Professional Documents
Culture Documents
General
The steam pressure is compared (in summing point) with the set point. The result is a deviation signal
which gives either a ”Power demand” signal or a dump signal.
Gain control
The PID controller has a variable gain, which is a function of the steam pressure deviation. When the
deviation is zero or small, the gain is low. If deviation increases, the gain will also increase in order to
compensate.
Stop increase
When “power demand” signal reach a certain level, the master controller is prevented to increase
further (due to the multiplication factor, see “H”).
If one burner is on, the master signal will stop on 33%. At this value, the burner demand is 100% and
maximum.
If two burners are on, the master signal will stop on 67%. At this value, the burner demand is 100% and
maximum.
If three burners are on, the master signal will continue to 100%. At this value, the burner demand is
100% and maximum.
Boiler balance
The power demand signal is normally distributed equally to the two boilers.
The operator can balance the boiler loads on the HMI by +/-10%.
A value from -10% to +10% can be entered. A positive value will increase the load on PORT boiler
If 2% is entered, the PORT will increase 2% and STBD will decrease 2%, i e there will be a diff of 4%
5-ACC.doc Page 3(11)
2009-12-05
Gain control
The power demand from master controller is multiplied with a factor depending on the number of burners in
operation. A burner is operation if burner shut off valves (oil or gas) are opened and Flame ON.
The purpose of this is that when starting or stopping burners, the load on the boiler will remain the same.
1 burner in operation: Multiplying factor is 3.0
2 burners in operation: Multiplying factor is 1.5
3 burners in operation: Multiplying factor is 1.0
Fuel limiter
The demand signal is prevented to increase if actual air flow is insufficient, i e vanes fully open. When
inlet vanes are 99% open, burner demand will stop to increase, but is free to reduce.
At 97% vanes signal, burner demand will be released and can increase again
General
The fuel oil flow is compared (in summing point) with the fuel oil modified set point.
The modified set point is obtained from the following:
o Burner demand
o Hot restart rate
o Cold start rate
o Ignition pressure
o Pressure at start of subsequent burner
Hot restart
In case of boiler trip, the steam pressure will be raised automatically, after restart of boiler, to set point
with the preset ”Hot restart rate”, if the following conditions are true:
1. Heavy fuel oil selected (i e not Diesel oil)
2. Fuel oil control in auto
3. Combustion air control in auto
4. Steam pressure (transmitter for this boiler) >15 bar
5. Steam pressure (transmitter for this boiler) deviation >5 bar
When steam pressure reaches set point within 0.5 bar, the firing will switch to demand signal.
Should the boiler pressure not have fallen below 5 bar under the set point, the firing will follow the
demand signal after the boiler is started.
Note: The hot start rate setting is a value that sets a fixed fuel oil pressure.
It will not take into account the rate of steam pressure rise or rate of steam temperature rise!
Cold start
After start of cold boiler, the steam pressure will be raised automatically with the preset ”Cold start
rate” if the following conditions are true:
1. Fuel oil control in auto
2. Comb. air control in auto
3. Steam pressure <15 bar
When steam pressure reaches 15 bar, the firing will switch to ”Hot restart” and firing will continue as
described above.
NB: The firing will continue in the cold start mode as long as "Diesel oil" is selected as fuel
(DIESEL OIL button is activated and the corresponding lamp is lit)
Note: The cold start rate setting is a value that sets a fixed fuel oil pressure.
It will not take into account the rate of steam pressure rise or rate of steam temperature rise!
5-ACC.doc Page 5(11)
2009-12-05
Control deviation
The algebraic sum of modified set point and measured fuel oil flow is the control deviation, which is the
PID-controller input.
General
The fuel gas flow is compared (in summing point) with the fuel gas demand signal (Burner demand).
Control deviation
The algebraic sum of modified set point and fuel gas flow is the control deviation, which is the PID-
controller input.
Stop increase
If the measured signal (differential pressure drop) is above 95%, alarm is given and PID-controller is
prevented from further increase.
General
The combustion air flow is compared (in summing point) with the combustion air modified set point. The
modified set point is obtained from the following:
o Demand signal
o Ignition setting
o Furnace purge setting
Air/Fuel ratio
This value is set on the HMI. It corrects for the specific calorific value for fuel oil
Feed forward
(To ensure air is sufficient at increasing fuel oil.)
The burner flow demand and the fuel oil flow are connected to derivating circuits. Gain and time
constants are individually set.
The highest of the outputs from the derivating circuits is selected and then connected to feed forward
input of the controller.
Control deviation
The algebraic sum of actual Air flow and the setpoint is the control deviation, which is the PID-controller
input.
Combustion trim
Drawing no. 461.21.228
General
The combustion trim is to control the content of oxygen in the smoke gas leaving the boiler.
HMI
See picture "Combustion air" / ”Combustion trim”
Load limit
Enter a value of the desired boiler load at which Combustion trim can start. It can start only when boiler
load is above this value.
Control deviation
The algebraic sum of measured oxygen and oxygen set point, is the control deviation, which is the PID-
controller input.
Control output
The output from the controller is 0-100%. This is converted to a factor ranging from 0.8 (0%) to
1.2(100%).
When the control is off, this factor is locked at 1.0
Multiplier
The “Combustion trim factor” is adjusting the air/fuel ratio in this multiplier
Oxygen analyzer
The O2 probe must be heated to 800ºC for correct measuring
A thermocouple (type "R") in the probe is measuring the temperature
The heating is controlled by means of controlling a static relay in the analyzer interface box.
General
The drum level is compared (in summing point) with the set point. The result is a deviation signal which
gives a signal to the PI-controller.
Transmitter selector
The two transmitters that are closest to each other are selected
The average of these two is used as the resulting level signal.
NOTE: Open the transmitter selection box on the HMI to un-select a faulty transmitter!
5-ACC.doc Page 10(11)
2009-12-05
Linearizer
The steam flow signal signal is linearized to correspond to the flow characteristics of the control valve.
PI controller
The controller is a “Feed forward controller”, i e the feed forward signal (steam flow) is the main
component in the controller. The level signal is correcting in order to keep the level on setpoint.
Level comparators
The water level is continuously compared to six different limits:
Extra High level +230mm Main Engine trip + Feed water motor valve close
Very High level +200mm Main Engine will slow down
High high level +150mm Alarm
Low Low level -150mm Alarm
Very Low level -180mm Main Engine slow down
Extra Low level -230mm Boiler Trip
NOTE: When the motorized feed water valve has been closed, it must be manually reset (on the valve)
before it can open again!
5-ACC.doc Page 11(11)
2009-12-05
General
The superheated steam temperature is compared (in summing point) with the set point. The result is a
deviation signal which gives a signal to the PID-controller.
PID controller
The controller is a "Cascade" controller and consists of
Primary controller. This is comparing the main setpoint (510°C) with the final temperature.
The output from this controller is the setpoint for the Secondary controller
Secondary controller. This is comparing the intermediate setpoint with the intermediate
temperature (de-superheater outlet). The outlet from the controller (0-100%) is connected to the
steam temperature control valve (F.W. spray valve)
Control output
The control output is 4-20mA to the water spray valve