Professional Documents
Culture Documents
Boys Hostel Building. GS - 50-200 - 15
Boys Hostel Building. GS - 50-200 - 15
Requested data
1 Pump type End Suction Volute Pump Fluid Water
2 Number of pumps / Reserve 1 / 0 Liquid temperature °C 20
3 Flow m³/h 94.3 Kin. viscosity mm²/s 1.005
4 Head m 35 Vapour pressure kPa 2.34
5 Geodetic head m 0 PH value
6 Inlet pressure (pin) kPa 0 Density kg/m³ 998.3
7 Available system NPSH Solids Weight % 0
8 Ambient temperature °C 20
Pump
9 Pump Name GS 50-200 /15 Frequency Hz 50
10 Design End Suction Volute Pump Installation type with ISO base, motor
11 Manufacturer EBARA Impeller Max. mm 219
12 Speed 1/min 2900 Diameter Designed mm 178
13 No. of Stage 1 Min. mm 171
Materials
22 Casing FC250
23 Impeller CAC406
24 Shaft SUS431eq.
25 Case wear ring CAC406
26 O-ring NBR
27 Mechanical Seal SiC/Carbon/FKM
Motor
28 Manufacturer EBARA Standard Insulation class F
29 Type 160M_15_3_380 Phases 3~
30 Specific design TEFC/B3/AESV1S / 50 Hz / Pole pairs 1 Frame size 160M
31 Rated power kW 15 Weight kg 120
32 Number of poles 2 Electric voltage V 380
33 Speed 1/min 2940 Electric current A 28.2
34 Degree of protection IP55
35
Remarks
Performance Curve Pump Name GS 50-200 /15
10
η /% Hydraulic efficiency
72.85
60
40
20
0
NPSH / m NPSH-values
5.5
5
4.5
4.434
4
3.5
3
2.5
2
1.5
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 94.66
95 100 105 110 115 Q / m³/h
Dimensions Pump name GS 50-200 /15