircontrols(USA),
BelimoAircontrols
©Belimo Inc.
(USA),Inc.
800-543-9038 USA
800-543-9038 USA 866-805-7089 CANADA
866-805-7089 CANADA 203-791-8396 LATIN LATIN
203-791-8396 AMERICA / CARIBBEAN
AMERICA
94
98
AFRBUP(-S), AFRXUP(-S) Actuators,
AFRBUP(-S), AFRXUP(-S) Actuators, On/Off
On/Off
Dimensions
Dimensions
D1369
D C
E F B
A
AFRB, AFRX
Models Valve Nominal Size Dimensions (Inches [mm])
AFRBUP Valve Body Inches DN [mm] A B
AFRBUP-S B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
AFRXUP B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
AFRXUP-S B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Technical Data B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power supply 24 to 240 VAC -20% / +10%, 50/60 Hz
24 to 125 VDC +10% B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Power consumption running 7 W
B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
holding 3.5 W
B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Transformer sizing 7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC
18 VA @ 240 VAC
Electrical connection
AFRBUP... 3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance Dimensions
cables with 1/2” conduit connectors
D1370
AFRXUP... 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
D C
16 ft. [5m] appliance cables, with or without
O50905 - 03/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRBUP-S, AFRXUP-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
95
AFRBUP(-S),
AFRBUP(-S),AFRXUP(-S)
AFRXUP(-S) Actuators,
Actuators, On/Off
On/Off
Wiring Diagrams
W066_AFB(X)UP
1 Provide overload protection and disconnect as required.
W067_AFB(X)UP-S
Meets cULus requirements without the need of an electrical ground
connection. Wht
Blk
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFBUP-S
AFXUP-S
Inc.
(USA),Inc.
Auxiliary Switches for AFRBUP-S, AFRXUP-S
O50905--09/13
P10419 Subjecttotochange.
03/12- -Subject Aircontrols(USA),
BelimoAircontrols
change.©©Belimo
800-543-9038USA
800-543-9038 USA 866-805-7089CANADA
866-805-7089 CANADA 203-791-8396
203-791-8396 LATIN AMERICA
LATIN AMERICA / CARIBBEAN
96100
AFRB24-SR, AFRX24-SR
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal AFRB24-SR, AFRX24-SR
Dimensions
D1369
Dimensions (Inches [mm])
D C
AFR_DIM
E F B
A
AFRB, AFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Technical Data
B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
Power supply 24 VAC ±20%, 50/60 Hz
B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
24 VDC +20% / -10%
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
Power consumption running 5.5 W
B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
holding 3 W
B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
Transformer sizing 8.5 VA (class 2 power source)
B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Electrical connection
B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
AFRB... 3 ft, 18 GA appliance cable, 1/2" conduit
B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
connector
B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
-S models: two 3 ft, 18 gauge appliance cables
B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
with 1/2” conduit connectors
AFX... 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA
appliance or plenum cables, with or without 1/2”
conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables, with or without 1/2"
conduit connectors Dimensions
Overload protection electronic throughout 0 to 95° rotation
D1370
Operating range Y 2 to 10 VDC, 4 to 20mA
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
Feedback output U 2 to 10 VDC (max. 0.5 mA)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038
800-543-9038USA
USA 866-805-7089
866-805-7089 CANADA
CANADA 203-791-8396
203-791-8396 LATIN AMERICA/ CARIBBEAN
LATIN AMERICA / CARIBBEAN
57 97
AFRB24-SR, AFRX24-SR
AFRB24-SR, AFRX24-SR Proportional, Spring Return, 24 V, for 2 to 10 VDC to 4 to 20 mA Control Signal
Accessories WARNING
G Live Electrical Components!
AV 8-25 Shaft extension During installation, testing, servicing and troubleshooting of this product, it may be
IND-AFB Damper position indicator necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
KH-AFB Crank arm
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
K7-2 Universal clamp for up to 1.05” dia jackshafts nents could result in death or serious injury.
TF-CC US Conduit fitting
Tool-06 8mm and 10 mm wrench
W068_AFB(X)24-SR
1 24 VAC Transformer
ZG-100 Universal mounting bracket
ZG-101 Universal mounting bracket
Line 1 Common
ZG-118 Mounting bracket for Barber Colman® MA 3../4.., Honeywell® 3
Volts
Mod III or IV or Johnson® Series 100 replacement or new crank 2 + Hot
arm type installations 3 Y1 Input, 2 to 10V
ZG-AFB Crank arm adaptor kit Control Signal (–)
ZG-AFB118 Crank arm adaptor kit 2 to 10 VDC (+)
ZS-100 Weather shield (metal) 5 U Output 2 to 10V
ZS-150 Weather shield (polycarbonate)
AFB24-SR, AFB24-SR-S
ZS-260 Explosion-proof housing AFX24-SR, AFX24-SR-S
2
ZS-300 NEMA 4X housing
NOTE: When using AFRB24-SR, AFRB24-SR-S, AFRX24-SR and AFRX24-SR-S actuators, only use
2 to 10 VDC control of AFRB24-SR and AFRX24-SR
accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
W069_AFB(X)24-SR
Typical Specification
Spring return control damper actuators shall be direct coupled type which require no
crank arm and linkage and be capable of direct mounting to a jackshaft up to a 1.05”
diameter. The actuator must provide proportional damper control in response to a 2 to
10 VDC or, with the addition of a 500Ω resistor, a 4 to 20 mA control input from an
electronic controller or positioner. The actuators must be designed so that they may be
used for either clockwise or counterclockwise fail-safe operation. Actuators shall use
a brushless DC motor controlled by a microprocessor and be protected from overload
at all angles of rotation. Run time shall be constant, and independent of torque. A 2 to
10 VDC feedback signal shall be provided for position feedback. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001 AFB24-SR, AFB24-SR-S
International Quality Control Standards. Actuators shall be as manufactured by Belimo. AFX24-SR, AFX24-SR-S
ATTENTION:
ATTENTION AFRB24-SR(-S)
AFRB24 AFRX24 SR( S) cannott bbe ttandem
SR( S) andd AFRX24-SR(-S) d mounted
t d
on the same damper or valve shaft. Only On/Off and MFT AF models can be used
for tandem mount applications.
800-543-9038USA
800-543-9038 USA 866-805-7089 CANADA
866-805-7089 CANADA 203-791-8396LATIN
203-791-8396 LATIN AMERICA
AMERICA/ /CARIBBEAN
CARIBBEAN
98 58
AFRX Actuators, Multi-Function Technology
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRX24-MFT
AFRX24-MFT-S Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Technical Data B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
Control MFT B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
Control signal 2 to 10 VDC, 4 to 20 mA (default) B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
variable (VDC, PWM, floating point, on/off) B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC, +/- 20%, 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC, +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption† running 7.5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 3W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing† 10 VA (Class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA ap- B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
pliance or plenum cables, with or without 1/2"
conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or 16 ft.
[5m] appliance cables with or without 1/2”
conduit connectors
Overload protection electronic throughout 0 to 90° rotation
Feedback output* 2 to 10 VDC, 0.5 mA max (variable) Dimensions
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
D1370
500 Ω for 4 to 20 mA
1500 Ω for on/off and floating point
Angle of rotation 95°
Direction of rotation* spring reversible with CW/CCW mounting
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
D C
motor reversible with built-in switch
Position indication visual indicator 0° to 95°(0° is spring return
position)
Manual override 5 mm hex crank (3/16” Allen), supplied
Running time motor* 150 seconds (default),
variable (70 to 220 seconds) E F B
spring <20 sec @ -4°F to 122°F [-20°C to 50°C] A
Ambient temperature -22° F to 122° F [-30° C to 50° C] AFRB, AFRX
Housing NEMA 2, IP54, Enclosure Type 2
Agency listings cULus according. To UL60730-1A/-2-14, Valve Nominal Size Dimensions (Inches [mm])
CAN/CSA E60730- 1:02, CE according. To Valve Body Inches DN [mm] A B C
2004/108/EC & 2006/95/EC B312-B316 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
Noise level <40dB(A) motor @ 150 seconds, run time B317-B321 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
dependent B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
<62dB(A)
62dB(A) spring return B329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
Quality standard ISO 9001 B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
† Programmed for 70 sec motor runtime. At 150 sec motor run time, transformer sizing is B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
8.5 VA and power consumption is 6 W running/3 W holding.
* Variable when configured with MFT options
‡ Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control
Pollution Degree 3.
AFRX24-MFT-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10° to 90°
99
AFRX Actuators, Multi-Function Technology
Dimensions
W600_AFB_AFX
AFR_LGCCV
D
I
C
G AFB24-MFT-S
AFX24-MFT-S
B
E F A Auxiliary Switches for AFRX24-MFT
AFRB, AFRX
W399_08
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
A B C
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
VDC/4-20 mA
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
100
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRX24-MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Technical Data B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]
Control MFT B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
Control signal 0 to 135 Ω Honeywell Electronic Series 90, B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
0 to 135 Ω input B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC, +/- 20%, 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC, +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption† running 7.5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 3W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing† 10 VA (Class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
plenum cables, with or without 1/2" conduit
connector
Overload protection electronic throughout 0 to 90° rotation
Feedback output* 2 to 10 VDC, 0.5 mA max (variable)
Angle of rotation 95°
Direction of rotation* spring reversible with CW/CCW mounting
Dimensions
motor reversible with built-in switch
Position indication visual indicator 0° to 95°(0° is spring return
D1370
position)
Manual override 5 mm hex crank (3/16” Allen), supplied
Running time motor* 150 seconds (default),
variable (70 to 220 seconds)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
D C
spring <20 sec @ -4°F to 122°F [-20°C to 50°C]
Ambient temperature -22° F to 122° F [-30° C to 50° C]
Housing NEMA 2, IP54, Enclosure Type 2
Agency listings cULus according. To UL60730-1A/-2-14,
CAN/CSA E60730- 1:02, CE according. To
2004/108/EC & 2006/95/EC E F B
A
Noise level <40dB(A) motor @ 150 seconds, run time
dependent AFRB, AFRX
<62dB(A)
62dB(A) spring return
Quality standard ISO 9001 Valve Nominal Size Dimensions (Inches [mm])
† Programmed for 70 sec motor runtime. At 150 sec motor run time, transformer sizing is Valve Body Inches DN [mm] A B C
8.5 VA and power consumption is 6 W running/3 W holding. B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
* Variable when configured with MFT options B317-B321 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
‡ Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
Pollution Degree 3. B329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
101
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
O verride ofA F24-M FT95 U S
Dimensions
W015_AFRX
D1378
Switch A Switch B r Position Dampe
Damper Open
Dampe
D The direction ofrotation sw itch is setso thatthe failsafe position and the
position ofthe dam peris closed w ith no signalatw ire R .
I
24 VA C Transform er
C 1
Line 1 C om m on,B lk
Volts 2 + H ot,R ed 3
A 4
G 3 W ,W ht
135 4 R ,W ht
B B
E F A
5 B ,W ht
6 ‘U 5’O utput2-10 VD C
AFRB, AFRX A FR X24-M FT95
24 VA C Transform er
1
Nominal Top Line 1 C om m on,B lk
Valve Flange Face-to-Face
Pipe Flange Height Volts 2 + H ot,R ed 3
Body Diameter Length
Size Design 4
A
A B C W 3 W ,W ht
Line R 4 R ,W ht
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4] Volts B
B 5 B ,W ht
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1] 2 C ontroller 6 ‘U 5’O utput2-10 VD C
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9] A F24-M FT95 U S used w ith AaFRSer
X24-i
Mes 90
FT95
controllerand a Series 90 low lim itcontrol
Override of AFRX24-MFT95
Wiring Diagrams 1 Provide overload protection and disconnectas required.
W016
2 ActVA
24 uatCorTr
s and
ansfcont
orm rer
ollerm usthave separate transform ers.
1 C onsultcontrollerinstruction data form ore detailed
3
Line installation inform ation. 1 C om m on,B lk
1 Provide overload protection and disconnect as required. Vol4ts To reverse controlrotation,use the
2 + H ot,R
rever 3
edsw itch.
sing
4
2 Actuators and controller must have separate transformers. 2
W W B R 3 W ,W ht
4 R ,W ht
Consult controller instruction data for more detailed installation Series 90 R
3 information.
C ontroller
B 5 B ,W ht
W017
1 Pr
kits may also be used. 24ovi
deC over
VA loadorpr
Transf m ot
erection and disconnectas required.
W015
1
2 Actuators and controllerm usthave separate transform ers.
Line C onsultcontrollerinstruction data1form
C om m on,B lk
WARNING Live Electrical Components! 3
Volts installation inform ation.
ore detailed
2 + H ot,R ed 3
During installation, testing, servicing and troubleshooting of this product, it may
4
be necessary to work with live electrical components. Have a qualified licensed electrician To reverse controlrotation,use the reversing sw itch.
4
2
or other individual who has been properly trained in handling live electrical components W 3 W ,W ht
perform these tasks. Failure to follow all electrical safety precautions when exposed to live R 4 R ,W ht
Series 90
electrical components could result in death or serious injury. C ontroller
B R W B 5 B ,W ht
6 ‘U 5’O utput2-10 VD C
Series 90 high lim itcontrol-280
A FR X24-M FT95
W016
102
W017
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
AFRX24-MFT95
W018_AFRX
W020_AFRX
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
103
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
D1363
D C
E F B
Models A
AFRB24 N4 Basic Version ARB N4, ARX N4, NRB N4, NRX N4
AFRB24 N4H Basic Version w/built in heater Valve Nominal Size Dimensions (Inches [mm])
AFRB24-S N4 Basic Version w/built-in aux. switch Valve Body Inches DN [mm] A B
AFRB24-S N4H Basic Version w/built-in aux. switch & heater B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
AFRX24 N4 Flexible Version B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
AFRX24-S N4 Flexible Version w/built-in aux. switch B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
AFRX24 N4H Flexible Version w/built in heater B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
AFRX24-S N4H Flexible Version aux. switch & heater
Technical Data
Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC +20% / -10%
Power consumption running 5 W / heater 25 W
holding 2.5 W
Transformer sizing 7.5 VA (class 2 power source) / heater 25 VA
Electrical connection 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
AFR... N4 cable, with or without 1/2” conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or D C
16 ft [5m] appliance cables with or without 1/2”
conduit connectors
104
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
W063_AFRBX24_N4
1 24 VAC Transformer
Line 1 Common
Volts 3
2 + Hot
AFRB24 N4
AFRB24 N4H 2
AFRB24-S N4
AFRB24-S N4H
AFRX24 N4
AFRX24-S N4
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off wiring
W064_AFRBX24_S_N4
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
2 must be observed.
AFRB24-S N4
AFRB24-S N4H
AFRX24-S N4
AFRX24-S N4H
Auxiliary Switches
GK-AF-NF N4H 24V heater
105
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA 4, On/Off, Spring Return, 24 to 240 VAC
D1363
D C
E F B
Models A
AFRBUP N4 Basic Version
AFRBUP-S N4 Basic Version w/built-in aux. switch ARB N4, ARX N4, NRB N4, NRX N4
AFRBUP N4H Basic Version w/built in heater Valve Nominal Size Dimensions (Inches [mm])
AFRBUP-S N4H Basic Version w/built-in aux. switch & heater Valve Body Inches DN [mm] A B
AFRXUP N4 Flexible Version B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
AFRXUP-S N4 Flexible Version w/built-in aux. switch B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
AFRXUP N4H Flexible Version w/built in heater B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
AFRXUP-S N4H Flexible Version w/built-in aux. switch & heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Power supply 24...240 VAC -20% / +10%, 50/60 Hz
24...125 VDC ±10%
Dimensions with 3-Way Valve1363
Power consumption running 7 W / heater 25 W
D1364
holding 3.5 W
Transformer sizing 7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC / heater 25 VA @120 VAC
18 VA @ 240 VAC
Electrical connection
AFRBUP... N4 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
AFRXUP... N4 cable, with or without 1/2” conduit connector D C
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with or without 1/2”
conduit connectors
heater (N4H) terminal block, 18-16 GA
Overload protection electronic throughout 0 to 95° rotation
Control on/off E F B
Torque 180 in-lb [20 Nm] minimum A
106
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA
A 4, On/Off, Spring Return, 24 to 240 VAC
Accessories
W066_AFRBUP_N4
Tool-06 8mm and 10 mm wrench
43442-00001 Gland (needed for additional wires)
11097-00001 Gasket for Gland (needed for additional wires)
NOTE: When using AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H, AFRXUP N4,
AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H actuators, only use accessories listed on this
page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
W067_AFRBUP-S_N4
shall be as manufactured by Belimo.
connection.
Auxiliary Switches
NEMA 4A Heater
107
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
D1363
Models
AFRB24-MFT N4 Basic Version
AFRB24-MFT-S N4 Basic Version w/built-in aux. switch D C
AFRB24-MFT N4H Basic Version w/built in heater
AFRB24-MFT-S N4H Basic Version w/built-in aux. switch & heater
AFRX24-MFT N4 Flexible Version
AFRX24-MFT-S N4 Flexible Version w/built-in aux. switch
AFRX24-MFT N4H Flexible Version w/built in heater E F B
AFRX24-MFT-S N4H Flexible Version w/built in aux. switch & heater A
Technical Data ARB N4, ARX N4, NRB N4, NRX N4
Power supply 24 VAC, +/- 20%, 50/60 Hz Valve Nominal Size Dimensions (Inches [mm])
24 VDC, +20% / -10% Valve Body Inches DN [mm] A B
Power running 7.5 W / heater 25 W
B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
consumption holding 3W
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
Transformer sizing 10 VA (Class 2 power source) / heater 25 VA
B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
Electrical connection 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance cables,
with 1/2” conduit connector B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
AFRB... N4
AFRX... N4 -S models: two 3 ft [1m], 10 ft [3m] or B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
16 ft [5m] appliance cables with 1/2” conduit connectors
heater (N4H) terminal block, 26-16 GA
Overload protection electronic throughout 0 to 95° rotation Dimensions with 3-Way Valve1363
Operating range Y* 2 to 10 VDC, 4 to 20 mA (default)
D1364
variable (VDC, PWM, floating point, on/off)
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and on/off control
Feedback output U* 2 to 10 VDC, 0.5 mA max
Torque minimum 180 in-lb (20 Nm)
D C
Direction of spring reversible with cw/ccw mounting inside housing
rotation* motor reversible with built-in switch
Mechanical 95° (adjustable with mechanical end stop, 35° to 95°)
angle of rotation*
Running time motor* 150 seconds (default), variable (70 to 220 seconds)
spring <20 sec @ -4°F to 122°F [-20°C to 50°C]; E F B
<60 sec @ -22°F [-30°C] A
108
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
Accessories
W399_08
Tool-06 8mm and 10 mm wrench
43442-00001 Gland (needed for additional wires)
11097-00001 Gasket for Gland (needed for additional wires)
NOTE: When using AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S
N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H actuators, only
use accessories listed on this page. For actuator wiring information and diagrams, refer to
Belimo Wiring Guide.
Typical Specification
The actuator must provide proportional damper control in response to a 2 to 10 VDC or, with
the addition of a 500Ω resistor, a 4 to 20 mA control input from an electronic controller or
positioner. The actuators must be designed so that they may be used for either clockwise or
counterclockwise fail-safe operation. Actuators shall use a brushless DC motor controlled by
a microprocessor and be protected from overload at all angles of rotation. Run time shall be
VDC/4-20 mA
constant, and independent of torque. A 2 to 10 VDC feedback signal shall be provided for
W399_08
position feedback. Actuators shall be cULus Approved and have a 5 year warranty, and be
manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as
manufactured by Belimo.
Wiring Diagrams
W399_08
Position feedback cannot be used with Triac sink controller.
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source) or the Com-
5 mon (sink) 24 VAC line.
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator must be con-
9 nected to the hot connection of the controller.
On/Off Control
Meets UL requirements without the need of an electrical ground
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
connection.
W399_08
The ZG-R01 500 Ω resistor may be used.
NEMA 4 Heater
AFB24-MFT-S N4
AFRB24-MFT-S N4H
AFR$X24-MFT-S N4
AFRX24-MFT-S N4H
Auxiliary Switches
109
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
Dimensions
D1378
D
I
C
B
E F A
AFRB24-S, AFRX24-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
110
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
Wiring Diagrams
W063_AFB(X)
1 24 VAC Transformer
W064_AFB(X)_-S
adjustable 10° to 90°. 1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
2 must be observed.
Meets cULus requirements without the need of an electrical ground
connection. 3 Actuator may also be powered by 24VDC.
AFB24-S
AFX24-S
W063
111
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
Dimensions
D1378
D
I
C
B
E F A
AFRBUP-S, AFRXUP-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
112
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
A
Wiring Diagrams
W066_AFB(X)UP
1 Provide overload protection and disconnect as required.
W067_AFB(X)UP-S
Meets cULus requirements without the need of an electrical ground
connection.
Wht
Blk
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFBUP-S
AFXUP-S
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
113
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
Dimensions
D1379
D
I C
B
E F A
GKRB, GKRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GKRB24-3-5-14
A B C
B6400 4” [100] 9.00" [228.6] 8.30” [210.8] 9.30” [235.9]
Technical Data B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
F05
Control on/off, floating point B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 3 W
Transformer sizing 18 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100 kΩ (0.1mA), 500 Ω, 1500 Ω (floating
point, on/off)
Angle of rotation max. 95°, adjustable with mechanical stop
Direction of rotation reversible with switch
114
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
L1
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
Note
There are no special restrictions on installation if 1 2 3 5 be necessary to work with live electrical components. Have a qualified licensed
the supply and data cable are routed separately. A electrician or other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all electrical safety
Cable colors: Cross section Max. cable length Example for DC precautions when exposed to live electrical components could result in death or
1 = black
2 = red
L2
~ Ltott = L1 + L2 serious injury.
/
T
AC DC
3 = white
5 = orange 0.75 mm2 <30 m <5 m 1 m (L 1) + 4 m (L 2)
1.00 mm2 <40 m <8 m 1 m (L 1) + 7 m (L 2)
A = Actuator 1.50 mm2 <70 m <12 m 1 m (L 1) + 11 m (L 2)
W399_10
C = Control unit 2.50 mm2 <100 m <20 m 1 m (L 1) + 19 m (L 2)
L1 = Belimo connecting cable, 1 m (4 x 0.75 mm2)
L2 = Customer cable A = Actuator
Ltot = Maximum cable length C = Control unit
L1 = Belimo connecting cable, 1 m (4 x 0.75 mm2)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
W399_10
115
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
Dimensions
D1379
D
I C
B
E F A
GKRB, GKRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
Models A B C
GKRX24-MFT-5-14 B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control 2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 3 W
Transformer sizing 21 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC, 0.5 mA max, VDC variable
116
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
PWM
WARNING Live Electrical Components!
W399_08
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical components could result in death or
serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
W399_08
117
Accessories
ZR-EXT-01, CCV and PICCV Valve Neck Extension Kit
Application
The ZR-EXT-01 can be used with most CCV’s* and PICCV in order to
achieve a large clearance over the pipe. The Extension Kit will provide
D165
an additional 2” of space between the top of the valve and the base of
the actuator. bracket is made from aluminum and is not intended as a
thermal block.
Technical Data
Extension Height 2"
Total Weight 0.7 lb
Material
Extension Housing Aluminum - Anodized
Shaft Stainless Steel
Threaded Hardware Stainless Steel
Bearing Oilite® Bearing
Retaining Clip Stainless Steel
1.65" 1.65"
118
Accessories
ZS-CCV... New Characterized Control Valve Weather Shield
Application
The ZS-CCV... weather shield provides moderate protection for valves
which are mounted outdoors. This product is designed as a water tight
enclosure. The housing allows easy mounting over the actuator, while
allowing easy viewing of the actuator in operation. Weather shield for
PICCV/CCV to provide protection for actuators in outdoor applications.
Specifications
Cover PETG with UV resistant smoke tint
Perimeter Gasket Silicon Rubber
Rubber Gasket Silicon Rubber
Spring Clips Stainless Steel
Temperature limitations: -22˚F to 122˚F (-30˚C to 50˚C)
Plate (ZS-CCV-100) Aluminum
Plate Galvaneal w/black powder coat
L W H
16.25” [413] 8.75” [222] 4.5” [114]
Parts List
Cover including Rubber Perimeter Gasket, Rubber Gasket
Back Plate
Anti-Rotation Post with screw and lock washer
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve Gasket
Assorted Cap plugs for unused holes
119
Accessories
Auxiliary Switches S1A, S2A
For non-spring return direct-coupled actuators
Application
The S1A and S2A auxiliary switches are used to indicate when a
desired position of a valve is reached or to interface additional
controls for a specific control sequence.
Operation
The S1A and S2A auxiliary switches are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams. The
switching points can be set over the full scale of 0 to 1 simply by
adjusting the slotted discs.
Types
S1A 1 SPDT 3 ft, 18 GA Appliance Cable
S1A/300 1 SPDT 6 ft, 18 GA Appliance Cable
S1A/500 1 SPDT 10 ft, 18 GA Appliance Cable
Wiring Diagram
Mounting Instructions
1. Press down the manual override button and rotate the actuator
fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.
120
Accessories
Feedback Potentiometer P...A
For the non-spring return direct-coupled actuators
Application
The P…A feedback potentiometers are used with LR and AR actuators
to provide a resistive signal which varies with valve position.
The P…A units are applied with commercial proportional temperature
controllers to provide feedback of the valve position, or with electric or
electronic meters to provide position indication. The signal can also be
used as a positioner for parallel operation of multiple actuators.
Operation
The P…A feedback potentiometers are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams.
Types
P140A Feedback Potentiometer 140 Ω
P200A Feedback Potentiometer 200 Ω
P500A Feedback Potentiometer 500 Ω
P1000A Feedback Potentiometer 1000 Ω
P2800A Feedback Potentiometer 2800 Ω
P5000A Feedback Potentiometer 5000 Ω
P10000A Feedback Potentiometer 10000 Ω
1. Press down the manual override button and rotate the Wiring Diagram
actuator fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.
Mounting Instructions
121
Wiring Accessories
Protective Terminal Cover
For the non-spring return direct-coupled actuators
Application
Belimo non-spring return actuators with terminal strips are can be con-
verted from NEMA 1/IP20 to NEMA 2/IP54 using the protective termi-
nal cover ZS-T.
Terminal
Cover Conduit
Fitting
Rubber
Seals
122
MFT Standard Configuration
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10028 A28 0.0 to 10.0 VDC 0.0 to 10.0 VDC 100 100 Manual
P-10031 A31 0.0 to 4.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 Manual
P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 Manual
P-20001 W01 0.59 to 2.93 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20002 W02 0.02 to 5.00 sec. 2.0 to 10.0 VDC 150 100 Manual
PWM
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual
P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual
Floating Point
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual
P-40001 J01 On/Off 2.0 to 10.0 VDC 75 100 Manual
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual
On/Off
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.
Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes.
Note: Most popular configurations available at no additional cost.
Note: If the configuration needed is not listed, please fill in pg. 112 or call Belimo Customer Service at 800-543-9038.
Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT configuration number.
123
MFT Programming Codes, Flexible Products
PRODUCTS
Base Actuator Angle of
MODEL Control Input Feedback Running Time Power Supply VA Rating Weight (lb)
Codes Rotation/Stroke
LRX24-3 LR000 On/Off, Floating Point — 95 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-SR LR030 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 24 VAC/DC 3 1.08
45 in-lb [5 Nm]
LRX24-PC LRXX0† 0-20 V Phasecut 2-10 VDC 95 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-MFT LR100 2-10 VDC (Default) 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-MFT95 LRXX0† 0 to 135 Ohm 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08
LRX120-3 LR060 On/Off, Floating Point — 95 (Default) 95 deg 120-240 VAC 3 1.08
LRX120-SR LR450 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 120-240 VAC 3 1.08
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual
P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual
Floating Point
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual
P-40001 J01 On/Off None 75 100 Manual
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual
On/Off
124
Custom MFT Configuration Order Form
FAX: USA Toll Free 1-800-228-8283
#1 Select an Actuator
(use one sheet for each unique actuator/configuration)
Name __________________________________________________________________________________________________
Quantity Quantity
AF24-MFT US ________ AMX24-MFT ________
Company ______________________________________________________________________________________________
AF24-MFT-S US ________ AMX24-MFTX1 ________
NF24-MFT US ________ NMX24-MFT ________
Address________________________________________________________________________________________________
LF24-MFT US ________ NMX24-MFTX1 ________
LF24-MFT-S US ________ LMX24-MFT ________
City ________________________________________________State ________________Zip __________________________
AF24-MFT95 US ________ LMX24-MFTX1 ________
NV24-MFT US ________ LRX24-MFT ________
Phone _____________________________________________Fax ________________________________________________
NVF24-MFT US ________ GMX24-MFT95 ________
NVF24-MFT-E US ________ AMX24-MFT95 ________
Email ______________________________________________
NVFD24-MFT US ________ NMX24-MFT95 ________
NVFD24-MFT-E US ________ LMX24-MFT95 ________
FIELD LABELING: LBL-MFT
GMX24-MFT ________ LHX24-MFT ________
GMX24-MFTX1 ________ LUX24-MFT ________ Custom configuration labels required
1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet.
(-S=Auxiliary Switch) Includes configuration code and wiring labels.
Stop Start
Stop .
5 Override control and Min. (min. position) = % (0...100%) (beginning of working range) default 0
electronic angle of ZS (intermediate position) = % (0...100%) (0% = Min.; 100% = Max.) default 50
rotation limiting Max. (max. position) = % (0...100%) (end of working range) default 100
125