DIRIS A-40
Strong points
Advantages
Assisted configuration Connected to the Cloud
The configuration wizard guides the The range comprises IoT ready connected
user step by step. It also detects and products that enable data to be exported For more information, see page
corrects configuration errors. This cuts the automatically for remote operation without any
commissioning time in half and always delivers limit on time, distance and time in storage.
a reliable result. Conformity to standards
Compliant with IEC 61557-12
Smart sensors Reference standard for PMDs (Performance > IEC 61557-12
Three current sensor formats (solid-core TE, metering & monitoring devices), > UL E257746
split-core TR and Rogowski coil TF) allow IEC 61557-12 standard guarantees > EN 50160
integration of the DIRIS A-40 into new and performance levels and satisfactory
existing electrical installations. performance from the PMDs under the
See page environmental conditions typical of industrial
and tertiary applications.
Functions
Multi-measurement Quality Monitoring of protection
• Currents • Voltage Unbalance • Auxiliary contact monitoring
- I1, I2, I3, In, Isystem - Vdir, Vinv, Vhom, Udir, Uinv, Unba, Vnba, Vnb, Unb • Report and alarm on trips
• Voltages & frequency • Current unbalance • Number of operations
- V1, V2, V3, VN, Vsystem, U12, U23, U31, - Idir, Iinv, Ihom, Inba, Inb Load curves and historical records (max. 130 days)
Usystem, f • Total harmonic distortion • Active, reactive and apparent power
• Powers - Currents THDi1, THDi2, THDi3,THDiN, TDDI • Currents, voltages and frequency
- P1, P2, P3, ΣP, Q1, Q2, Q3, ΣQ, S1, S2, S3, ΣS - Phase-to-neutral voltage THDv1, THDv2, THDv3 Alarms
- Predictive powers ΣP, ΣQ, ΣS - Phase-to-phase voltage THDu12, THDu23, • Alarms for all electrical values, events and input
• Power factor THDu31 status changes, possibility of logical combination
- PF1, PF2, PF3, ΣPF • Individual harmonics up to rank 63 • Time-stamping of events
• Cos ϕ & tangent ϕ - Currents: I1h, I2h, I3h, INh Communication
- Instantaneous values per phase - Phase-to-neutral voltage: V1h, V2h, V3h • DIRIS A-40 RS485 Modbus as standard
Metering - Phase-to-phase voltage: U12h, U23h, U31h • DIRIS A-40 Ethernet Modbus
• Active energy: +/- kWh • Quality events • DIRIS A-40 PROFIBUS DPV1
• Reactive energy: +/- kvarh - Voltage sags, cut-offs and swells EN50160 Inputs
• Apparent power: kVAh - Kfactor & Crest factor • 3 digital inputs
• Multi-tariff (8 max.) • Events according to EN 50160 - Power supplied from DIRIS A-40 or an external source
• Hour Meter - Voltage dips, outages, voltage surges - Function: logic status, status of circuit breaker, counting
of pulses or synchronization multifluid metering
• 2 logical outputs
- Function: Command, energy pulse output,
load sheeding, alarm
Functions
Monitoring Metering Alarming
• Real-time measurement of electrical values. • Measurement of active, reactive • Display of alarms.
• View data as graphs or tables. and apparent energies. • History of alarms.
• Power quality analysis of the utility supply • Historical record of measurements.
and of loads. • Graphic display on monthly, weekly, daily or
soft_027_a_1_fr_cat.eps hourly basis.
soft_036_a_1_fr_cat.eps
soft_025_a_1_fr_cat.eps
Terminals Dimensions (mm)
98
diris_967_a_1_x_cat.ai
USB Profibus 92 68 17
98
Ethernet
3 digital
inputs
diris_968_a_1_en_cat.ai
Current
measurement
2 digital
outputs
RJ12 L1
RS485
diris-b_024_b_1_x_cat.ai
Slave
I 01 I 02 I 03 L2 NC
L3
LIYCY-CY
N
3 inputs supplied by the product 110-230VAC I 01
1 1 1
diris_971_a_1_x_cat.ai
12 VDC
diris_977_a.ai
V1 V2 V3 VN
1 L
IN
2 N
3
1. 0.5 INPUT
A gG / 0.5 A class CC fuses.
1
2
3
OUTPUT
Connections
Associated current sensors
Various types of current sensors can be connected to the DIRIS A-40: solid-core (TE), split-core (TR) or Rogowski (TF). This range of sensors is suitable for all types of
new or existing installations. A quick RJ12 connection makes wiring easy and reliable and prevents wiring errors. The DIRIS A-40 automatically recognizes the sensor
size and type. This guarantees the overall accuracy of the DIRIS A-40 + current sensor measurement chain.
For more information: see page 488)
TF
diris-t_001_a_1_cat.eps
diris-t_003_a_1_cat.eps
DIRIS A-40
TR/iTR
RJ12 Connection
diris-t_016_a_1_cat.eps
diris_991_a.eps
tore_082_a.eps
L1 L1
L2 L2
L3 L3
N
3 +N 3
diris_973_a.ai
diris_974_a.ai
Three-phase Single-phase
3P - 1CT (1 balanced three-phase load) 1P+N - 1CT (1 single-phase load)
L1 L1
L2 N
L3
1
3
diris_976_a.ai
diris_975_a.ai
References
DIRIS A-40 monitoring devices Reference
DIRIS A-40 RS485 Modbus - 3 inputs / 2 outputs 4825 0500
DIRIS A-40 Ethernet Modbus TCP and webserver - RS485 Modbus - 3 inputs / 2 outputs 4825 0501
DIRIS A-40 Profibus DPV1 - RS485 Modbus - 3 inputs / 2 outputs 4825 0502