TECHNICAL DATA
Ratings Indicators
NX233A Overcurrent Relay User's Guide
Rated current In ......................5 A Rev M0 (04/19)
Auxiliary supply .......................Green LED indicator
Frequency ...............................50 Hz or 60 Hz Pick up ....................................Red LED indicator
Burden ....................................< 0.3 VA at In Trip ..........................................7 segment LED and 2. LIGHT INDICATORS
Thermal withstand....................4 x In continuous Red LED indicators The indicators display the status of the system as follow:
Auxiliary Supply Environmental conditions Indicator
NX233A-240A.........................198~265 VAC Temperature ...............................-10ºC to 55ºC Aux l> l>> FUNC DT Status
NX233A-110A..........................94~127 VAC Humidity .....................................5% to 95% non-condensing 0 0 0 0 0 No Auxiliary power supply.
Supply frequency ....................50 Hz or 60 Hz 1 0 0 X X Normal condition, no tripping.
VA rating ..................................3 VA typical Mechanical 1 1 0 X X Low-set overcurrent triggered,
Mounting..................................... Panel mounting time delay countdown started.
Setting Ranges Dimension (mm) ......................... 96(w) x 96(h) x 110(d) 1 0 1 X X High-set overcurrent triggered,
Low-set setting I>.....................0.10 - 10.00 A (2%-200%)
Enclosure protection................... IP54 at the panel time delay countdown started.
Time multiplier kt> ...................0.01 - 1.00
Low-set definite time t> ...........0.00 - 100 s Approximate weight .................... 0.8 kg 1 B 0 B B Low-set tripped,
High-set setting I>> .................0.50 - 100 A (10%-2000%) FUNC LED indicates tripping source,
High-set definite time t>>.........0.00 - 100 s DT LEDs show tripped value.
(0.00 - 1.00, step 0.01; 1.00-10.0, step 0.10; 1 0 B B B High-set tripped,
7. CONNECTION DIAGRAMS FUNC LED indicates tripping source,
10.0-100, step 0.5)
a) Overcurrent Relay DT LEDs show tripped value.
Accuracy 1 X X 1 B Programming mode.
NX233A
Protection thresholds ...............± 5% Table 1: System Status
Time delay.................................± 5% with a start/
1 = ON 0 = OFF X= don’t care, not blinking
mimimum of 50ms start/ B = blinking DT = DATA FUNC = FUNCTION
Outputs
R1 R2
Rated voltage ..........................250 VAC
Continuous carry .....................5A (cos = 1.0)
5
Expected electrical life ............10 operations / Indicator
6 time delay
Expected mechanical life ........5 x10 operations L1 FUNCTION DP DATA
L2
1 off L1 load current
L3
2 off L2 load current
N
3 off L3 load current
b) Overcurrent Relay and Earth fault relay (3 phase 4 wire system) t blink Last trip elapsed time
NX232A 1 blink Previous L1 tripped current
NX233A
2 blink Previous L2 tripped current
3 blink Previous L3 tripped current
1. DESCRIPTION 4 off Low-set current setting
R1 R2 R1 R2 5 off Low-set time multiplier/ delay
The NX233A is a microprocessor based numerical setting
overcurrent relay. It uses fundamental frequency 6 off High-set current setting
current measurement for excellent harmonic current 7 off High-set time delay setting
rejection. The relay consists of independent low-set 8 off Soft switch setting
and high-set elements. The high-set element can
be disabled by the user. The time current Table 2: FUNCTION Code
characteristics of the low-set elements are definite
time or five selectable IDMT curves. The high-set Auto Scroll
element is a definite time or instantaneous relay. Under normal operating condition, the 4-digit LED will
The 4-digit panel display on the NX233A allows the auto scroll through function 1 to 3 to show current
8. CASE DIMENSIONS display of the present load current; recorded fault readings. To toggle auto scroll mode, press
110mm
100mm
90mm current for last tripping; and all settings of the relay. “UP”+”DOWN” simultaneously for 2 seconds.
96 mm