Contents
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-2
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-2
Standard Metal-Clad Switchgear Assembly Ratings . . 5.3-6
Usual and Unusual Service Conditions . . . . . . . . . . . . 5.3-7
Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-8
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-8
Switchgear Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Protective Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Ohmic Voltage Sensing (OVS) . . . . . . . . . . . . . . . . . . . 5.3-22
Thermal Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-23
Dummy Element (Dummy Breaker). . . . . . . . . . . . . . . 5.3-23
Roll-on-the-Floor Breaker Option . . . . . . . . . . . . . . . . . 5.3-24
Integral Motorized Remote Racking Option
(VC-W MR2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-25
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-29
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-30
Ratings
Maximum Voltages: VCP-W Circuit Breaker
4.76 kV, 8.25 kV, 15 kV
Fixed
Interrupting Ratings: Stem
4.76 kV: Up to 63 kA
8.25 kV: Up to 63 kA
15.0 kV: Up to 63 kA
Contacts
Continuous Current—Circuit Breakers:
Bellows
1200 A, 2000 A, 3000 A (5 and 15 kV) Shield Arc-Resistant Switchgear
4000 A Forced cooled (5 and 15 kV) with Plenum Installed
Movable
Continuous Current—Main Bus: Stem
1200 A, 2000 A, 3000 A (5 and 15 kV)
4000 A (5 and 15 kV)
Support Gasket Only
Note: Continuous currents above 4000 A,
(Seal Formed by Bellows)
contact Eaton.
Cut-Away View of Vacuum Interrupter
(Enlarged to Show Detail)
Certifications
■ UL® and CSA® listings are available for
many configurations; consult Eaton
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-3
Arc-resistant features are intended to Circuit Breakers Internal arcing faults are those faults
provide an additional degree of protec The Type VCP-W and VCP-WC vacuum occurring in air, phase-to-phase or
tion to the personnel performing normal circuit breakers, used in VacClad-W phase-to-ground, within the confines
operating duties in close proximity to arc-resistant switchgear, meet or exceed of the switchgear enclosure. Arcing
the equipment while the equipment is all ANSI and IEEE standards applicable to faults can occur within a switchgear
operating under normal conditions. The ac high-voltage circuit breakers rated on compartment as a result of insulation
normal operating conditions for proper symmetrical current basis, including but failure or human error. The arcing fault
application of arc-resistant switchgear not limited to: C37.04, C37.06, and C37.09. produces a tremendous release of heat
designs are as follows: Also available are type VCP-WG vacuum energy at the point of the fault, which
circuit breakers conforming to IEEE heats and expands the air volume within
■ All doors and covers providing access the enclosure, and may decompose or
to high-voltage components are standard C37.013 for ac high-voltage
generator circuit breakers. vaporize materials exposed to an arc or
properly closed and latched involved in its path.
■ Pressure relief devices are free
to operate The effects of this type of fault vary
Third-Party Certification depending on enclosure volume, arc
■ The fault energy available to the 5 and 15 kV arc-resistant metal-clad duration, arc voltage, and available
equipment does not exceed the switchgear assemblies can be provided short-circuit current. If the switchgear
rating of the equipment (short- with CSA (Canada or USA) or UL is not designed and tested to withstand
circuit current and duration) (USA only) listing. Contact Eaton effects of internal arcing faults, its parts
■ There are no obstructions around the for available ratings. could blow away along with discharge
equipment that could direct the arc of hot decomposed matter, gaseous or
fault products into an area intended to particulate, causing injury to personnel
be protected Arc-Resistant Metal-Clad Switchgear that may be present in its vicinity.
■ The equipment is properly grounded Arc-resistant metal-clad switchgear also Arc-resistant switchgear is designed
conforms to C37.20.2 and is tested as such to channel and control effects of the
The user should also refer to documents for short time and momentary short- arcing fault and its enclosure is tested
such as NFPA 70E, for safety training circuit withstand for through bolted fault. for withstand against such fault in
and safe work practices and methods In addition, the enclosure is also tested in accordance with IEEE guide C37.20.7.
of evaluating safe work distances from accordance with IEEE guide C37.20.7 for
energized equipment based on the withstand against the effects of internal
potential flash hazard, and use proper arcing faults as shown in Figure 5.3-1. Medium-Voltage Vacuum Circuit
PPE when working on or near energized Breaker Features and Ratings
equipment with the door/cover opened
VacClad-W metal-clad arc-resistant
or not properly secured. Three-Phase switchgear is designed for use with
Test Source
Main (High Voltage)
Eaton’s state-of-the-art medium-
Standards Bus voltage vacuum type VCP-W (standard
ANSI), VCP-WC (extra capability), and
Switchgear Assembly VCP-WG (generator) circuit breakers.
Eaton’s VacClad-W metal-clad arc- Refer to Table 5.3-6, Table 5.3-9 and
resistant switchgear meets or exceeds Table 5.3-11 for complete list of
the following standards and test guides: BKR available ratings.
Ground
North American Documents Bus
■ IEEE C37.20.2—Standards for
Metal-Clad Switchgear 0.5 mm Dia. (24 AWG) Wire
Used to Initiate Arcing Fault
■ IEEE C37.20.7—Guide for Testing
Metal-Enclosed Switchgear for
Internal Arcing Faults Figure 5.3-1. Arc-Resistant Switchgear
Enclosure Internal Arcing Short-Circuit
Canadian Documents Withstand Test
■ CSA C22.2 No. 31-04—
Switchgear Assemblies
■ EEMAC G8-3.2—Metal-Clad and
Station Type Cubicle Switchgear
■ EEMAC G14-1—Procedure for testing
the resistance of metal-clad switchgear
under conditions of arcing due to an
internal fault. The G14-1 was the first
North American testing guide
introduced in 1987
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-4
Arc-Resistant Enclosure and ■ Easy access and viewing ports are Control Compartments
provided on the door to allow operator
Arc Exhaust to carry out normal functions with
The control compartment doors can be
opened to access control wiring without
VacClad-W arc-resistant switchgear is the door closed and latched, with no having to de-energize the primary circuit.
designed to withstand effects of internal exposure to potential arc flash. Those The control compartments have been
arcing faults up to its rated arc short- functions include: Breaker levering tested to provide arc-resistant protection
circuit current and duration. The arc- and manual opening of the circuit with its door opened under normal
withstand capability of the switchgear breaker, viewing of open/close status operating condition. Please note the
enclosure is achieved by use of reinforced of the breaker main contacts, viewing control compartment door should be
heavier gauge steel where needed, of charged/discharged status of opened only for access to control wiring
smart latching of doors and covers, and the closing springs, viewing of when needed, and should remain closed
top-mounted built-in pressure relief mechanical operations counter, at all other times.
system. Following are standard design and breaker position
features built into each arc-resistant
switchgear assembly. Relay Box on Breaker Compartment
Auxiliary Compartments
■ The formed steel compartment design VacClad arc-resistant 5/15 and 38 kV Door in 5/15 kV Switchgear
provides sealed joints under fault designs permit maximum of two auxiliary When needed for additional relays/
conditions.This prevents smoke and gas drawers in one vertical section. The 27 kV instruments/controls, a relay box
from escaping to other compartments, design permits maximum of only one mounted on the breaker compartment
a condition that can occur with auxiliary drawer per vertical section. door provides ample space for individual
switchgear compartments designed breaker relaying and controls. Access to
with conventional flat bolted panels ■ Each auxiliary drawer is equipped with
control wiring or device terminals that
cell-mounted levering mechanism. The
■ Integral, pressure release flap vents are enclosed within the relay box does
mechanism is mechanically interlocked
mounted on top of each individual not require opening of the circuit breaker
with its compartment door such that
vertical section provide for controlled compartment door.
the door cannot be opened and access
upward release of arc created over
to auxiliary drawer cannot be gained
pressure, fire, smoke, gases and
until the drawer is first levered out Arc Exhaust Wall and Arc Exhaust
molten material out of the assembly
to the disconnected position. This
without affecting structural integrity,
interlocking ensures that the levering Chamber (Plenum)
and protect personnel who might be Refer to Page 5.3-38.
of the auxiliary drawer into or out from
present in the vicinity of the switchgear
the connected position is done with
■ The structure roof, including the compartment door closed and latched,
pressure release flap vents, is drip with no exposure to potential arc flash Three-Phase
proof. The design is made strong such Test Source
■ A viewing window is provided on the
that the roof can be “walked-on” when (Low Voltage)
door and on front panel of the drawer Main Bus
the gear is completely de-energized
to allow viewing of the drawer position
(for example, during installation)
and the primary fuses
■ Since arc pressure is vented out
■ In 5/15 kV designs, each auxiliary
through the top of each individual
drawer can also accommodate a single-
vertical section, the equipment
phase CPT rated up to 15 kVA, with BKR
damage is confined to individual
primary fuses, or the drawer can also
structures, minimizing damage to
be configured as a fuse drawer with
adjacent structures
two or three primary fuses, and
connected to a fixed mounted CPT
Circuit Breaker Compartment (single-phase or three-phase 45 kVA Shorting Bar
(Bolted Fault)
maximum) in the rear of the structure
■ The levering mechanism is
mechanically interlocked with the ■ In 27 kV designs, an auxiliary drawer
can be configured as a fuse drawer Figure 5.3-2. Metal-Clad Switchgear Short-
compartment door such that the door Circuit and Momentary Withstand Tests
cannot be opened until the circuit with two primary fuses and connected
breaker is opened and levered out to to a fixed-mounted CPT (single-
the test/disconnect position. This phase 25 kVA maximum) in the rear VacClad is Corona Free
interlocking ensures that the levering of the structure Corona emissions within the standard
of the circuit breaker into or out from ■ In 38 kV designs, fuse drawer can be VacClad switchgear assemblies have
the connected position is done with provided with two primary fuses and been eliminated or reduced to very
compartment door closed and latched, connected to a fixed-mounted CPT low levels by special fabrication and
with no exposure to potential arc flash (single-phase 25 kVA maximum) in the assembly techniques, such as rounding
rear of the structure. Please note that in and buffing of all sharp copper edges
38 kV designs, a fuse drawer requires a at the joints, employing star washers
full vertical section, because it occupies for bolting metal barriers, and using
the same compartment space as specially crafted standoff insulators
required for a circuit breaker for primary bus supports. By making
switchgear assemblies corona-free,
Eaton has made its standard switchgear
more reliable.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-5
Ground Bus
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-6
EEMAC G14-1
(2-Second)
IEEE C37.20.7
60 Hz, [LIWV]
1 Minute (BIL) K*I e 2.7 *K*I 1.6 *K* I g Isc 2.6*Isc
f
(Ref. only)
kV rms kA rms kV rms kV Peak Amperes kA rms kA kA rms kA rms kA Peak Sec.
Sym. Crest Asym. Sym.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-7
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-8
Circuit Breakers VCP-W Circuit Breaker Ratings The new 1997 and 2000 editions of ANSI
standard C37.06 still include the earlier
■ Table 5.3-5 includes 5/15 kV circuit
breakers rated on the basis of K > 1 ratings as Table A1 and A1A. The
VCP-W Circuit Breakers K = 1.0 in accordance with revised change from K > 1.0 to K = 1.0 should
Eaton’s VCP-W medium-voltage circuit ANSI standards be implemented by manufacturers
breakers offer the latest in vacuum as they develop and test new circuit
■ Table 5.3-6 includes capabilities of breakers designs. The change does
technology, providing superior control traditional 5/15 kV circuit breakers rated
and protection of medium-voltage not require, recommend or suggest
on the basis of K > 1.0. Contact Eaton that manufactures re-rate and re-test
power equipment in utility, industrial, for availability of these
commercial, mining and marine existing breakers to new standard.
circuit breakers
installations. Built in a state-of-the-art And accordingly, Eaton continues to
ISOT 9002 certified facility, they meet and The following discussion provides a brief offer both circuit breakers rated on the
exceed all ANSI and IEC requirements. explanation of rated voltage range factor traditional basis of K > 1.0 just as
Available in drawout configurations, K = 1 and K > 1.0. thousands of those breakers have been
Eaton’s vacuum circuit breakers are a applied for variety of circuit switching
result of our ongoing commitment to applications worldwide, and also as Eaton
research and development, which have Discussion of changes in the develops new breakers, they are rated
resulted in significant breakthrough Rated Voltage Range Factor, and tested to the new K = 1 ratings.
technologies. Each breaker is provided
with its unique Quality Assurance
K, or “K-factor” As a leader in vacuum interruption
Certificate that documents all tests In 1997 and 2000 editions of ANSI C37.06, technology, Eaton continues to provide
and inspections performed. under Table 1, preferred values for the a wide choice of modern vacuum circuit
rated voltage range factor, K, were set to breakers so that the user can select the
VCP-W Standard Features 1.0 for all indoor circuit breaker ratings. most economical circuit breaker that can
This was done because interrupting satisfy their circuit switching application.
■ Eaton’s maintenance-free vacuum capabilities of today’s vacuum circuit
interrupters with visual contact breakers are better represented by
erosion indicator K = 1.0.
■ Non-sliding/non-rolling V-Flex™
current transfer system Unlike old air-magnetic and oil circuit
breakers, today’s vacuum breakers
■ Glass polyester insulation generally do not require a reduction in
■ Front-accessible operating interrupting current, as the operating
mechanism voltage is raised to rated maximum
■ Electrically operated trip-free, voltage, for example from 11.5 kV up to
spring stored energy mechanism 15 kV. The interrupting capability of
vacuum circuit breakers is essentially
■ Interlocks that prevent moving a constant over the entire range of
closed circuit breaker into or out operating voltages, up to and including
of the connected position its rated maximum voltage.
■ Closing springs automatically
discharge before moving the circuit The change was also made as a step
breaker into or out of the enclosure toward harmonizing preferred ANSI
ratings with the preferred ratings of
■ Provisions for manual charging of IEC standards. It was further recognized
closing springs that it is much simpler to select and
■ Manual close and trip pushbuttons apply circuit breakers rated on the
■ Operations counter basis of K = 1.0.
■ Closing spring charged/discharged The change in the K value, however,
indicator in no way affects the ratings and
■ Circuit breaker Open/Closed capabilities of circuit breakers originally
indicator tested and rated on the basis of K > 1
in the earlier editions of C37.06. Existing
■ Auxiliary switch with 2A/3B for dc
circuit breakers, with ratings based on
and 1A/3B for ac spare contacts K > 1.0, are still perfectly valid, meet the
■ Spring charging motor, close coil, latest editions of the standards, and
trip coil, latch check switch and should be continued to be applied as
anti-pump relay they have been in the past. The original
K > 1.0 ratings are neither “obsolete”
nor “inferior” to the new K = 1.0 ratings;
they are just different.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-9
Table 5.3-5. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0)
(Continued on next page)
Identification Rated Values
Drawout Circuit Insulation Level Short-Circuit Ratings (Reference C37.04-1999 and C37.06-2009 Except as Noted a)
Breaker Type Transient Recovery Voltage
Asymmetrical Interrupting
Symmetrical Interrupting
dc Component (% dc) d
Short-Time Withstand
Maximum Voltage (V)
Continuous Current b
Interrupting Time
Voltage (1 min.)
Current (2.6 x I)
(T2 = t3 x 1.137)
RRRV = uc/t3 g
Time to Peak
Current (It) e
Peak Voltage
Current (I) c
Current f
(E2) = (uc)
Units kV rms Hz kV kV A kA rms % kA rms kA rms kV µsec µsec kV/ ms Cycles
rms Peak rms sym asym Peak Peak µsec (60 Hz)
Total
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-10
Table 5.3-5. Available VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0) (Continued)
Identification Rated Values
Drawout Capacitance Current Switching Capability Out-of-Phase
Circuit Breaker (Reference C37.04a-2003, C37.06-2009 and C37.09a-2005) Switching
Type Back-to-Back Capacitor Switching
Voltage = 1.44 x V
Inrush Frequency
Current = 0.25 x I
Operating Duty
Inrush Current
Bank Current
Units A Duty No-Load Class A Class A Class A kA kHz kV kA
rms Cycle Operations rms rms rms Peak rms rms
ab
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-11
Table 5.3-6. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K > 1) abcd
Identification Rated Values Related Required Capabilities
Recovery Voltage g
Rated Continuous
Current at 60 Hz
Voltage (1 min.)
K Times Rated 2.7 K 1.6 K
Rate of Rise of
Short-Circuit Times Times
Current f Rated Rated
Short- Short-
Rated
Circuit Circuit
Current Current
V Ie E2 V/K KI KI 2.7 KI 1.6 KI l m
kV MVA kV K e kV kV f kA kV T2 h Yi j kV kA kA rms S
Class Class rms rms Crest Amp rms Crest µS kV/ Cycles Sec. ms rms kA rms kA rms Crest asym.
µS
50 VCP-WND 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250
50 VCP-W 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250 2000
3000
50 VCP-W 4.16 350 4.76 1.19 19 60 1200 41 8.9 50 0.2 5 2 300 4.0 49 49 132 78 1.2
350 2000
3000
75 VCP-W 7.2 500 8.25 1.25 36 95 1200 33 15.5 60 0.29 5 2 300 6.6 41 41 111 66 1.2
500 2000
3000
150 VCP-W 13.8 500 15 1.30 36 95 1200 18 28 75 0.42 5 2 300 11.5 23 23 62 37 1.2
500 2000
3000
150 VCP-W 13.8 750 15 1.30 36 95 1200 28 28 75 0.42 5 2 300 11.5 36 36 97 58 1.2
750 2000
3000
150 VCP-W 13.8 1000 15 1.30 36 95 1200 37 28 75 0.42 5 2 300 11.5 48 48 130 77 1.2
1000 2000
3000
a For capacitor switching, refer to Table 5.3-5 and Table 5.3-7. h 3-cycle rating available, refer to Table 5.3-5 and Table 5.3-7.
b 5 and 15 kV circuit breakers are UL listed. i Tripping may be delayed beyond the rated permissible tripping delay at
c Circuit breakers shown in this table were tested in accordance with lower values of current in accordance with the following formula:
IEEE standard C37.09-1979.
( )
2
d Contact Eaton for availability of these circuit breakers. (KTimes Rated Short-Circuit Current)
T (seconds) =Y Short-Circuit CurrentThrough Breaker
e For three-phase and line-to-line faults, the symmetrical interrupting
capability at an operating voltage The aggregate tripping delay on all operations within any 30-minute period
must not exceed the time obtained from the above formula.
Isc = V (Rated Short-Circuit Current)
Vo j For reclosing service, there is No derating necessary for Eaton’s
VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
But not to exceed KI.
the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws
Single line-to-ground fault capability at an operating voltage
have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Contact Eaton for special reclosing requirements.
Isc = 1.15 V (Rated Short-Circuit Current)
Vo k For higher close and latch ratings, refer to Table 5.3-7.
But not to exceed KI. l Included for reference only.
The above apply on predominately inductive or resistive three-phase m Asymmetrical interrupting capability = “S” times symmetrical
circuits with normal-frequency line-to-line recovery voltage equal interrupting capability, both at specified operating voltage.
to the operating voltage.
f 4000 A forced cooled rating is available for 5/15 kV. 3000 A forced
cooled rating is available for 38 kV. Contact Eaton for details.
E2
g RRRV = 1.137
T2
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-12
Clearing Time
Interrupting Time
Standard: 83 ms (5 Cycle)
Optional Available: 50 ms (3 Cycle)
ab
Contact Parting Time
Maximum Contact Parting Time = 38 ms (2-1/4 Cycle) Based on Minimum Tripping
Delay Equal to 8 ms (1/2 Cycle)
38 ms 12 ms 47 ms
52-1 Load 52-2 52-1 Opening Time Arcing Dead Time (With Arcing)
Time
7
ms 52 ms
52-2 Closing Time
Source #1 Source #2
52-1 “b”
Contact
+ Makes
59 ms
Transfer 52-1
Dead Bus Time (No Arcing)
Initiate b
Control Standard Approx. 100 ms
Supply ”b“ Contact
Total Transfer Time
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-13
WCP-W Load Current Switching VCP-WC Extra Capabilities Breakers Eaton is a world leader in vacuum
Table 5.3-8 showing number of operations Introducing the VCP-WC extra capability interrupter and vacuum circuit breaker
is a guide to normal maintenance for medium-voltage drawout circuit breaker. technology, offering VCP-WC with
circuit breakers operated under usual Designed to provide all the industry- extra capabilities without sacrificing
service conditions for most repetitive leading features expected of the VCP-W, the proven features already standard
duty applications including isolated plus extra capabilities for those application with other VCP-W circuit breakers.
capacitor bank switching and shunt requirements that go beyond what is Features such as:
reactor switching, but not for arc furnace usually experienced.The performance ■ Vacuum interrupters with
switching.The numbers in the table are enhancement features of the VCP-WC copper-chrome contacts
equal to or in excess of those required make it an ideal choice for capacitor
■ V-Flex non-sliding current
by ANSI C37.06. switching duty, high altitude applications,
transfer system
transformer secondary fault protection,
Maintenance shall consist of adjusting, locations with concentrations of rotating ■ Visible contact erosion indicators
cleaning, lubricating, tightening, etc., machinery or high operating endurance ■ Visible contact wipe indicators
as recommended by the circuit breaker requirements, just to mention a few.
instruction book. ■ Front, functionally grouped controls
Consider these capability enhancements:
and indicators
Continuous current switching assumes Definite purpose capacitor switching
■ ■ Glass-polyester (5/15 kV), or epoxy
opening and closing rated continuous
■ Higher close and latch insulation (27/38 kV)
current at rated maximum voltage with
power factor between 80% leading and ■ Faster rate of rise of recovery voltage ■ Front, vertically mounted stored energy
80% lagging. mechanism
■ Higher short-circuit current
■ Drawout on extension rails
Inrush current switching ensures a ■ Higher mechanical endurance
closing current equal to 600% of rated ■ Integrally mounted wheels
■ Higher insulation level
continuous current at rated maximum ■ Quality Assurance Certificate
voltage with power factor of 30% lagging ■ Higher voltage ratings with K=1
or less, and an opening current equal ■ 3-cycle interrupting time
to rated continuous current at rated ■ Higher switching life
maximum voltage with power factor
between 80% leading and 80% lagging. ■ Designed and tested to ANSI
standards and higher
In accordance with ANSI C37.06, if a ■ WR fixed retrofit configuration
short-circuit operation occurs before available
the completion of the listed switching
operations, maintenance is recommended
and possible functional part replacement
may be necessary, depending on previous
accumulated duty, fault magnitude and
expected future operations.
4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
4.76, 8.25, 15 3000 All 1000 5000 5000 400
4.76, 15 All 37 kA and above 1000 5000 5000 400
27 All All 500 2500 2500 100
38 All All 250 1500 1500 100
a Each operation is comprised of one closing plus one opening.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-14
Table 5.3-9. Extra Capability Type VCP-WC Ratings (Symmetrical Current Basis), Rated K = 1
Identification Rated Values Mechanical
Circuit Voltage Insulation Current Maximum Rate of Capacitor Switching Ratings Endurance
Breaker Level Short-Circuit Current Permissible Rise of General Definite Purpose
Type Tripping Recovery Purpose
Delay Voltage Back-to-Back
Short-Time Current
Interrupting Time b
Current
Sym. Interrupting
Inrush Frequency
Voltage (1 min.)
for 3 Seconds a
Capacitor Bank
at Voltage (Isc)
Inrush Current
Capability
at 60 Hz
Current
kV K kV kV A kA % kA kA kA ms Seconds kV/µs A rms A rms kA kHz No-Load
rms rms Peak rms rms rms Peak rms Peak Operations
Total
50 VCP-W 25C 5.95 1 24 75 1200 25 50 31 97 25 50 2.0 0.9 400 & 630 400 & 630 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 1000 18 2.7 10,000
3000 d 75 36 0.8 250 — — — 5,000
50 VCP-W 40C 5.95 1 24 75 1200 40 75 58 139 40 50 2.0 0.9 630 630 15 3.5 10,000
2000 0.9 1000 1000 18 2.7 10,000
3000 d 0.8 250 — — — 5,000
50 VCP-W 50C 5.95 1 24 75 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
50 VCP-W 63C 5.95 1 24 75 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
75 VCP-W 50C 10.3 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
150 VCP-W 25C 17.5 1 42 95 1200 25 50 31 97 f 25 50 2.0 0.9 400 & 600 g 400 & 600 g 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 75 36 0.8 250 g — — — 5,000
150 VCP-W 40C 17.5 1 42 95 1200 40 75 58 139 40 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 0.8 250 g — — — 5,000
150 VCP-W 50C 17.5 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 57 64 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 52 62 0.8 250 g — — — 5,000
150 VCP-W 63C 15 1 42 95 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
a Except as noted.
b 3 cycles.
c Contact Eaton for higher RRRV or for more information.
d 4000 A FC rating available.
e C37.04.a-2003 Class C2 at 15 kV.
f Close and Latch Current for 1200 A Type 150 VCP-W 25C is proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
g Capacitor Switching Ratings are proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
h 2.5 seconds.
i 1.6 second.
j 1 second.
k 2000 A FC to 3000 A.
l 2500 A FC to 3000 A.
m Tested at 27 kV, 350 A isolated or back-to-back capacitor bank, inrush current 4.6 kA, inrush frequency 1.2 kHz.
Note: 38 kV, 2500 A and 3000 A WC breakers are not rated for rapid reclosing.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-15
Type VCP-WG Generator Generator circuits have unique Generator Circuit Configuration
characteristics that require specially The transformer and generator can be
Circuit Breakers designed and tested circuit breakers. in close proximity to the circuit breaker.
The IEEE developed the special industry See Figure 5.3-5. Applications with
standard C37.013 and amendment high continuous current levels require
C37.013a-2007 to address these connections with large conductors of
characteristics. Eaton has dedicated years very low impedance. This construction
of research, design, enhancement and causes unique fault current and voltage
testing to create Eaton’s family of conditions as shown in Figure 5.3-6.
generator breakers.
The VCP-WG (drawout) and VCP-WRG Generator High Voltage
(fixed) circuit breakers meet, and even Circuit Breaker Circuit Breaker
exceed, the rigorous service duty “a” “b”
requirements for generator circuit
applications as defined by IEEE.
~
Generator Step-up
Eaton’s VCP-WG and VCP-WRG generator Transformer
breakers are available in two frame sizes.
The 29.00-inch frame (29.00 inches wide Figure 5.3-5. Generator Circuit Application
with front cover on) has ratings up to
VCP-WG Breaker (Front View) 15 kV, 63 kA and 3000 A (4000 A with High Continuous Current Levels
forced-air cooling). The 31.00-inch frame Generator circuit breakers must be able to
(31.00 inches wide with front cover on) handle high continuous current levels
has ratings up to 15 kV, 75 kA and 4000 A without overheating. VCP-WG drawout
(5000 A with forced-air cooling). The circuit breakers are designed to reliably
31.00-inch frame is also available in a operate up to 4000 A with natural air
fixed version with ratings up to 15 kV, convection cooling, and up to 5000 A with
75 kA and 6000 A (7000 A with forced- suitable enclosure fan cooling during
air cooling). overload conditions. VCP-WRG fixed
Count on Eaton’s innovative technology circuit breakers are designed to reliably
to handle high continuous ac current operate up to 6000 A with natural air
and voltage, then safely switch through convection cooling and up to 7000 A with
extreme out-of-phase voltages and suitable enclosure fan cooling during
high-stress asymmetrical currents overload conditions.
using “clean and green” vacuum
interruption without fail for over
10,000 normal operations.
Eaton’s VCP-WG generator circuit
VCP-WG Breaker (Rear View) breakers meet the strict service duty
requirements set forth by IEEE for
generator circuit applications, including:
Why generator circuit breakers?
■ Specially rated generator breakers ■ Generator circuit configuration
typically should be used on generator ■ High continuous current levels
applications 10,000 kW and above ■ Unique fault current conditions
■ A generator circuit breaker, properly
❏ Transformer-fed faults
rated and tested to the appropriate
industry standard, can protect the ❏ Generator-fed faults
generator from damage, or even ■ Unique voltage conditions
complete failure, that could occur when ❏ Very fast RRRV
feeding a faulted transformer, and also
can protect the transformer, in the event ❏ Out-of-phase switching
that a fault should occur in the generator
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-16
Contact Parting
faults, see Figure 5.3-5, fault location “b”) 8
can cause a severe condition called Current
“Delayed Current Zero,” see Figure 5.3-6). pu
6
The high ratio of inductive reactance to
resistance (X/R ratio) of the system can
cause the dc component of the fault 4
Idc
current to exceed 100%. The asymmetrical
fault current peak becomes high enough
and its decay becomes slow enough 2
that the natural current zero is delayed
for several cycles. The circuit breaker 0
experiences longer arcing time and more
electrical, thermal and mechanical stress
during the interruption. -2
The IEEE standard requires verification
that the circuit breaker can interrupt -4
under these severe conditions. Eaton’s
VCP-WG generator circuit breakers have
demonstrated their ability to interrupt -6
three-phase fault current levels up to 0 20 40 60 80 100 120 140 160
135% dc content under delayed current
zero conditions.
Figure 5.3-6. Generator-Fed Faults Can Experience Delayed Current Zero, Where the High Inductance to
Resistance Ratio of the System Can Cause the dc Component of the Fault Current to Exceed 100%
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-17
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-18
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-19
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-20
When three VTs are used, they are The minimum number of current
connected line-to-ground, and provide transformers for circuit relaying and
phase-to-phase (Vab, Vbc, Vca), as well instruments is three current transformers,
as phase-to-ground (Va, Vb, Vc) voltages one for each phase or two-phase
for metering and relaying. connected current transformers and
one zero-sequence current transformer.
If metering or relaying application requires Separate sets of current transformers
phase-to-ground voltages, use three VTs, are required for differential relays.
each connected L-G. If not, use of two
VTs connected L-L is sufficient. The minimum pickup of a ground
relay in the residual of three-phase
Protective Relays For ground detection, three VTs connected current transformers is
connected in Line-to-ground/ primarily determined by the current
Eaton can provide a wide range of broken-delta are used. transformer ratio. The relay pickup
protective relays to meet you most
A single VT, when used, can be connected can be reduced by adding one residual
complex protection and system needs.
line-to-line (it will provide line-to-line connected auxiliary current transformer.
output, for example Vab or Vbc or Vca), This connection is very desirable on main
or line-to-ground (it will provide line-to- incoming and tie circuits of low resistance
ground output, for example Va or Vb or grounded circuits.
Vc). Generally, a single VT is used to Standard accuracy current transformers
derive voltage signal for synchronizing are normally more than adequate for most
or Over Voltage/Under Voltage function. standard applications of microprocessor-
based protective relays and meters. See
Table 5.3-14 for CT accuracy information.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-21
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-22
CAPDIS
Amplifier
R2m Adapter
120 V Signal
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-23
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-24
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-25
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-26
A solid (non-blinking) light indicates that The remote LED lights are not included Technical Data
the breaker/auxiliary has reached and with MR2. If the customer needs to
stopped in the selected position. In case operate the MR2 with the hand-held Control Supply Ratings
normal operation fails, the appropriate pendant, the pendant becomes the ■ Nominal control voltage—120 Vac,
error code is displayed in a separate master and will override the customer’s 50 or 60 Hz, single-phase
two-character LED display window on the remote control signals.
pendant. A list of various error codes and ■ Control voltage range—100 to 140 Vac,
their descriptions along with suggested The VC-W MR2 controller is also equipped 50 or 60 Hz
corrective actions are printed on the with terminal blocks to allow the customer ■ Time to travel from connect to
back side of the pendant. Examples of to interface with the controller via their disconnect, or disconnect to
error states: motor overcurrent, motor SCADA system using a Modbus interface. connect—50 seconds maximum
overtemperature, motor timed out, Please note that only one of the two
options, discrete I/O interface or Modbus ■ Current draw during the travel—
breaker position unknown, open 15 A maximum for about 3 seconds
permissive, communication error interface, can be used, but not both.
Figure 5.3-13 shows an illustration of a and 3.6 A for about 24 seconds
and no breaker/auxiliary.
typical Modbus control example. ■ Optional dry output contacts when
In addition to pendant, three optional I/O Additional components shown outside included for position indications are
interfaces can be supplied as follows: the MR2 controller in Figure 5.3-13 are not rated for 125 Vac, 2 A
included with the MR2. System-level ■ External permissive contacts, when
1. I/O interface to allow racking of controls can be optionally supplied by
breaker (connect, test, disconnect) or used, must be rated for 24 Vdc, 50 mA
Eaton’s Engineering Services & Systems.
auxiliary drawer (connect, disconnect) If the customer needs to operate the MR2
by external hardwired dry contacts with the hand-held pendant, the pendant Requirements for External Contacts
and 24 Vdc output for corresponding becomes the master and will override and LEDs when Interfacing with MR2
remote position indicating LEDs. the Modbus interface. Error codes are ■ External contacts should be rated for
2. I/O board that provided dry contacts displayed on Modbus devices when minimum open circuit voltage of
for remote indication of breaker controlling the MR2 with Modbus and 24 Vdc, and be able to close and
(connect, intermediate, test, on the pendant when controlling with carry 5 mA at 24 Vdc
disconnect)/auxiliary drawer (connect, the pendant. ■ When remote LEDs are used, use
test) position within its compartment. 24 Vdc rated LEDs, current up to 20 mA
■ Optional dry output contacts when
3. I/O interface to allow breaker open/
close functions via external hardwired included for position indications are
dry contacts and 24 Vdc output for rated for 125 Vac, 2 A
corresponding remote open/close ■ External permissive contacts, when
status LEDs. used, must be rated for 24 Vdc, 50 mA
It is the customer’s responsibility to
provide single-phase 120 V, 50 or 60 Hz
nominal supply for the MR2 controller.
It can be derived from within the
switchgear if an appropriate control
power transformer is available within
the switchgear.
Type VC-W MR2 motorized racking
accessory has been endurance tested
and guaranteed for 500 operations as
required by IEEE C37.20.2.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-27
Figure 5.3-12. VC-W MR2 Controller Interface for a VCB with Distinct Test Position and Open/Close Functions
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-28
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-29
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-30
System Options
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-31
Input
Temp Sensor Terminal InsulGard
Block Relay Optional
Humidity Sensor Modem
120 Vac
Auxiliary
Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
RFCT Sensor, RTD Input, etc.) Status
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-32
Radio Frequency Current Sensor (RFCT) Epoxy Bottles with Stress Shield
(5/15 kV Switchgear)
PD Sensors
PD Sensors
PD Sensors are Installed
in Switchgear Cubicle
0
Cub12
Cub13
Cub14
Cub15
Cub16
Cub11
Cub1
Cub2
Cub3
Cub4
Cub5
Cub6
Cub7
Cub8
Cub9
Figure 5.3-17. How the Process Works—Data Analysis and Report (Sample)
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-33
Standard
Typical Application Layouts
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-34
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-35
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-36
Available Configurations
32.00
(812.8)
95.00
(2413.0) Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent
Notes:
1 = Please note that the only control space available for relays and LV devices for this configuration
is the relay box located on the breaker compartment door.
2 = Maximum current through a 2000 A breaker in this location must be limited to 1750 A.
3 = This configuration requires use of a 4000 A main bus.
4 = Maximum current through each 2000 A breaker in this configuration must be limited to 1750 A each.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-37
Auxiliary Auxiliary
Control (VT, CPT Control (VT, CPT Ampgard Ampgard
Compartment or Fuses) Compartment or Fuses) Transition Transition
Bolted Door Bolted Door
(no relays) (no relays)
(no relays) (no relays)
32.00
(812.8)
Fan Fan
Control
95.00 Compartment
(2413.0) Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent
Dynamic Vent
(Notes 2, 5) (Notes 1, 5) (Note 6) (Notes 1, 6) (Note 7)
36.00
(914.14)
Notes:
1 = Please note that the only control space available for relays and LV devices for this configuration
is the relay box located on the breaker compartment door.
2 = Maximum current through a 2000 A breaker in this location must be limited to 1750 A.
5 = Maximum current through a 3000 A breaker in this location must be limited to 2500 A.
6 = Maximum current allowed through a 3000 A circuit breaker in this configuration is 3000 A
with fans running, and 2500 A when fans are not running.
7 = Maximum current allowed through a 3000 A circuit breaker in this configuration is 4000 A
with fans running, and 2500 A when fans are not running.
Figure 5.3-21. Available Arc-Resistant Switchgear Configurations (Front Views)—5 and 15 kV (Continued)
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-38
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-39
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-40
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-41
9.00
(228.6)
6.00 6.00 9.00 6.00 6.00
(152.4) (152.4) (228.6) (152.4) (152.4)
81.00 108.00 a
(2057.4) (2743.2)
Plenum
15.25
(387.4)
VS #1 VS #2 VS #3
Front
Top View
Figure 5.3-25. Typical Arc-Resistant Switchgear, Top Entry Cables—Typical Conduit Entrance Locations—5 and 15 kV
Note: For switchgear with enclosure arc ratings of up to 41 kA rms symmetrical, minimum two vertical sections and one arc duct exit are required.
For switchgear with enclosure arc ratings of 50 kA rms symmetrical or higher, minimum three vertical sections and two arc duct exits are required.
a Depth shown is based on use of maximum one 500 kcmil per phase, or two 250 kcmil per phase power cables for each breaker entering from the top;
otherwise, use structures with 121.50-inch (3086.1-mm) depth.
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-42
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-43
Typical Weights
Table 5.3-15. Assemblies (Less Breakers) abc
Type of Main Bus Indoor Structure Indoor Structure Indoor Structure
Vertical Section Rating 36.00-Inch (914.4 mm) W 36.00-Inch (914.4 mm) W 36.00-Inch (914.4 mm) W
97.50-Inch (2476.5 mm) D 109.50-Inch (2781.3 mm) D 121.50-Inch (3086.1 mm) D
Amperes Lb (kg) Lb (kg) Lb (kg)
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-44
Typical Schematics
P
(+)
CS CS PR
C T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12
1 2
9A
4 7 5 6 7 8 9 10 3
3A
3
9
13
61
Y
51
53
55
57
LS1 a
bb a
Y SR
62
ST
52
56
58
54
ST 18 17 16 15 22 2
M b b 1
a
LC a
PS2 LS2 LS2
10A
PS Y
bb 1 bb aa
Not Available when Second 13
14
10
4
24 21 20 19
Trip Coil Option is Chosen
TRCO_51N
TRCS_
TCSSLT
LOCATION
Options
LOCATION
CCBSN CGL
LOCATION LOCATION
TCSSLT
TRCS_
TRCO_51N
N
(-)
1 S-CPU
S-TRU
FUSE
CAC120
LOCATION
S-MRU
CS
C
CS PR
T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
9UV
10UV
ac Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
ac (+) 12 UV
1 2
9A
4 5 9 6 7 8 10 3
10UV
7
Cap Trip Dev
3A
9
3
13
55
61
Y
51
57
53
a a
LS1 ac (–)
bb
Y SR
62
52
58
ST
54
ST 2
M 1
18 17 15 22 For ac UV
b b a
LC
a Trip Only
PS2 LS2 LS2 a
10A
bb PS Y
1 bb aa
Not Available when Second 13
14
56
10
4
2
LOCATION
CCBSN CRL
LOCATION LOCATION
TRCS_
TRSS
TRCO_51N
Options
Figure 5.3-27. Typical 5/15/27 kV VCP-W “dc” and “ac” Control Schematics
Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay
PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-45
(+)
CS CS PR
C T
11 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
Spring WL GL RL
Charged
9UV
Indicating
Light U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
UV U24
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12 OPTIONS
1 2 4 7 5 6 7 8 9 10 3
9A
13
57
3
61
3A
51
53
55
Y
LS1 a
bb a
54
62
Y
52
56
58
SR
ST
ST 18 17 16 15 22 2
b
LOCATION
M 1
b
10A
LC a
PS2 PS Y LS2 LS2 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
4
24 21 20 19
N
LOCATION
TRCS_
TCSSLT
TRCO_51N
CS
C U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
CS PR
T
11
Spring WL GL RL
Charged
9UV
U24 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
Indicating
Light
Auxiliary Switch #2 Optional
UV
10UV
ac Source
9UV
OPTIONS
TRCO_51N
TRCS_
TCSSLT
LOCATION
14
ac (+) 12 UV
1 2 4 7 5 9 6 7 8 10 3
10UV
9A
9
3A
3
61
55
51
a
53
57
Y
LS1 ac (-) a
bb
62
52
58
54
Y SR
ST
ST
1
18 17 15 22 2
For ac UV
M b a
LOCATION
b
Trip Only
10A
LC
PS2 PS Y LS2 LS2 a 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
56
4
24 21 20 16 19
2
LOCATION
TRCS_
TRSS
TRCO_51N
Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>
EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
5.3-46
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.