Yard to install
Yard to install
Field power cable
+F01
+F01
PdT
-PDT01
578-GC0015
578-PDT0015
Heater cable to the gland on AHU -32W9
F-RFOU 0,6/1kV P1/P8 3x10 mm²
-EH02
-EH01
27 kW
27 kW
+EH02
+EH01
3x400 VAC
3x400 VAC
Heater cable to the gland on AHU -121W11
F-RFOU (i) 150/250 V S1/S5 1x2x0.75 mm²
TS
TS
-TS01
-TS01
+EH02
+EH01
=LIR
=LIR
+EH02
+EH01
Pre Heater
Pre Heater
578-FE0016B
578-FE0016A
TS
TS
-TS02
-TS02
+EH02
+EH01
578-FE0016B 578-FE0016B
578-FE0016A 578-FE0016A
3way valve located at outside on chilled water line -162W8
F-RFOU 0,6/1 kV P5/P12 3x1,5 mm²
-Y01
-Y02
+XAM01
Y
Shut off valve located on chilled water line -162W5
F-RFOU 0,6/1 kV P5/P12 3x1,5 mm²
Y
-Y01
+XAM01 578-GJ0017A
-Y01
dx
dx
-135W2
578-HV0020
Shut off valve located on chilled water line F-RFOU (i) 150/250 V S1/S5 1x3x0.75 mm²
Y
Y
Motor heater cable to the gland on AHU -161W11
+XAM01 578-GJ0017A
F-RFOU 0,6/1 kV P5/P12 2x1,5 mm²
+XAM02 578-GJ0017B
Control cable to gland at switch -122W15
F-RFOU (i) 150/250 V S1/S5 1x2x0.75 mm²
yard's power to gland at switch, then swtich to motor. Switch to motor is connected -31W7
F-RFOU 0,6/1kV P1/P8 3x2.5 mm²
AHU AC1
578-GA0010
-161W5
Motor heater cable to the gland on AHU F-RFOU 0,6/1 kV P5/P12 2x1,5 mm²
-EH01
-EH01
0,1 kW
0,1 kW
+XAM02
+XAM01
-121W15
1x230 VAC
1x230 VAC
Control cable to gland at switch F-RFOU (i) 150/250 V S1/S5 1x2x0.75 mm²
-IS01
+XAM02
-IS01
+XAM01
yard's power to gland at switch, then swtich to motor. Switch to motor is-31W3
connected
F-RFOU 0,6/1kV P1/P8 3x2.5 mm²
-M01
2,5 kW
+XAM02
-M01
2,5 kW
3x400 VAC
+XAM01
578-DE0011B
3x400 VAC
578-DE0011A
-161W10
Overheat protection cable to the gland on AHU F-RFOU (i) 150/250 V S1/S5 1x2x0.75 mm²
=LIR
=LIR
+XAM02
+XAM01 -121W4
PDS located outside (cable to the instrument) F-RFOU (c) 150/250 V S2/S6 2x2x0.75 mm²
PS
PS
-PDS01
-PDS01
+XAM02
+XAM01
578-PDS0015
578-PDS0014
B
A
-161W7
Y
-D01
Shut off damper F-RFOU 0,6/1 kV P5/P12 2x1,5 mm²
+XAM02
Y
-D01
578-GS0013B
Control/Starter Panel
+XAM01
578-GS0013A
-TT01
578-TE0019
-21W10
F-RFOU 0,6/1kV P1/P8 3x2,5 mm²
Supply 3x440V Imax=12,5A
-101W11
F-RFOU 0,6/1kV P1/P8 2x2,5 mm²
UPS Supply 1 230Vac
-101W14
F-RFOU 0,6/1kV P1/P8 2x2,5 mm²
UPS Supply 2 230Vac
-121W17
F-RFOU (c) 150/250 V S2/S6 2x2x0.75 mm²
General Alarm
DRC PANEL
Control/Starter Panel Local Instrumentation Room =LIR +CSP001 578-EC0001
Used Symbols
M Y
DAMPER MIST ELIMINATOR NON RETURN VALVE FILTER HEATER ISOLATOR SWITCH
M
+TAG
-TAG
Yard TAG
PRESSURE SWITCH PRESSURE TRANSMITTER PRESSURE DIFFERENTIAL TEMPERATURE SWITCH TEMPERATURE FLOW SWITCH
TRANSMITTER TRANSMITTER
PS PT PdT TS TT FS