IO Summary Illustrate

1. Station code is omitted before instrument position number;


Type Description Quantity 2, The figures is the actual number of I/O, manufacturer for
PCS-AI Analog input of two-wire 420 Ma Amine PCS system 63 template configuration should be not less than 20% of the
PCS-AO Analog output of two-wire 420 Ma Amine PCS system 11 allowance;
PCS-CIO RS485 serial port, Modbus communication 9 3, Terminal, and lightning protection terminal and relay shall be
PCS-DI Passive dry contact, PCS system switch input 58 not less than 20% of the allowance;
PCS-DO 24VDC, 2A dry contact, PCS system switch output 7 4, Analog active input template should use channel segregation
PCS-DO2 24VDC, 15W active, PCS system switch output 10 or differential input, should be separated from passive input
PCS-DO220Relay contact, 220VACCPA5A DCS system switch output 6
template configuration.

164

RENTAL EARLY Project code: AT2204DD


Designer
PRODUCTION Monitoring data sheet of PCS
Proofreader File code: IO-0000IN01-02
FACILITIES(EPF) FOR RBG control system
Auditor CADD code: IO-0000IN01-02-0.XLS
BLOCK I FIELD
ShenDing_Pic Major: Automatic Control Page 1 of 17 Date:2023.04.12 Stage: Detailed design Version 0
Automatic Control
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning
Safety
Other requirements Input/Output
Tag Number Uses Range Unit
Setpoints High High low
relay protectio
barrier handle record trend accumulate report Type
Notes
High
low low n forms
Wellhead section
Remote temperature
TIT-0101 0~100 ℃ √ √ √ √ PCS-AI
transmission of wellhead natural
gas pipeline
EZIO-0101 Wellhead natural gas ESDV- √ √ PCS-DI
0101 fully open indication
EZIC-0101 Wellhead natural gas ESDV- 1 √ √ PCS-DI
0101 fully close indication
Export valve group part
PIT-0502 Pressure detection and remote 0~900 psig 575 √ √ √ √ PCS-AI
transmission of export pipelines
PV-0501 Product gas outlet regulator √ √ √ √ PCS-AO
valve
PVT-0501 Electric control valve PV-0501 √ √ √ √ PCS-AI
valve position feedback
PIT-0503 Pressure detection and remote 0~900 psig 575 √ √ √ √ PCS-AI
transmission of export pipelines
PV-0502 Product gas outlet regulator √ √ √ √ PCS-AO
valve
PVT-0502 Electric control valve PV-0502 575 √ √ √ √ PCS-AI
valve position feedback
FIT-0501 Flow detection and remote 2.5~30 m2/h √ √ √ √ √ PCS-CIO
transmission of export pipelines
FIT-0502 Flow detection and remote 2.5~30 m2/h √ √ √ √ √ PCS-CIO
transmission of export pipelines
Project code: AT2204DD
Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 2 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting
Lightning Safety
Other requirements Input/Output
Tag Number Uses Range Unit Setpoints High low
relay
protection barrier handle record trend accumulat report Type
Notes
High low
High low e forms
EZIO-0501 Product gas outlet pipeline 1 √ √ PCS-DI
ESDV-0501 fully open
EZIC-0501 Product gas outlet pipeline 1 1 √ √ PCS-DI
ESDV-0501 fully close
EZIO-0502 Product gas outlet pipeline 2 √ √ PCS-DI
ESDV-0502 fully open
EZIC-0502 Product gas outlet pipeline 2 1 √ √ PCS-DI
ESDV-0502 fully close
BZIO-0501 Export metering inlet pipeline 1 √ √ PCS-DI
BDV-0501 fully open indication
Export metering inlet pipeline
BZIC-0501 √ √ PCS-DI
BDV-0501 fully close
indication

Membrane separation pry PE-0401


The measurement range, alarm values, and control settings of the instrument can be found in the monitoring data sheet and IO table of the pry manufacturer
MOD-0401 Electric heater on-site control √ √ √ √ PCS-CIO
cabinet RS485 signal
PIT-0401X Membrane inlet pressure √ √ √ √ PCS-AI
PV-0401X Control of electric control √ √ √ √ PCS-AO
valve for secondary
membrane leakage gas
PVT-0401X Electric control valve PV- √ √ √ √ PCS-AI
0401X valve position feedback
PDIT-0401X Agglomeration separator √ √ √ √ PCS-AI
FT-0401X differential pressure
Project code: AT2204DD
Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 3 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Alarm value setting Lightning Other requirements
Control Safety Input/Output
Tag Number Uses Range Unit
Setpoints High low relay protectio
barrier accumulat report
Type
Notes
High low n
handle record trend
High low e forms
Agglomeration separator
PDIT-0402X √ √ √ √ PCS-AI
FT-0402X differential
pressure
LIT-0401X Aggregation separator √ √ √ √ PCS-AI
FT-0401X liquid level 1
LIT-0402X Aggregation separator √ √ √ √ PCS-AI
FT-0401X liquid level 2

FIT-0401X Secondary membrane √ √ √ √ PCS-AI


residual gas flow rate
FIT-0402X Primary membrane residual √ √ √ √ PCS-AI
gas flow rate

TT-0403X Outlet pipeline temperature √ √ √ √ PCS-AI


of electric heater H-0401X

TT-0404X Outlet pipeline temperature √ √ √ √ PCS-AI


of heat exchanger E-0401X
From on-
TIT-0401AX Electric heater H-0401X √ √ √ √ PCS-AI
site control
furnace temperature 1
boxon-
From
TIT-0401BX Electric heater H-0401X √ √ √ √ PCS-AI
site control
furnace temperature 2
boxon-
From
TIT-0402X Outlet temperature of electric √ √ √ √ PCS-AI
site control
heater H-0401X
boxon-
From
YC-0403X Electric heater SCR √ √ √ √ PCS-AO
site control
remote control
box

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 4 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control Alarm value setting Other requirements
Lightning Safety Input/Output
Tag Number Uses Range Unit Setpoint High low
relay
protection barrier accumulat report Type
Notes
s High low handle record trend
High low e forms

XSO-0401X Electric on-off valve XV- √ √ PCS-DI


0401X open in place

XSC-0401X Electric on-off valve XV- 1 √ √ PCS-DI


0401X closed in place

YSO-0401X XV-0401X Control of √ √ √ PCS-DO2


Electric on-off Valve
XV-0401X closing
YSC-0401X √ √ √ PCS-DO2
Control of Electric on-off
Valve
Remote allowable
YLP1-H0401X √ √ PCS-DI From the field
start/stop of electric
control box
heater
YLP2-H0401X Electric heater allows √ √ PCS-DI From the field
PID adjustment remotely control box

YA-H0401X Comprehensive fault √ √ PCS-DI From the field


alarm of electric heater control box

YL1-H0401X Electric heater in √ √ PCS-DI From the field


operation control box

YL2-H0401X Electric heater in √ √ PCS-DI From the field


operation control box

YL3-H0401X Electric heater in √ √ PCS-DI From the field


operation control box

YR-H0401X Remote start of electric √ √ √ PCS-DO From the field


heater control box

YS-H0401X Remote stop of electric √ √ √ PCS-DO From the field


heater control box
Project code: AT2204DD

Monitoring data sheet of PCS control system File code: IO-0000IN01-02


Page 5 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning Safety Other requirements
Input/Outp
Tag Number Uses Range Unit Setpoints High High low
relay protectio barrie accumulat report ut Type Notes
low n r handle record trend
High low e forms
Gas-liquid separation PE-0201
The measuring range, alarm value and control setting value of the instrument shall be subject to the manufacturer's monitoring data table and IO table.
PIT-0201X Vmur0201X pressure 0~700 psig √ √ √ √ PCS-AI
test
Detection of
LGT-0201X 100~700 mm 400 600 200 √ √ √ √ PCS-AI
condensate liquid level
of Vmurl 0201
FIT-0201X Natural gas flow 4~10 MMSCFD 10 4 √ √ √ √ PCS-AI
measurement
FIT-0202X Condensate flow 200 50 √ √ √ √ PCS-AI
measurement
LV-0201X Vmur0201 condensate √ √ √ √ PCS-AI
level control √ √ √ √ PCS-AO

Desulphurization pry PE-0301


PIT-0301X Natural gas pressure 0~700 psig √ √ √ √ PCS-AI
detection
PDIT-0301X V-0302X differential 0~20 psig 14.5 √ √ √ √ PCS-AI
pressure detection

LGT-0301X V-0301X condensate 100~700 mm 500 100 √ √ √ √ PCS-AI


level detection

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 6 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning Safety
Other requirements Input/Output
Tag Number Uses Range Unit Setpoints High High low relay
protection barrier handle record accumulat report Type
Notes
High
low low
trend
e forms
Condensate stabilization skid PE-0601
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer
PIT-0604X V-0601X condensate 0~100 psig 30 √ √ √ √ PCS-AI
pressure detection
PIT-0607X T-0601X pressure 0~100 psig 15 20 10 √ √ √ √ PCS-AI
detection
PDIT-0601X T-0601X differential 0~20 psig 14.5 √ √ √ √ PCS-AI
pressure detection
TT-0608X T-0601X temperature 0~400 ℉ √ √ √ √ PCS-AI
detection
TT-0609X T-0601X temperature 0~200 ℉ 240 220 √ √ √ √ PCS-AI
detection
TT-0610X E-0602X temperature 0~400 ℉ 230 250 √ √ √ √ AI To the electric
detection control cabinet
LGT-0601X V-0601X condensate 50~450 mm 280 80 √ √ √ √ PCS-AI
level control
LDIT-0601X V-0601X condensate 50~450 mm 300 400 200 √ √ √ √ PCS-AI
boundary control
LGT-0602X T-0601X condensate 100~500 mm 300 400 100 √ √ √ √ PCS-AI
level control
LS-0601X V-0601X condensate √ √ PCS-DI
level control
LS-0603X V-0601X condensate √ √ PCS-DI
level control
Project code: AT2204DD
Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 7 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control Alarm value setting Other requirements
Lightning Safety Input/Outpu
Tag Number Uses Range Unit Setpoint High low
relay
protection barrier accumulat report t Type
Notes
s High
High low low
handle record trend
e forms
FIT-0601X T-0601X incoming liquid √ √ √ √ PCS-AI
flow measurement
LDV-0601X V-0601X boundary √ √ √ √ PCS-AI
control
√ √ √ √ PCS-AO
Valve position feedback

LV-0601X V-0601X condensate √ √ √ √ PCS-AI


level control
√ √ √ √ PCS-AO
Valve position feedback

PV-0601X V-0601X pressure √ √ √ √ PCS-AI


control
√ √ √ √ PCS-AO
Valve position feedback

PV-0602X T-0601X pressure √ √ √ √ PCS-AI


control
√ √ √ √ PCS-AO
Valve position feedback

LV-0602X T-0601X condensate √ √ √ √ PCS-AI


level control
√ √ √ √ PCS-AO
Valve position feedback

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 8 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control Alarm value setting Lightning Other requirements
Safety Input/Output
Tag Number Uses Range Unit Setpoint High low
relay protectio
barrier accumula repor Type
Notes
s High
High low low
n handle record trend
te t
Stable condensate storage tank skid PE-0701
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry
PT-0701X V-0701AX pressure remote 0~15 psig 0.3 -0.05 √ √ √ √ PCS-AI
transmission
LGT-0701AX V-0701AX liquid level remote 100~2400 mm 2300 300 200 √ √ √ √ PCS-AI
transmission
PT-0702X V-0701BX pressure remote 0~15 psig 0.3 -0.05 √ √ √ √ PCS-AI
transmission
LGT-0701BX V-0701BX liquid level remote 100~2400 mm 2300 300 200 √ √ √ √ PCS-AI
transmission
HSO-0701AX Remote start of condensate loading √ √ √ PCS-DO220
pump P-0701AX
HSC-0701AX Remote stop of condensate loading √ √ √ PCS-DO220
pump P-0701AX
SA-0701AX-1 Condensate loading pump √ √ PCS-DI
P-0701AX manual state
SA-0701AX-2 Automatic status of condensate √ √ PCS-DI
loading pump P-0701AX
Operation status of motor for
KM-0701AX √ √ PCS-DI
condensate loading pump P-
0701AX

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 9 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control Alarm value setting Lightning
Safety
Other requirements Input/Out
Tag Number Uses Range Unit Setpoint High low
relay protectio
barrier handle accumulat report put Type Notes
s High
High low low
n record trend
e forms
KH-0701AX Condensate loading pump √ √ PCS-DI
P-0701AX motor fault alarm
HSO-0701BX Remote start of condensate √ √ √ PCS-DO220

loading pump P-0701BX


HSC-0701BX Remote stop of condensate √ √ √ PCS-DO220

loading pump P-0701BX


SA-0701BX-1 Condensate loading pump √ √ PCS-DI
P-0701BX manual state
Automatic status of
SA-0701BX-2 √ √ PCS-DI
condensate loading pump P-
0701BX
KM-0701BX Operation status of condensate √ √ PCS-DI
loading pump P-0701BX motor
KH-0701BX Condensate loading pump √ √ PCS-DI
P-0701BX motor fault alarm

Fuel Gas Skid PE-0801


The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer
PIT-0802X V-0801X inlet pressure 0~100 psig 40 √ √ √ √ PCS-AI
remote transmission
LGT-0801X V-0801X liquid level remote mm 500 100 √ √ √ √ PCS-AI
transmission
FIT-0801X V-V-0801X outlet flow √ √ √ √ √ PCS-CIO
remote transmission

Project code: AT2204DD

Monitoring data sheet of PCS control system File code: IO-0000IN01-02


Page 10 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control Alarm value setting Other requirements
Lightning Safety Input/Outp
Tag Number Uses Range Unit Setpoint High low
relay
protection barrier handle record accumulat report ut Type
Notes
s High
High low low
trend
e forms
Vent separation skid PE-0901
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer
LGT-0901X Remote transmission of liquid level in 0.1~2.4 m 2.3 0.3 0.2 √ √ √ √ PCS-AI
vent knockout tank V-0901X
PIT-P-0901X P-0901X shaft seal system pressure PCS-AI
remote transmission
HSO-0901X Remote start of bottom pump √ √ √ PCS-DO220
P-0901X of vent knockout tank
HSC-0901X Remote stop of the bottom pump √ √ √ PCS-DO220
P-0901X of the vent knockout tank
SA-0901X-1 Condensate loading pump P-0901X √ √ PCS-DI
manual
SA-0901X-2 Automatic status of condensate √ √ PCS-DI
loading pump P-0901X
KM-0901X Operation status of the bottom pump √ √ PCS-DI
P-0901X of the vent knockout tank
KH-0901X Fault alarm of the bottom pump 1 √ √ PCS-DI
P-0901X of the vent knockout tank
Methanol filling skid PE-1001
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer

PT-1001 Remote transmission of outlet pipeline psig 1350 1300 √ √ √ √ PCS-AI


pressure of methanol injection pump

LGT-1001 V-1001X liquid level remote 0~600 mm 500 100 √ √ √ √ PCS-AI


transmission
Project code: AT2204DD
Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 11 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning Safety
Other requirements Input/Outpu
Tag Number Uses Range Unit Setpoints High low
relay
protection barrier accumulat repor t Type
Notes
High low handle record trend
High low e t
Release flare
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer

MOD-0901 Release flare sled RS485 √ √ √ √ PCS-CIO


signal
H/A-0901 √ √ PCS-DI
Manual/automatic signal

TI-0901 Temperature status √ √ PCS-DI


signal
FI-0901 Status signal of vent √ √ PCS-DI
pipeline flow meter
RI-0901 √ √ PCS-DI
Bursting disc status

XA-0901 Flame extinguishing √ √ PCS-DI


alarm signal
XA-0902 √ √ PCS-DI
Fault signal

HSO-0901 √ √ PCS-DO
Torch ignition
Remote valve opening
HSO-0902 √ √ PCS-DO
signal (permanent light
valve)
L/R-0901 Local/remote control √ √ PCS-DO
switching signal

Project code: AT2204DD

Monitoring data sheet of PCS control system File code: IO-0000IN01-02


Page 12 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Alarm value setting Lightning Other requirements
Control Safety Input/Outpu
Tag Number Uses Range Unit
Setpoints High low
relay protectio
barrier accumulat report t Type
Notes
High low n handle record trend
High low e forms
Production water pump skid WT-0201
MOD-0201 Production water pump skid √ √ √ √ PCS-CIO
RS485 signal
Remote transmission of
PIT-WT0101AX 0~100 psig √ √ √ √ PCS-AI
produced water outlet
pressure
PIT-WT0101BX Remote transmission of 0~100 psig √ √ √ √ PCS-AI
produced water outlet
Condensate stabilization skid heat exchanger E-0602X control cabinet
The measurement range, alarm value, and control setting value of the instrument shall be based on the monitoring data sheet or IO table of the pry manufacturer
From the
YL-E-0602X Operating status of heat √ √ PCS-DI
field control
exchanger boxthe
From
YA1-E-0602X Heat exchanger √ √ PCS-DI
field control
overtemperature alarm boxthe
From
YA2-E-0602X Heat exchanger failure √ √ PCS-DI
field control
alarm boxthe
From
YR-E-0602X Remote start of heat √ √ √ PCS-DO
field control
exchanger box
From the
YS-E-0602X Remote stop of heat √ √ √ PCS-DO
field control
exchanger box
From the
TT-E-0602X Heat exchanger medium √ √ √ √ PCS-AI
field control
temperature signal box
From the
YVT-E-0602X √ √ √ √ PCS-AI
Power feedback signal field control
box
From the
YC-E-0602X √ √ √ √ PCS-AO
Power control signal field control
box
Project code: AT2204DD
Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 13 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning Safety
Other requirements Input/Outpu
Tag Number Uses Range Unit Setpoints High High low
relay
protection barrier accumulat report t Type
Notes
High
low low
handle record trend
e forms
XL-0101B Operation status of extraction √ √ PCS-DI
water pump P-WT0201B

XA-0101B Production water pump 1 √ √ PCS-DI


P-WT0201B fault alarm
Fire protection part
The process information for the fire protection part is incomplete, and the following IO points are for reference only and not the final version
PIT-FW-0101A Fire cooling water pump 0~2.5 Mpa √ √ √ √ PCS-AI
outlet pressure detection
PIT-FW-0101B Fire cooling water pump 0~2.5 Mpa √ √ √ √ PCS-AI
outlet pressure detection
PIT-FW-0102A Fire cooling water pump 0~2.5 Mpa √ √ √ √ PCS-AI
outlet pressure detection
PIT-FW-0102B Fire cooling water pump 0~2.5 Mpa √ √ √ √ PCS-AI
outlet pressure detection
PIT-FW-0103 0~2.5 Mpa √ √ √ √ PCS-AI
Fire return pressure detection

Pressure detection of the


PIT-FW-0104 0~2.5 Mpa √ √ √ √ PCS-AI
outlet pipe of the fire
stabilizing pump
LIT-FW0101 Remote transmission of liquid 0~1.4 m 1.3 1.1 0.5 0.3 √ √ √ √ PCS-AI
level in public water tanks
Stop the water source well pump when the liquid level is too high, and start the water source well pump when the liquid level is too low

Project code: AT2204DD

Monitoring data sheet of PCS control system File code: IO-0000IN01-02


Page 14 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Safet
Control
Alarm value setting Lightning
y
Other requirements Input/Outp
Tag Number Uses Range Unit Setpoints High High low
relay protectio
barrie handle record accumulat report ut Type
Notes
High
low low
n trend
e forms
r
Remote transmission of
LIT-FW0102A 0~2.8 m 2.6 2.5 0.3 √ √ √ √ PCS-AI
liquid level in fire water
tank A
LIT-FW0102B Remote transmission of 0~2.8 m 2.6 2.5 0.3 √ √ √ √ PCS-AI
liquid level in fire water
HSO-P0101 Remote start of water √ √ √ PCS-DO2
source well pump P-0101
HSC-P0101 Remote stop of water √ √ √ PCS-DO2
source well pump P-0101
XI-P0101 Operation status of water √ √ PCS-DI
source well pump P-0101
XB-P0101 Water source well pump 1 √ √ PCS-DI
P-0101 fault alarm
Remote start of fire
HSO-0201 `` √ √ √ PCS-DO2
stabilizing pump P-FW-
0201
Remote shutdown of fire
HSC-0201 √ √ √ PCS-DO2
stabilizing pump P-FW-
Operation0201
status of fire
XL-0201 √ √ PCS-DI
stabilizing pump P-FW-
0201
XA-0201 Fire stabilized pressure 1 √ √ PCS-DI
pump P-FW-0201 fault
FIT-FW-0101 Remote transmission of 5.43~181 m3/h √ √ √ √ √ PCS-CIO
fire reflux flow detection
FIT-FW-0102 Remote transmission of water 0.87~28.9 m3/h √ √ √ √ √ PCS-CIO
source well pump flow detection

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 15 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Lightning
Safety
Other requirements Input/Outpu
Tag Number Uses Range Unit
Setpoints High High low
relay protectio
barrier handle accumulat report t Type
Notes
High
low low
n record trend
e forms
HSO-Y0001 Remote start of gas √ √ √ PCS-DO2
generator room fan unit
HSC-Y0001 Remote shutdown of gas √ √ √ PCS-DO2
generator room fan unit
HSO-Y0002 Remote start of diesel √ √ √ PCS-DO2
generator room fan unit
HSC-Y0002 Remote shutdown of fan unit √ √ √ PCS-DO2
in diesel generator room
XI-Y2001 Operation status of fan in √ √ PCS-DI
gas generator room
XA-Y2001 Gas generator room fan √ √ PCS-DI
failure alarm
XI-Y2002 Operation status of fan in √ √ PCS-DI
diesel generator room
XA-Y2002 Diesel generator room fan √ √ PCS-DI
fault alarm
GAH-0001 High alarm for combustible 1 √ √ PCS-DI
gas detection at the wellhead
High alarm for combustible
GAH-0002 1 √ √ PCS-DI
gas detection in the device
High alarm area
for combustible
GAH-0003 1 √ √ PCS-DI
gas detection in the device
High alarm area
for combustible
GAH-0004 1 √ √ PCS-DI
gas detection in the device
area
Project code: AT2204DD

Monitoring data sheet of PCS control system File code: IO-0000IN01-02


Page 16 of 17
This document may not be disseminated to third parties without the written permission of LKEC.
Control
Alarm value setting Other requirements Input/Outpu
Lightning Safety
Tag Number Uses Range Unit Setpoints High low
relay
protection barrier handle accumulat report t Type
Notes
High low record trend
High low e forms
GAH-0005 High alarm for combustible gas 1 √ √ PCS-DI
detection in the device area
GAH-0006 High alarm for combustible gas 1 √ √ PCS-DI
detection in the device area
GAH-0007 High alarm for combustible gas 1 √ √ PCS-DI
detection in the device area
GAH-0008 High alarm for combustible gas 1 √ √ PCS-DI
detection in the device area
GAH-0009 High alarm for combustible gas 1 √ √ PCS-DI
detection in the device area
AAH-0001 High alarm for wellhead 1 √ √ PCS-DI
hydrogen sulfide detection
AAH-0002 High alarm for hydrogen sulfide 1 √ √ PCS-DI
detection in the device area
AAH-0003 High alarm for hydrogen sulfide 1 √ √ PCS-DI
detection in the device area
GU-0001 Combustible gas detection √ √ PCS-DI
public fault alarm
MOD-0001 √ √ PCS-CIO
UPS data monitoring

MOD-0002 Distribution panel data √ √ PCS-CIO


monitoring
FA-0001 √ √ PCS-CIO
Fire alarm controller alarm signal

Project code: AT2204DD


Monitoring data sheet of PCS control system File code: IO-0000IN01-02
Page 17 of 17