Report :

DESIGN CALCULATION REPORT


Design Calculation Report for Curtain Wall of Tower Area

Project :

No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom
Table of Contents

1.0 INTRODUCTION & SYNOPSIS 1

2 DESIGN CRITERIA 3

3 LOAD COMPUTATION & APPLICATION 5

4 GLASS PANEL CHECKING 7

5 CLADDING & FRAMING CHECK 34

6 TRANSOM CHECK 47

7 MULLION CHECK 86

8 BRACKET CHECKING 99

9 EMBED CHECKING 115


No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Introduction & Design Synopsis

1.0 INTRODUCTION & SYNOPSIS

Introduction

This structural calculation will cover the following coponents;

a) Unitized Curtainwall system


b) Cladding feautre system

1.1 Design Synopsis

Unitized Curtainwall System


The System is made up of Glazing, in ching vison panels are IGU (HS+Air+FT) & spandrel panels is monolethic (HS). The
framing will be aluminum extrusion of varrying sections to fit both fixed and openable glass panels. The spandrel part of
the system will also have aluminum cladding stsem incorportaed to the UCW framing.

Cladding System
The vertical cladding, that covers the vertical main structure will be indpendent from the UCW. This will have own framing
and fixing to the parent structure

1
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Introduction & Design Synopsis

1.2 Load Path

Unitized Curtainwall System


Dead Load & Wind Load

Glass Panel / Cladding Aluminum Framing Brackets & Cast-in Channels

Existing RC Structure

Cladding Sytem System


Dead Load & Wind Load

Cladding Aluminum Framing Brackets & Post Drill Anchors

Existing RC Structure

2
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Design Criteria

2 DESIGN CRITERIA

Code of Practice & References


Code of Practice on Wind Effects in Hong Kong - 2004
Code of Practice for Dead and Imposed Loads - 2011
Hong Kong Building (Construction) Regulation
Code of Practice for the Structural use of concrete -2013
British Standard 8118 : 1991 - Structural Use of Aluminum
British Standard 5950-1 : 2000 - Structural Use of Steel

Material Properties
Glass
ρg = 2,560 kg/m3 ; Density
Eg = 70,000 MPa ; Modulus of Elasticity
νg = 0.2 ; Poisson's Ratio
σga = 12.5 MPa ; Allowable Stress , Annealed
σgh = 25.0 MPa ; Allowable Stress , Heat Strengthened
σgt = 50.0 MPa ; Allowable Stress ,Tempered

Aluminum
ρa = 2,710 kg/m3 ; Density
Ea = 70,000 MPa ; Modulus of Elasticity
νa = 0.3 ; Poisson's Ratio
Limiting Stresses, MPa
Alloy Bending, po Shear, pv Axial, pa
6063-T6 (H9-TE) 160 95 175
6061-T6 (H20-TF) 240 145 260

Mild Steel
ρms = 7,850 kg/m3 ; Density
ρms = 205,000 MPa ; Modulus of Elasticity
ρms = 0.3 ; Poisson's Ratio
Ys = 275 MPa ; Minimum Yield Strength
Us = 430 MPa ; Ultimate Tensile Strength
py = 275 MPa ; Design Strength
pv = 159 MPa ; Design Shear Strength
pb = 460 MPa ; Design Bearing Strength

Stainless Steel
Es = 205,000 MPa ; Modulus of Elasticity
ρss = 8,000 kg/m3 ; Density
ρss = 205,000 MPa ; Modulus of Elasticity
ρss = 0.3 ; Poisson's Ratio
Ys = 205 MPa ; Minimum Yield Strength
Us = 500 MPa ; Ultimate Tensile Strength
py = 205 MPa ; Design Strength
pv = 123 MPa ; Design Shear Strength
pb = 460 MPa ; Design Bearing Strength

3
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Design Criteria

Stainless Steel Fastener, Grade A4-70


Ysb = 450 MPa ; Minimum Yield Strength
Usb = 700 MPa ; Ultimate Tensile Strength
pvb = 311 MPa ; Shear Strength
ptb = 374 MPa ; Tension Strength
pbb = 828 MPa ; Bearing Strength

Weld
pw = 220 MPa ; Design Strength

Structural Sealant
pts = 138 kPa ; Allowable Tensile Strength

Deflection Limits
Curtain Wall System
Aluminum framing members supporting aluminum & glass panel;
Perpendicular to the plane of the wall = L/180 or 20 mm, whichever is less
Parallel to the plane of the wall = L/250 or 3 mm, whichever is less
Steel framing members supporting aluminum & glass panel;
Perpendicular to the plane of the wall = L/240
Parallel to the plane of the wall = 3 mm
Glass Panel
Center Deflection = L/60
Aluminum Spandrel Panel
Center Deflection = L/120

4
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Load Computation & Application

3 LOAD COMPUTATION & APPLICATION


Wind Load
Wind Load computation as Code of Practice on Wind Effects in Hong Kong - 2004
Basic Wind Pressure

hg = 3.75 m ; Height of Ground


hb = 99.77 m ; Height of Building
H = hb-hg
= 96.02 m ; Height of Tower from ground
As per Table 1;
Height Wind Pressure
75.00 2.73 kPa
96.02 Wp
100.00 2.86 kPa
By Linear Interpolation
Wp = 2.84 kPa ; Site wind Pressure

Pressure Coefficients (Table E1)


Wall & Claddings
Cpe = -1.4 ; Maximum Negative (edge zones)
Cpe = -1.0 ; Maximum Negative (other surfaces)
Cpe = 1.0 ; Maximum Positive (edge &other surfaces)

Open Framework individual elements


Cpe = 2.0 ; Open Frame (Feature w/ projection)

Design Wind Pressures


Wall & Claddings
WLne = Wp*Cpe
= - 3.98 kPa ; Maximum Negative (edge zones), say 4.0 kPa
Wlno = Wp*Cpe
= - 2.84 kPa ; Maximum Negative (other surfaces)
WLp = Wp*Cpe
= 2.84 kPa ; Maximum Positive (edge & other surfaces)

Open Framework individual elements (projected feature)


WLind = Wp*Cpe
= 5.68 kPa ; Open Frame (Feature w/ projection)

Dead Load
Glass Panel (based on thickest)
tg = 22 mm ; Total Glass Thickness (10HS + Air + 12FT)
ρg = 26.00 kN/m3 ; Density
DLg = tg*ρg
= 0.57 kPa ; Glass Panel DL
Aluminum Profiles (based on Largest Cross-section Profile)
ρa = 26.59 kN/m3 ; Density
Mullion Profile
Am = 3261 mm2 ; Cross-sectional Area (See Appendix)
DLM = Am*ρa
= 0.09 kN/m

5
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Load Computation & Application

Transom Profile
At = 3885 mm2 ; Cross-sectional Area (See Appendix)
DLT = At*ρa
= 0.10 kN/m

Total Dead Load per Unit Area


Ht = 3.33 m ; Tributary Height
Wt = 2.44 m ; Tributary Width
nm = 3 ; number of mullion
nt = 4 ; number of transom
TW = ((DLg*Ht*Wt)+(nm*DLM*Ht)
+(nt*DLT*Wt)) + 10%
= 7.17 kN ; total weight + 10% for accessories
DL = TW / (Ht*Wt)
= 0.88 kPa
= say 1.0 kPa ; DL per unit area (Conservative)

Imposed Loads
Imposed Load on Protective Barriers
IL1 = 0.75 kN/m ; Line load @ 1.1m from FL
IL2 = 1.00 kPa ; Uniformly Distributed at infill
IL3 = 0.50 kN ; Concentrated load at infill

6
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

4 GLASS PANEL CHECKING

4.1 Vision Glass Panels (G01) (Largest Panel is 2.448m x 1.410m)

Largest G01
Panel

Glass Panel (10HS + A + 12FT)


Glass Panel Capacity
py.ft = 80.0 MPa ; Design Strength ,Tempered
γd.sh = 1.00 ; Strength Reduction Factor (Short-term load)
γd.mi = 0.81 ; Strength Reduction Factor (Medium-term load)
γd.lo = 0.66 ; Strength Reduction Factor (Long-term load)
pyg.sh = py.ft*γd.sh
= 80.0 MPa ; Design Strength , Short-term load
pyg.mi = py.ft*γd.mi
= 64.8 MPa ; Design Strength , Medium-term load
pyg.lo = py.ft*γd.lo
= 52.8 MPa ; Design Strength , Long-term load

Checking of the Largest Glass Panel


H = 1,410 mm ; Maximum Panel Height
W = 2,448 mm ; Maximum Panel Width

Minimum Glass Thickness


tout = 9.02 mm ; Individual Pane (Out)
tin = 11.91 mm ; Individual Pane (In)

Load Computations
Wind Load Application
WL = 4.00 kPa ; Design Wind Load (Governing Suction)

7
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Checking Glass Outer Panes

Load Sharing Factor of Outer Pane


kouter = 1.25*t3 / [tout13 + tout23 + tin3]
= 0.379 ; Load Share Factor for t
wl = k*WL
= 1.51 kPa
a = 2.45 m ; Length of shorter side of glass pane
b = 1.41 m ; Length of longer side of glass pane
γf = 1.40 ; Wind Load Factor
wl = 1.51 kPa ; Load Shared to the outer panes

Checking of Minimum Glass Pane Thickness (SUOG 2018)


R = γf*wl
= 2.12 kPa ; Factored design pressure on individual glass pane
c1 = 2.0 ; Heat Strengthened Glass
γd = 1.0 ; Strength reduction factor, Short-term
γs = 1.0 ; Glass surface treatment reduction factor
c = c1*γd*γs
= 2.0 ; Strength coefficient
tmin.1 = 4.87 * a0.965 * b0.22 * (R/c)0.545
= 12.86 mm
0.665
tmin.2 = 2.33 * (a*b) * (R/c)0.87 - 1.62(a/b) + 1.2
= 3.97 mm
b/a = 0.58 ; < 5.0
tmin = min(tmin.1,tmin.2) ; Minimum Glass Thickness
= 3.97 mm < t = 9.02 mm OK

Glass Panel Deflection Check (SUOG 2018)


t = 9.02 mm
Eg = 70,000,000 Pa ; Modulus of Elasticity
a = 1,410.00 mm ; Length of shorter side of glass pane
b = 2,448.00 mm ; Length of longer side of glass pane
p = 1.51 ; Load Per Pane
2 3
r0 = 0.553 - 3.83(b/a) + 1.11(b/a) - 0.0969(b/a)
= - 1.30
r1 = -2.29 + 5.83(b/a) - 2.17(b/a)2 + 0.2067(b/a)3
= 0.39
r2 = 1.485 - 1.908(b/a) + 0.815(b/a)2 - 0.0822(b/a)3
= 0.64
x = ln [ ln * [(p*(a*b)2) / (Eg*t4)]
= 1.30
r0 + (r1*x) + (r2*x^2)
δ = t*e
= 11.92 mm ; Maximum Deflection
δlimit = b/60
= 23.50 mm ; Maximum Allowable Deflection
δ/δlimit = 0.51 ; < 1.0 O.K.

8
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Checking Glass Inner Panes


Load Sharing Factor of Outer Pane
kouter = 1.25*t3 / [tout13 + tout23 + tin3]
= 0.871 ; Load Share Factor for t
wl = k*WL
= 3.49 kPa
a = 2.45 m ; Length of shorter side of glass pane
b = 1.41 m ; Length of longer side of glass pane
γf = 1.40 ; Wind Load Factor
wl = 3.49 kPa ; Load Shared to the outer panes

Checking of Minimum Glass Pane Thickness (SUOG 2018)


R = γf*wl
= 4.88 kPa ; Factored design pressure on individual glass pane
c1 = 4.0 ; Heat Strengthened Glass
γd = 1.0 ; Strength reduction factor, Short-term
γs = 1.0 ; Glass surface treatment reduction factor
c = c1*γd*γs
= 4.0 ; Strength coefficient
0.965 0.22 0.545
tmin.1 = 4.87 * a * b * (R/c)
= 13.89 mm
tmin.2 = 2.33 * (a*b)0.665 * (R/c)0.87 - 1.62(a/b) + 1.2
= 4.70 mm
b/a = 0.58 ; < 5.0
tmin = min(tmin.1,tmin.2) ; Minimum Glass Thickness
= 4.70 mm < t = 11.91 mm OK

Glass Panel Deflection Check (SUOG 2018)


t = 11.91 mm
Eg = 70,000,000 Pa ; Modulus of Elasticity
a = 1,410.00 mm ; Length of shorter side of glass pane
b = 2,448.00 mm ; Length of longer side of glass pane
p = 3.49 ; Load Per Pane
r0 = 0.553 - 3.83(b/a) + 1.11(b/a)2 - 0.0969(b/a)3
= - 1.30
r1 = -2.29 + 5.83(b/a) - 2.17(b/a)2 + 0.2067(b/a)3
= 0.39
r2 = 1.485 - 1.908(b/a) + 0.815(b/a)2 - 0.0822(b/a)3
= 0.64
x = ln [ ln * [(p*(a*b)2) / (Eg*t4)]
= 1.22
r0 + (r1*x) + (r2*x^2)
δ = t*e
= 13.45 mm ; Maximum Deflection
δlimit = b/60
= 23.50 mm ; Maximum Allowable Deflection
δ/δlimit = 0.57 ; < 1.0 O.K.

9
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Checking (Strand Modelling)

Outer Panel (10mm HS)


WL = 1.51 kPa ;Design Wind Load for Stress
σ = 18.16 MPa ; Stress
σF = 1.4*σ
= 25.4 MPa ; Factored Stress
< 40 MPa ; Therefore OK

Inner Panel (12mm FT)


WL = 3.49 kPa ;Design Wind Load for Stress
σ = 25.03 MPa ; Stress
σF = 1.4*σ
= 35.0 MPa ; Factored Stress
< 80 MPa ; Therefore OK

10
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Deflection Checking (Strand Modelling)

δmax.G01 out.wl = 10.73 mm ; Maximum Deflection


δallow = min(H,W) / 60
= 23.50 mm ; Maximum Alllowable Deflection
δmax.G01.out.wl / δallow = 0.46 ; < 1.0 - OK

δmax.G01.in.wl = 11.14 mm ; Maximum Deflection


δallow = min(H,W) / 60
= 23.50 mm ; Maximum Alllowable Deflection
δmax.G01.in.wl / δallow = 0.47 ; < 1.0 - OK

11
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

G01 - Inner Pane (Imposed Load)

Design Strength
py.ft = 80.0 MPa ; Design Strength, Fully Tempered
γd.sh = 1.00 ; Strength Reduction Factor (Short-term load)
Ru.ft.IL = py.hs*γd.sh
= 80.0 MPa ; Panel Design Strength
γf = 1.40 ; Imposed Load Factor

Stress Check (Imposed Load 1)


IL1 = 0.75 kN/m ; Line load

σ = 8.82 MPa ; Stress


σF = 1.4*σ
= 12.3 MPa ; Factored Stress
< 80 MPa ; Therefore OK

12
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Check (Imposed Load 2)


IL2 = 1.00 kPa ; Uniformly Distributed

σ = 7.66 MPa ; Stress


σF = 1.4*σ
= 10.7 MPa ; Factored Stress
< 80 MPa ; Therefore OK

13
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Check (Imposed Load 3)


IL3 = 0.50 kPa ; Concentrated

σ = 9.47 MPa ; Stress


σF = 1.4*σ
= 13.3 MPa ; Factored Stress
< 80 MPa ; Therefore OK

14
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

4 GLASS PANEL CHECKING

4.2 Vision Glass Panels (G02) (Largest Panel is 0.47m x 1.410m)


Largest G02
Panel

Glass Panel (10HS + A + 8FT)


Glass Panel Capacity
py.ft = 80.0 MPa ; Design Strength ,Tempered
γd.sh = 1.00 ; Strength Reduction Factor (Short-term load)
γd.mi = 0.81 ; Strength Reduction Factor (Medium-term load)
γd.lo = 0.66 ; Strength Reduction Factor (Long-term load)
pyg.sh = py.ft*γd.sh
= 80.0 MPa ; Design Strength , Short-term load
pyg.mi = py.ft*γd.mi
= 64.8 MPa ; Design Strength , Medium-term load
pyg.lo = py.ft*γd.lo
= 52.8 MPa ; Design Strength , Long-term load

Checking of the Largest Glass Panel


H = 1,410 mm ; Maximum Panel Height
W = 472 mm ; Maximum Panel Width

Minimum Glass Thickness


tout = 7.42 mm ; Individual Pane (Out)
tin = 7.42 mm ; Individual Pane (In)

Load Computations
Wind Load Application
WL = 4.00 kPa ; Design Wind Load (Governing Suction)

15
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Checking Glass Outer Panes

Load Sharing Factor of Outer Pane


kouter = 1.25*t3 / [tout13 + tout23 + tin3]
= 0.625 ; Load Share Factor for t
wl = k*WL
= 2.50 kPa
a = 0.47 m ; Length of shorter side of glass pane
b = 1.41 m ; Length of longer side of glass pane
γf = 1.40 ; Wind Load Factor
wl = 2.50 kPa ; Load Shared to the outer panes

Checking of Minimum Glass Pane Thickness (SUOG 2018)


R = γf*wl
= 3.50 kPa ; Factored design pressure on individual glass pane
c1 = 2.0 ; Heat Strengthened Glass
γd = 1.0 ; Strength reduction factor, Short-term
γs = 1.0 ; Glass surface treatment reduction factor
c = c1*γd*γs
= 2.0 ; Strength coefficient
tmin.1 = 4.87 * a0.965 * b0.22 * (R/c)0.545
= 3.45 mm
0.665
tmin.2 = 2.33 * (a*b) * (R/c)0.87 - 1.62(a/b) + 1.2
= 3.55 mm
b/a = 2.99 ; < 5.0
tmin = min(tmin.1,tmin.2) ; Minimum Glass Thickness
= 3.45 mm < t = 7.42 mm OK

Glass Panel Deflection Check (SUOG 2018)


t = 7.42 mm
Eg = 70,000,000 Pa ; Modulus of Elasticity
a = 472.00 mm ; Length of shorter side of glass pane
b = 1,410.00 mm ; Length of longer side of glass pane
p = 2.50 ; Load Per Pane
2 3
r0 = 0.553 - 3.83(b/a) + 1.11(b/a) - 0.0969(b/a)
= - 3.57
r1 = -2.29 + 5.83(b/a) - 2.17(b/a)2 + 0.2067(b/a)3
= 1.27
r2 = 1.485 - 1.908(b/a) + 0.815(b/a)2 - 0.0822(b/a)3
= 0.87
x = ln [ ln * [(p*(a*b)2) / (Eg*t4)]
= 0.50
r0 + (r1*x) + (r2*x^2)
δ = t*e
= 0.49 mm ; Maximum Deflection
δlimit = b/60
= 7.87 mm ; Maximum Allowable Deflection
δ/δlimit = 0.06 ; < 1.0 O.K.

16
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Checking Glass Inner Panes


Load Sharing Factor of Outer Pane
kouter = 1.25*t3 / [tout13 + tout23 + tin3]
= 0.625 ; Load Share Factor for t
wl = k*WL
= 2.50 kPa
a = 0.47 m ; Length of shorter side of glass pane
b = 1.41 m ; Length of longer side of glass pane
γf = 1.40 ; Wind Load Factor
wl = 2.50 kPa ; Load Shared to the outer panes

Checking of Minimum Glass Pane Thickness (SUOG 2018)


R = γf*wl
= 3.50 kPa ; Factored design pressure on individual glass pane
c1 = 4.0 ; Heat Strengthened Glass
γd = 1.0 ; Strength reduction factor, Short-term
γs = 1.0 ; Glass surface treatment reduction factor
c = c1*γd*γs
= 4.0 ; Strength coefficient
0.965 0.22 0.545
tmin.1 = 4.87 * a * b * (R/c)
= 2.37 mm
tmin.2 = 2.33 * (a*b)0.665 * (R/c)0.87 - 1.62(a/b) + 1.2
= 2.24 mm
b/a = 2.99 ; < 5.0
tmin = min(tmin.1,tmin.2) ; Minimum Glass Thickness
= 2.24 mm < t = 7.42 mm OK

Glass Panel Deflection Check (SUOG 2018)


t = 7.42 mm
Eg = 70,000,000 Pa ; Modulus of Elasticity
a = 472.00 mm ; Length of shorter side of glass pane
b = 1,410.00 mm ; Length of longer side of glass pane
p = 2.50 ; Load Per Pane
r0 = 0.553 - 3.83(b/a) + 1.11(b/a)2 - 0.0969(b/a)3
= - 3.57
r1 = -2.29 + 5.83(b/a) - 2.17(b/a)2 + 0.2067(b/a)3
= 1.27
r2 = 1.485 - 1.908(b/a) + 0.815(b/a)2 - 0.0822(b/a)3
= 0.87
x = ln [ ln * [(p*(a*b)2) / (Eg*t4)]
= 0.50
r0 + (r1*x) + (r2*x^2)
δ = t*e
= 0.49 mm ; Maximum Deflection
δlimit = b/60
= 7.87 mm ; Maximum Allowable Deflection
δ/δlimit = 0.06 ; < 1.0 O.K.

17
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Checking (Strand Modelling)

Outer Panel (8mm HS)


WL = 2.50 kPa ;Design Wind Load for Stress
σ = 10.64 MPa ; Stress
σF = 1.4*σ
= 14.9 MPa ; Factored Stress
< 40 MPa ; Therefore OK

Inner Panel (8mm FT)


WL = 2.50 kPa ;Design Wind Load for Stress
σ = 10.64 MPa ; Stress
σF = 1.4*σ
= 14.9 MPa ; Factored Stress
< 80 MPa ; Therefore OK

18
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Deflection Checking (Strand Modelling)

δmax.G01 out.wl = 0.69 mm ; Maximum Deflection


δallow = min(H,W) / 60
= 7.87 mm ; Maximum Alllowable Deflection
δmax.G01.out.wl / δallow = 0.09 ; < 1.0 - OK

δmax.G01.in.wl = 0.69 mm ; Maximum Deflection


δallow = min(H,W) / 60
= 7.87 mm ; Maximum Alllowable Deflection
δmax.G01.in.wl / δallow = 0.09 ; < 1.0 - OK

19
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

G02 - Inner Pane (Imposed Load)


Design Strength
py.ft = 80.0 MPa ; Design Strength, Fully Tempered
γd.sh = 1.00 ; Strength Reduction Factor (Short-term load)
Ru.ft.IL = py.hs*γd.sh
= 80.0 MPa ; Panel Design Strength
γf = 1.40 ; Imposed Load Factor

Stress Check (Imposed Load 1)

IL1 = 0.75 kN/m ; Line load

σ = 7.31 MPa ; Stress


σF = 1.4*σ
= 10.2 MPa ; Factored Stress
< 80 MPa ; Therefore OK

20
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Check (Imposed Load 2)

IL2 = 1.00 kPa ; Uniformly Distributed

σ = 4.90 MPa ; Stress


σF = 1.4*σ
= 6.9 MPa ; Factored Stress
< 80 MPa ; Therefore OK

21
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Check (Imposed Load 3)

IL3 = 0.50 kPa ; Concentrated

σ = 30.67 MPa ; Stress


σF = 1.4*σ
= 42.9 MPa ; Factored Stress
< 80 MPa ; Therefore OK

22
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

4 GLASS PANEL CHECKING

4.3 Vision Glass Panels (G03) (Largest Panel is 2.448m x 325m)

Largest G03
Panel

Glass Panel (10HS + A + 8FT)


Glass Panel Capacity
py.ft = 80.0 MPa ; Design Strength ,Tempered
γd.sh = 1.00 ; Strength Reduction Factor (Short-term load)
γd.mi = 0.81 ; Strength Reduction Factor (Medium-term load)
γd.lo = 0.66 ; Strength Reduction Factor (Long-term load)
pyg.sh = py.ft*γd.sh
= 80.0 MPa ; Design Strength , Short-term load
pyg.mi = py.ft*γd.mi
= 64.8 MPa ; Design Strength , Medium-term load
pyg.lo = py.ft*γd.lo
= 52.8 MPa ; Design Strength , Long-term load

Checking of the Largest Glass Panel


H = 325 mm ; Maximum Panel Height
W = 2,448 mm ; Maximum Panel Width

Minimum Glass Thickness


t = 7.42 mm ; Individual Pane (Out)

Load Computations
Wind Load Application
WL = 4.00 kPa ; Design Wind Load (Governing Suction)

23
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Checking Glass

a = 2.45 m ; Length of shorter side of glass pane


b = 0.33 m ; Length of longer side of glass pane
γf = 1.40 ; Wind Load Factor
wl = 4.00 kPa ; Load Shared to the outer panes

Checking of Minimum Glass Pane Thickness (SUOG 2018)


R = γf*wl
= 5.60 kPa ; Factored design pressure on individual glass pane
c1 = 2.0 ; Heat Strengthened Glass
γd = 1.0 ; Strength reduction factor, Short-term
γs = 1.0 ; Glass surface treatment reduction factor
c = c1*γd*γs
= 2.0 ; Strength coefficient
0.965 0.22 0.545
tmin.1 = 4.87 * a * b * (R/c)
= 15.81 mm
0.665
tmin.2 = 2.33 * (a*b) * (R/c)0.87 - 1.62(a/b) + 1.2
= - 6.10 mm
b/a = 0.13 ; < 5.0
tmin = min(tmin.1,tmin.2) ; Minimum Glass Thickness
= - 6.10 mm < t = 7.42 mm OK

Glass Panel Deflection Check (SUOG 2018)


t = 7.42 mm
Eg = 70,000,000 Pa ; Modulus of Elasticity
a = 325.00 mm ; Length of shorter side of glass pane
b = 2,448.00 mm ; Length of longer side of glass pane
p = 4.00 ; Load Per Pane
2 3
r0 = 0.553 - 3.83(b/a) + 1.11(b/a) - 0.0969(b/a)
= 0.06
r1 = -2.29 + 5.83(b/a) - 2.17(b/a)2 + 0.2067(b/a)3
= - 1.55
r2 = 1.485 - 1.908(b/a) + 0.815(b/a)2 - 0.0822(b/a)3
= 1.25
x = ln [ ln * [(p*(a*b)2) / (Eg*t4)]
= 0.91
r0 + (r1*x) + (r2*x^2)
δ = t*e
= 5.39 mm ; Maximum Deflection
δlimit = b/60
= 5.42 mm ; Maximum Allowable Deflection
δ/δlimit = 0.99 ; < 1.0 O.K.

24
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Stress Checking (Strand Modelling)

Outer Panel (8mm HS)


WL = 6.06 kPa ;Design Wind Load for Stress
σ = 10.64 MPa ; Stress
σF = 1.4*σ
= 14.9 MPa ; Factored Stress
< 40 MPa ; Therefore OK

Deflection Checking (Strand Modelling)

δmax.G01 out.wl = 0.13 mm ; Maximum Deflection


δallow = min(H,W) / 60
= 5.42 mm ; Maximum Alllowable Deflection
δmax.G01.out.wl / δallow = 0.02 ; < 1.0 - OK

25
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Façade Components of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

4.4 Glass Fixing Components (Applicable to all glazing)

Geometry & Parameters


H = 2,400 mm ; Panel Height
W = 1,410 mm ; Panel Width
WL = 3.98 kPa ; Design Wind Load

Structural Silicone Bite

pts = 138 kPa ; Silicone Allowable Tensile Strength


wbite.req = [min(H,W)*WL*0.5]/pts
= 20.31 mm ; Required Bite, say 22mm

Structural Silicone Bite (Secondary Seal) - Tall Glass Fin Area

kouter = tout13 + tout23 / [tout13 + tout23 + tin3]


= 0.667
WLout = WL*kouter
= 2.65 kPa
pts = 138 kPa ; Silicone Allowable Tensile Strength
Required Bite Checking:
wbite.req = W*WLout*0.5/pts
= 13.54 ; Required Bite, say 14mm
26
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Façade Components of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Capture Plate
Computation of Force Acting in every pressure plate (one side):
H = 1,410 mm ; Largest Panel Height
sp = 300 mm ; Pressure Plate Spacing
Fpl = [min(H,W)*0.5*WL*Sp]
= 0.84 kN ; Force acting on pressure plate
e = 40 mm ; pressure plate lever arm
M = F*e
= 33,628.72 Nmm ; Bending Moment

Section Property:
tp = 3.5 mm ; Thickness of Pressure Plate
lp = 300 mm ; Length of Plate
po = 240 MPa ; Design Bending Strength
pv = 145 MPa ; Design Shear Strength
ϒm = 1.2 ; Material Factor

Shear Capacity Check:


Pvcap = tp*lp*pv / ϒm
= 126.88 kN ; Shear Capacity
1.4F/Pvcap = 0.01 ; < 1.0, Therefore OK

Bending Capacity Check:


Zx = (lp*tp2)/6
= 612.5 mm3 ; Section Modulus
Mbcap = po*Zx/ϒm
= 122,500.00 kN ; Bending Moment Capacity
1.4M/Mbcap = 0.38 ; < 1.0, Therefore OK

Bolt Fixing Check (M5 A4-70)

F = 2*Fpl*1.25
= 1.68 kN ; Force in Bolt (1.25 Amplification factor)
nb = 1 ; number of bolt
Ab = 14.2 mm2 ; effective tensile area

Tension Capacity Check:


ϒm = 1.0 ; Material Factor
ptb = 374 MPa ; Tension Strength
Tcap = nb*Ab*ptb / ϒm
= 5.31 kN
1.4F/Tcap = 0.44 ; < 1.0, Therefore OK

Thread Engagement Check:


db = 5.0 mm ; Bolt Diameter
le = 5.0 mm ; Engagement Length
p = 1.0 mm ; Pitch Length
np = (le / p) - 1
= 4 ; number of pitch engaged
27
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Façade Components of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

hp = p - (p/8) - (p/4)
= 0.625 mm ; height of pitch
Av = np*π*db*hp
= 39.270 mm2 ; Pull-out Shear Area

Bolt Thread Capacity


pvb = 311 MPa ; Shear Strength (A4-70)
Ptcap = Av * pvb
= 12 kN
1.4F/Ptcap = 0.19 ; < 1.0, Therefore OK

Aluminum Thread Capacity


pva = 95 MPa ; Shear Strength (6063-T6 Aluminum)
Ptcap = Av * pva
= 4 kN
1.4F/Ptcap = 0.63 ; < 1.0, Therefore OK

Dead Load Chair

tg = 22 mm ; Total Glass Thickness (10HS + Air + 12FT)


3
ρg = 26.00 kN/m ; Density
ns = 2 ; number of setting block
ws = 200 mm ; setting block length
Wtg = tg*ρg*H*W / ns
= 0.97 kN ; Glass Panel Weight at Setting Block Point
e = 30 mm ; Lever Arm
M = F*e
= 29,034.72 Nmm ; Bending Moment

Section Stress Checking:

ta = 4 mm ; Thickness of adaptor
da = ws+2e
= 260 mm ; Effective load carrying width of the adaptor
28
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Façade Components of Tower Area Rev.: 00
Glass Panel & Fixing Components Checking

Zx = (da*ta2)/6
= 693.33 mm3 ; Section Modulus
po = 160 MPa ; Design Bending Strength
Mbcap = po*Zx/ϒm
= 92,444.44 Nmm ; Bending Moment Capacity
1.4M/Mbcap = 0.44 ; < 1.0, Therefore OK

29
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

4.5 Openable Window Frame Checking

Aluminum Profile Section Property


Limiting Stresses
Aluminum Extrusion Alloy: 6063-T5 ; Table 4.1, BS8118:1:1991
po = 110 MPa ; Bending & Overall Yielding
pa = 170 MPa ; Local Capacity
pv = 65 MPa ; Shear
ε = (250 / po)0.5
= 1.51 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 33.17 7ε = 10.55
β1 = 18ε = 27.14 6ε = 9.045

30
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Classification

Element 2 Element 1

Element 3

Element 1 (Flat Internal element under stress gradient)


d = 40.60 mm ; depth of element
t = 3.00 mm ; thickness of element
yc = 24.60 mm ; distance compressed edge
yo = -16.00 mm ; distance to other edge of element
yo / yc = -0.65
g = 0.42 ; stress gradient factor, Figure 4.2
β = g*d/t
= 5.68 β < β1 ; Element is Fully Compact
Element 2 (Flat Internal element under uniform compression)
b = 12.9 mm ; width of element
t = 3 mm ; thickness of element
β = b/t
= 4.30 β < β1 ; Element is Semi-Compact
Element 3 (Flat Outstand element under uniform compression)
b = 18.8 mm ; width of element
t = 3 mm ; thickness of element
β = b/t
= 6.27 β < β1 ; Element is Fully Compact

Section Properties
A = 538.89 mm2 ; cross sectional area (gross)
Ix = 156,430.00 mm4 : moment of inertia about x-axis
Iy = 109,625.78 mm4 ; moment of inertia about y-axis
cy = 30.15 mm ; distance from y-axis to remotest element
cx = 32.25 mm ; distance from x-axis to remotest element
rx = 17.04 mm ; radius of gyration about stronger axis
ry = 14.26 mm ; radius of gyration about weaker axis
Znx = 5,189.15 mm3 ; elastic section modulus about x-axis
Zny = 3,398.81 mm3 ; elastic section modulus about y-axis
Snx = 6,226.98 mm3 ; plastic section modulus about x-axis
Sny = 4,078.57 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

31
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Shear Force Resistance


49*ε = 73.9
Shear force resistance in Y direction
d = 42 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 201.6 mm2 ; effective shear area
d/tm = 14 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 10,920.00 N ; shear force resistance for yielding check
Shear force resistance in X direction
d = 69 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 331.2 mm2 ; effective shear area
d/tm = 23 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 17,940.00 N ; shear force resistance for yielding check

Bending Moment Resistance


Section is Unwelded & Compact
MRSx = poSnx/ϒm ; bending moment resistance
= 570,806 Nmm
MRSy = poSny/ϒm ; bending moment resistance
= 373,869 Nmm

Lateral-Torsional Buckling (Major Axis)


Lb = 705 mm ; maximum unbraced length (1/4 of H x 2)
ry = 14.26 mm
40ε*rx = 860.1 > Lb ; LTB Check not required

32
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Load & Forces on Frame

Load Application
WL = 4.00 kPa ; Design Wind Load
B = 470 mm ; Panel Width
S = 705 mm ; length/4 of H x 2
wl = WL*(B)/2
= 0.94 N/mm ; Applied Wind Load on frame

470
1410

Shear Forces on Member


V = (wl*S)/2
= 331 N ; Shear Force
VRS = 10,920 N ; shear force resistance for yielding check
1.4V/VRS = 0.04 ; < 1.0, Therefore OK

Bending Moment on Members


2
Mb = (wl*S )/8
= 58,400 Nmm ; Bending Moment
Mrx = 570,806 Nmm ; Section Moment Resistance
1.4Mb/Mrx = 0.14 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
4
Ixm = 156,430 mm ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = min(L/180, 20mm)
= 3.92 mm ; allowable deflection
δwlmax = (5*wl*Lt4)/(384*Ea*Ixm)
= 0.28 mm < δwlallow ; OK

33
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Spandrel Cladding & Stiffener

5.0 CLADDING CHECK

5.1 Cladding Panel Check

Aluminum Panel Properties & Geometry


po = 125 MPa ; Bending Stress, 3003 H14, BS EN 485
Ea = 70,000 MPa ; Modulus of Elasticity
SP = 300 mm ; Stiffener Spacing
WL = 4.00 KPa

Bending stress check


Conservatively considering a simply beam analysis of clad panel across the stiffener spacing
B = 1.00 mm ; Analyzed cladding strip
t = 3.00 mm ; Panel Thickness
Sx = B*t2 / 6
= 1.50 mm3 ; Section modulus per mm strip
Bending moment capacity
Mbc = Sx*po
= 187.50 Nmm ; Bending moment capacity per mm

Bending Capacity Check


2
Mb = (WL*B)*SP / 8
= 45.00 Nmm ; Bending moment
1.2Mb/Mbc = 0.29 ; < 1.0, Therefore OK

Deflection check
2
Ix = B*t / 6
= 2.25 mm4 ; Moment of Inertia per mm strip
Wind Load Deflection
δwlallow = L/120
= 2.5 mm ; allowable deflection
4
δwlmax = (5*(WL*B)*SP )/(384*Ea*Ix)
= 2.7 mm < δwlallow ; OK

34
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Spandrel Cladding & Stiffener

Checking of Stud Bolts

Bolt Tension Capacity


ϒm = 1.2 ; material factor
Ab = 20.1 mm2 ; Effective bolt area (M6)
ptb = 95 MPa ; Yield Strength
Tcap = 0.8*ptb*Ab / ϒm
= 1,273 N ; Tension Load Capacity
F.al.bolt = 0.6 ; 6.4.3, BS8118, reduction factor
Tbolt.cap = F.al.bolt * Tcap
= 764 N ; Tension Load Capacity, final
Force acting on Bolt
Sb = 300 mm ; Maximum Spacing of Stud bolt
T = WL*Lcl*Sb
= 360 N ; Force on support
1.4Tbolt/Tbolt.cap = 0.66 ; < 1.0, OK

5.2 Aluminum Stiffener


Aluminum Stiffener Profile Section Property (For Spandrel Modulation up to 1900mm)
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
0.5
ε = (250 / po)
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification

Element 1

Element 2
Element 3

35
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Spandrel Cladding & Stiffener

Element 1 (Flat Internal element under stress gradient)


d = 25.00 mm ; depth of element
t = 3.00 mm ; thickness of element
yc = 17.20 mm ; distance compressed edge
yo = -7.80 mm ; distance to other edge of element
yo / yc = -0.45
g = 0.62 ; stress gradient factor, Figure 4.2
β = g*d/t
= 5.17 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 38 mm ; width of element
t = 3 mm ; thickness of element
β = b/t
= 12.67 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 12 mm ; width of element
t = 5 mm ; thickness of element
β = b/t
= 2.4 β < β1 = 6ε ; Element is Fully Compact

Section Properties
A = 483.8 mm2 ; cross sectional area (gross)
Iy = 82,358.6 mm4 ; moment of inertia about y-axis
cx = 20.2 mm ; distance from x-axis to remotest element
ry = 13.0 mm ; radius of gyration about weaker axis
Zny = 4,085.2 mm3 ; elastic section modulus about y-axis
Sny = 4,902.3 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3
Shear force resistance in X direction
d = 69 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 331.2 mm2 ; effective shear area
d/tm = 23 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 26220 N ; shear force resistance for yielding check

Bending Moment Resistance


Section is Unwelded & Compact
MRSx = poSn/ϒm ; bending moment resistance
= 653,639 Nmm

36
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Spandrel Cladding & Stiffener

Checking of Aluminum Stiffener Capacity (up 670mm max)


Load Application

WL = 4.00 kPa ; Design Wind Load


B1 = 300 mm ; Stiffener Spacing
B2 = 300 mm ; Stiffener Spacing
L = 620 mm ; Stiffener length
wl = WL*(B1+B2)/2
= 1.20 N/mm ; Applied Wind Load

Shear Forces on Member


V = (wl*Ht)/2
= 372 N ; Shear Force
VRS = 26,220 N ; shear force resistance for yielding check
1.4V/VRS = 0.02 ; < 1.0, Therefore OK

Bending Moment on Members


2
Mb = (wl*Lt )/8
= 57,660 Nmm ; Bending Moment
Mr = 653,639 Nmm ; Section Moment Resistance
1.4Mb/Mr = 0.12 ; < 1.0, Therefore OK

Deflection Checking
Combined Profile Deflection Capacity
Ea = 70,000 MPa ; Modulus of Elasticity
Iy = 82,359 mm4 ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = L/180
= 3.44 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Ixm)
= 0.4 mm < δwlallow ; OK

37
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

5.3 Cladding Frame AL-17

1148 max
664 max

1100 max

1100 max

AL-17
AL-16

AL-17 (Horizontal Frame Member)


Load Application

WL = 4.00 kPa ; Design Wind Load


B1 = 300 mm ; Frame Spacing
B2 = 300 mm ; Frame Spacing
L = 1,148 mm ; Stiffener length
wl = WL*(B1+B2)/2
= 1.20 N/mm ; Applied Wind Load

Shear Forces on Member


V = (wl*Ht)/2
= 689 N ; Shear Force

Bending Moment on Members


Mb = (wl*Lt2)/8
= 197,686 Nmm ; Bending Moment

38
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Section Classification (AL-17)

Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991


po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Element 1 (Flat Internal element under stress gradient)


d = 32.00 mm ; depth of element
t = 3.00 mm ; thickness of element
yc = 16.00 mm ; distance compressed edge
yo = -16.00 mm ; distance to other edge of element
yo / yc = -1.00
g = 0.35 ; stress gradient factor, Figure 4.2
β = g*d/t
= 3.73 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 32 mm ; width of element
t = 3 mm ; thickness of element
β = b/t
= 10.67 β < β1 = 18ε ; Element is Fully Compact

Section Properties
Am = 663.93 mm2 ; cross sectional area (gross)
Ixm = 126,551 mm4 : moment of inertia about x-axis
Iym = 138,020 mm4 ; moment of inertia about y-axis
cym = 20.00 mm ; distance from y-axis to remotest element
cxm = 20.00 mm ; distance from x-axis to remotest element
rxm = 13.81 mm ; radius of gyration about stronger axis
rym = 14.42 mm ; radius of gyration about weaker axis
Znxm = 6,327.55 mm3 ; elastic section modulus about x-axis
Znym = 6,901.00 mm3 ; elastic section modulus about y-axis
Snxm = 7,593.06 mm3 ; plastic section modulus about x-axis
Snym = 8,281.20 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

39
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Shear Force Resistance


49*ε = 61.3
Dm = 40 mm ; overall depth of section
d = 32 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Avm = 0.8*Dm*t*N
= 192 mm2 ; effective shear area
d/tm = 11 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 15,200 N ; shear force resistance for yielding check
1.4V/VRS = 0.06 ; < 1.0, Therefore OK

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm ; bending moment resistance
= 1,457,868 Nmm

Lateral-Torsional Buckling
Section is square, LTB check not needed
Mr = 1,457,868 Nmm ; Section Moment Resistance
1.4Mb/Mr = 0.19 ; < 1.0, Therefore OK

Deflection Checking

Combined Profile Deflection Capacity


Ea = 70,000 MPa ; Modulus of Elasticity
Ix = 126,551 mm4 ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = L/180
= 6.38 mm ; allowable deflection
δwlmax = (5*wl*Lt4)/(384*Ea*Ixm)
= 3.1 mm < δwlallow ; OK

40
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

5.4 Cladding Frame AL-16

1148 max
664 max

1100 max

1100 max

AL-17
AL-16

AL-16 (Vertical Frame Member)


Load Application

WL = 4.00 kPa ; Design Wind Load


B1 = 1,148 mm ; Stiffener Spacing
B2 = - mm ; Stiffener Spacing
L = 1,100 mm ; Stiffener length
wl = WL*(B1+B2)/2
= 2.30 N/mm ; Applied Wind Load

Shear Forces on Member


V = (wl*Ht)/2
= 1,263 N ; Shear Force

Bending Moment on Members


Mb = (wl*Lt2)/8
= 347,270 Nmm ; Bending Moment

41
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Section Classification (AL-16)

Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991


po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Element 1

Element 2

Element 1 (Flat element under stress gradient)


d = 75.00 mm ; depth of element
t = 6.00 mm ; thickness of element
yc = 51.40 mm ; distance compressed edge
yo = -23.60 mm ; distance to other edge of element
yo / yc = -0.46
g = 0.48 ; stress gradient factor, Figure 4.2
β = g*d/t
= 6.00 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 58.2 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 9.70 β < β1 = 18ε ; Element is Fully Compact

Section Properties
Am = 1,297.67 mm2 ; cross sectional area (gross)
Ixm = 880,069 mm4 : moment of inertia about x-axis
Iym = 1,063,824 mm4 ; moment of inertia about y-axis
cym = 56.58 mm ; distance from y-axis to remotest element
cxm = 39.96 mm ; distance from x-axis to remotest element
rxm = 26.04 mm ; radius of gyration about stronger axis
rym = 28.63 mm ; radius of gyration about weaker axis
Znxm = 15,555.55 mm3 ; elastic section modulus about x-axis
Znym = 26,619.16 mm3 ; elastic section modulus about y-axis
Snxm = 18,666.65 mm3 ; plastic section modulus about x-axis
Snym = 31,942.99 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

42
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Shear Force Resistance


49*ε = 61.3
Dm = 40 mm ; overall depth of section
d = 32 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Avm = 0.8*Dm*t*N
= 192 mm2 ; effective shear area
d/tm = 11 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 15,200 N ; shear force resistance for yielding check
1.4V/VRS = 0.12 ; < 1.0, Therefore OK

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm ; bending moment resistance
= 3,583,998 Nmm

Lateral-Torsional Buckling
Lb = 1,148 mm ; maximum unbraced length (transom spacing)
ry = 28.63 mm
40ε*ry = 1,432 > Lb Section is square, LTB check not needed
MRX.ltb = psSn/ϒm
= 2,146,665 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = min (MRS,MRX.ltb)
= 2,146,665 Nmm ; Section Moment Resistance
Mr = 3,583,998 Nmm ; Section Moment Resistance
1.4Mb/Mr = 0.14 ; < 1.0, Therefore OK

Deflection Checking

Combined Profile Deflection Capacity


Ea = 70,000 MPa ; Modulus of Elasticity
Ix = 880,069 mm4 ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = L/180
= 6.11 mm ; allowable deflection
δwlmax = (5*wl*Lt4)/(384*Ea*Ixm)
= 0.7 mm < δwlallow ; OK

43
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

5.5 Cladding Frame AL-15


500 max

1100 max

1100 max

AL-17
AL-15

AL-15 (Vertical Frame Member)


Load Application

WL = 4.00 kPa ; Design Wind Load


B1 = 500 mm ; Stiffener Spacing
B2 = - mm ; Stiffener Spacing
L = 1,100 mm ; Stiffener length
wl = WL*(B1+B2)/2
= 1.00 N/mm ; Applied Wind Load

Shear Forces on Member


V = (wl*Ht)/2
= 550 N ; Shear Force

Bending Moment on Members


Mb = (wl*Lt2)/8
= 151,250 Nmm ; Bending Moment

44
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Section Classification (AL-15)

Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991


po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Element 1

Element 2

Element 1 (Flat element under stress gradient)


d = 59.30 mm ; depth of element
t = 6.00 mm ; thickness of element
yc = 55.00 mm ; distance compressed edge
yo = -4.30 mm ; distance to other edge of element
yo / yc = -0.08
g = 0.65 ; stress gradient factor, Figure 4.2
β = g*d/t
= 6.42 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 64.2 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 10.70 β < β1 = 18ε ; Element is Fully Compact

Section Properties
Am = 981.72 mm2 ; cross sectional area (gross)
Ixm = 569,359 mm4 : moment of inertia about x-axis
Iym = 426,318 mm4 ; moment of inertia about y-axis
cym = 55.19 mm ; distance from y-axis to remotest element
cxm = 53.57 mm ; distance from x-axis to remotest element
rxm = 24.08 mm ; radius of gyration about stronger axis
rym = 20.84 mm ; radius of gyration about weaker axis
Znxm = 10,316.79 mm3 ; elastic section modulus about x-axis
Znym = 7,957.55 mm3 ; elastic section modulus about y-axis
Snxm = 12,380.15 mm3 ; plastic section modulus about x-axis
Snym = 9,549.06 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

45
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Cladding Frame Check

Shear Force Resistance


49*ε = 61.3
Dm = 40 mm ; overall depth of section
d = 32 mm ; depth of web member
tm = 3.00 mm ; minimum thickness of member
N = 2 ; number of web member
Avm = 0.8*Dm*t*N
= 192 mm2 ; effective shear area
d/tm = 11 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 15,200 N ; shear force resistance for yielding check
1.4V/VRS = 0.05 ; < 1.0, Therefore OK

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm ; bending moment resistance
= 2,376,989 Nmm

Lateral-Torsional Buckling
Lb = 500 mm ; maximum unbraced length (transom spacing)
ry = 20.84 mm
40ε*ry = 1,042 > Lb Section is square, LTB check not needed
MRX.ltb = psSn/ϒm
= 1,423,717 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = min (MRS,MRX.ltb)
= 1,423,717 Nmm ; Section Moment Resistance
Mr = 2,376,989 Nmm ; Section Moment Resistance
1.4Mb/Mr = 0.09 ; < 1.0, Therefore OK

Deflection Checking

Combined Profile Deflection Capacity


Ea = 70,000 MPa ; Modulus of Elasticity
Ix = 569,359 mm4 ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = L/180
= 6.11 mm ; allowable deflection
δwlmax = (5*wl*Lt4)/(384*Ea*Ixm)
= 0.5 mm < δwlallow ; OK

46
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6 TRANSOM CHECK
6.1 SJT1 (AL-04 & AL-05)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-04)


Element 1
Element 2

Element 3

Element 1 (Flat Internal element under uniform compression)


b = 42.5 mm ; width of element
t = 6.5 mm ; thickness of element
β = b/t
= 6.54 β < β1 ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 44 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 11 β < β1 ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 14 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 3.5 β < β1 ; Element is Fully Compact

47
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 3,122.0 mm2 ; cross sectional area (gross)
Ixt = 1,358,129.0 mm4 : moment of inertia about x-axis
Iyt = 7,133,714.0 mm4 ; moment of inertia about y-axis
cyt = 32.2 mm ; distance from y-axis to remotest element
cxt = 88.9 mm ; distance from x-axis to remotest element
rxt = 20.9 mm ; radius of gyration about stronger axis
ryt = 47.8 mm ; radius of gyration about weaker axis
Znxt = 42,191.0 mm3 ; elastic section modulus about x-axis
Znyt = 80,271.3 mm3 ; elastic section modulus about y-axis
Snxt = 50,629.2 mm3 ; plastic section modulus about x-axis
Snyt = 96,325.6 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance

49*ε = 61.3

Shear force resistance in Y direction


d = 154 mm ; depth of web member
tm = 6.50 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 1601.6 mm2 ; effective shear area
d/tm = 24 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 126,793 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 59.5 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 380.8 mm2 ; effective shear area
d/tm = 15 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 30,147 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Compact


Minor Axis:
MRSx = poSnx/ϒm
= 6,750,564 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poSny/ϒm
= 12,843,414 Nmm ; bending moment resistance (major axis)

48
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 20.86 mm
40ε*rx = 1042.9 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 117.37 < 130
ps = 60 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 4,816,280 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 6,750,564 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 4,816,280 Nmm ; Section Moment Resistance (Major Axis)

49
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Member Properties & Capacity

Aluminum Profile Section Property


Limiting Stresses

Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991


po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-05)

Element 3
Element 2

Element 1

Element 1 (Flat Internal element under stress gradient)


d = 111.00 mm ; depth of element
t = 6.50 mm ; thickness of element
yc = 80.80 mm ; distance compressed edge
yo = -30.20 mm ; distance to other edge of element
yo / yc = -0.37
g = 0.53 ; stress gradient factor, Figure 4.2
β = g*d/t
= 9.05 β < β1 ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 48.4 mm ; width of element
t = 5 mm ; thickness of element
β = b/t
= 9.68 β < β1 ; Element is Fully Compact

Element 3 (Flat Internal element under uniform compression)


b = 38.7 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 9.68 β < β1 ; Element is Fully Compact

50
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 3,885 mm2 ; cross sectional area (gross)
Ixt = 3,687,729 mm4 : moment of inertia about x-axis
Iyt = 14,373,992 mm4 ; moment of inertia about y-axis
cyt = 82.3 mm ; distance from y-axis to remotest element
cxt = 112.2 mm ; distance from x-axis to remotest element
rxt = 30.8 mm ; radius of gyration about stronger axis
ryt = 60.8 mm ; radius of gyration about weaker axis
Znxt = 44,805 mm3 ; elastic section modulus about x-axis
Znyt = 128,076 mm3 ; elastic section modulus about y-axis
Snxt = 53,765 mm3 ; plastic section modulus about x-axis
Snyt = 153,691 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance

49*ε = 61.3
Shear force resistance in Y direction
d = 111 mm ; depth of web member
tm = 6.50 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 1154.4 mm2 ; effective shear area
d/tm = 17 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 91,390 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 48.4 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 309.76 mm2 ; effective shear area
d/tm = 12 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 24,523 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Compact


Minor Axis:
MRSx = poSnx/ϒm
= 7,168,730 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poSny/ϒm
= 20,492,192 Nmm ; bending moment resistance (major axis)

51
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 30.81 mm
40ε*rx = 1540.5 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 79.46 < 130
ps = 140 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 17,930,668 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 7,168,730 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 17,930,668 Nmm ; Section Moment Resistance (Major Axis)

52
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Load & Forces on Transom ( Up to 2.448M Modulation) (STJ1 - L04 & L05)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 2,448 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 2,338 mm ; Transom Length
h1 = 325 mm ; Upper Panel Height
h2 = 750 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 538 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 3,122.0 mm2 ; Transom profile cross sectional area (L04)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.083 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 379.93 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 476.95 N ; Dead Load Shear Force
VRSy = 30,147 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.022 ; < 1.0, Therefore OK 53
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear (Vertical)


WLopen = 5.68 kPa ; Open Frame (Feature w/ projection)
s = 300 mm ; Projection
Vwl.v = [s*Lt*WLopen]/2
= 1,991 N ; Wind Load Shear Force
VRSy = 30,146.67 N ; Shear force resistance for yielding check
1.4VR/VRSy = 0.092 ; < 1.0, Therefore OK

1.4Vdl/VRSy + 1.4Vwl.v/VRSy = 0.115 ; < 1.0, Therefore OK

Wind Load Shear (Horizontal)


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 1,256.68 N ; Wind Load Shear Force
VRSx = 126,793.33 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.01 ; < 1.0, Therefore OK

Bending Moment on Member

Wind Load Bending Moment (Load Share)


Material & Section Properties
Eal04 = 70,000 MPa ; Modulus of Elasticity (AL-04)
Ixal04 = 1,358,129 mm4 : moment of inertia about x-axis
Iyal04 = 7,133,714 mm4 ; moment of inertia about y-axis
Eal05 = 70,000 MPa ; Modulus of Elasticity (AL-05)
Ixal05 = 3,687,729 mm4 : moment of inertia about x-axis
Iyal05 = 14,373,992 mm4 ; moment of inertia about y-axis

Bending Moment Load Sharing (AL04 + AL05)


kal04 = Eal04*Iy.al04 / (Eal04*Iyt.al04)+(Eal05*Iyal05)
= 0.332
kal05 = Eal05*Iy.al05 / (Eal04*Iyt.al04)+(Eal05*Iyal05)
= 0.668

Bending (AL04)

Dead Load Bending Moment (AL04)


a = Lt/4
= 584.50 mm ; Setting Block Distance From End
2
Mmax = (dlprof*Lt /8)+(P*a)
= 278,778 Nmm ; Maximum bending moment
MRSx = 6,750,564 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.058 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL04) - Minor Axis


wl = s*WLopen
= 1.704 N/mm ; Wind Load Application
Mmax = (wl*Lt2/12)
= 850,755 Nmm ; Maximum bending moment
MRYx = 6,750,564 Nmm ; Section Moment Resistance (Minor Axis)
1.4Mmax/MRx = 0.176 ; < 1.0, Therefore OK 54
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Bending Moment (AL04) - Major Axis


wl = kal04*WL*Htrib
= 0.713 N/mm ; Wind Load Application
Mmax = (wl*Lt2/12)
= 324,839 Nmm ; Maximum bending moment
MRY = 4,816,280 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.094 ; < 1.0, Therefore OK

1.4Mmax/MRSx + 1.4Mmax/MRx + 1.4Mmax/MRy = 0.33 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal04 = 1,358,129 mm4 : moment of inertia about x-axis
Iyal04 = 7,133,714 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 3.0 mm ; allowable deflection
δdlmax = [(5*dlproof*Lt /(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt2-4*a2)]
4)

= 1.8 mm < δdlallow ; OK

Wind Load Deflection - Minor Axis


δwlallow = min(L/180, 20mm)
= 12.99 mm ; allowable deflection
4
δwlmax = (wl*Lt )/(120*Ea*Iy)
= 0.8 mm < δwlallow ; OK

Wind Load Deflection - Major Axis


δwlallow = min(L/180, 20mm)
= 12.99 mm ; allowable deflection
4
δwlmax = (wl*Lt )/(120*Ea*Iy)
= 0.4 mm < δwlallow ; OK

Bending (AL05)

Wind Load Bending Moment (AL05)

wl = kal05*WL*Htrib
= 1.437 N/mm ; Wind Load Application
2
Mmax = (wl*Lt /12)
= 654,530 Nmm ; Maximum bending moment
MRY = 20,492,192 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.045 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal05 = 3,687,729 mm4 : moment of inertia about x-axis
Iyal05 = 14,373,992 mm4 ; moment of inertia about y-axis 55
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 20.00 mm ; allowable deflection
δwlmax = (wl*Lt4)/(120*Ea*Iy)
= 0.356 mm < δwlallow ; OK

56
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6 TRANSOM CHECK
6.2 T2 (AL-06)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses

Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991


po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
0.5
ε = (250 / po)
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-06)


Element 1
Element 3

Element 2

Element 1 (Flat Internal element under stress gradient)


d = 108.50 mm ; depth of element
t = 4.00 mm ; thickness of element
yc = 72.50 mm ; distance compressed edge
yo = -36.00 mm ; distance to other edge of element
yo / yc = -0.50
g = 0.50 ; stress gradient factor, Figure 4.2
β = g*d/t
= 13.56 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 88 mm ; width of element
t = 5 mm ; thickness of element
β = b/t
= 17.6 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 44 mm ; width of element
t = 5 mm ; thickness of element
β = b/t
= 8.8 β < β1 = 6ε ; Element is Fully Compact

57
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 2,784.2 mm2 ; cross sectional area (gross)
Ixt = 3,805,451.8 mm4 : moment of inertia about x-axis
Iyt = 7,732,689.7 mm4 ; moment of inertia about y-axis
cyt = 52.8 mm ; distance from y-axis to remotest element
cxt = 86.5 mm ; distance from x-axis to remotest element
rxt = 37.0 mm ; radius of gyration about stronger axis
ryt = 52.7 mm ; radius of gyration about weaker axis
Znxt = 72,086.6 mm3 ; elastic section modulus about x-axis
Znyt = 89,436.6 mm3 ; elastic section modulus about y-axis
Snxt = 86,503.9 mm3 ; plastic section modulus about x-axis
Snyt = 107,323.9 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance

49*ε = 61.3

Shear force resistance in Y direction


d = 122 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 780.8 mm2 ; effective shear area
d/tm = 31 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 61,813 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 100 mm ; depth of web member
tm = 5.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 800 mm2 ; effective shear area
d/tm = 20 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 63,333 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Semi-Compact


Minor Axis:
MRSx = poSnx/ϒm
= 11,533,857 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poSny/ϒm
= 14,309,858 Nmm ; bending moment resistance (major axis)

58
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 36.97 mm
40ε*rx = 1848.5 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 66.22 < 130
ps = 125 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 11,179,577 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 11,533,857 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 11,179,577 Nmm ; Section Moment Resistance (Major Axis)

59
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.2 Load & Forces on Transom (Up to 2.448M Modulation) (T2 - AL06)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 2,448 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 2,338 mm ; Transom Length
h1 = 840 mm ; Upper Panel Height
h2 = 235 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 538 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 2,784.2 mm2 ; Transom profile cross sectional area (L06)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.074 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 981.96 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 1068.49 N ; Dead Load Shear Force
VRSy = 63,333 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.024 ; < 1.0, Therefore OK 60
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 1,256.68 N ; Wind Load Shear Force
VRSx = 61,813 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.03 ; < 1.0, Therefore OK

Bending (AL06)

Dead Load Bending Moment (AL06) - Minor Axis


a = Lt/4
= 584.50 mm ; Setting Block Distance From End
Mmax = (dlprof*Lt2/8)+(P*a)
= 624,531 Nmm ; Maximum bending moment
MRSx = 11,533,857 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.076 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL06)

wl = WL*Htrib
= 2.150 N/mm ; Wind Load Application
2
Mmax = (wl*Lt /8)
= 1,469,053 Nmm ; Maximum bending moment
MRY = 11,179,577 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.184 ; < 1.0, Therefore OK

1.4Mmax/MRSy + 1.4Mmax/MRy = 0.26 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal06 = 3,805,452 mm4 : moment of inertia about x-axis
Iyal06 = 7,732,690 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 3.0 mm ; allowable deflection
4) 2 2
δdlmax = [(5*dlproof*Lt /(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt -4*a )]
= 1.5 mm < δdlallow ; OK

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 12.99 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Iy)
= 1.5 mm < δwlallow ; OK

61
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

62
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6 TRANSOM CHECK
6.3 T3 (AL-07)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-07)

Element 1

Element 3
Element 2

Element 1 (Flat Internal element under stress gradient)


d = 109.50 mm ; depth of element
t = 4.00 mm ; thickness of element
yc = 68.10 mm ; distance compressed edge
yo = -41.40 mm ; distance to other edge of element
yo / yc = -0.61
g = 0.44 ; stress gradient factor, Figure 4.2
β = g*d/t
= 12.05 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 88 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 22.00 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 41 mm ; width of element
t = 4 mm ; thickness of element
β = b/t

63
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

= 10.25 β1 < β < β0 ; Element is Semi-Compact

Section Properties
At = 2,376.0 mm2 ; cross sectional area (gross)
Ixt = 3,485,948.3 mm4 : moment of inertia about x-axis
Iyt = 5,861,310.7 mm4 ; moment of inertia about y-axis
cyt = 50.1 mm ; distance from y-axis to remotest element
cxt = 91.8 mm ; distance from x-axis to remotest element
rxt = 38.3 mm ; radius of gyration about stronger axis
ryt = 49.7 mm ; radius of gyration about weaker axis
Znxt = 69,607.6 mm3 ; elastic section modulus about x-axis
Znyt = 63,848.7 mm3 ; elastic section modulus about y-axis
Snxt = 83,529.1 mm3 ; plastic section modulus about x-axis
Snyt = 76,618.4 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance

49*ε = 61.3

Shear force resistance in Y direction


d = 131 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 838.4 mm2 ; effective shear area
d/tm = 33 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 66,373 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 100 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 640 mm2 ; effective shear area
d/tm = 25 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 50,667 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Semi-Compact


Minor Axis:
MRSx = poZnx/ϒm
= 9,281,013 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poZny/ϒm
= 8,513,160 Nmm ; bending moment resistance (major axis)

64
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 38.30 mm
40ε*rx = 1915.2 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 63.91 < 130
ps = 138 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 8,811,121 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 9,281,013 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 8,513,160 Nmm ; Section Moment Resistance (Major Axis)

65
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

66
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.3 Load & Forces on Transom (Up to 2.448M Modulation) (T3 - AL07)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 2,448 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 2,338 mm ; Transom Length
h1 = 750 mm ; Upper Panel Height
h2 = 1,410 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 1,080 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 2,376.0 mm2 ; Transom profile cross sectional area (L06)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.063 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 876.75 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 950.59 N ; Dead Load Shear Force
VRSy = 50,667 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.026 ; < 1.0, Therefore OK 67
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 2,525.04 N ; Wind Load Shear Force
VRSx = 66,373.33 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.05 ; < 1.0, Therefore OK

Bending (AL07)

Dead Load Bending Moment (AL07)


a = Lt/4
= 584.50 mm ; Setting Block Distance From End
Mmax = (dlprof*Lt2/8)+(P*a)
= 555,621 Nmm ; Maximum bending moment
MRSx = 9,281,013 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.084 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL07)

wl = WL*Htrib
= 4.320 N/mm ; Wind Load Application
2
Mmax = (wl*Lt /8)
= 2,951,772 Nmm ; Maximum bending moment
MRY = 8,513,160 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.485 ; < 1.0, Therefore OK

1.4Mmax/MRSy + 1.4Mmax/MRy = 0.57 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal07 = 3,485,948 mm4 : moment of inertia about x-axis
Iyal07 = 5,861,311 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 3.0 mm ; allowable deflection
4) 2 2
δdlmax = [(5*dlproof*Lt /(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt -4*a )]
= 1.4 mm < δdlallow ; OK

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 12.99 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Iy)
= 4.1 mm < δwlallow ; OK

68
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

69
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.4 T4 (AL-08)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-08)


Element 1

Element 3

Element 2

Element 1 (Flat Internal element under stress gradient)


d = 105.50 mm ; depth of element
t = 6.00 mm ; thickness of element
yc = 61.70 mm ; distance compressed edge
yo = -43.80 mm ; distance to other edge of element
yo / yc = -0.71
g = 0.40 ; stress gradient factor, Figure 4.2
β = g*d/t
= 7.03 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 88 mm ; width of element
t = 7 mm ; thickness of element
β = b/t
= 12.57 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 40 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 10.00 β1 < β < β0 ; Element is Semi-Compact

70
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 3,315.2 mm2 ; cross sectional area (gross)
Ixt = 4,506,639.6 mm4 : moment of inertia about x-axis
4
Iyt = 8,436,528.5 mm ; moment of inertia about y-axis
cyt = 50.0 mm ; distance from y-axis to remotest element
cxt = 95.3 mm ; distance from x-axis to remotest element
rxt = 36.9 mm ; radius of gyration about stronger axis
ryt = 50.4 mm ; radius of gyration about weaker axis
Znxt = 90,132.8 mm3 ; elastic section modulus about x-axis
Znyt = 88,502.2 mm3 ; elastic section modulus about y-axis
Snxt = 108,159.3 mm3 ; plastic section modulus about x-axis
Snyt = 106,202.7 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance

49*ε = 61.3

Shear force resistance in Y direction


d = 122 mm ; depth of web member
tm = 6.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 1171.2 mm2 ; effective shear area
d/tm = 20 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 92,720 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 100 mm ; depth of web member
tm = 7.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 1120 mm2 ; effective shear area
d/tm = 14 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 88,667 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Semi-Compact


Minor Axis:
MRSx = poZnx/ϒm
= 12,017,706 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poZny/ϒm
= 11,800,298 Nmm ; bending moment resistance (major axis)

71
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 36.87 mm
40ε*rx = 1843.5 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 66.40 < 130
ps = 128 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 11,328,286 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 12,017,706 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 11,328,286 Nmm ; Section Moment Resistance (Major Axis)

72
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.4 Load & Forces on Transom (Up to 2.448M Modulation) (ST4 - AL08)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 2,448 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 2,338 mm ; Transom Length
h1 = 1,410 mm ; Upper Panel Height
h2 = 840 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 1,125 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 3,315.2 mm2 ; Transom profile cross sectional area (L06)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.088 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 1,648 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 1,751 N ; Dead Load Shear Force
VRSy = 88,667 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.028 ; < 1.0, Therefore OK 73
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 2,630.25 N ; Wind Load Shear Force
VRSx = 92,720.00 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.04 ; < 1.0, Therefore OK

Bending (AL08)

Dead Load Bending Moment (AL08)


a = Lt/4
= 584.50 mm ; Setting Block Distance From End
2
Mmax = (dlprof*Lt /8)+(P*a)
= 1,023,647 Nmm ; Maximum bending moment
MRSx = 12,017,706 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.119 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL08)

wl = WL*Htrib
= 4.500 N/mm ; Wind Load Application
Mmax = (wl*Lt2/8)
= 3,074,762 Nmm ; Maximum bending moment
MRY = 11,328,286 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.380 ; < 1.0, Therefore OK

1.4Mmax/MRSy + 1.4Mmax/MRy = 0.50 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal08 = 4,506,640 mm4 : moment of inertia about x-axis
Iyal08 = 8,436,528 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 3.0 mm ; allowable deflection
δdlmax = [(5*dlproof*Lt4)/(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt2-4*a2)]
= 2.0 mm < δdlallow ; OK

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 12.99 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Iy)
= 3.0 mm < δwlallow ; OK

74
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.5 T5 (AL-09)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-09)

Element 1

Element 3

Element 2

Element 1 (Flat Internal element under stress gradient)


d = 110.00 mm ; depth of element
t = 4.00 mm ; thickness of element
yc = 54.80 mm ; distance compressed edge
yo = -55.20 mm ; distance to other edge of element
yo / yc = -1.01
g = 0.35 ; stress gradient factor, Figure 4.2
β = g*d/t
= 9.63 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 88 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 22.00 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Internal element under uniform compression)


b = 54.4 mm ; width of element
t = 3 mm ; thickness of element
β = b/t
= 18.13 β < β1 = 18ε ; Element is Fully Compact

75
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 2,022.8 mm2 ; cross sectional area (gross)
Ixt = 2,773,242.7 mm4 : moment of inertia about x-axis
4
Iyt = 3,905,190.0 mm ; moment of inertia about y-axis
cyt = 55.7 mm ; distance from y-axis to remotest element
cxt = 72.4 mm ; distance from x-axis to remotest element
rxt = 37.0 mm ; radius of gyration about stronger axis
ryt = 43.9 mm ; radius of gyration about weaker axis
Znxt = 49,815.7 mm3 ; elastic section modulus about x-axis
Znyt = 53,961.4 mm3 ; elastic section modulus about y-axis
Snxt = 59,778.9 mm3 ; plastic section modulus about x-axis
Snyt = 64,753.7 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3

Shear force resistance in Y direction


d = 121 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 774.4 mm2 ; effective shear area
d/tm = 30 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 61,307 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 100 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 640 mm2 ; effective shear area
d/tm = 25 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 50,667 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Compact


Minor Axis:
MRSx = poSnx/ϒm
= 7,970,520 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poSny/ϒm
= 8,633,832 Nmm ; bending moment resistance (major axis)

76
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 37.03 mm
40ε*rx = 1851.4 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 66.11 < 130
ps = 130 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 7,014,988 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 7,970,520 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 7,014,988 Nmm ; Section Moment Resistance (Major Axis)

77
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

78
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.5 Load & Forces on Transom (Up to 0.47M Modulation) (ST5 - AL09)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 470 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 360 mm ; Transom Length
h1 = 750 mm ; Upper Panel Height
h2 = 1,410 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 1,080 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 2,022.8 mm2 ; Transom profile cross sectional area (L06)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.054 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 135 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 145 N ; Dead Load Shear Force
VRSy = 50,667 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.004 ; < 1.0, Therefore OK 79
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 388.80 N ; Wind Load Shear Force
VRSx = 61,306.67 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.01 ; < 1.0, Therefore OK

Bending (AL09)

Dead Load Bending Moment (AL09)


a = Lt/4
= 90.00 mm ; Setting Block Distance From End
2
Mmax = (dlprof*Lt /8)+(P*a)
= 13,021 Nmm ; Maximum bending moment
MRSx = 7,970,520 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.002 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL09)

wl = WL*Htrib
= 4.320 N/mm ; Wind Load Application
Mmax = (wl*Lt2/8)
= 69,984 Nmm ; Maximum bending moment
MRY = 8,633,832 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.011 ; < 1.0, Therefore OK

1.4Mmax/MRSy + 1.4Mmax/MRy = 0.01 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal08 = 2,773,243 mm4 : moment of inertia about x-axis
Iyal08 = 3,905,190 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 1.0 mm ; allowable deflection
δdlmax = [(5*dlproof*Lt4)/(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt2-4*a2)]
= 0.001 mm < δdlallow ; OK

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 2.00 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Iy)
= 0.003 mm < δwlallow ; OK

80
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.6 T6 (AL-09a)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-09a)

Element 2

Element 3

Element 1
Element 1 (Flat Internal element under stress gradient)
d = 108.00 mm ; depth of element
t = 4.00 mm ; thickness of element
yc = 56.30 mm ; distance compressed edge
yo = -51.70 mm ; distance to other edge of element
yo / yc = -0.92
g = 0.38 ; stress gradient factor, Figure 4.2
β = g*d/t
= 10.26 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 88 mm ; width of element
t = 5.5 mm ; thickness of element
β = b/t
= 16.00 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Internal element under uniform compression)


b = 54.4 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 13.60 β < β1 = 18ε ; Element is Fully Compact

81
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Section Properties
At = 2,384.6 mm2 ; cross sectional area (gross)
Ixt = 2,900,001.7 mm4 : moment of inertia about x-axis
4
Iyt = 5,544,616.0 mm ; moment of inertia about y-axis
cyt = 45.1 mm ; distance from y-axis to remotest element
cxt = 63.8 mm ; distance from x-axis to remotest element
rxt = 34.9 mm ; radius of gyration about stronger axis
ryt = 48.2 mm ; radius of gyration about weaker axis
Znxt = 64,246.0 mm3 ; elastic section modulus about x-axis
Znyt = 86,858.6 mm3 ; elastic section modulus about y-axis
Snxt = 77,095.2 mm3 ; plastic section modulus about x-axis
Snyt = 104,230.3 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3

Shear force resistance in Y direction


d = 121 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 774.4 mm2 ; effective shear area
d/tm = 30 < 49*ε Shear Web is Compact
VRSy = pv*Av/ϒm
= 61,307 N ; shear force resistance for yielding check

Shear force resistance in X direction


d = 100 mm ; depth of web member
tm = 4.00 mm ; minimum thickness of member
N = 2 ; number of web member
Av = 0.8*d*t*N
= 640 mm2 ; effective shear area
d/tm = 25 < 49*ε Shear Web is Compact
VRSx = pv*Av/ϒm
= 50,667 N ; shear force resistance for yielding check

Bending Moment Resistance

Section is Unwelded & Compact


Minor Axis:
MRSx = poSnx/ϒm
= 10,279,365 Nmm ; bending moment resistance (minor axis)

Major Axis:
MRSy = poSny/ϒm
= 13,897,369 Nmm ; bending moment resistance (major axis)

82
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Lateral-Torsional Buckling (Major Axis)

Lb = 2,448 mm ; maximum unbraced length (mullion spacing)


rx = 34.87 mm
40ε*rx = 1743.7 < Lb provide check for Lateral Torsional Buckling Check
λ = Lb/rx ; slenderness parameter
= 70.20 < 130
ps = 120 MPa ; buckling stress as per Fig 4.9
MRY.ltb = psSn/ϒm
= 10,423,027 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = 10,279,365 Nmm ; Section Moment Resistance (Minor Axis)
Mry = min (MRS,MRy.ltb)
= 10,423,027 Nmm ; Section Moment Resistance (Major Axis)

83
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

6.6 Load & Forces on Transom (Up to 0.47M Modulation) (ST5 - AL09a)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
W = 470 mm ; Modulation
mw = 110 ; Mullion Width
Lt = W - tw
= 360 mm ; Transom Length
h1 = 750 mm ; Upper Panel Height
h2 = 1,410 mm ; Lowe Panel Height
Htrib = (h1 + h2)
= 1,080 mm ; Transom Tributary Load Height

Shear Forces on Member


Dead Load Shear
At = 2,384.6 mm2 ; Transom profile cross sectional area (L06)
ρa = 2,710 kg/m3 ; Density
dlprof = At * ρa
= 0.063 N/mm ; Profile Dead Load
P = (DL*h1*Lt)/2
= 135 N ; Dead Load at Setting Blocks
Vdl = [(dlprof*Lt)+2P]/2
= 146 N ; Dead Load Shear Force
VRSy = 61,307 N ; Shear force resistance for yielding check
1.4Vdl/VRSy = 0.003 ; < 1.0, Therefore OK 84
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Transom & Fixing Components

Wind Load Shear


Vwl = [(0.5*Htrib*Lt)*WL]/2
= 388.80 N ; Wind Load Shear Force
VRSx = 50,666.67 N ; Shear force resistance for yielding check
1.4VR/VRSx = 0.011 ; < 1.0, Therefore OK

Bending (AL09a)

Dead Load Bending Moment (AL09a)


a = Lt/4
= 90.00 mm ; Setting Block Distance From End
2
Mmax = (dlprof*Lt /8)+(P*a)
= 13,177 Nmm ; Maximum bending moment
MRSx = 10,279,365 Nmm ; Bending moment resistance (minor axis)
1.4Mmax/MRSx = 0.002 ; < 1.0, Therefore OK

Wind Load Bending Moment (AL09a)

wl = WL*Htrib
= 4.320 N/mm ; Wind Load Application
Mmax = (wl*Lt2/8)
= 69,984 Nmm ; Maximum bending moment
MRY = 13,897,369 Nmm ; Section Moment Resistance (Major Axis)
1.4Mmax/MRy = 0.007 ; < 1.0, Therefore OK

1.4Mmax/MRSy + 1.4Mmax/MRy = 0.01 ; < 1.0, Therefore OK

Deflection Checking
Ea = 70,000 MPa ; Modulus of Elasticity
Ixal08 = 2,900,002 mm4 : moment of inertia about x-axis
Iyal08 = 5,544,616 mm4 ; moment of inertia about y-axis

Dead Load Deflection


δdlallow = min(L/360, 3mm)
= 1.0 mm ; allowable deflection
δdlmax = [(5*dlproof*Lt4)/(384*Ea*Ix)] + [(P*a/(24*Ea*Ix))*(3*Lt2-4*a2)]
= 0.001 mm < δdlallow ; OK

Wind Load Deflection


δwlallow = min(L/180, 20mm)
= 2.00 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Iy)
= 0.002 mm < δwlallow ; OK

85
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

7 MULLION CHECK
7.1 MF1 (AL-01 & AL-02)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-01)

Element 2 Element 3

Element 1

Element 1 (Flat Internal element under stress gradient)


d = 59.90 mm ; depth of element
t = 6.00 mm ; thickness of element
yc = 50.01 mm ; distance compressed edge
yo = -9.89 mm ; distance to other edge of element
yo / yc = -0.20
g = 0.60 ; stress gradient factor, Figure 4.2
β = g*d/t
= 5.99 β < β1 = 18ε ; Element is Fully Compact

86
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Element 2 (Flat Internal element under uniform compression)


b = 34 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 5.67 β < β1 = 18ε ; Element is Fully Compact

Element3 (Flat Outstand element under uniform compression)


b = 14.5 mm ; width of element
t = 4 mm ; thickness of element
β = b/t
= 3.63 β < β1 = 6ε ; Element is Fully Compact

Section Properties
Am = 2,479.34 mm2 ; cross sectional area (gross)
Ixm = 3,796,189 mm4 : moment of inertia about x-axis
Iym = 1,226,313 mm4 ; moment of inertia about y-axis
cym = 64.90 mm ; distance from y-axis to remotest element
cxm = 49.89 mm ; distance from x-axis to remotest element
rxm = 39.13 mm ; radius of gyration about stronger axis
rym = 22.24 mm ; radius of gyration about weaker axis
Znxm = 58,493.80 mm3 ; elastic section modulus about x-axis
Znym = 24,582.30 mm3 ; elastic section modulus about y-axis
Snxm = 70,192.56 mm3 ; plastic section modulus about x-axis
Snym = 29,498.76 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3
Dm = 122 mm ; overall depth of section
d = 59.9 mm ; depth of web member
tm = 6.00 mm ; minimum thickness of member
N = 2 ; number of web member
Avm = 0.8*Dm*t*N
= 1171.2 mm2 ; effective shear area
d/tm = 10 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 92,720 N ; shear force resistance for yielding check

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm ; bending moment resistance
= 9,359,007 Nmm

Lateral-Torsional Buckling
Lb = 1,410 mm ; maximum unbraced length (transom spacing)
ry = 22.24 mm
40ε*ry = 1,112 < Lb provide check for Lateral Torsional Buckling Check

87
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Slenderness Parameter (Conservative)


λ = Lb/ry ; slenderness parameter
= 63.40 < 130
ps = 138 MPa ; buckling stress as per Fig 4.9
MRX.ltb = psSn/ϒm
= 8,072,144 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = min (MRS,MRX.ltb)
= 8,072,144 Nmm ; Section Moment Resistance

Tension Resistance (Axial) (Mullion is Supported @ top for DL)


A = Am
= 2479 mm2 ; cross sectional area (gross)
PRS = po*A/γm
= 330,578.7 N ; tension resistance

88
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-02)

Element 3

Element 2

Element 1

Element 1 (Flat Internal element under uniform compression)


b = 36 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 6.00 β < β1 = 18ε ; Element is Fully Compact

Element 2 (Flat Internal element under uniform compression)


b = 34 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 5.67 β < β1 = 18ε ; Element is Fully Compact

Element 3 (Flat Outstand element under uniform compression)


b = 43 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 7.17 β < β1 = 6ε ; Element is Fully Compact

Section Properties
Am = 2,393.51 mm2 ; cross sectional area (gross)
Ixm = 3,521,045.9 mm4 : moment of inertia about x-axis
Iym = 746,336.8 mm4 ; moment of inertia about y-axis
cym = 64.06 mm ; distance from y-axis to remotest element
cxm = 26.83 mm ; distance from x-axis to remotest element
rxm = 38.35 mm ; radius of gyration about stronger axis
rym = 17.66 mm ; radius of gyration about weaker axis
89
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Znxm = 54,965.67 mm3 ; elastic section modulus about x-axis


Znym = 27,821.40 mm3 ; elastic section modulus about y-axis
Snxm = 65,958.80 mm3 ; plastic section modulus about x-axis
Snym = 33,385.68 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3
Dm = 35 mm ; overall depth of section
d = 59.9 mm ; depth of web member
tm = 6.00 mm ; minimum thickness of member
N = 4 ; number of web member
Avm = 0.8*Dm*t*N
= 672 mm2 ; effective shear area
d/tm = 10 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 53,200 N ; shear force resistance for yielding check

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm
= 8,794,507 Nmm ; bending moment resistance

Lateral-Torsional Buckling
Lb = 1,410 mm ; maximum unbraced length (transom spacing)
ry = 17.66 mm
40ε*ry = 883 < Lb provide check for Lateral Torsional Buckling Check
Slenderness Parameter (Doubly Symmetrical Section)
E = 70,000 MPa ; Modulus of Elasticity
v = 0.33 ; Poisson's Ratio
G = Ea / 2(1+ν)
= 26,315.8 MPa ; Shear Modulus
Iym = 746,337 mm4 ; moment of inertia at minor axis
Torsional Constant
t1 = 6 mm
t2 = 6 mm
a = 44 mm
b = 43 mm
Jm = (2*t1*t2*a2*b2) / (a*t1 + b*t2)
= 493,747 mm4
S = 65959 mm3 ; plastic section modulus
l = 1410 mm ; Effective Length
H = 0 ; Warping Factor
Mcr = (π/l)(EIymGJ)1/2(1 + π2 EH/l2GJ)1/2
= 58,048,999 Nmm ; Elastic Critical Uniform Moment
λ = π(ES/Mcr)1/2
= 28.02 ; Slenderness Parameter
p1 = po ; Since Section is Compact
ps = 160 MPa ; buckling stress as per Fig 4.9
MRX.ltb = psSn/ϒm
= 8,794,507 Nmm ; moment resistance to lateral torsional buckling

90
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Governing Moment Resistance


Mrx = min (MRS,MRX.ltb)
= 8,794,507 Nmm ; Section Moment Resistance

Tension Resistance (Axial) (Mullion is Supported @ top for DL)


A = Am
= 2394 mm2 ; cross sectional area (gross)
PRS = po*A/γm
= 319,134.7 N ; tension resistance

91
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Load & Forces Computation (AL01 + AL02)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
B1 = 470 mm ; Panel Width (left)
B2 = 2,448 mm ; Panel Width (right)
Ht = 3,325 mm ; Mullion Height
wl = WL*(B1+B2)/2
= 5.84 N/mm ; Applied Wind Load
dl = DL*(B1+B2)/2
= 1.46 N/mm ; Applied Dead Load

Axial Force (Tension)


Conservatively considering only the Smaller Section will carry the load.
Pdl = (dl*Ht)
= 2,426 N ; Axial Force
PRS = 319,135 N ; tension resistance
1.4Pdl/PRS = 0.01 ; < 1.0, Therefore OK

Shear Forces on Member


Conservatively considering only the Smaller Section will carry the load.
V = (wl*Ht)/2
= 9,702 N ; Shear Force
VRS = 53,200 N ; shear force resistance for yielding check
1.4V/VRS = 0.26 ; < 1.0, Therefore OK

92
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Bending Moment on Members


Applying Load sharing between Aluminum Profiles
Mb = (wl*Ht2)/8
= 8,065,078 Nmm ; Bending Moment

Load Sharing Computation (for reinforced transoms)


Material & Section Properties
Eal = 70,000 MPa ; Aluminum Modulus of Elasticity
IxAL-01 = 3,796,189 mm4 : moment of inertia about x-axis
IyAL-01 = 1,226,313 mm4 ; moment of inertia about y-axis
IxAL-02 = 3,521,046 mm4 : moment of inertia about x-axis
IyAL-02 = 746,337 mm4 ; moment of inertia about y-axis

Bending Moment Load Sharing (AL-01 + AL-02)

kal01 = Ix.al01 / (Ix.al01 + Ix.al02)


= 0.519 ; Load Share AL-01
kal02 = Ix.al02 / (Ix.al01 + Ix.al02)
= 0.481 ; Load Share AL-02

Aluminum Bending Stress (AL-01)


Mb.AL01 = kal01*Mb
= 4,184,171 Nmm ; Bending Moment
Mrx = 8,072,144 Nmm ; Section Moment Resistance
1.4Mb/Mrx = 0.62 ; < 1.0, Therefore OK

Aluminum Bending Stress (AL-02)


Mb.AL02 = kal02*Mb
= 3,880,907 Nmm ; Bending Moment
Mrx = 8,794,507 Nmm ; Section Moment Resistance
1.4Mb/Mrx = 0.62 ; < 1.0, Therefore OK

Deflection Checking
Combined Profile Deflection Capacity
Ea = 70,000 MPa ; Modulus of Elasticity
Est = 205,000 MPa ; Steel Modulus of Elasticity
Ixm1 = 3,796,189 mm4 ; moment of inertia about y-axis
Ixm2 = 3,521,046 mm4 : Steel section moment of inertia about x-axis
I.comb = Ixm1 + Ixm2
= 7,317,235 mm4
Wind Load Deflection
δwlallow = min(L/180, 20mm)
= 18.47 mm ; allowable deflection
4
δwlmax = (5*wl*Lt )/(384*Ea*Ixcomb)
= 18.1 mm < δwlallow ; OK

93
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

7.2 MF1 (AL-03)

Member Properties & Capacity


Aluminum Profile Section Property
Limiting Stresses
Aluminum Extrusion Alloy: 6063-T6 ; Table 4.1, BS8118:1:1991
po = 160 MPa ; Bending & Overall Yielding
pa = 175 MPa ; Local Capacity
pv = 95 MPa ; Shear
ε = (250 / po)0.5
= 1.25 ; Constant
Section Type: Unwelded
Internal Elements Outstand Elements
βo = 22ε = 27.5 7ε = 8.75
β1 = 18ε = 22.5 6ε = 7.5

Section Classification (AL-01)

Element 2

Element 1

Element 3

Element 1 (Flat Internal element under stress gradient)


d = 65.90 mm ; depth of element
t = 6.00 mm ; thickness of element
yc = 61.00 mm ; distance compressed edge
yo = -4.90 mm ; distance to other edge of element
yo / yc = -0.08
g = 0.62 ; stress gradient factor, Figure 4.2
β = g*d/t
= 6.81 β < β1 = 18ε ; Element is Fully Compact

94
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Element 2 (Flat Internal element under uniform compression)


b = 40 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 6.67 β < β1 = 18ε ; Element is Fully Compact

Element3 (Flat Outstand element under uniform compression)


b = 30 mm ; width of element
t = 6 mm ; thickness of element
β = b/t
= 5.00 β < β1 = 6ε ; Element is Fully Compact

Section Properties
Am = 3,621.18 mm2 ; cross sectional area (gross)
Ixm = 6,414,176 mm4 : moment of inertia about x-axis
Iym = 5,485,612 mm4 ; moment of inertia about y-axis
cym = 67.03 mm ; distance from y-axis to remotest element
cxm = 55.00 mm ; distance from x-axis to remotest element
rxm = 42.09 mm ; radius of gyration about stronger axis
rym = 38.92 mm ; radius of gyration about weaker axis
Znxm = 95,691.12 mm3 ; elastic section modulus about x-axis
Znym = 99,738.40 mm3 ; elastic section modulus about y-axis
Snxm = 114,829.35 mm3 ; plastic section modulus about x-axis
Snym = 119,686.08 mm3 ; plastic section modulus about y-axis
ϒm = 1.2 ; material factor

Shear Force Resistance


49*ε = 61.3
Dm = 124 mm ; overall depth of section
d = 65.90 mm ; depth of web member
tm = 6.00 mm ; minimum thickness of member
N = 2 ; number of web member
Avm = 0.8*Dm*t*N
= 1190.4 mm2 ; effective shear area
d/tm = 11 < 49*ε Shear Web is Compact
For Compact Shear web
VRS = pv*Avm/ϒm
= 94,240 N ; shear force resistance for yielding check

Bending Moment Resistance


Section is Unwelded & Compact
MRS = poSn/ϒm ; bending moment resistance
= 15,310,580 Nmm

Lateral-Torsional Buckling
Lb = 1,410 mm ; maximum unbraced length (transom spacing)
ry = 38.92 mm
40ε*ry = 1,946 < Lb provide check for Lateral Torsional Buckling Check

95
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Slenderness Parameter (Conservative)


λ = Lb/ry ; slenderness parameter
= 36.23 < 130
ps = 160 MPa ; buckling stress as per Fig 4.9
MRX.ltb = psSn/ϒm
= 15,310,580 Nmm ; moment resistance to lateral torsional buckling

Governing Moment Resistance


Mrx = min (MRS,MRX.ltb)
= 15,310,580 Nmm ; Section Moment Resistance

Tension Resistance (Axial) (Mullion is Supported @ top for DL)


A = Am
= 3621 mm2 ; cross sectional area (gross)
PRS = po*A/γm
= 482,824.0 N ; tension resistance

96
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Load & Forces Computation (AL03)

Load Application
WL = 4.00 kPa ; Design Wind Load
DL = 1.00 kPa ; Dead Load
B1 = 775 mm ; Panel Width (left)
B2 = 471 mm ; Panel Width (right)
Ht = 3,325 mm ; Mullion Height
wl = WL*(B1+B2)/2
= 2.49 N/mm ; Applied Wind Load
dl = DL*(B1+B2)/2
= 0.62 N/mm ; Applied Dead Load

Axial Force (Tension)


Conservatively considering only the Smaller Section will carry the load.
P = (dl*Ht)
= 1,036 N ; Axial Force
PRS = 482,824 N ; tension resistance
1.4P/PRS = 0.0030 ; < 1.0, Therefore OK

Shear Forces on Member


Conservatively considering only the Smaller Section will carry the load.
V = (wl*Ht)/2
= 4,143 N ; Shear Force
VRS = 94,240 N ; shear force resistance for yielding check
1.4V/VRS = 0.06 ; < 1.0, Therefore OK

97
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Mullion Checking

Bending Moment on Members


Applying Load sharing between Aluminum Profiles
Mb = (wl*Ht2)/8
= 3,443,827 Nmm ; Bending Moment
Mrx = 15,310,580 Nmm ; Section Moment Resistance
1.4Mb/Mrx = 0.31 ; < 1.0, Therefore OK

Deflection Checking
Combined Profile Deflection Capacity
Ea = 70,000 MPa ; Modulus of Elasticity
Ixm = 6,414,176 mm4 ; moment of inertia about y-axis
Wind Load Deflection
δwlallow = min(L/180, 20mm)
= 18.47 mm ; allowable deflection
δwlmax = (5*wl*Lt4)/(384*Ea*Ixcomb)
= 8.8 mm < δwlallow ; OK

98
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

8 BRACKET CHECKING

8.1 Tyical Floor Bracket System

99
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Reaction Forces (Point of Support)

Considering the maximum force acting on a support (largest modulation) at one Side.

Vertical Dead Load


Rv.dl = Pdl/2
= 1,213 N ; Vertical Load (DL)
Vertical Wind Load
Rv.dl = (2*Vwl.v(transom))/2
= 1,991 N ; Vertical Load (WL)
Horizontal Wind Load
Rh.wl = (2*Vwl.v(Mullion))/2
= 9,702.35 N ; Horizontal Load (WL)

Checking for Bracket Components

Bolt Checking (M12 A4-70)

37

25

42

Check forces in one side


nb = 3 pcs ; quantity of bolts
nw = 1 wall ; number of walls in contact

Direct Shear on Bolt


Fv.dir = ((Rh.wl2 + (Rv.dl + Rv.wl)2)0.5] / (nb * nw)
= 3,405.93 N ; Shear Load

Shear Due Vertical Load Eccentricity


x = 0 mm ; horizontal dist. from to centroid of bolt group
y = 50 mm ; vertical dist. from to centroid of bolt group
RWL = VWL
= 1,991 N ; horizontal shear due to wind load
RDL = VDL
= 1,213 N ; vertical shear due to dead load
Pv = 3,204 N ; DL + WL (Vertical)
ev = 25 mm ; eccentricity
Mz = Pv*e
= 80,107 Nmm ; torsional moment
100
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Σ (x2 +y2) = 5,000 mm2 ; summation of x&y distance of bolt group


Fv.e = Mz*y / Σ (x2 +y2)
= 801.1 N ; shear due to eccentricity
Fv = (Fv.dir2 + Fv.e2)0.5
= 3,303 N ; shear reaction of most stressed bolt

Tension Due Vertical & Horizontal Load Eccentricity


eh = 42 mm ; eccentricity
a = 37 mm ; horizontal distance to edge from bolt
Ft.h = Rh.wl*eh / a*n
= 3,671.2 N ; tension per bolt, due to horizontal load
z = 125 mm ; Vertical distance to edge from bolt
Ft.v = Mz / z
= 640.9 N ; tension per bolt, due to vertical
Ft = Ft.h + Ft.v
= 4,312.0 N ; tension per bolt

Shear Capacity
pvb = 311 MPa ; Shear Strength
ϒm = 1.0 ; material factor
Ab = 84.3 mm2 ; Effective bolt area (M12)
Fvcap = (pvb*Ab / ϒm)
= 26,217.30 N ; Allowable Single Shear
1.4Fv/Fvcap = 0.18 ; < 1.0, Therefore OK

Tension Capacity
ptb = 450 MPa ; Tension Strength
Tcap = Ab*ptb / ϒm
= 37,935.00 N
1.4F/Tcap = 0.16 ; < 1.0, Therefore OK

1.4Fv/Fvcap + 1.4Fv/Fvcap = 0.34 ; < 1.0, Therefore OK

Bearing Capacity
df = 12 mm ; diameter of bolt
t = 6 mm ; thickness of mullion wall (6063-T6 Alloy)
e = 37 mm ; minimum edge distance of bolt
ϒm = 1.2 ; material factor
kbs = 1.0 ; factor for slotted hole
Pa = 175 MPa ; bearing strength of connected parts
Pbs1 = kbs*df*t*Pa/γm
= 10,500.00 N ; bearing capacity without edge distance
Pbs1 = 0.5*kbs*e*t*Pa/γm
= 16,187.50 N ; bearing capacity for critical edge distance
Pbs = min(Pbs1 , Pbs2)
= 10,500.00 N ; bearing capacity of connected ply
1.4Fv/Pbs = 0.44 ; < 1.0, Therefore OK

101
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Bracket Check (AL-12) 16

check
82.5

28

Shear Capacity
pv = 145 MPa ; Shear
ϒm = 1.2 ; material factor
VRS = pv*Av/ϒm
d = 82.5 mm ; depth of web member
t = 16.0 mm ; minimum thickness of member
Av = d*t
= 1,320.00 mm2 ; effective shear area
VRS = pv*Av/ϒm
= 159,500 N ; shear force resistance
2 2 0.5
V = ((Rh.wl + (Rv.dl + Rv.wl) )
= 3,406 N ; Resultant Shear
1.4V/VRS = 0.03 ; < 1.0, Therefore OK

Bending Capacity
po = 240 MPa ; Bending & Overall Yielding
2
Zmin = d*t /6
= 3,520 mm3 ; Section Modulus (Min)
MRS = poZ/ϒm
= 704,000 Nmm ; bending moment resistance
e = 28 Nmm ; eccenticity
Mbmin = Rh.wl * e
= 271,666 Nmm ; Minor Axis Bending
1.4Mbmin/MRS = 0.540 ; < 1.0, Therefore OK

Zmaj = d2*t/6
= 18,150 mm3 ; Section Modulus (Maj)
MRS = poZ/ϒm
= 3,630,000 Nmm ; bending moment resistance
Mbmaj = Pv * e
= 89,720 Nmm ; Minor Axis Bending
1.4Mbmaj/MRS = 0.035 ; < 1.0, Therefore OK
1.4Mbmin/MRS + 1.4Mbmaj/MRS = 0.57 ; < 1.0, Therefore OK

102
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Bracket Check (AL-13)

16

check 85

83.5

Shear Capacity
pv = 145 MPa ; Shear
ϒm = 1.2 ; material factor
VRS = pv*Av/ϒm
d = 83.5 mm ; depth of web member
t = 16.0 mm ; minimum thickness of member
Av = d*t
= 1,336.00 mm2 ; effective shear area
VRS = pv*Av/ϒm
= 161,433 N ; shear force resistance
2 2 0.5
V = ((Rh.wl + (Rv.dl + Rv.wl) )
= 3,406 N ; Resultant Shear
1.4V/VRS = 0.03 ; < 1.0, Therefore OK

Bending Capacity
po = 240 MPa ; Bending & Overall Yielding
e = 85 Nmm ; eccenticity
2
Zmaj = d *t/6
= 18,593 mm3 ; Section Modulus (Maj)
MRS = poZ/ϒm
= 3,718,533 Nmm ; bending moment resistance
Mbmaj = Rh.wl * e
= 824,700 Nmm ; Minor Axis Bending
1.4Mbmaj/MRS = 0.310 ; < 1.0, Therefore OK

103
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Bolt Checking (M20 A4-70)

16

93

83.5
check

Check forces in one side


nb = 1 pcs ; quantity of bolts
nw = 1 wall ; number of walls in contact

Direct Shear on Bolt


Fv.dir = Rh.wl
= 9,702.35 N ; Shear Load

Tension Due Horizontal Load Eccentricity


eh = 98 mm ; eccentricity
a = 40 mm ; horizontal distance to edge from bolt
Ft.h = Rh.wl*eh / a*n
= 45,552.0 N ; tension per bolt, due to horizontal load

Shear Capacity
pvb = 311 MPa ; Shear Strength
ϒm = 1.0 ; material factor
Ab = 245 mm2 ; Effective bolt area (M20)
Fvcap = (pvb*Ab / ϒm)
= 76,195.00 N ; Allowable Single Shear
1.4Fv/Fvcap = 0.18 ; < 1.0, Therefore OK

Tension Capacity
ptb = 450 MPa ; Tension Strength
Tcap = Ab*ptb / ϒm
= 110,250.00 N
1.4F/Tcap = 0.58 ; < 1.0, Therefore OK

1.4Fv/Fvcap + 1.4Fv/Fvcap = 0.76 ; < 1.0, Therefore OK

104
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Bearing Capacity
df = 20 mm ; diameter of bolt
t = 6 mm ; thickness of Washer (6061-T6 Washer)
e = 37 mm ; minimum edge distance of bolt
ϒm = 1.2 ; material factor
kbs = 1.0 ; factor for slotted hole
Pa = 260 MPa ; bearing strength of connected parts
Pbs1 = kbs*df*t*Pa/γm
= 26,000.00 N ; bearing capacity without edge distance
Pbs1 = 0.5*kbs*e*t*Pa/γm
= 24,050.00 N ; bearing capacity for critical edge distance
Pbs = min(Pbs1 , Pbs2)
= 24,050.00 N ; bearing capacity of connected ply
1.4Fv/Pbs = 0.56 ; < 1.0, Therefore OK

Bracket Check (AL-11)

160

100

check

28

Shear Capacity
pv = 145 MPa ; Shear
ϒm = 1.2 ; material factor
VRS = pv*Av/ϒm
b = 240 mm ; depth of web member
t = 28 mm ; minimum thickness of member
Av = b*t
= 6,720.00 mm2 ; effective shear area
VRS = pv*Av/ϒm
= 812,000 N ; shear force resistance
V = Rv.dl + Rv.wl
= 3,204 N ; Resultant Shear
1.4V/VRS = 0.006 ; < 1.0, Therefore OK

105
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Tension Capacity
po = 260 MPa ; Axial Strength
ϒm = 1.2 ; material factor
b = 160 mm ; depth of web member
t = 28.0 mm ; minimum thickness of member
Av = b*t
= 4,480.00 mm2 ; effective shear area
PRS = po*A/γm
= 970,667 N ; tension resistance
Pt = Rh.wl
= 9,702 N
1.4Pt/PRS = 0.010 ; < 1.0, Therefore OK

Bending Capacity
po = 260 MPa ; Bending & Overall Yielding
2
Zmin = d*t /6
= 31,360 mm3 ; Section Modulus (Min)
MRS = poZ/ϒm
= 6,794,667 Nmm ; bending moment resistance
ev = 83 Nmm ; eccenticity (e + 25mm), due to Vertical Load
Mbmin.v = Pv*ev
= 265,955 Nmm ; Minor Axis Bending
eh = 50 Nmm ; eccenticity (e + 25mm), due to Horizontal Load
Mbmin.h = Rh.wl*eh
= 485,118 Nmm ; Minor Axis Bending
Mbmin = Mbmin.v + Mbmin.h
= 751,073 Nmm ; Total Minor Axis Bending
1.4Mbmin/MRS = 0.155 ; < 1.0, Therefore OK

106
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

8.2 Starter Panel Bracket System

Reaction Forces (Point of Support)


Considering the maximum force acting on a support (largest modulation) at one Side.

Horizontal Wind Load


Rh.wl = Vwl.v(Mullion)
= 9,702.35 N ; Horizontal Load (WL)

Checking for Bracket Components

Bolt Checking (M12 A4-70)

110

check

Check forces in one side


nb = 2 pcs ; quantity of bolts
nw = 1 wall ; number of walls in contact

107
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Direct Shear on Bolt


Fv.dir = Rh.wl / (nb * nw)
= 4,851.18 N ; Shear Load

Tension Due Vertical & Horizontal Load Eccentricity


eh = 110 mm ; eccentricity
a = 58 mm ; horizontal distance to edge from bolt
Ft.h = Rh.wl*eh / a*n
= 9,200.5 N ; tension per bolt, due to horizontal load

Shear Capacity
pvb = 311 MPa ; Shear Strength
ϒm = 1.0 ; material factor
Ab = 84.3 mm2 ; Effective bolt area (M12)
Fvcap = (pvb*Ab / ϒm)
= 26,217.30 N ; Allowable Single Shear
1.4Fv/Fvcap = 0.26 ; < 1.0, Therefore OK

Tension Capacity
ptb = 450 MPa ; Tension Strength
Tcap = Ab*ptb / ϒm
= 37,935.00 N
1.4F/Tcap = 0.34 ; < 1.0, Therefore OK

1.4Fv/Fvcap + 1.4Fv/Fvcap = 0.60 ; < 1.0, Therefore OK

Bearing Capacity
df = 12 mm ; diameter of bolt
t = 6.5 mm ; thickness of mullion wall (6063-T6 Alloy)
e = 57 mm ; minimum edge distance of bolt
ϒm = 1.2 ; material factor
kbs = 1.0 ; factor for slotted hole
Pa = 175 MPa ; bearing strength of connected parts
Pbs1 = kbs*df*t*Pa/γm
= 11,375.00 N ; bearing capacity without edge distance
Pbs1 = 0.5*kbs*e*t*Pa/γm
= 27,015.63 N ; bearing capacity for critical edge distance
Pbs = min(Pbs1 , Pbs2)
= 11,375.00 N ; bearing capacity of connected ply
1.4Fv/Pbs = 0.60 ; < 1.0, Therefore OK

108
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Steel Angle Check

200

check

Check for Bending

e = 200 mm ; eccentric load distance


Mb = Rh * e
= 1,940,470 Nmm ; bending moment about major axis
b = 500 mm ; depth of fin plate
t = 15 mm ; thickness of fin plate
Zx = b*t2/6
= 18,750 mm3 ; Elastic section modulus about x-axis
pb = 275 MPa ; bending strength

Bending Moment Resistance


MRSX = pb*Zx
= 5,156,250 Nmm ; bending moment resistance
1.4Mb/MRSX = 0.527 ; < 1.0, Therefore OK

Check For Shear


Ag = 7,500 mm2 ; cross sectional area
Pv = Rh.wl
= 9,702 N ; Shear Force
pv = 159 MPa ; Design Shear Strength
Pvcap = Ag*pv
= 1,192,500 N ; Shear strength of plate
1.4Pv/Pvcap = 0.0114 ; < 1.0, Therefore OK

109
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Weld Checking

160mm

50mm min.

check

Weld Properties

pw = 220.0 Mpa ; Weld Strength


tw = 8.0 mm ; Weld Thickness
tweff = 0.707tw
= 5.7 mm ; Effective Weld Thickness
l = 400.0 mm ; Weld Length (300+50+50)
Aw = l*tweff
= 2,262.40 mm2 ; Effective Weld Area
Zx = 7,980 mm3 ; Effective Weld Section Modulus (C-shape)

Calculation of Forces
Fz = 9,702 N ; Direct Tension
e = 160 mm ; eccentric load distance
Mb = Rh * e
Mx = 1,552,376 Nmm ; Overturning moment

Direct Stress
σvdz = Fz / Aw
= 4.29 MPa ; Direct Pull-out Stress

Stresses Due Bending Moments


σb = Mx / Zx
= 194.53 MPa ; Stress due to bending @ x

Total Stress (Normal to plain):


σb = σvdz + σb
= 198.82 MPa ; Combined Stress
1.4pwa/pw = 0.90 ; < 1.0, Therefore OK

110
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

8.3 Top Fixing Bracket

check
110

210

Reaction Forces (Point of Support)

Considering the maximum force acting on a support (largest modulation) at one Side.

Vertical Dead Load


Rv.dl = Pdl
= 2,426 N ; Vertical Load (DL)
Vertical Wind Load
Rv.wl = (2*Vwl.v(transom))
= 3,983 N ; Vertical Load (WL)
Horizontal Wind Load
Rh.wl = 9,702.35 N ; Horizontal Load (WL)

111
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Steel Angle Check

Shear Capacity
b = 500 mm ; depth of fin plate
t = 16 mm ; thickness of fin plate
Ag = 8,000 mm2 ; cross sectional area
pv = 159 MPa ; Design Shear Strength
Pvcap = Ag*pv
= 1,272,000 N ; Shear strength of plate
Pv = Rv.dl + Rv.wl
= 6,409 N ; Resultant Shear
1.4Pv/Pvcap = 0.0071 ; < 1.0, Therefore OK

Tension Capacity
fy = 275 MPa ; Axial Strength
Ptcap = fy*Ag
= 2,200,000 N ; tension resistance
Pt = Rh.wl
= 9,702 N
1.4Pt/PRS = 0.004 ; < 1.0, Therefore OK

Bending Capacity

Zx = b*t2/6
= 21,333 mm3 ; Elastic section modulus about x-axis
pb = 275 MPa ; bending strength

Bending Moment Resistance


MRSX = pb*Zx
= 5,866,667 Nmm ; bending moment resistance
ev = 235 Nmm ; eccenticity due to Vertical Load
Mbmin.v = Pv*ev
= 1,506,012 Nmm ; Minor Axis Bending
eh = 135 Nmm ; eccenticity (e + 25mm), due to Horizontal Load

Mbmin.h = Rh.wl*eh
= 1,309,817 Nmm ; Minor Axis Bending
Mbmin = Mbmin.v + Mbmin.h
= 2,815,830 Nmm ; Total Minor Axis Bending
1.4Mbmin/MRS = 0.672 ; < 1.0, Therefore OK

112
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

8.4 Cladding Bracket System

Reaction Forces (Point of Support)


Considering the maximum force acting on a support (largest modulation) at one Side.

Horizontal Wind Load


Rh.wl = Vclad x 2
= 2,525.60 N ; Horizontal Load (WL)

Checking for Bracket Components

Bolt Checking (M12 A4-70)

Check forces in one side


nb = 1 pcs ; quantity of bolts
nw = 1 wall ; number of walls in contact

Direct Shear on Bolt


Fv.dir = 2,525.60 N ; Shear Load

Shear Capacity
pvb = 311 MPa ; Shear Strength
ϒm = 1.0 ; material factor
Ab = 84.3 mm2 ; Effective bolt area (M12)
Fvcap = (pvb*Ab / ϒm)
= 26,217.30 N ; Allowable Single Shear
1.4Fv/Fvcap = 0.13 ; < 1.0, Therefore OK

113
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Brackets & Fixing Components

Bearing Capacity
df = 12 mm ; diameter of bolt
t = 6 mm ; thickness of mullion wall (6063-T6 Alloy)
e = 25 mm ; minimum edge distance of bolt
ϒm = 1.2 ; material factor
kbs = 1.0 ; factor for slotted hole
Pa = 175 MPa ; bearing strength of connected parts
Pbs1 = kbs*df*t*Pa/γm
= 10,500.00 N ; bearing capacity without edge distance
Pbs1 = 0.5*kbs*e*t*Pa/γm
= 10,937.50 N ; bearing capacity for critical edge distance
Pbs = min(Pbs1 , Pbs2)
= 10,500.00 N ; bearing capacity of connected ply
1.4Fv/Pbs = 0.34 ; < 1.0, Therefore OK

Steel Angle Check

Check for Bending


e = 120 mm ; eccentric load distance
Mb = Rh * e
= 303,072 Nmm ; bending moment about major axis
b = 300 mm ; depth of fin plate
t = 9 mm ; thickness of fin plate
2
Zx = b*t /6
= 4,050 mm3 ; Elastic section modulus about x-axis
pb = 275 MPa ; bending strength

Bending Moment Resistance


MRSX = pb*Zx
= 1,113,750 Nmm ; bending moment resistance
1.4Mb/MRSX = 0.381 ; < 1.0, Therefore OK

Check For Shear


Ag = 2,700 mm2 ; cross sectional area
Pv = Rh.wl
= 2,526 N ; Shear Force
pv = 159 MPa ; Design Shear Strength
Pvcap = Ag*pv
= 429,300 N ; Shear strength of plate
1.4Pv/Pvcap = 0.0082 ; < 1.0, Therefore OK

114
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

9 EMBED CHECKING
9.1 Checking for Embed - CA01 (FAC-70-550)

Reaction Forces
Conservatively considering the maximum force acting on a support (largest modulation)
Pdl = 2,425.59 N ; Vertical Load (DL)
Rv.dl = 3,982.98 N ; Vertical Load (WL)
Rh.wl = 19,404.70 N ; Horizontal Load (WL)

25

80
Applied Loads
Dead Load:
Fy = 2.43 kN ; Vertical Load (DL)
ev = 105 mm ; eccenticity (80mm + 25mm tol)
Mx = Fy*ev
= 0.25 kNm ; Moment Due To DL

Wind Load:
Fy = 3.98 kN ; Vertical Load (WL)
ev = 105 mm ; eccenticity (80mm + 25mm tol)
Mx = Fy*ev
= 0.42 kNm ; Moment Due To WL

Fz = 19.40 kN ; Horizontal Load (WL)


ev = 50 mm ; eccenticity (25mm + 25mm tol)
Mx = Fz*ev
= 0.97 kNm ; Moment Due To WL

Combined Applied Load in Hilti Profis


Fy = 6.41 kN
Fz = 19.40 kN
Mx = 1.64 kNm

using HAC-70-550 with 4 T-bolts is Sufficient. See following report


Note: FOS = 3.0 is applied in the Hilti Profis Channel Analysis

115
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 1
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA01
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
Specifier's comments:

1 Input data
Channel type HAC-70 175/550 F
bolt HBC-C 8.8F, M16 x 60 mm
Effective embedment depth hef = 175 mm
Channel specification Length: 550 mm, anchor spacing: 250 mm, projection: 25 mm,
width: bch = 45 mm, height: hch = 40 mm
Material Anchor & Channel: hot-dip galvanized
Channel bolt: hot-dip galvanized
Europ. Tech. Assessment (ETA) ETA-11/0006
Issued I Valid 27/9/2019 | -
Standard Based on EN 1992-4 with global safety factor of 3
Base material cracked, C35/45, fck,cylinder = 35.0 N/mm2, h = 200 mm
Reinforcement Exist. Reinf.: Closely spaced
Edge reinf. and stirrups present
Reinf. to control splitting present
Tolerance data tolerance interval: -500 mm/500 mm
most unfavorable tolerance: 15 mm

2 Overall Result
Design ok! (Maximum utilization: 76%)

2.1 Fixtures/Channel bolt groups


Fixture 1

3 Load case / Resulting bolt forces


Load case: Service load

Input data and results must be checked for agreement with the existing conditions and for plausibility!
116
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 2
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA01
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.1 Load distribution
3.1.1 Fixture 1: bolt: HBC-C 8.8F, M16 x 60 mm
Profile: -
Standoff: No standoff
Plate dimensions: 478 mm x 209 mm x 28 mm
Anchorplate design calculated: no
Bolt N [kN] V [kN] Vx [kN] Vy [kN]
1.1 9.028 1.600 0.000 -1.600
1.2 9.028 1.600 0.000 -1.600
1.3 9.028 1.600 0.000 -1.600
1.4 9.028 1.600 0.000 -1.600 1.1 1.2 1.3 1.4
Tension

max. concrete compressive strain: 0.08 [‰]


max. concrete compressive stress: 2.9 [N/mm2]
resulting tension force in (x/y)=(239.0/104.5): 36.113 [kN] Compression
resulting compression force in (x/y)=(239.0/8.2): 16.713 [kN]
Anchor forces are calculated based on the assumption of a rigid anchor plate.

3.2 Derivation of forces acting on anchor channels

Anchor forces [kN]


Anchor N [kN] V [kN]
a1 9.654 -1.711
a2 15.388 -2.727
a3 11.071 -1.962

3.3 Verifications for anchor channels under tension loadingBased on (EOTA TR 047 section 7.2 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Flexure channel 0.796 1.053 76 ok

3.4 Verifications for anchor channels under shear loadingBased on (EOTA TR 047 section 7.3 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete edge - perpendicular 2.727 11.418 24 ok

Input data and results must be checked for agreement with the existing conditions and for plausibility!
117
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 3
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA01
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5 Combined tension and shear loads (Based on EN 1992-4 section 8.3.3 FOS = 3.0, Hilti method based on CEN/TR
17080 section 7.3)

Proof of interaction performed independently for steel failure of channel bolt, steel failure of the channel and concrete failure
3.5.1 Channel bolt (Fixture 1, Channel bolt 1.1)
2 2

(NN ) + (√V V + V ) ≤ 1.000


cb cb 2 cb 2
Ed Ed,y Ed,x
bN+V,s =
Rd,s,cb Rd,s,cb

2
=( ) = 0.04650
cb
N Ed
bN,s
N Rd,s,cb

2
=( ) = 0.00584
√V cb 2
+V
Ed,y
cb 2
Ed,x
bV,s
V Rd,s,cb

bN+V,s = (0.04650) + (0.00584) = 0.05235 ≤ 1.000


(Utilization : 6%)

3.5.2 Point of load application - channel lip (Fixture 1, Channel bolt 1.2)
k71 k71 2

(NN ; MM ) + (VV ) + (VV ) ≤ 1.0


cb ch cb cb
Ed Ed Ed,y Ed,x
bN+V,la,c = max
Rd,s,l Rd,s,flex Rd,s,l,y Rd,s,l,x

2.0
= max ( ) = 0.57141
cb ch
N M Ed Ed
bN,la,c ;
N M Rd,s,l Rd,s,flex

2.0
=( ) = 0.00518
cb
V Ed,y
bV,la,c,y
V Rd,s,l,y

2
=( ) = 0.00000
cb
V Ed,x
bV,la,c,x
V Rd,s,l,x

bN+V,la,c = 0.57141 + 0.00518 + 0.00000 ≤ 1.0


(Utilization : 58%)

bN,la,c, governing failure mode: Flexure channel


bV,la,c,y, governing failure mode: Flexure channel lip w/o lever arm - perpendicular
bV,la,c,x, governing failure mode: N/A

3.5.3 Anchor and connection between anchor and channel (Anchor a2)
k72 k72 2

(NN ) (VV ) (VV ) ≤ 1.0


a
Ed NaEd a
Ed,y VaEd,y a
Ed,x VaEd,x
bN+V,ac = max , + max , + max ,
Rd,s,a NRd,s,c Rd,s,a,y VRd,s,c,y Rd,s,a,x VRd,s,c,x
2.0
= max( )
a
N Ed NaEd
bN,ac , = 0.42277
N Rd,s,a NRd,s,c
2.0
= max( ) = 0.01328
a
V Ed,y VaEd,y
bV,ac,y ,
V Rd,s,a,y VRd,s,c,y
2
= max( ) = 0.00000
a
V Ed,x VaEd,x
bV,ac,x ,
V Rd,s,a,x VRd,s,c,x
bN+V,ac = 0.42277 + 0.01328 + 0.00000 ≤ 1.0

(Utilization : 44%)

bN,ac, governing failure mode: Connection anchor-channel


bV,ac,y, governing failure mode: Anchor - perpendicular
bV,ac,x, governing failure mode: N/A

Input data and results must be checked for agreement with the existing conditions and for plausibility!
118
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 4
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA01
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5.4 Concrete anchor (Anchor a2)
a a a
bN+V,c =( NaEd
NRd ) ( ) ( ) ≤ 1.0
+
VaEd,y
VRd,y
+
VaEd,x
VRd,x
1.5
=( ) = 0.46442
a
N Ed
bN,c
N Rd

1.5
=( ) = 0.11673
a
V Ed,y
bV,c,y
V Rd,y

1.5
=( ) = 0.00000
a
V Ed,x
bV,c,x
V Rd,x

bN+V,c = 0.46442 + 0.11673 + 0.00000 = 0.58115 ≤ 1.0


(Utilization : 59%)

bN,c, governing failure mode: Concrete cone


bV,c,y, governing failure mode: Concrete edge - perpendicular
bV,c,x, governing failure mode: N/A

Remarks and warnings


• Please consider all details and hints/warnings given in the detailed report!

Design ok! (Maximum utilization: 76%)


4 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the
principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and
assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures,
and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations
carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you
bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of
the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you
must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by
Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the
current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti
will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable
breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
119
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

9.2 Checking for Embed - CA03 (FAC-70-350)

Reaction Forces
Computing the values of the reaction at the smaller modulation based on the largest modulation, by pro-rata:

Large modulation reaction (FAC-70-550):


Pdl = 2,425.59 N ; Vertical Load (DL)
Rv.dl = 3,982.98 N ; Vertical Load (WL)
Rh.wl = 19,404.70 N ; Horizontal Load (WL)
B1 = 470 mm ; Panel Width (left)
B2 = 2,448 mm ; Panel Width (right)
wl = (B1+B2)/2
= 1,459.00 mm ; tributary load width

End modulation reaction (FAC-70-350):


B1 = 2,448 mm ; Panel Width (left)
B2 = - mm ; Panel Width (right)
ws = (B1+B2)/2
= 1,224.00 mm ; tributary load width
% = ws/wl
= 0.84

Pdl = 2,034.90 N ; Vertical Load (DL)


Rv.dl = 3,341.44 N ; Vertical Load (WL)
Rh.wl = 16,279.20 N ; Horizontal Load (WL)

50

25

80

120
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

Applied Loads
Dead Load:
Fy = 2.03 kN ; Vertical Load (DL)
ev = 105 mm ; eccenticity (80mm + 25mm tol)
Mx = Fy*ev
= 0.21 kNm ; Moment Due To DL

Wind Load:
Fy = 3.34 kN ; Vertical Load (WL)
ev = 105 mm ; eccenticity (80mm + 25mm tol)
Mx = Fy*ev
= 0.35 kNm ; Moment Due To DL

Fz = 16.28 kN ; Horizontal Load (WL)


ev = 50 mm ; eccenticity (25mm + 25mm tol)
Mx = Fy*ev
= 0.81 kNm ; Moment Due WL
eh = 75 mm ; eccenticity (50mm + 25mm tol)
My = Fz*eh
= 1.22 kNm ; Moment Due WL

Combined Applied Load in Hilti Profis


Fy = 5.38 kN
Fz = 16.28 kN
Mx = 1.38 kNm
My = 1.22 kNm

using HAC-70-350 with 2 T-bolts is Sufficient. See report


Note: FOS = 3.0 is applied in the Hilti Profis Channel Analysis

121
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 1
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA02
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
Specifier's comments:

1 Input data
Channel type HAC-70 175/350 F
bolt HBC-C 8.8F, M16 x 60 mm
Effective embedment depth hef = 175 mm
Channel specification Length: 350 mm, anchor spacing: 150 mm, projection: 25 mm,
width: bch = 45 mm, height: hch = 40 mm
Material Anchor & Channel: hot-dip galvanized
Channel bolt: hot-dip galvanized
Europ. Tech. Assessment (ETA) ETA-11/0006
Issued I Valid 27/9/2019 | -
Standard Based on EN 1992-4 with global safety factor of 3
Base material cracked, C35/45, fck,cylinder = 35.0 N/mm2, h = 200 mm
Reinforcement Exist. Reinf.: Closely spaced
Edge reinf. and stirrups present
Reinf. to control splitting present
Tolerance data tolerance interval: -300 mm/300 mm
most unfavorable tolerance: 0 mm

2 Overall Result
Design ok! (Maximum utilization: 94%)

2.1 Fixtures/Channel bolt groups


Fixture 1

3 Load case / Resulting bolt forces


Load case: Service load

Input data and results must be checked for agreement with the existing conditions and for plausibility!
122
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 2
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA02
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.1 Load distribution
3.1.1 Fixture 1: bolt: HBC-C 8.8F, M16 x 60 mm
Profile: -
Standoff: No standoff
Plate dimensions: 160 mm x 209 mm x 28 mm
Anchorplate design calculated: no
Bolt N [kN] V [kN] Vx [kN] Vy [kN]
1.1 11.320 2.690 0.000 -2.690
1.2 20.756 2.690 0.000 -2.690
1.1 1.2
Tension
max. concrete compressive strain: 0.38 [‰]
max. concrete compressive stress: 13.0 [N/mm2]
resulting tension force in (x/y)=(91.8/104.5): 32.075 [kN]
resulting compression force in (x/y)=(26.7/17.1): 15.795 [kN]
Compression
Anchor forces are calculated based on the assumption of a rigid anchor plate.

3.2 Derivation of forces acting on anchor channels

Anchor forces [kN]


Anchor N [kN] V [kN]
a1 7.630 -1.405
a2 15.327 -2.571
a3 9.118 -1.405

3.3 Verifications for anchor channels under tension loadingBased on (EOTA TR 047 section 7.2 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Channel lip 20.756 22.236 94 ok

3.4 Verifications for anchor channels under shear loadingBased on (EOTA TR 047 section 7.3 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete edge - perpendicular 2.571 11.821 22 ok

Input data and results must be checked for agreement with the existing conditions and for plausibility!
123
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 3
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA02
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5 Combined tension and shear loads (Based on EN 1992-4 section 8.3.3 FOS = 3.0, Hilti method based on CEN/TR
17080 section 7.3)

Proof of interaction performed independently for steel failure of channel bolt, steel failure of the channel and concrete failure
3.5.1 Channel bolt (Fixture 1, Channel bolt 1.2)
2 2

(NN ) + (√V V + V ) ≤ 1.000


cb cb 2 cb 2
Ed Ed,y Ed,x
bN+V,s =
Rd,s,cb Rd,s,cb

2
=( ) = 0.24577
cb
N Ed
bN,s
N Rd,s,cb

2
=( ) = 0.01651
√V cb 2
+V
Ed,y
cb 2
Ed,x
bV,s
V Rd,s,cb

bN+V,s = (0.24577) + (0.01651) = 0.26229 ≤ 1.000


(Utilization : 27%)

3.5.2 Point of load application - channel lip (Fixture 1, Channel bolt 1.2)
k71 k71 2

(NN ; MM ) + (VV ) + (VV ) ≤ 1.0


cb ch cb cb
Ed Ed Ed,y Ed,x
bN+V,la,c = max
Rd,s,l Rd,s,flex Rd,s,l,y Rd,s,l,x

2.0
= max ( ) = 0.87126
cb ch
N M Ed Ed
bN,la,c ;
N M Rd,s,l Rd,s,flex

2.0
=( ) = 0.01463
cb
V Ed,y
bV,la,c,y
V Rd,s,l,y

2
=( ) = 0.00000
cb
V Ed,x
bV,la,c,x
V Rd,s,l,x

bN+V,la,c = 0.87126 + 0.01463 + 0.00000 ≤ 1.0


(Utilization : 89%)

bN,la,c, governing failure mode: Channel lip


bV,la,c,y, governing failure mode: Flexure channel lip w/o lever arm - perpendicular
bV,la,c,x, governing failure mode: N/A

3.5.3 Anchor and connection between anchor and channel (Anchor a2)
k72 k72 2

(NN ) (VV ) (VV ) ≤ 1.0


a
Ed NaEd a
Ed,y VaEd,y a
Ed,x VaEd,x
bN+V,ac = max , + max , + max ,
Rd,s,a NRd,s,c Rd,s,a,y VRd,s,c,y Rd,s,a,x VRd,s,c,x
2.0
= max( )
a
N Ed NaEd
bN,ac , = 0.41943
N Rd,s,a NRd,s,c
2.0
= max( ) = 0.01180
a
V Ed,y VaEd,y
bV,ac,y ,
V Rd,s,a,y VRd,s,c,y
2
= max( ) = 0.00000
a
V Ed,x VaEd,x
bV,ac,x ,
V Rd,s,a,x VRd,s,c,x
bN+V,ac = 0.41943 + 0.01180 + 0.00000 ≤ 1.0

(Utilization : 44%)

bN,ac, governing failure mode: Connection anchor-channel


bV,ac,y, governing failure mode: Anchor - perpendicular
bV,ac,x, governing failure mode: N/A

Input data and results must be checked for agreement with the existing conditions and for plausibility!
124
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 4
Specifier: Project: Gilles Ave. South
Address: Fastening point: CA02
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5.4 Concrete anchor (Anchor a2)
a a a
bN+V,c =( NaEd
NRd ) ( ) ( ) ≤ 1.0
+
VaEd,y
VRd,y
+
VaEd,x
VRd,x
1.5
=( ) = 0.52750
a
N Ed
bN,c
N Rd

1.5
=( ) = 0.10143
a
V Ed,y
bV,c,y
V Rd,y

1.5
=( ) = 0.00000
a
V Ed,x
bV,c,x
V Rd,x

bN+V,c = 0.52750 + 0.10143 + 0.00000 = 0.62892 ≤ 1.0


(Utilization : 63%)

bN,c, governing failure mode: Concrete cone


bV,c,y, governing failure mode: Concrete edge - perpendicular
bV,c,x, governing failure mode: N/A

Remarks and warnings


• Please consider all details and hints/warnings given in the detailed report!

Design ok! (Maximum utilization: 94%)


4 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the
principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and
assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures,
and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations
carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you
bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of
the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you
must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by
Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the
current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti
will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable
breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
125
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 1
Specifier: Project:
Address: Fastening point: CA01_Starter
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
Specifier's comments:

1 Input data
Channel type HAC-70 175/550 F
bolt HBC-C 8.8F, M16 x 50 mm
Effective embedment depth hef = 175 mm
Channel specification Length: 550 mm, anchor spacing: 250 mm, projection: 25 mm,
width: bch = 45 mm, height: hch = 40 mm
Material Anchor & Channel: hot-dip galvanized
Channel bolt: hot-dip galvanized
Europ. Tech. Assessment (ETA) ETA-11/0006
Issued I Valid 27/9/2019 | -
Standard Based on EN 1992-4 with global safety factor of 3
Base material cracked, C35/45, fck,cylinder = 35.0 N/mm2, h = 300 mm
Reinforcement Exist. Reinf.: Closely spaced
Edge reinf. and stirrups present
Reinf. to control splitting present
Tolerance data tolerance interval: -500 mm/500 mm
most unfavorable tolerance: 0 mm

2 Overall Result
Design ok! (Maximum utilization: 91%)

2.1 Fixtures/Channel bolt groups


Fixture 1

3 Load case / Resulting bolt forces


Load case: Service load

Input data and results must be checked for agreement with the existing conditions and for plausibility!
126
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 2
Specifier: Project:
Address: Fastening point: CA01_Starter
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.1 Load distribution
3.1.1 Fixture 1: bolt: HBC-C 8.8F, M16 x 50 mm
Profile: Flat bar; L x W x T = 500 x 15 x 0 mm
Standoff: No standoff
Plate dimensions: 500 mm x 150 mm x 15 mm
Anchorplate design calculated: no
Bolt N [kN] V [kN] Vx [kN] Vy [kN]
1.1 8.078 2.425 0.000 -2.425
1.2 8.078 2.425 0.000 -2.425
1.3 8.078 2.425 0.000 -2.425 1.1 1.2 1.3 1.4
1.4 8.078 2.425 0.000 -2.425 Tension

max. concrete compressive strain: 0.13 [‰]


max. concrete compressive stress: Compression
4.4 [N/mm2]
resulting tension force in (x/y)=(250.0/85.0): 32.311 [kN]
resulting compression force in (x/y)=(250.0/9.8): 32.311 [kN]
Anchor forces are calculated based on the assumption of a rigid anchor plate.

3.2 Derivation of forces acting on anchor channels

Anchor forces [kN]


Anchor N [kN] V [kN]
a1 9.224 -2.769
a2 13.863 -4.162
a3 9.224 -2.769

3.3 Verifications for anchor channels under tension loadingBased on (EOTA TR 047 section 7.2 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete cone 13.863 19.959 70 ok

3.4 Verifications for anchor channels under shear loadingBased on (EOTA TR 047 section 7.3 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete edge - perpendicular 4.162 8.737 48 ok

Input data and results must be checked for agreement with the existing conditions and for plausibility!
127
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 3
Specifier: Project:
Address: Fastening point: CA01_Starter
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5 Combined tension and shear loads (Based on EN 1992-4 section 8.3.3 FOS = 3.0, Hilti method based on CEN/TR
17080 section 7.3)

Proof of interaction performed independently for steel failure of channel bolt, steel failure of the channel and concrete failure
3.5.1 Channel bolt (Fixture 1, Channel bolt 1.1)
2 2

(NN ) + (√V V + V ) ≤ 1.000


cb cb 2 cb 2
Ed Ed,y Ed,x
bN+V,s =
Rd,s,cb Rd,s,cb

2
=( ) = 0.03722
cb
N Ed
bN,s
N Rd,s,cb

2
=( ) = 0.01342
√V cb 2
+V
Ed,y
cb 2
Ed,x
bV,s
V Rd,s,cb

bN+V,s = (0.03722) + (0.01342) = 0.05064 ≤ 1.000


(Utilization : 6%)

3.5.2 Point of load application - channel lip (Fixture 1, Channel bolt 1.2)
k71 k71 2

(NN ; MM ) + (VV ) + (VV ) ≤ 1.0


cb ch cb cb
Ed Ed Ed,y Ed,x
bN+V,la,c = max
Rd,s,l Rd,s,flex Rd,s,l,y Rd,s,l,x

2.0
= max ( ) = 0.44136
cb ch
N M Ed Ed
bN,la,c ;
N M Rd,s,l Rd,s,flex

2.0
=( ) = 0.01189
cb
V Ed,y
bV,la,c,y
V Rd,s,l,y

2
=( ) = 0.00000
cb
V Ed,x
bV,la,c,x
V Rd,s,l,x

bN+V,la,c = 0.44136 + 0.01189 + 0.00000 ≤ 1.0


(Utilization : 46%)

bN,la,c, governing failure mode: Flexure channel


bV,la,c,y, governing failure mode: Flexure channel lip w/o lever arm - perpendicular
bV,la,c,x, governing failure mode: N/A

3.5.3 Anchor and connection between anchor and channel (Anchor a2)
k72 k72 2

(NN ) (VV ) (VV ) ≤ 1.0


a
Ed NaEd a
Ed,y VaEd,y a
Ed,x VaEd,x
bN+V,ac = max , + max , + max ,
Rd,s,a NRd,s,c Rd,s,a,y VRd,s,c,y Rd,s,a,x VRd,s,c,x
2.0
= max( )
a
N Ed NaEd
bN,ac , = 0.34314
N Rd,s,a NRd,s,c
2.0
= max( ) = 0.03093
a
V Ed,y VaEd,y
bV,ac,y ,
V Rd,s,a,y VRd,s,c,y
2
= max( ) = 0.00000
a
V Ed,x VaEd,x
bV,ac,x ,
V Rd,s,a,x VRd,s,c,x
bN+V,ac = 0.34314 + 0.03093 + 0.00000 ≤ 1.0

(Utilization : 38%)

bN,ac, governing failure mode: Connection anchor-channel


bV,ac,y, governing failure mode: Anchor - perpendicular
bV,ac,x, governing failure mode: N/A

Input data and results must be checked for agreement with the existing conditions and for plausibility!
128
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 4
Specifier: Project:
Address: Fastening point: CA01_Starter
Phone | Fax: | Location | Date: 23/12/2021
E-Mail:
3.5.4 Concrete anchor (Anchor a2)
a a a
bN+V,c =( NaEd
NRd ) ( ) ( ) ≤ 1.0
+
VaEd,y
VRd,y
+
VaEd,x
VRd,x
1.5
=( ) = 0.57891
a
N Ed
bN,c
N Rd

1.5
=( ) = 0.32877
a
V Ed,y
bV,c,y
V Rd,y

1.5
=( ) = 0.00000
a
V Ed,x
bV,c,x
V Rd,x

bN+V,c = 0.57891 + 0.32877 + 0.00000 = 0.90768 ≤ 1.0


(Utilization : 91%)

bN,c, governing failure mode: Concrete cone


bV,c,y, governing failure mode: Concrete edge - perpendicular
bV,c,x, governing failure mode: N/A

Remarks and warnings


• Please consider all details and hints/warnings given in the detailed report!

Design ok! (Maximum utilization: 91%)


4 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the
principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and
assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures,
and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations
carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you
bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of
the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you
must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by
Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the
current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti
will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable
breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
129
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

9.3 Checking for Embed - CA01 (FAC-70-550) @ Starter

Reaction Forces

Conservatively considering the maximum force acting on a support (largest modulation)


Rh.wl = Vwl.v(Mullion)
= 9,702.35 N ; Horizontal Load (WL)

225

Applied Loads:

Wind Load:
Fz = 9.70 kN ; Horizontal Load (WL)
ev = 250 mm ; eccenticity (225mm + 25mm tol)
Mx = Fz*ev
= 2.43 kNm ; Moment Due To WL

Combined Applied Load in Hilti Profis


Fz = 9.70 kN
Mx = 2.43 kNm

using HAC-70-550 with 4 T-bolts is Sufficient. See following report


Note: FOS = 3.0 is applied in the Hilti Profis Channel Analysis

130
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

9.4 Checking for Embed - CA01 (FAC-70-550)

Reaction Forces
Conservatively considering the maximum force acting on a support (largest modulation)
Pdl = 2,425.59 N ; Vertical Load (DL)
Rv.wl = 3,982.98 N ; Vertical Load (WL)
Rh.wl = 9,702.35 N ; Horizontal Load (WL)

300

150 150

110

210

Applied Loads
Dead Load:
Fy = 2.43 kN ; Vertical Load (DL)
ev = 235 mm ; eccenticity (210mm + 25mm tol)
Mx = Fy*ev
= 0.57 kNm ; Moment Due To DL

Wind Load:
Fy = 3.98 kN ; Vertical Load (WL)
ev = 235 mm ; eccenticity (210mm + 25mm tol)
Mx = Fy*ev
= 0.94 kNm ; Moment Due To WL

Fz = 9.70 kN ; Horizontal Load (WL)


ev = 135 mm ; eccenticity (110mm + 25mm tol)
Mx = Fz*ev
= 1.31 kNm ; Moment Due To WL

Combined Applied Load in Hilti Profis


Fy = 6.41 kN
Fz = 9.70 kN
Mx = 2.82 kNm

using HAC-70-550 with 4 T-bolts is Sufficient. See following report


Note: FOS = 3.0 is applied in the Hilti Profis Channel Analysis

131
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 1
Specifier: Project:
Address: Fastening point: CA01_Top
Phone | Fax: | Location | Date: 24/12/2021
E-Mail:
Specifier's comments:

1 Input data
Channel type HAC-70 175/550 F
bolt HBC-C 8.8F, M16 x 60 mm
Effective embedment depth hef = 175 mm
Channel specification Length: 550 mm, anchor spacing: 250 mm, projection: 25 mm,
width: bch = 45 mm, height: hch = 40 mm
Material Anchor & Channel: hot-dip galvanized
Channel bolt: hot-dip galvanized
Europ. Tech. Assessment (ETA) ETA-11/0006
Issued I Valid 27/9/2019 | -
Standard Based on EN 1992-4 with global safety factor of 3
Base material cracked, C35/45, fck,cylinder = 35.0 N/mm2, h = 300 mm
Reinforcement Exist. Reinf.: Closely spaced
Edge reinf. and stirrups present
Reinf. to control splitting present
Tolerance data tolerance interval: -500 mm/500 mm
most unfavorable tolerance: 0 mm

2 Overall Result
Design ok! (Maximum utilization: 77%)

2.1 Fixtures/Channel bolt groups


Fixture 1

3 Load case / Resulting bolt forces


Load case: Service load

Input data and results must be checked for agreement with the existing conditions and for plausibility!
132
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 2
Specifier: Project:
Address: Fastening point: CA01_Top
Phone | Fax: | Location | Date: 24/12/2021
E-Mail:
3.1 Load distribution
3.1.1 Fixture 1: bolt: HBC-C 8.8F, M16 x 60 mm
Profile: -
Standoff: No standoff
Plate dimensions: 500 mm x 300 mm x 15 mm Compression
Anchorplate design calculated: no
Bolt N [kN] V [kN] Vx [kN] Vy [kN]
1.1 6.719 2.425 0.000 -2.425
1.2 6.719 2.425 0.000 -2.425
1.3 6.719 2.425 0.000 -2.425
1.4 6.719 2.425 0.000 -2.425 1.1 1.2 1.3 1.4
Tension

max. concrete compressive strain: 0.07 [‰]


max. concrete compressive stress: 2.2 [N/mm2]
resulting tension force in (x/y)=(250.0/150.0): 26.875 [kN]
resulting compression force in (x/y)=(250.0/287.8): 20.465 [kN]
Anchor forces are calculated based on the assumption of a rigid anchor plate.

3.2 Derivation of forces acting on anchor channels

Anchor forces [kN]


Anchor N [kN] V [kN]
a1 7.672 -2.769
a2 11.531 -4.162
a3 7.672 -2.769

3.3 Verifications for anchor channels under tension loadingBased on (EOTA TR 047 section 7.2 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete cone 11.531 19.959 58 ok

3.4 Verifications for anchor channels under shear loadingBased on (EOTA TR 047 section 7.3 FOS = 3.0)
Load [kN], [kNm] Resistance [kN], [kNm] Utilization [%] Status
Concrete edge - perpendicular 4.162 8.737 48 ok

Input data and results must be checked for agreement with the existing conditions and for plausibility!
133
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 3
Specifier: Project:
Address: Fastening point: CA01_Top
Phone | Fax: | Location | Date: 24/12/2021
E-Mail:
3.5 Combined tension and shear loads (Based on EN 1992-4 section 8.3.3 FOS = 3.0, Hilti method based on CEN/TR
17080 section 7.3)

Proof of interaction performed independently for steel failure of channel bolt, steel failure of the channel and concrete failure
3.5.1 Channel bolt (Fixture 1, Channel bolt 1.1)
2 2

(NN ) + (√V V + V ) ≤ 1.000


cb cb 2 cb 2
Ed Ed,y Ed,x
bN+V,s =
Rd,s,cb Rd,s,cb

2
=( ) = 0.02575
cb
N Ed
bN,s
N Rd,s,cb

2
=( ) = 0.01342
√V cb 2
+V
Ed,y
cb 2
Ed,x
bV,s
V Rd,s,cb

bN+V,s = (0.02575) + (0.01342) = 0.03917 ≤ 1.000


(Utilization : 4%)

3.5.2 Point of load application - channel lip (Fixture 1, Channel bolt 1.2)
k71 k71 2

(NN ; MM ) + (VV ) + (VV ) ≤ 1.0


cb ch cb cb
Ed Ed Ed,y Ed,x
bN+V,la,c = max
Rd,s,l Rd,s,flex Rd,s,l,y Rd,s,l,x

2.0
= max ( ) = 0.30534
cb ch
N M Ed Ed
bN,la,c ;
N M Rd,s,l Rd,s,flex

2.0
=( ) = 0.01189
cb
V Ed,y
bV,la,c,y
V Rd,s,l,y

2
=( ) = 0.00000
cb
V Ed,x
bV,la,c,x
V Rd,s,l,x

bN+V,la,c = 0.30534 + 0.01189 + 0.00000 ≤ 1.0


(Utilization : 32%)

bN,la,c, governing failure mode: Flexure channel


bV,la,c,y, governing failure mode: Flexure channel lip w/o lever arm - perpendicular
bV,la,c,x, governing failure mode: N/A

3.5.3 Anchor and connection between anchor and channel (Anchor a2)
k72 k72 2

(NN ) (VV ) (VV ) ≤ 1.0


a
Ed NaEd a
Ed,y VaEd,y a
Ed,x VaEd,x
bN+V,ac = max , + max , + max ,
Rd,s,a NRd,s,c Rd,s,a,y VRd,s,c,y Rd,s,a,x VRd,s,c,x
2.0
= max( )
a
N Ed NaEd
bN,ac , = 0.23739
N Rd,s,a NRd,s,c
2.0
= max( ) = 0.03093
a
V Ed,y VaEd,y
bV,ac,y ,
V Rd,s,a,y VRd,s,c,y
2
= max( ) = 0.00000
a
V Ed,x VaEd,x
bV,ac,x ,
V Rd,s,a,x VRd,s,c,x
bN+V,ac = 0.23739 + 0.03093 + 0.00000 ≤ 1.0

(Utilization : 27%)

bN,ac, governing failure mode: Connection anchor-channel


bV,ac,y, governing failure mode: Anchor - perpendicular
bV,ac,x, governing failure mode: N/A

Input data and results must be checked for agreement with the existing conditions and for plausibility!
134
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROFIS Anchor Channel 1.7.7
www.hilti.com.hk
Company: Page: 4
Specifier: Project:
Address: Fastening point: CA01_Top
Phone | Fax: | Location | Date: 24/12/2021
E-Mail:
3.5.4 Concrete anchor (Anchor a2)
a a a
bN+V,c =( NaEd
NRd ) ( ) ( ) ≤ 1.0
+
VaEd,y
VRd,y
+
VaEd,x
VRd,x
1.5
=( ) = 0.43915
a
N Ed
bN,c
N Rd

1.5
=( ) = 0.32877
a
V Ed,y
bV,c,y
V Rd,y

1.5
=( ) = 0.00000
a
V Ed,x
bV,c,x
V Rd,x

bN+V,c = 0.43915 + 0.32877 + 0.00000 = 0.76792 ≤ 1.0


(Utilization : 77%)

bN,c, governing failure mode: Concrete cone


bV,c,y, governing failure mode: Concrete edge - perpendicular
bV,c,x, governing failure mode: N/A

Remarks and warnings


• Please consider all details and hints/warnings given in the detailed report!

Design ok! (Maximum utilization: 77%)


4 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the
principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and
assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures,
and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations
carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you
bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of
the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you
must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by
Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the
current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti
will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable
breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
135
PROFIS Anchor Channel © 2010 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
No. 30-34 Gillies Avenue South, 75-77 Baker Street, Hung Hom Date: 24-Dec-21
Design Calculation Report for Curtain Wall of Tower Area Rev.: 00
Embed Checking

9.5 Post Drill

Reaction Forces

Conservatively considering the maximum force acting on a support (largest modulation)


Rh.wl = Vwl.v(Mullion)
= 9,702.35 N ; Horizontal Load (WL)

200
85

Applied Loads:

Wind Load:
Fz = 2.53 kN ; Horizontal Load (WL)
ev = 120 mm ; eccenticity
Mx = Fz*ev
= 0.30 kNm ; Moment Due To WL

Combined Applied Load in Hilti Profis


Ft = 2.53 kN
Mx = 0.30 kNm

using 2-M12 is Sufficient. See following report


Note: FOS = 3.0 is applied in the Hilti Profis Channel Analysis

136
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3-R M12 hef1
Return period (service life in years): 50
Item number: 2114051 HST3-R M12x85 10/-
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,opti = 50.0 mm (hef,limit = 69.0 mm), hnom = 60.0 mm
Material: A4
Evaluation Service Report: ETA 98/0001
Issued I Valid: 4/5/2021 | -
Proof: Based on SOFA design method + fib (07/2011) - after ETAG testing with a load factor 2 and global
safety factor 3
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm

Anchor plate :
R lx x ly x t = 200.0 mm x 300.0 mm x 8.0 mm; (Recommended plate thickness: 7.0 mm)

Profile: Flat bar, ; (L x W x T) = 300.0 mm x 9.0 mm


Base material: cracked concrete, C35/45, fc,cyl = 35.00 N/mm ; h = 125.0 mm
2

Installation: hammer drilled hole, Installation condition: Dry


Reinforcement: reinforcement spacing < 150 mm (any Ø) or < 100 mm (Ø <= 10 mm)
with longitudinal edge reinforcement d >= 12.0 [mm] + close mesh (stirrups, hangers) s <= 100.0
[mm]

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
137
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 2.530; Vx = 0.000; Vy = 0.000; no no 93
Mx = 0.000; My = -0.300; Mz = 0.000;

2 Load case/Resulting anchor forces y

2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 3.736 0.000 0.000 0.000
2 3.736 0.000 0.000 0.000 x
Compression Tension
max. concrete compressive strain: 0.06 [‰]
max. concrete compressive stress: 1.90 [N/mm ]
2

resulting tension force in (x/y)=(14.0/0.0): 7.472 [kN]


resulting compression force in (x/y)=(-90.2/0.0): 4.942 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
138
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

3 Tension load (Based on SOFA (fib (07/2011), section 10.1) FOS = 3)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 3.736 14.167 27 OK
Pullout Strength* 3.736 5.445 69 OK
Combined pullout-concrete cone failure* N/A N/A N/A N/A
Concrete Breakout Failure** 3.736 4.026 93 OK
Splitting failure** 3.736 4.346 86 OK

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


42.500 3.000 14.167 3.736

3.2 Pullout Strength

NRk,p [kN] yc g M,p NRd,p [kN] NSd [kN]


12.175 1.342 3.000 5.445 3.736

3.3 Concrete Breakout Failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] y A,N ccr,N [mm] scr,N [mm]
22,500 22,500 1.000 75.0 150.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 0.750
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.700 16.106 3.000 4.026 3.736

Group anchor ID
2

3.4 Splitting failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
30,960 32,400 0.956 90.0 180.0 1.160

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1


0.0 1.000 0.0 1.000 0.973 0.750 7.700
0
NRk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
16.106 3.000 4.346 3.736

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
139
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

4 Shear load (Based on SOFA (fib (07/2011), section 10.2) FOS = 3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

5 Displacements (highest loaded anchor)


Short term loading:

NSk = 2.768 [kN] dN = 0.1815 [mm]


VSk = 0.000 [kN] dV = 0.0000 [mm]
dNV = 0.1815 [mm]
Long term loading:

NSk = 2.768 [kN] dN = 0.7259 [mm]


VSk = 0.000 [kN] dV = 0.0000 [mm]
dNV = 0.7259 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
140
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

7 Anchor plate stress check


Scope: For the loads / load combinations applied on the anchor plate, an anchor plate stress check is performed (based on the results of a
FE calculation). This stress check contains normal stresses resulting from bending moments in two directions. The user is responsible to
select an anchor plate thickness that meets the requirement per guideline for a rigid anchor plate (to ensure that the assumed load distribution
(1)
is correct). A detailed description can be found in Mallée.

(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999

7.1 Base material properties

Steel type: EN S235


2
Yield stress: fy = 235.00 [N/mm ]
Partial safety factor: gm,s = 1.000
2
Ultimate strength: fu = 360.00 [N/mm ]
2
Young's modulus: Es = 205,000.00 [N/mm ]
Poisson ratio: n = 0.3

7.2 Results

Relevant load combination: LC 01

Stress distribution s 11

2
183.59 [N/mm ]

2
0.00 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
141
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

Stress distribution s 22

2
56.44 [N/mm ]

2
-23.35 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
142
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

Deformations (z-direction)
0.0 [mm]

-2.6 [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
143
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

8 Installation data
2 2
Anchor plate, steel: EN S235; E = 205,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3-R M12 hef1
Profile: Flat bar, ; (L x W x T) = 300.0 mm x 9.0 mm Item number: 2114051 HST3-R M12x85 10/-
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 60 Nm
Plate thickness (input): 8.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: 7.0 mm Hole depth in the base material: 80.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST3 stud anchor with 50 mm embedment, M12 hef1, Stainless steel, installation per ETA 98/0001, with annular gaps filled with Hilti
Filling set or any suitable gap solutions

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Hilti SIW 6AT-A22 + SI AT-A22
• Properly sized drill bit • Filling set
• Torque wrench
• Hammer

95.0
y
100.0 100.0
50.0

2
150.0
200.0

x
150.0

1
50.0

110.0 90.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 10.0 -100.0 - 82.0 - -
2 10.0 100.0 - 82.0 - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
144
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

9 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
145
Hilti PROFIS Engineering 3.0.74

www.hilti.com.hk
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Cladding Anchor Date: 24/12/2021
Fastening point:

10 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
146

You might also like