Design Guide DG022003EN Effective August 2020

Medium-voltage power distribution and control systems > Switchgear >

VacClad-W 5–15 kV, arc-resistant


metal-clad medium-voltage switchgear

Contents
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-2
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-2
Standard Metal-Clad Switchgear Assembly Ratings . . 5.3-6
Usual and Unusual Service Conditions . . . . . . . . . . . . 5.3-7

Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-8
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-8
Switchgear Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Protective Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . 5.3-20
Ohmic Voltage Sensing (OVS) . . . . . . . . . . . . . . . . . . . 5.3-22
Thermal Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-23
Dummy Element (Dummy Breaker). . . . . . . . . . . . . . . 5.3-23
Roll-on-the-Floor Breaker Option . . . . . . . . . . . . . . . . . 5.3-24
Integral Motorized Remote Racking Option
(VC-W MR2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-25
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-29
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-30

Layouts and Dimensions . . . . . . . . . . . . . . . . . . . . . . . 5.3-31


Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-33

Application Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-43


Typical Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-43
Control Power Requirements. . . . . . . . . . . . . . . . . . . . 5.3-43
Typical Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3-44

More about this product


Eaton.com/mva

Complete library of design guides


Eaton.com/designguides
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-2

General Description Additional VacClad-W Metal-Clad Arc-Resistant Switchgear—


Switchgear Offerings Accessibility Types
Eaton’s VacClad-W metal-clad switchgear VacClad-W metal-clad switchgear is also
withType VCP-W vacuum breakers available in the following designs: Arc-resistant switchgear performance is
provides centralized control and protection defined by its accessibility type
of medium-voltage power equipment and ■ 5–15 kV in accordance with IEEE test guide
circuits in industrial, commercial and ■ 5 kV 26-inch narrow wide C37.20.7 as follows:
utility installations involving generators,
motors, feeder circuits, and transmission ■ 27 kV Type 1—Switchgear with arc-resistant
and distribution lines. ■ 27 kV arc resistant designs or features at the freely
accessible front of the equipment only.
Eaton has been manufacturing arc- ■ 38 kV
resistant metal-clad switchgear since ■ 38 kV arc resistant Type 2—Switchgear with arc-resistant
1990. Eaton was the first major North designs or features at the freely acces­
Refer to the Eaton website for sible exterior (front, back and sides) of
American manufacturer to design, test
additional details. the equipment only. (Type 2 incorporates
and manufacture arc-resistant switch­gear
in accordance with EEMAC G14.1. We Type 1.)
now offer Type 2 and 2B arc-resis­tant Type 2B—Switchgear with Type 2
switchgear assemblies, designed and accessibility plus arc-resistant in front of
tested in accordance with the IEEE the instrument/control compartment with
C37.20.7, with Type VCP-W drawout the instrument/control compart­ment door
vacuum circuit breakers. opened. (Type 2B incorpo­rates Type 2.)
Eaton’s VacClad-W metal-clad arc- Eaton’s 5/15 kV switchgear is designed
resistant switchgear with Type VCP-W and tested for IEEE Type 2B accessibility,
vacuum circuit breakers can be and 27 and 38 kV switchgear is designed
configured in various combinations and tested to IEEE Type 2.
of breakers and auxiliaries to satisfy
user’s application requirements. One-
high and two-high arrangements can
be provided when required.

Ratings
Maximum Voltages: VCP-W Circuit Breaker
4.76 kV, 8.25 kV, 15 kV
Fixed
Interrupting Ratings: Stem
4.76 kV: Up to 63 kA
8.25 kV: Up to 63 kA
15.0 kV: Up to 63 kA
Contacts
Continuous Current—Circuit Breakers:
Bellows
1200 A, 2000 A, 3000 A (5 and 15 kV) Shield Arc-Resistant Switchgear
4000 A Forced cooled (5 and 15 kV) with Plenum Installed

Movable
Continuous Current—Main Bus: Stem
1200 A, 2000 A, 3000 A (5 and 15 kV)
4000 A (5 and 15 kV)
Support Gasket Only
Note: Continuous currents above 4000 A,
(Seal Formed by Bellows)
contact Eaton.
Cut-Away View of Vacuum Interrupter
(Enlarged to Show Detail)
Certifications
■ UL® and CSA® listings are available for
many configurations; consult Eaton

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-3

Arc-resistant features are intended to Circuit Breakers Internal arcing faults are those faults
provide an additional degree of protec­ The Type VCP-W and VCP-WC vacuum occurring in air, phase-to-phase or
tion to the personnel performing normal circuit breakers, used in VacClad-W phase-to-ground, within the confines
operating duties in close proximity to arc-resistant switchgear, meet or exceed of the switchgear enclosure. Arcing
the equipment while the equipment is all ANSI and IEEE standards applicable to faults can occur within a switchgear
operating under normal conditions. The ac high-voltage circuit breakers rated on compartment as a result of insulation
normal operating conditions for proper symmetrical current basis, including but failure or human error. The arcing fault
application of arc-resistant switchgear not limited to: C37.04, C37.06, and C37.09. produces a tremen­dous release of heat
designs are as follows: Also avail­able are type VCP-WG vacuum energy at the point of the fault, which
circuit breakers conforming to IEEE heats and expands the air volume within
■ All doors and covers providing access the enclosure, and may decompose or
to high-voltage components are standard C37.013 for ac high-voltage
generator circuit breakers. vaporize materials exposed to an arc or
properly closed and latched involved in its path.
■ Pressure relief devices are free
to operate The effects of this type of fault vary
Third-Party Certification depending on enclosure volume, arc
■ The fault energy available to the 5 and 15 kV arc-resistant metal-clad duration, arc voltage, and available
equipment does not exceed the switchgear assemblies can be provided short-circuit current. If the switchgear
rating of the equipment (short- with CSA (Canada or USA) or UL is not designed and tested to with­stand
circuit current and duration) (USA only) listing. Contact Eaton effects of internal arcing faults, its parts
■ There are no obstructions around the for available ratings. could blow away along with discharge
equipment that could direct the arc of hot decomposed matter, gaseous or
fault products into an area intended to particulate, causing injury to personnel
be protected Arc-Resistant Metal-Clad Switchgear that may be present in its vicinity.
■ The equipment is properly grounded Arc-resistant metal-clad switchgear also Arc-resistant switchgear is designed
conforms to C37.20.2 and is tested as such to channel and control effects of the
The user should also refer to docu­ments for short time and momentary short- arcing fault and its enclosure is tested
such as NFPA 70E, for safety training circuit withstand for through bolted fault. for withstand against such fault in
and safe work practices and methods In addition, the enclosure is also tested in accordance with IEEE guide C37.20.7.
of evaluating safe work distances from accordance with IEEE guide C37.20.7 for
energized equipment based on the withstand against the effects of internal
potential flash hazard, and use proper arcing faults as shown in Figure 5.3-1. Medium-Voltage Vacuum Circuit
PPE when working on or near energized Breaker Features and Ratings
equipment with the door/cover opened
VacClad-W metal-clad arc-resistant
or not properly secured. Three-Phase switchgear is designed for use with
Test Source
Main (High Voltage)
Eaton’s state-of-the-art medium-
Standards Bus voltage vacuum type VCP-W (standard
ANSI), VCP-WC (extra capability), and
Switchgear Assembly VCP-WG (generator) circuit breakers.
Eaton’s VacClad-W metal-clad arc- Refer to Table 5.3-6, Table 5.3-9 and
resistant switchgear meets or exceeds Table 5.3-11 for complete list of
the following standards and test guides: BKR available ratings.

Ground
North American Documents Bus
■ IEEE C37.20.2—Standards for
Metal-Clad Switchgear 0.5 mm Dia. (24 AWG) Wire
Used to Initiate Arcing Fault
■ IEEE C37.20.7—Guide for Testing
Metal-Enclosed Switchgear for
Internal Arcing Faults Figure 5.3-1. Arc-Resistant Switchgear
Enclosure Internal Arcing Short-Circuit
Canadian Documents Withstand Test
■ CSA C22.2 No. 31-04—
Switchgear Assemblies
■ EEMAC G8-3.2—Metal-Clad and
Station Type Cubicle Switchgear
■ EEMAC G14-1—Procedure for testing
the resistance of metal-clad switchgear
under conditions of arcing due to an
internal fault. The G14-1 was the first
North American testing guide
introduced in 1987

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-4

Arc-Resistant Enclosure and ■ Easy access and viewing ports are Control Compartments
provided on the door to allow operator
Arc Exhaust to carry out normal functions with
The control compartment doors can be
opened to access control wiring without
VacClad-W arc-resistant switchgear is the door closed and latched, with no having to de-energize the primary circuit.
designed to withstand effects of internal exposure to potential arc flash. Those The control compart­ments have been
arcing faults up to its rated arc short- functions include: Breaker levering tested to provide arc-resistant protection
circuit current and duration. The arc- and manual opening of the circuit with its door opened under normal
withstand capability of the switch­gear breaker, viewing of open/close status operating condition. Please note the
enclosure is achieved by use of reinforced of the breaker main contacts, viewing control compartment door should be
heavier gauge steel where needed, of charged/discharged status of opened only for access to control wiring
smart latching of doors and covers, and the closing springs, viewing of when needed, and should remain closed
top-mounted built-in pressure relief mechanical operations counter, at all other times.
system. Following are standard design and breaker position
features built into each arc-resistant
switchgear assembly. Relay Box on Breaker Compartment
Auxiliary Compartments
■ The formed steel compartment design VacClad arc-resistant 5/15 and 38 kV Door in 5/15 kV Switchgear
provides sealed joints under fault designs permit maximum of two auxiliary When needed for additional relays/
conditions.This prevents smoke and gas drawers in one vertical section. The 27 kV instruments/controls, a relay box
from escaping to other compartments, design permits maximum of only one mounted on the breaker compartment
a condition that can occur with auxiliary drawer per vertical section. door provides ample space for individ­ual
switchgear compartments designed breaker relaying and controls. Access to
with conventional flat bolted panels ■ Each auxiliary drawer is equipped with
control wiring or device terminals that
cell-mounted levering mecha­nism. The
■ Integral, pressure release flap vents are enclosed within the relay box does
mechanism is mechanically interlocked
mounted on top of each individual not require opening of the circuit breaker
with its compartment door such that
vertical section provide for controlled compartment door.
the door cannot be opened and access
upward release of arc created over­
to auxiliary drawer cannot be gained
pressure, fire, smoke, gases and
until the drawer is first levered out Arc Exhaust Wall and Arc Exhaust
molten material out of the assembly
to the disconnected position. This
without affecting structural integrity,
interlock­ing ensures that the levering Chamber (Plenum)
and protect personnel who might be Refer to Page 5.3-38.
of the auxiliary drawer into or out from
present in the vicinity of the switchgear
the connected position is done with
■ The structure roof, including the compartment door closed and latched,
pressure release flap vents, is drip with no exposure to potential arc flash Three-Phase
proof. The design is made strong such Test Source
■ A viewing window is provided on the
that the roof can be “walked-on” when (Low Voltage)
door and on front panel of the drawer Main Bus
the gear is completely de-energized
to allow viewing of the drawer position
(for example, during installation)
and the primary fuses
■ Since arc pressure is vented out
■ In 5/15 kV designs, each auxiliary
through the top of each individual
drawer can also accommodate a single-
vertical section, the equipment
phase CPT rated up to 15 kVA, with BKR
damage is confined to individual
primary fuses, or the drawer can also
structures, minimizing damage to
be configured as a fuse drawer with
adjacent structures
two or three primary fuses, and
connected to a fixed mounted CPT
Circuit Breaker Compartment (single-phase or three-phase 45 kVA Shorting Bar
(Bolted Fault)
maximum) in the rear of the structure
■ The levering mechanism is
mechanically interlocked with the ■ In 27 kV designs, an auxiliary drawer
can be configured as a fuse drawer Figure 5.3-2. Metal-Clad Switchgear Short-
compartment door such that the door Circuit and Momentary Withstand Tests
cannot be opened until the circuit with two primary fuses and connected
breaker is opened and levered out to to a fixed-mounted CPT (single-
the test/disconnect position. This phase 25 kVA maximum) in the rear VacClad is Corona Free
interlocking ensures that the levering of the structure Corona emissions within the standard
of the circuit breaker into or out from ■ In 38 kV designs, fuse drawer can be VacClad switchgear assemblies have
the connected position is done with provided with two primary fuses and been eliminated or reduced to very
compartment door closed and latched, connected to a fixed-mounted CPT low levels by special fabrication and
with no exposure to potential arc flash (single-phase 25 kVA maximum) in the assembly techniques, such as rounding
rear of the structure. Please note that in and buffing of all sharp copper edges
38 kV designs, a fuse drawer requires a at the joints, employing star washers
full vertical section, because it occupies for bolting metal barriers, and using
the same compartment space as specially crafted standoff insulators
required for a circuit breaker for primary bus supports. By making
switchgear assemblies corona-free,
Eaton has made its standard switchgear
more reliable.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-5

5/15 kV Arc-Resistant Switchgear

Front View—Type VCP-W 5/15 kV Arc-Resistant 5/15 kV Auxiliary 5/15 kV Breaker


Switchgear (Plenum Above the Switchgear Not Shown) Over Auxiliary Over Breaker

Breaker Compartment Breaker Shown Fully VTs Drawer—Shown Fuse Drawer—Shown


Withdrawn on Fully Withdrawn Fully Withdrawn
Extension Rails

Ground Bus

Rear View 5/15 kV VCP-W Rear View—Breaker Over Rear View—Bottom


Arc-Resistant Switchgear Breaker Cable Termination Cable Compartment

Note: Application layouts and dimensions—refer to Page 5.3-33 to Page 5.3-42.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-6

Arc-Resistant Switchgear Assembly Ratings


VacClad-W metal-clad arc-resistant switchgear is available for application at voltages up to 38 kV, 50 or 60 Hz.
Refer to the table below for complete list of available ratings.
Table 5.3-1. VacClad-W Arc-Resistant Metal-Clad Switchgear ab
Rated (Ref.) (Ref.) Ratings per IEEE C37.20.2-2015 Enclosure Internal Arc Withstand
Maximum Rated Rated Insulation Level Rated Main Bus Rated Rated Momentary Accessibility Rated Arc Rated Arc
Voltage c Voltage Short- Continuous Current d Short-Time Short-Circuit Type Short-Circuit Duration
Range Circuit Short- Current Withstand Withstand Current
Factor Current Power Lightning
Frequency Impulse Circuit (10-Cycle) (167 ms)
K I Current
Withstand Withstand
Voltage, Voltage Withstand

EEMAC G14-1
(2-Second)

IEEE C37.20.7
60 Hz, [LIWV]
1 Minute (BIL) K*I e 2.7 *K*I 1.6 *K* I g Isc 2.6*Isc
f
(Ref. only)
kV rms kA rms kV rms kV Peak Amperes kA rms kA kA rms kA rms kA Peak Sec.
Sym. Crest Asym. Sym.

4.76 1 25 19 60 1200, 2000, 3000, 4000 25 68 40 2B — 25 65 0.5


1.24 29 1200, 2000, 3000, 4000 36 97 58 2B — 36 93.6 0.5
1 40 1200, 2000, 3000, 4000 40 108 64 2B — 40 104 0.5
1.19 41 1200, 2000, 3000, 4000 49 132 78 2B — 49 127.4 0.5
1 50 1200, 2000, 3000, 4000 50 135 80 2B — 50 130 0.5
1 63 1200, 2000, 3000, 4000 63 170 101 2B — 63 170 0.5
8.25 1.25 33 36 95 1200, 2000, 3000, 4000 41 111 66 2B — 41 106.6 0.5
1 50 1200, 2000, 3000, 4000 50 135 80 2B — 50 130 0.5
15 1.3 18 36 95 1200, 2000, 3000, 4000 23 62 37 2B — 23 59.8 0.5
1 25 1200, 2000, 3000, 4000 25 68 40 2B — 25 65 0.5
1.3 28 1200, 2000, 3000, 4000 36 97 58 2B — 36 93.6 0.5
1 40 1200, 2000, 3000, 4000 40 108 64 2B — 40 104 0.5
1.3 37 1200, 2000, 3000, 4000 48 130 77 2B — 48 124.8 0.5
1 50 1200, 2000, 3000, 4000 50 135 80 2B — 50 130 0.5
1 63 1200, 2000, 3000, 4000 63 170 101 2B — 63 170 0.5
27 ch 1 16 60 125 1200, 2000, 2500, 3000 16 43 26 2 B 16 41.6 0.5
1 22 1200, 2000, 2500, 3000 22 60 35 2 B 22 57.2 0.5
1 25 1200, 2000, 2500, 3000 25 68 40 2 B 25 65 0.5
1 31.5 1200, 2000, 2500, 3000 31.5 85 51 2 B 31.5 81.9 0.5
1 40 1200, 2000, 2500, 3000 40 108 64 2 B 40 104 0.5
38 c 1 16 80 150 1200, 2000, 2500, 3000 16 43 26 2 B 16 41.6 0.5
1 25 1200, 2000, 2500, 3000 25 68 40 2 B 25 65 0.5
1 31.5 1200, 2000, 2500, 3000 31.5 85 51 2 B 31.5 81.9 0.5
1.65 23 1200, 2000, 2500, 3000 35 95 56 2 B 35 91 0.5
1 40 1200, 2000, 2500, 3000 40 108 64 2 B 40 104 0.5
a The switchgear assembly is designed for use with type VCP-W, VCP-WC and VCP-WG circuit breakers. However, please note that certain VCP-WC circuit breakers
may have higher capabilities than required by ANSI standards. In such cases, switchgear assembly ratings as given in this table will apply.
b Switchgear assemblies can be supplied with UL/CSA label. Contact Eaton for availability.
c 5–15 kV switchgear is supplied with a plenum. 27–38 kV switchgear is supplied with arc wall. For plenum requirements at 27 and 38 kV, contact Eaton.
d Maximum continuous current rating for circuit breaker that can be supplied at 38 kV is 2500 A.
e Please note that use of certain current transformers (for example, bar type CTs) and protective devices
may limit the duration to a value less than 2 seconds.
f These values exceed 2.6*K*I required by IEEE C37.20.2-2015.
g These values exceed 1.55*K*I required by IEEE C37.20.2-2015.
h 27 kV arc-resistant switchgear can be supplied in one-high configuration only.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
General Description 5.3-7

Usual and Unusual Applications at Frequencies Power Frequency and Impulse


Service Conditions Less Than 60 Hz Withstand Voltage Ratings
No derating is required for lower
Rated Short-Circuit Current frequency.
Usual Service Conditions Based on series of actual tests performed
Usual service conditions for operation on Type VCP-W circuit breakers and
of metal-clad switchgear are as follows: CTs, VTs, Relays and Instruments
analysis of these test data and physics
of vacuum interrupters, it has been Application at frequency other than
■ Altitude does not exceed rated frequency must be verified for
3300 feet (1000 m) found that the current interruption
limit for Type VCP-W circuit breakers is each device on an individual basis.
■ Ambient temperature within the limits
proportional to the square root of the Table 5.3-4. Altitude Derating Factors
of –30 °C and +40 ºC (–22 °F and +104 °F) frequency. Table 5.3-2 provides derating
Altitude Above Altitude Correction Factor
■ The effect of solar radiation is factors, which must be applied to breaker Sea Level in to be Applied to:
not significant interrupting current at various Feet (m) Voltage Rated
frequencies. Continuous
Current
Applications Above Table 5.3-2. Derating Factors
3300 Feet (1006 m) Interrupting Current 3300 (1006)
(and Below) 1.0 1.0
Derating Factors
Equipment utilizing sealed interrupting
50 Hz 25 Hz 16 Hz 12 Hz 4000 (1219) 0.98 0.995
devices (such as vacuum interrupters) 5000 (1524) 0.95 0.991
does not require derating of rated None 0.65 0.52 0.45 6000 (1829) 0.92 0.987
maximum voltage. The rated one-minute 6600 (2012) 0.91 0.985
power frequency withstand voltage, 7000 (2137) 0.89 0.98
the impulse withstand voltage and the 8000 (2438) 0.86 0.97
continuous current rating must be
Rated Short-Time and
9000 (2743) 0.83 0.965
multiplied by the appropriate correction Close and Latch Currents 10,000 (3048) 0.80 0.96
factor in Table 5.3-4 to obtain modified No derating is required for short time and 12,000 (3658) 0.75 0.95
ratings that must equal or exceed the close and latch current at lower frequency. 13,200 (4023) 0.72 0.94
application requirements. 14,000 (4267) 0.70 0.935
16,000 (4877) 0.65 0.925
Note: Intermediate values may be obtained Rated Continuous Current 16,400 (5000) 0.64 0.92
by interpolation. 18,000 (5486) 0.61 0.91
Because the effective resistance of circuit 20,000 (6096) 0.56 0.90
conductors is less at lower frequency,
continuous current through the circuit can
Applications Above or Below be increased somewhat. Table 5.3-3
40 °C Ambient provides nominal current rating for VCP-W
Refer to ANSI C37.20.2, Section 8.4 breakers when operated at frequencies
for load current-carrying capabilities below 60 Hz.
under various conditions of ambient Table 5.3-3. Current Ratings
temperature and load.
Rated Continuous Nominal Current at
Current at 60 Hz Frequency Below 60 Hz
Unusual Service Conditions 50 25 16 12
Hz Hz Hz Hz
Applications of metal-clad switchgear at
other than usual altitude or temperature, 1200 A 1243 1410 1519 1589
or where solar radiation is significant, 2000 A 2075 2374 2573 2703
require special consideration. Other 3000 A 3119 3597 3923 4139
unusual service conditions that may
affect design and application include:
■ Exposure to salt air, hot or humid
climate, excessive dust, dripping water,
falling dirt, or other similar conditions
■ Unusual transportation or
storage conditions
■ Switchgear assemblies when used
as the service disconnecting means
■ Installations accessible to the
general public
■ Exposure to seismic shock
■ Exposure to nuclear radiation

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-8

Circuit Breakers VCP-W Circuit Breaker Ratings The new 1997 and 2000 editions of ANSI
standard C37.06 still include the earlier
■ Table 5.3-5 includes 5/15 kV circuit
breakers rated on the basis of K > 1 ratings as Table A1 and A1A. The
VCP-W Circuit Breakers K = 1.0 in accordance with revised change from K > 1.0 to K = 1.0 should
Eaton’s VCP-W medium-voltage circuit ANSI standards be implemented by manufacturers
breakers offer the latest in vacuum as they develop and test new circuit
■ Table 5.3-6 includes capabilities of breakers designs. The change does
technology, providing superior control traditional 5/15 kV circuit breakers rated
and protection of medium-voltage not require, recommend or suggest
on the basis of K > 1.0. Contact Eaton that manufactures re-rate and re-test
power equipment in utility, industrial, for availability of these
commercial, mining and marine existing breakers to new standard.
circuit breakers
installations. Built in a state-of-the-art And accordingly, Eaton continues to
ISOT 9002 certified facility, they meet and The following discussion provides a brief offer both circuit breakers rated on the
exceed all ANSI and IEC requirements. explanation of rated voltage range factor traditional basis of K > 1.0 just as
Available in drawout configurations, K = 1 and K > 1.0. thousands of those breakers have been
Eaton’s vacuum circuit breakers are a applied for variety of circuit switching
result of our ongoing commitment to applications worldwide, and also as Eaton
research and development, which have Discussion of changes in the develops new breakers, they are rated
resulted in significant breakthrough Rated Voltage Range Factor, and tested to the new K = 1 ratings.
technologies. Each breaker is provided
with its unique Quality Assurance
K, or “K-factor” As a leader in vacuum interruption
Certificate that documents all tests In 1997 and 2000 editions of ANSI C37.06, technology, Eaton continues to provide
and inspections performed. under Table 1, preferred values for the a wide choice of modern vacuum circuit
rated voltage range factor, K, were set to breakers so that the user can select the
VCP-W Standard Features 1.0 for all indoor circuit breaker ratings. most economical circuit breaker that can
This was done because interrupting satisfy their circuit switching application.
■ Eaton’s maintenance-free vacuum capabilities of today’s vacuum circuit
interrupters with visual contact breakers are better represented by
erosion indicator K = 1.0.
■ Non-sliding/non-rolling V-Flex™
current transfer system Unlike old air-magnetic and oil circuit
breakers, today’s vacuum breakers
■ Glass polyester insulation generally do not require a reduction in
■ Front-accessible operating interrupting current, as the operating
mechanism voltage is raised to rated maximum
■ Electrically operated trip-free, voltage, for example from 11.5 kV up to
spring stored energy mechanism 15 kV. The interrupting capability of
vacuum circuit breakers is essentially
■ Interlocks that prevent moving a constant over the entire range of
closed circuit breaker into or out operating voltages, up to and includ­ing
of the connected position its rated maximum voltage.
■ Closing springs automatically
discharge before moving the circuit The change was also made as a step
breaker into or out of the enclosure toward harmonizing preferred ANSI
ratings with the preferred ratings of
■ Provisions for manual charging of IEC standards. It was further recognized
closing springs that it is much simpler to select and
■ Manual close and trip pushbuttons apply circuit breakers rated on the
■ Operations counter basis of K = 1.0.
■ Closing spring charged/discharged The change in the K value, however,
indicator in no way affects the ratings and
■ Circuit breaker Open/Closed capabilities of circuit breakers originally
indicator tested and rated on the basis of K > 1
in the earlier editions of C37.06. Existing
■ Auxiliary switch with 2A/3B for dc
circuit breakers, with ratings based on
and 1A/3B for ac spare contacts K > 1.0, are still perfectly valid, meet the
■ Spring charging motor, close coil, latest editions of the standards, and
trip coil, latch check switch and should be continued to be applied as
anti-pump relay they have been in the past. The original
K > 1.0 ratings are neither “obsolete”
nor “inferior” to the new K = 1.0 ratings;
they are just different.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-9

Table 5.3-5. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0)
(Continued on next page)
Identification Rated Values
Drawout Circuit Insulation Level Short-Circuit Ratings (Reference C37.04-1999 and C37.06-2009 Except as Noted a)
Breaker Type Transient Recovery Voltage

Lightning Impulse Withstand


Power Frequency Withstand
Parameters are Based on TD-4

Asymmetrical Interrupting
Symmetrical Interrupting

dc Component (% dc) d

Short-Time Withstand
Maximum Voltage (V)

Continuous Current b

Closing and Latching


Voltage (1.2 x 50 µs)
Power Frequency a

TRV Rise Time (t3)

Interrupting Time
Voltage (1 min.)

Current (2.6 x I)

(T2 = t3 x 1.137)

RRRV = uc/t3 g
Time to Peak
Current (It) e

Peak Voltage
Current (I) c

Current f

(E2) = (uc)
Units kV rms Hz kV kV A kA rms % kA rms kA rms kV µsec µsec kV/ ms Cycles
rms Peak rms sym asym Peak Peak µsec (60 Hz)
Total

50 VCP-W 25 4.76 60 19 60 1200 25 50 31 65 25 8.2 50 44 0.19 50 3


2000
3000
50 VCP-W 40 4.76 60 19 60 1200 40 50 49 104 40 8.2 50 44 0.19 50 3
2000
3000
50 VCP-W 50 4.76 60 19 60 1200 50 44 59 130 50 8.2 50 44 0.19 50 3
2000
3000
50 VCP-W 63 4.76 60 19 60 1200 63 55 80 164 63 8.2 50 44 0.19 50 3
2000
3000
150 VCP-W 25 15 60 36 95 1200 h 25 50 31 65 25 28 h 75 66 0.42 50 3
2000 25.7 0.39
3000
150 VCP-W 40 15 60 36 95 1200 40 50 49 104 40 25.7 75 66 0.39 50 3
2000
3000
150 VCP-W 50 15 60 36 95 1200 50 44 59 130 50 25.7 75 66 0.39 50 3
2000
3000
150 VCP-W 63 15 60 36 95 1200 h 63 55 80 164 63 28 h 75 66 0.42 50 3
2000 h
3000 h
a All circuit breakers are tested at 60 Hz; however, they can also be applied at 50 Hz with no derating.
b 4000 A fan-cooled rating is available for 3000 A circuit breakers.
c Because the voltage range factor K = 1, the short-time withstand current and the maximum symmetrical interrupting current are equal to the rated symmetrical
interrupting current.
d Based on the standard dc time constant of 45 ms (corresponding to X/R of 17 for 60 Hz) and the minimum contact parting time as determined from the minimum
opening time plus the assumed minimum relay time of 1/2 cycle (8.33 ms for 60 Hz).
e The asymmetrical interrupting current, I total, is given by (It) = I x Sqrt (1 + 2 x %dc x %dc) kA rms asymmetrical total.
f Duration of short-time current and maximum permissible tripping delay are both 2 seconds for all circuit breakers listed in this table, as required in C37.04-1999,
C37.06-2000 and C37.06-2009.
g RRRV can also be calculated as = 1.137 x E2/T2.
h These circuit breakers were tested to the preferred TRV ratings specified in C37.06-2000.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-10

Table 5.3-5. Available VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0) (Continued)
Identification Rated Values
Drawout Capacitance Current Switching Capability Out-of-Phase
Circuit Breaker (Reference C37.04a-2003, C37.06-2009 and C37.09a-2005) Switching
Type Back-to-Back Capacitor Switching

Isolated Shunt Capacitor


Cable-Charging Current

Capacitor Bank Current


Mechanical Endurance
Continuous Current

Voltage = 1.44 x V
Inrush Frequency

Current = 0.25 x I
Operating Duty

Inrush Current
Bank Current
Units A Duty No-Load Class A Class A Class A kA kHz kV kA
rms Cycle Operations rms rms rms Peak rms rms
ab

50 VCP-W 25 1200 O—0.3s—CO—3m—CO 10,000 C2 3–10 C2 75–630 C2 75–630 6 0.8 7 6.3


2000 75–1000 75–1000 0.5
3000 75–1600 75–1600 0.3
50 VCP-W 40 1200 O—0.3s—CO—3m—CO 10,000 C2 3–10 C2 75–630 C2 75–630 6 0.8 7 10
2000 75–1000 75–1000 0.5
3000 75–1600 75–1600 0.3
50 VCP-W 50 1200 O—0.3s—CO—3m—CO 10,000 C2 3–10 C2 75–630 C2 75–630 6 0.8 7 12.5
2000 75–1000 75–1000 0.5
3000 75–1600 75–1600 0.3
50 VCP-W 63 1200 O—0.3s—CO—3m—CO 10,000 C2 7.5–25 C2 75–630 C2 75–630 6 0.8 7 15.8
2000 75–1000 75–1000 0.5
3000 75–1600 75–1600 0.3
150 VCP-W 25 1200 O—0.3s—CO—3m—CO 10,000 C2 7.5–25 C2 75–630 C2 75–630 6 0.8 22 6.3
2000 C2 75–1000 C2 75–1000 0.5
3000 C1 75–1600 C1 75–1600 0.3
150 VCP-W 40 1200 O—0.3s—CO—3m—CO 10,000 C2 7.5–25 C2 75–630 C2 75–630 6 0.8 22 10
2000 C2 75–1000 C2 75–1000 0.5
3000 C1 75–1600 C1 75–1600 0.3
150 VCP-W 50 1200 O—0.3s—CO—3m—CO 10,000 C2 7.5–25 C2 75–630 C2 75–630 6 0.8 22 12.5
2000 C2 75–1000 C2 75–1000 0.5
3000 C1 75–1600 C1 75–1600 0.3
150 VCP-W 63 1200 O—0.3s—CO—3m—CO 10,000 C2 7.5–25 C2 75–630 C2 75–630 6 0.8 22 15.8
2000 75–1000 75–1000 0.5
3000 75–1600 75–1600 0.3
a Each operation consists of one closing plus one opening.
b All 40 and 50 kA circuit breakers exceed required 5000 no-load operations; all 63 kA circuit breakers exceed the required 2000 no-load ANSI operations.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-11

Table 5.3-6. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K > 1) abcd
Identification Rated Values Related Required Capabilities

Asymmetry Factor for VCP-W Breakers


Circuit Voltage Insulation Current Rated Transient Current Values
Breaker Type Level Recovery Voltage

Rated Permissible Tripping Delay

Maximum Voltage Divided by K


Maximum 3-Second Closing and

Lightning Impulse Withstand


Nominal 3-Phase MVA Class

Power Frequency Withstand


Sym. Short-Time Latching

Rated Voltage Range Factor

Rated Short-Circuit Current


Rated Maximum Voltage Inter- Current Capability

(at Rated Maximum kV)

Rated Interrupting Time


rupting Carrying (Momentary) k
Nominal Voltage Class

Rated Reclosing Time


Capability Capability

Voltage (1.2 x 50 µs)

Rated Crest Voltage

Rated Time to Crest

Recovery Voltage g
Rated Continuous
Current at 60 Hz
Voltage (1 min.)
K Times Rated 2.7 K 1.6 K

Rate of Rise of
Short-Circuit Times Times
Current f Rated Rated
Short- Short-

Rated
Circuit Circuit
Current Current
V Ie E2 V/K KI KI 2.7 KI 1.6 KI l m
kV MVA kV K e kV kV f kA kV T2 h Yi j kV kA kA rms S
Class Class rms rms Crest Amp rms Crest µS kV/ Cycles Sec. ms rms kA rms kA rms Crest asym.
µS

50 VCP-WND 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250
50 VCP-W 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250 2000
3000
50 VCP-W 4.16 350 4.76 1.19 19 60 1200 41 8.9 50 0.2 5 2 300 4.0 49 49 132 78 1.2
350 2000
3000
75 VCP-W 7.2 500 8.25 1.25 36 95 1200 33 15.5 60 0.29 5 2 300 6.6 41 41 111 66 1.2
500 2000
3000
150 VCP-W 13.8 500 15 1.30 36 95 1200 18 28 75 0.42 5 2 300 11.5 23 23 62 37 1.2
500 2000
3000
150 VCP-W 13.8 750 15 1.30 36 95 1200 28 28 75 0.42 5 2 300 11.5 36 36 97 58 1.2
750 2000
3000
150 VCP-W 13.8 1000 15 1.30 36 95 1200 37 28 75 0.42 5 2 300 11.5 48 48 130 77 1.2
1000 2000
3000
a For capacitor switching, refer to Table 5.3-5 and Table 5.3-7. h 3-cycle rating available, refer to Table 5.3-5 and Table 5.3-7.
b 5 and 15 kV circuit breakers are UL listed. i Tripping may be delayed beyond the rated permissible tripping delay at
c Circuit breakers shown in this table were tested in accordance with lower values of current in accordance with the following formula:
IEEE standard C37.09-1979.

( )
2
d Contact Eaton for availability of these circuit breakers. (KTimes Rated Short-Circuit Current)
T (seconds) =Y Short-Circuit CurrentThrough Breaker
e For three-phase and line-to-line faults, the symmetrical interrupting
capability at an operating voltage The aggregate tripping delay on all operations within any 30-minute period
must not exceed the time obtained from the above formula.
Isc = V (Rated Short-Circuit Current)
Vo j For reclosing service, there is No derating necessary for Eaton’s
VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
But not to exceed KI.
the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws
Single line-to-ground fault capability at an operating voltage
have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Contact Eaton for special reclosing requirements.
Isc = 1.15 V (Rated Short-Circuit Current)
Vo k For higher close and latch ratings, refer to Table 5.3-7.
But not to exceed KI. l Included for reference only.
The above apply on predominately inductive or resistive three-phase m Asymmetrical interrupting capability = “S” times symmetrical
circuits with normal-frequency line-to-line recovery voltage equal interrupting capability, both at specified operating voltage.
to the operating voltage.
f 4000 A forced cooled rating is available for 5/15 kV. 3000 A forced
cooled rating is available for 38 kV. Contact Eaton for details.
E2
g RRRV = 1.137
T2

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-12

VCP-W Circuit Breaker Operating Times


The closing time (initiation of close signal Figure 5.3-3 below shows the sequence
to contact make) and opening time of events in the course of circuit
(initiation of the trip signal to contact interruption, along with applicable
break) are shown in Table 5.3-7. VCP-W circuit breaker timings.
Table 5.3-7. Closing Time and Opening Time
Rated Breaker Closing Time Opening Time Milliseconds
Control Voltage Rating Milliseconds Standard 5-Cycle Breaker Optional 3-Cycle Breaker

48 V, 125 V, 250 Vdc All 45–60 30–45 30–38


120 V, 240 Vac All 45–60 — —
120 V or 240 Vac capacitor trip All — 26–41 26–38
Optional—undervoltage trip release 48 V, 125 V, 250 Vdc All — 30–45 30–45

Clearing Time

Interrupting Time
Standard: 83 ms (5 Cycle)
Optional Available: 50 ms (3 Cycle)
ab
Contact Parting Time
Maximum Contact Parting Time = 38 ms (2-1/4 Cycle) Based on Minimum Tripping
Delay Equal to 8 ms (1/2 Cycle)

Tripping Delay Time Opening Time Arcing Time


8 ms (1/2 Cycle) Minimum Delay 30–45 ms for 5 Cycle VCP-W 5–17 ms
2 sec = (120 Cycle) Maximum Delay 30–38 ms for 3 Cycle VCP-W

Protective Relay Auxiliary Relay Shunt Trip Mechanism


Operating Time Operating Time Operating Time Operating Time

Short- Rated Control Main Last


Circuit Voltage Energizes Contacts Pole
Begins Trip Coil Parts Clears

Figure 5.3-3. Sequence of Events and Circuit Breaker Operating Times


a Times shown are based on 60 Hz.
b % dc component capability (and asymmetry factor S) depend on the minimum contact parting time.
The % dc component capability is M 50% (S factor M 1.2) for all VCP-W circuit breakers.

0 10 20 30 40 50 60 70 80 90 100 Time (ms)

38 ms 12 ms 47 ms

52-1 Load 52-2 52-1 Opening Time Arcing Dead Time (With Arcing)
Time

7
ms 52 ms
52-2 Closing Time
Source #1 Source #2
52-1 “b”
Contact
+ Makes
59 ms
Transfer 52-1
Dead Bus Time (No Arcing)
Initiate b
Control Standard Approx. 100 ms
Supply ”b“ Contact
Total Transfer Time

Trip 52-1 Close 52-2 Transfer


Initiate
Signal

Figure 5.3-4. Typical Transfer Times c—Fast Sequential Transfer


c Times shown are based on 60 Hz.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-13

WCP-W Load Current Switching VCP-WC Extra Capabilities Breakers Eaton is a world leader in vacuum
Table 5.3-8 showing number of operations Introducing the VCP-WC extra capability interrupter and vacuum circuit breaker
is a guide to normal maintenance for medium-voltage drawout circuit breaker. technology, offering VCP-WC with
circuit breakers operated under usual Designed to provide all the industry- extra capabilities without sacrificing
service conditions for most repetitive leading features expected of the VCP-W, the proven features already standard
duty applications including isolated plus extra capabilities for those application with other VCP-W circuit breakers.
capacitor bank switching and shunt requirements that go beyond what is Features such as:
reactor switching, but not for arc furnace usually experienced.The performance ■ Vacuum interrupters with
switching.The numbers in the table are enhancement features of the VCP-WC copper-chrome contacts
equal to or in excess of those required make it an ideal choice for capacitor
■ V-Flex non-sliding current
by ANSI C37.06. switching duty, high altitude applica­tions,
transfer system
transformer secondary fault protection,
Maintenance shall consist of adjusting, locations with concentra­tions of rotating ■ Visible contact erosion indicators
cleaning, lubricating, tightening, etc., machinery or high operating endurance ■ Visible contact wipe indicators
as recommended by the circuit breaker requirements, just to mention a few.
instruction book. ■ Front, functionally grouped controls
Consider these capability enhancements:
and indicators
Continuous current switching assumes Definite purpose capacitor switching
■ ■ Glass-polyester (5/15 kV), or epoxy
opening and closing rated continuous
■ Higher close and latch insulation (27/38 kV)
current at rated maximum voltage with
power factor between 80% leading and ■ Faster rate of rise of recovery voltage ■ Front, vertically mounted stored energy
80% lagging. mechanism
■ Higher short-circuit current
■ Drawout on extension rails
Inrush current switching ensures a ■ Higher mechanical endurance
closing current equal to 600% of rated ■ Integrally mounted wheels
■ Higher insulation level
continuous current at rated maximum ■ Quality Assurance Certificate
voltage with power factor of 30% lagging ■ Higher voltage ratings with K=1
or less, and an opening current equal ■ 3-cycle interrupting time
to rated continuous current at rated ■ Higher switching life
maximum voltage with power factor
between 80% leading and 80% lagging. ■ Designed and tested to ANSI
standards and higher
In accordance with ANSI C37.06, if a ■ WR fixed retrofit configuration
short-circuit operation occurs before available
the completion of the listed switching
operations, maintenance is recommended
and possible functional part replacement
may be necessary, depending on previous
accumulated duty, fault magnitude and
expected future operations.

The Type VCP-WC Breakers are not


Interchangeable with Standard VCP-W
Breakers. They are Equipped with Different
Code Plates and Taller Front Panels.

Table 5.3-8. Breaker Operations Information


Circuit Breaker Ratings Maximum Number of Operations a
Rated Rated Rated Between No-Load Rated Inrush
Maximum Continuous Short-Circuit Servicing Mechanical Continuous Current
Voltage Current Current Current Switching
kV rms Amperes kA rms, sym. Switching

4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
4.76, 8.25, 15 3000 All 1000 5000 5000 400
4.76, 15 All 37 kA and above 1000 5000 5000 400
27 All All 500 2500 2500 100
38 All All 250 1500 1500 100
a Each operation is comprised of one closing plus one opening.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-14

Table 5.3-9. Extra Capability Type VCP-WC Ratings (Symmetrical Current Basis), Rated K = 1
Identification Rated Values Mechanical
Circuit Voltage Insulation Current Maximum Rate of Capacitor Switching Ratings Endurance
Breaker Level Short-Circuit Current Permissible Rise of General Definite Purpose
Type Tripping Recovery Purpose
Delay Voltage Back-to-Back

Lightning Impulse Withstand


Isolated Capacitor Switching
Power Frequency Withstand
(RRRV)
c Shunt
Capacitor

Asym. Interrupting (It)


% dc Component (Idc)
Maximum Voltage (V)

Voltage Range Factor

Closing and Latching


Bank
Continuous Current
Voltage (1.2 x 50 µs)

Short-Time Current

Interrupting Time b
Current

Sym. Interrupting

Inrush Frequency
Voltage (1 min.)

for 3 Seconds a

Capacitor Bank
at Voltage (Isc)

Inrush Current
Capability
at 60 Hz

Current
kV K kV kV A kA % kA kA kA ms Seconds kV/µs A rms A rms kA kHz No-Load
rms rms Peak rms rms rms Peak rms Peak Operations
Total

50 VCP-W 25C 5.95 1 24 75 1200 25 50 31 97 25 50 2.0 0.9 400 & 630 400 & 630 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 1000 18 2.7 10,000
3000 d 75 36 0.8 250 — — — 5,000
50 VCP-W 40C 5.95 1 24 75 1200 40 75 58 139 40 50 2.0 0.9 630 630 15 3.5 10,000
2000 0.9 1000 1000 18 2.7 10,000
3000 d 0.8 250 — — — 5,000
50 VCP-W 50C 5.95 1 24 75 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
50 VCP-W 63C 5.95 1 24 75 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
75 VCP-W 50C 10.3 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
150 VCP-W 25C 17.5 1 42 95 1200 25 50 31 97 f 25 50 2.0 0.9 400 & 600 g 400 & 600 g 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 75 36 0.8 250 g — — — 5,000
150 VCP-W 40C 17.5 1 42 95 1200 40 75 58 139 40 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 0.8 250 g — — — 5,000
150 VCP-W 50C 17.5 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 57 64 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 52 62 0.8 250 g — — — 5,000
150 VCP-W 63C 15 1 42 95 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
a Except as noted.
b 3 cycles.
c Contact Eaton for higher RRRV or for more information.
d 4000 A FC rating available.
e C37.04.a-2003 Class C2 at 15 kV.
f Close and Latch Current for 1200 A Type 150 VCP-W 25C is proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
g Capacitor Switching Ratings are proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
h 2.5 seconds.
i 1.6 second.
j 1 second.
k 2000 A FC to 3000 A.
l 2500 A FC to 3000 A.
m Tested at 27 kV, 350 A isolated or back-to-back capacitor bank, inrush current 4.6 kA, inrush frequency 1.2 kHz.
Note: 38 kV, 2500 A and 3000 A WC breakers are not rated for rapid reclosing.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-15

Type VCP-WG Generator Generator circuits have unique Generator Circuit Configuration
characteristics that require specially The transformer and generator can be
Circuit Breakers designed and tested circuit breakers. in close proximity to the circuit breaker.
The IEEE developed the special industry See Figure 5.3-5. Applications with
standard C37.013 and amendment high continuous current levels require
C37.013a-2007 to address these connections with large conductors of
characteristics. Eaton has dedicated years very low impedance. This construction
of research, design, enhancement and causes unique fault current and voltage
testing to create Eaton’s family of conditions as shown in Figure 5.3-6.
generator breakers.
The VCP-WG (drawout) and VCP-WRG Generator High Voltage
(fixed) circuit breakers meet, and even Circuit Breaker Circuit Breaker
exceed, the rigorous service duty “a” “b”
requirements for generator circuit
applications as defined by IEEE.
~
Generator Step-up
Eaton’s VCP-WG and VCP-WRG generator Transformer
breakers are available in two frame sizes.
The 29.00-inch frame (29.00 inches wide Figure 5.3-5. Generator Circuit Application
with front cover on) has ratings up to
VCP-WG Breaker (Front View) 15 kV, 63 kA and 3000 A (4000 A with High Continuous Current Levels
forced-air cooling). The 31.00-inch frame Generator circuit breakers must be able to
(31.00 inches wide with front cover on) handle high continuous current levels
has ratings up to 15 kV, 75 kA and 4000 A without overheating. VCP-WG drawout
(5000 A with forced-air cooling). The circuit breakers are designed to reliably
31.00-inch frame is also available in a operate up to 4000 A with natural air
fixed version with ratings up to 15 kV, convection cooling, and up to 5000 A with
75 kA and 6000 A (7000 A with forced- suitable enclosure fan cooling during
air cooling). overload conditions. VCP-WRG fixed
Count on Eaton’s innovative technology circuit breakers are designed to reliably
to handle high continuous ac current operate up to 6000 A with natural air
and voltage, then safely switch through convection cooling and up to 7000 A with
extreme out-of-phase voltages and suitable enclosure fan cooling during
high-stress asymmetrical currents overload conditions.
using “clean and green” vacuum
interruption without fail for over
10,000 normal operations.
Eaton’s VCP-WG generator circuit
VCP-WG Breaker (Rear View) breakers meet the strict service duty
requirements set forth by IEEE for
generator circuit applications, including:
Why generator circuit breakers?
■ Specially rated generator breakers ■ Generator circuit configuration
typically should be used on generator ■ High continuous current levels
applications 10,000 kW and above ■ Unique fault current conditions
■ A generator circuit breaker, properly
❏ Transformer-fed faults
rated and tested to the appropriate
industry standard, can protect the ❏ Generator-fed faults
generator from damage, or even ■ Unique voltage conditions
complete failure, that could occur when ❏ Very fast RRRV
feeding a faulted transformer, and also
can protect the trans­former, in the event ❏ Out-of-phase switching
that a fault should occur in the generator

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-16

Unique Fault Current Conditions Table 5.3-10. Breaker Operations Information


System-source (aka, transformer-fed) Circuit Breaker Ratings Maximum Number of Operations a
faults (see Figure 5.3-5, fault location “a”) Rated Rated Rated Between No-Load Rated Inrush
can be extremely high. The full energy of Maximum Continuous Short-Circuit Servicing Mechanical Continuous Current
the power system feeds the fault, and the Voltage Current Current Current Switching
low impedance of the fault current path kV rms Amperes kA rms, sym. Switching
does very little to limit the fault current. 4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
Eaton’s type VCP-WG Generator Circuit 4.76, 8.25, 15 3000 All 1000 5000 5000 400
Breakers are ideal for interrupting such 4.76, 15 All 37 kA and above 1000 5000 5000 400
high fault currents because they have 27 All All 500 2500 2500 100
demonstrated high interruption ratings 38 All All 250 1500 1500 100
up to 75 kA, with high dc fault content a Each operation is comprised of one closing plus one opening.
up to 75%, as proven by high power
laboratory tests.
Generator-source (aka, generator-fed)

Contact Parting
faults, see Figure 5.3-5, fault location “b”) 8
can cause a severe condition called Current
“Delayed Current Zero,” see Figure 5.3-6). pu
6
The high ratio of inductive reactance to
resistance (X/R ratio) of the system can
cause the dc component of the fault 4
Idc
current to exceed 100%. The asymmetrical
fault current peak becomes high enough
and its decay becomes slow enough 2
that the natural current zero is delayed
for several cycles. The circuit breaker 0
experiences longer arcing time and more
electrical, thermal and mechanical stress
during the interruption. -2
The IEEE standard requires verification
that the circuit breaker can interrupt -4
under these severe conditions. Eaton’s
VCP-WG generator circuit breakers have
demonstrated their ability to interrupt -6
three-phase fault current levels up to 0 20 40 60 80 100 120 140 160
135% dc content under delayed current
zero conditions.
Figure 5.3-6. Generator-Fed Faults Can Experience Delayed Current Zero, Where the High Inductance to
Resistance Ratio of the System Can Cause the dc Component of the Fault Current to Exceed 100%

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-17

Unique Voltage Conditions


Generator circuits typically produce
10.00 10.00 10.00 10.00
very fast rates of rise of recovery voltage (254.0) (254.0) (254.0) (254.0)
(RRRV) due to the high natural frequency
and low impedance and very low stray 29.00 30.00 29.00 26.60
(736.6) (762.0) (736.6) (675.6)
capacitance. VCP-WG generator circuit
breakers are designed to interrupt fault
current levels with very fast RRRV in
accordance with IEEE standard C37.013 31.40 31.20
and C37.013a. VCP-WG generator circuit (797.6) (792.5)
breakers have a distinct ability to perform
under out-of-phase conditions when
the generator and power system voltages
are not in sync. The voltages across the 24.60 24.60
open contacts can be as high as twice (624.8) (624.8)
the rated line-to-ground voltage of the
system. The IEEE standard requires 29-Inch Frame Drawout VCP-WG 29-Inch Frame Fixed VCP-WRG
demonstration by test that the genera­tor
circuit breaker can switch under specified
out-of-phase conditions. 10.00 10.00 10.00 10.00
(254.0) (254.0) (254.0) (254.0)
30.60 30.00 30.60 26.80*
Versatility in Application (777.2) (762.0) (777.2) (680.7)
Eaton’s generator vacuum circuit breakers
are available in drawout (VCP-WG) or fixed
(VCP-WRG) configurations to provide for
superior performance and versatility. 39.60 39.30
Many industrial and commercial power (1005.8) (998.2)
systems now include small generators as
a local source of power. New applications
are arising as a result of the de-regulation
of the utility industry, and the construction
of smaller pack­aged power plants. Eaton’s 24.60 *6000 A has a depth of 28.50 (723.9)
(624.8)
generator breakers interrupt large
short-circuit currents in a small three- 31-Inch Frame Drawout VCP-WG 31-Inch Frame Fixed VCP-WRG
pole package.
Typical applications include: Figure 5.3-7. Type VCP-WG (Drawout) and Type VCP-WRG (Fixed) Circuit Breakers
■ Electric utilities: fossil, hydro and
wind power
■ Packaged power plants
■ Industrial companies using combined
cycle/combustion turbine plants
■ Government and military
■ Commercial institutions
■ Petrochemical and process industries
■ Forestry, pulp and paper
■ Mining, exploration and marine
The VCP-WG is the world’s generator
circuit breaker for reliable and robust
power generation protection.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-18

5 kV Class Generator Circuit Breaker Ratings


Table 5.3-11. Generator Circuit Breaker Types: VCP-WG (Drawout—DO) / VCP-WRG (Fixed—FIX)
Description Units Short-Circuit Current (Isc)
50 kA 63 kA 75 kA
Maximum Voltage (V): 5 kV
Frame in Inches (mm) — 29.00 29.00 31.00 31.00 29.00 29.00 31.00 31.00 31.00 31.00
(see Figure 5.3-7 on Page 5.1-17) (736.6) (736.6) (787.4) (787.4) (736.6) (736.6) (787.4) (787.4) (787.4) (787.4)
Ratings Assigned — DO FIX DO FIX DO FIX DO FIX DO FIX
Continuous Current A rms 1200 1200 — — 1200 1200 — — 1200 1200
2000 2000 — — 2000 2000 — — 2000 2000
3000 3000 — — 3000 3000 — — 3000 3000
4000 a 4000 a 4000 4000 4000 a 4000 a 4000 4000 4000 4000
— — 5000 a 5000 — — 5000 a 5000 5000 a 5000
— — — 6000 — — — 6000 — 6000
— — — 6300 a — — — 6300 a — 6300 a
— — — 7000 a — — — 7000 a — 7000 a
Dielectric Strength
Power frequency withstand voltage kV rms 19 19 19 19 19 19 19 19 19 19
Lightning impulse withstand voltage kV peak 60 60 60 60 60 60 60 60 60 60
InterruptingTime ms 50 50 83 83 50 50 83 83 83 83
ClosingTime ms 47 47 47 47 47 47 47 47 47 47
Short-Circuit Current kA rms 50 50 50 50 63 63 63 63 75 75
Asymmetrical current interrupting capability % dc 75 75 75 75 75 75 75 75 63 63
Ref: Minimum opening time ms 30 30 54 54 30 30 54 54 54 54
Short-time current carrying capability kA rms 50 50 50 50 63 63 63 63 75 75
Duration of short-time current sec 3 3 2.3 2.3 3 3 1.4 1.4 1 1
Closing and Latching Capability kA peak 137 137 137 137 173 173 173 173 206 206
First Generator-Source Symmetrical
Current Interrupting Capability kA rms 25 25 25 25 31.5 31.5 31.5 31.5 40 40
First Generator-Source Asymmetrical
Current Interrupting Capability % dc 130 130 130 130 130 130 130 130 130 130
Second Generator-Source Symmetrical
Current Interrupting Capability kA rms — — 31.5 31.5 40 40 40 40 50 50
Second Generator-Source Asymmetrical
Current Interrupting Capability % dc — — 110 110 110 110 110 110 110 110
ProspectiveTRV—Rate of Rise of Recovery Voltage (RRRV) kV / µs 3.0 3.0 3.0 b 3.0 b 3.0 3.0 3.0 b 3.0 b 3.0 b 3.0 b
Transient recovery voltage—Peak (E2 = 1.84 x V) kV peak 9.2 9.2 9.2 b 9.2 b 9.2 9.2 9.2 b 9.2 b 9.2 b 9.2 b
Transient recovery voltage—Time to Peak
(T2 = 0.62 x V) µs 3.1 3.1 3.1 b 3.1 b 3.1 3.1 3.1 b 3.1 b 3.1 b 3.1 b
Load Current Switching Endurance Capability Opera- 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
tions
No-Load Mechanical Endurance Capability Opera- 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
tions
Out-of-Phase Current Switching Capability kA 25 25 25 25 31.5 31.5 31.5 31.5 37.5 37.5
90º out-of-phase power frequency recovery
voltage ( = 1.5 x sqrt(2/3) x V) kV rms 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
90º out-of-phase inherentTRV—
Rate of Rise of Recovery Voltage (RRRV) kV / µs 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Transient recovery voltage—Peak (E2 = 2.6 x V) kV peak 13 13 13 13 13 13 13 13 13 13
Transient recovery voltage—Time to Peak
(T2 = 0.89 x V) µs 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
a Ratings achieved using forced-air cooling by blowers in the enclosure.
b TRV capacitors are required if RRRV is >0.5 kV/µs; or T2 is <65 µs.
Note: Rated frequency: 60 Hz.
Note: Standard operating duty: CO - 30 m - CO.
Note: Relevant Standard: IEEE standards C37.013-1997 and C37.013a-2007.
Note: Test certificates available.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-19

15 kV Class Generator Circuit Breaker Ratings


Table 5.3-11. Generator Circuit Breaker Types: VCP-WG (Drawout—DO) / VCP-WRG (Fixed—FIX) (Continued)
Description Units Short-Circuit Current (Isc)
50 kA 63 kA 75 kA
Maximum Voltage (V): 15 kV
Frame in Inches (mm) — 29.00 29.00 31.00 31.00 29.00 29.00 31.00 31.00 31.00 31.00
(see Figure 5.3-7 on Page 5.1-17) (736.6) (736.6) (787.4) (787.4) (736.6) (736.6) (787.4) (787.4) (787.4) (787.4)
Ratings Assigned — DO FIX DO FIX DO FIX DO FIX DO FIX
Continuous Current A rms 1200 1200 — — 1200 1200 — — 1200 1200
2000 2000 — — 2000 2000 — — 2000 2000
3000 3000 — — 3000 3000 — — 3000 3000
4000 a 4000 a 4000 4000 4000 a 4000 a 4000 4000 4000 4000
— — 5000 a 5000 — — 5000 a 5000 5000 a 5000
— — — 6000 — — — 6000 — 6000
— — — 6300 a — — — 6300 a — 6300 a
— — — 7000 a — — — 7000 a — 7000 a
Dielectric Strength
Power frequency withstand voltage kV rms 36 36 36 36 36 36 36 36 36 36
Lightning impulse withstand voltage kV peak 95 95 95 95 95 95 95 95 95 95
InterruptingTime ms 50 50 83 83 50 50 83 83 83 83
ClosingTime ms 47 47 47 47 47 47 47 47 47 47
Short-Circuit Current kA rms 50 50 50 50 63 63 63 63 75 75
Asymmetrical current interrupting capability % dc 75 75 75 75 75 75 75 75 63 63
Ref: Minimum opening time ms 30 30 54 54 30 30 54 54 54 54
Short-time current carrying capability kA rms 50 50 50 50 63 63 63 63 75 75
Duration of short-time current s 3 3 2.3 2.3 3 3 1.4 1.4 1 1
Closing and Latching Capability kA peak 137 137 137 137 173 173 173 173 206 206
First Generator-Source Symmetrical
Current Interrupting Capability kA rms 25 25 25 25 31.5 31.5 31.5 31.5 40 40
First Generator-Source Asymmetrical
Current Interrupting Capability % dc 130 130 130 130 130 130 130 130 130 130
Second Generator-Source Symmetrical
Current Interrupting Capability kA rms — — 31.5 31.5 40 40 40 40 50 50
Second Generator-Source Asymmetrical
Current Interrupting Capability % dc — — 110 110 110 110 110 110 110 110
ProspectiveTRV—Rate of Rise of Recovery Voltage kV / µs 3.4 3.4 3.4 b 3.4 b 3.4 3.4 3.4 b 3.4 b 3.4 b 3.4 b
(RRRV) kV peak 27.6 27.6 27.6 b 27.6 b 27.6 27.6 27.6 b 27.6 b 30.9 b 30.9 b
Transient recovery voltage—Peak (E2 = 1.84 x V)
Transient recovery voltage—Time to Peak
(T2 = 0.62 x V) µs 9.3 9.3 9.3 b 9.3 b 9.3 9.3 9.3 b 9.3 b 9.3 b 9.3 b
Load Current Switching Endurance Capability Operations 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
No-Load Mechanical Endurance Capability Operations 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
Out-of-Phase Current Switching Capability kA 25 25 25 25 31.5 31.5 31.5 31.5 37.5 37.5
90º out-of-phase power frequency recovery
voltage ( = 1.5 x sqrt(2/3) x V) kV rms 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.4
90º out-of-phase inherentTRV—
Rate of Rise of Recovery Voltage (RRRV) kV / µs 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Transient recovery voltage—Peak (E2 = 2.6 x V) kV peak 39 39 39 39 39 39 39 39 39 39
Transient recovery voltage—Time to Peak
(T2 = 0.89 x V) µs 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4
a Ratings achieved using forced-air cooling by blowers in the enclosure.
b TRV capacitors are required if RRRV is >0.5 kV/µs; or T2 is <65 µs.
Note: Rated frequency: 60 Hz.
Note: Standard operating duty: CO - 30 m - CO.
Note: Relevant Standard: IEEE standards C37.013-1997 and C37.013a-2007.
Note: Test certificates available.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-20

Switchgear Meters Instrument Transformers Current Transformers


The current transformer ratio is generally
Instrument transformers are used to selected so that the maximum load
protect personnel and secondary devices current will read about 70% full scale
from high voltage, and permit use of on a standard 5 A coil ammeter. Therefore,
reasonable insulation levels for relays, the current transformer primary rating
meters and instruments. The secondaries should be 140–150% of the maximum
of standard instrument transformers are load current.
rated at 5 A and/or 120 V, 60 Hz.
Maximum system fault current can
Switchgear Meters sometimes influence the current
Voltage Transformers transformer ratio selection because
Eaton’s Power XpertT Power and Energy
Selection of the ratio for voltage the connected secondary devices have
Meters, and Power Xpert Dashboard
transformers is seldom a question since published one-second ratings.
products allow switchgear owners and
operators to interface with their equipment the primary rating should be equal to or
The zero-sequence current transformer is
at varying levels of sophistication.To learn higher than the system line-to-line voltage.
used for sensitive ground fault relaying
more about these devices, visit our web or The number of potential transformers per
or self-balancing primary current type
click on links above. set and their connection is determined by
machine differential protection. The
the type of system and the relaying and
zero-sequence current transformer is
metering required.
available with a nominal ratio of 50/5 or
Protective Relays When two VTs are used, they are 100/5 and available opening size for
typically connected L-L, and provide power cables of 7.25 inches (184.2 mm).
phase-to-phase voltages, (Vab, Vbc, Vca) Special zero-sequence transformers with
for metering and relaying. larger windows are also available.

When three VTs are used, they are The minimum number of current
connected line-to-ground, and provide transformers for circuit relaying and
phase-to-phase (Vab, Vbc, Vca), as well instruments is three current transformers,
as phase-to-ground (Va, Vb, Vc) voltages one for each phase or two-phase
for metering and relaying. connected current transformers and
one zero-sequence current transformer.
If metering or relaying application requires Separate sets of current transformers
phase-to-ground voltages, use three VTs, are required for differential relays.
each connected L-G. If not, use of two
VTs connected L-L is sufficient. The minimum pickup of a ground
relay in the residual of three-phase
Protective Relays For ground detection, three VTs connected current transformers is
connected in Line-to-ground/ primarily determined by the current
Eaton can provide a wide range of broken-delta are used. transformer ratio. The relay pickup
protective relays to meet you most
A single VT, when used, can be connected can be reduced by adding one residual
complex protection and system needs.
line-to-line (it will provide line-to-line connected auxiliary current transformer.
output, for example Vab or Vbc or Vca), This connection is very desirable on main
or line-to-ground (it will provide line-to- incoming and tie circuits of low resistance
ground output, for example Va or Vb or grounded circuits.
Vc). Generally, a single VT is used to Standard accuracy current transformers
derive voltage signal for synchronizing are normally more than adequate for most
or Over Voltage/Under Voltage function. standard applications of microprocessor-
based protective relays and meters. See
Table 5.3-14 for CT accuracy information.

Table 5.3-12. Standard Voltage Transformer Ratio Information


Rating-Volts 2400 4200 4800 7200 8400 10800 12000 14400

Ratio 20-1 35-1 40-1 60-1 70-1 90-1 100-1 120-1

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-21

Table 5.3-13. Standard Voltage Transformer, 60 Hz Accuracy Information


Switchgear Voltage Transformer—ANSI Accuracy
kV kV Maximum Number Standard Burdens at 120 Volts Burdens at 69.3 Volts Thermal Rating Volt-Ampere
Class BIL Per Set and Connection Ratios W, X, Y Z M ZZ W, X Y M Z 55 °C Connection

5 60 2LL 20, a 0.3 1.2 — — 0.3 — — — LL 700


or 3LG 35, LG 400
40 LG b 700
7.5 95 2LL 35, 40, 0.3 0.3 0.3 0.6 0.3 0.3 0.3 1.2 LL 1000
and or 3LG 60, 70, LG 550
15 100, 120 LG b 1000
a For solidly grounded 4160 V system only or any type 2400 V system.
b For solidly grounded system only.
Note: LL = Line-to-line connection. LG = Line-to-ground connection.

Table 5.3-14. Current Transformers, 55 ºC Ambient


CT Ratio Metering Accuracy Classification Relaying Accuracy Classification
(MR = Multi-Ratio) At 60 Hz At 60 Hz At 60 Hz Minimum Accuracy Standard Accuracy Optional High Accuracy
Standard Burden Standard Burden Standard Burden Required per IEEE Supplied in VCP-W Available in VCP-W
B 0.1 B 0.5 B 1.8 C37.20.2 Switchgear Switchgear

50:5 1.2 — — C10 — C10


75:5 1.2 2.4 — C10 C10 C20
100:5 1.2 2.4 — C10 C10 C20
150:5 0.6 2.4 — C20 C20 C50
200:5 0.6 2.4 — C20 C20 C50
c
250:5 0.6 2.4 — C20 C50
300:5 0.6 2.4 2.4 C20 C20 C100
400:5 0.3 1.2 2.4 C50 C50 C100
c
500:5 0.3 0.3 2.4 C50 C100
600:5 0.3 0.3 2.4 C50 C100 C200
800:5 0.3 0.3 1.2 C50 C100 C200
c
1000:5 0.3 0.3 0.3 C100 C200
1200:5 0.3 0.3 0.3 C100 C200 C400
1500:5 0.3 0.3 0.3 C100 C200 C400
2000:5 0.3 0.3 0.3 C100 C200 C400
2500:5 0.3 0.3 0.3 c C200 C400
3000:5 0.3 0.3 0.3 C100 C200 C400
4000:5 0.3 0.3 0.3 C100 C200 C400
600:5 MR 0.3 0.3 2.4 c C100 C200
1200:5 MR 0.3 0.3 0.3 c C200 C400
2000:5 MR 0.3 0.3 0.3 c C200 C400
3000:5 MR 0.3 0.3 0.3 c C200 C400
50:5 zero sequence — — — — C10 —
100:5 zero sequence — — — — C20 —
c Not listed in C37.20.2.
Note: Maximum number of CTs—Two sets of standard accuracy or one set of high accuracy CTs can be installed in the breaker compartment on each side
of the circuit breaker.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-22

Ohmic Voltage Sensing (OVS)


Eaton’s Ohmic Voltage Sensing (OVS) is an alternative to
traditional VTs in medium voltage. While traditional VTs are
susceptible to transients and ferro-resonance, the OVS system
is not. The OVS sensor consists of four non-inductive resistors
(two medium-voltage resistors in series and two low-voltage
resistors in parallel) that serve as a voltage divider; a low-
voltage signal from the sensor is sent to the R2m adapter that
is connected to the CAPDIS device. The CAPDIS device then
sends 120 V signals to the relays and meters in the system
(see Figure 5.3-8). The system is designed to be agnostic
when meter and relay devices are being selected for use
in a protection and controls scheme.
The OVS system is rated for applications 2.4 to 36 kV as a
replacement for VTs. The selection of sensors and R2m adapter
for the system is dependent on the nominal voltage being
applied to the switchgear. The OVS systems must be applied Figure 5.3-9. OVS Sensors Mounted in Cable Compartment
with three sensors installed line to ground; the low-voltage
control circuit can be configured to provide a line-to-line or a OVS is not to be used to provide any control power to devices in
line-to-ground output dependent upon the wiring to the relay the switchgear, or to be used for utility metering applications.
or meter. Relays and meters installed in the protection and
The OVS system has been tested to IEEE C37.20.2.2015 Annex D.
controls scheme would process the signal from the OVS system
in the same manner it would a VT. The sensors are traditionally
mounted in the rear switchgear compartment (see Figure 5.3-9). Technical Data
However, if an existing installation requires the OVS system, it
can be retrofitted into the existing VT drawer. ■ 24 to 230 Vac or Vdc control power for CAPDIS
■ Voltage system accuracy better than 2%
■ Phase angle accuracy of better than 0.1% over frequency
range of 2 kHz
■ Burden 0.78 VA L-L, 0.45 VA L-N
OVS Sensors

CAPDIS
Amplifier

R2m Adapter

120 V Signal

Figure 5.3-8. Typical OVS System Setup

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-23

Thermal Monitoring Dummy Element (Dummy Breaker)


Eaton can provide multiple options for thermal monitoring in Dummy element is a drawout element with primary disconnects
switchgear. From infrared (IR) windows to continuous thermal similar to a drawout circuit breaker, but consists of solid copper
monitoring solutions. conductors in place of vacuum interrupters, and is designed for
manual racking, it is typically used as drawout disconnect link in
IR windows are placed on the rear covers of the switchgear the primary system for circuit isolation or bypass.
doors providing the ability to use an IR camera for checking
cable connections to circuit breakers. IR windows are applied The device is insulated to suit the voltage rating of the switchgear
in different configurations depending on the field of view each and will carry required levels of short-circuit current, but it is
window has into the cable compartment of the switchgear. not rated for any current interruption. It must be key interlocked
An IR camera is needed for taking pictures through the with all source devices such that it can only be inserted into or
window to check system health. See Figure 5.3-10 for IR removed from its connected position only after the primary
window installation example. circuit in which it is to be applied is completely de-energized.
Continuous thermal monitoring systems consist of sensors Before using a dummy element, it is recommended that each
mounted in the cable compartment, which are hardwired or user develop detailed operating procedure consis­tent with
wireless and connected to a data card or collector to put the safe operating practices. Only qualified personnel should be
information over a control network to be monitored. The authorized to use the dummy element.
temperature measured is a delta t (ambient to bus temperature);
some systems require a second sensor for ambient temperature.
See Figure 5.3-11 for a continuous thermal monitoring system
installation example.
The delta t that can be taken from both systems should be
analyzed and compared to industry standards to determine
any corrective action required.

Figure 5.3-10. Typical Install for IR Window on Rear Door

Figure 5.3-11. Typical Install for Continuous Thermal Monitoring Sensors

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-24

Roll-on-the-Floor Breaker Option

VCP-W Direct Roll-in Breaker with


Fixed Wheels

Roll-on-the-Floor Switchgear Compartment

An optional direct roll-in breaker When using a 1200 or 2000 A circuit


designed for use in upper and lower breaker in the lower compartment, the
compartment of 5/15 kV indoor and compartment above the breaker can be
outdoor walk-in aisle switchgear is left blank or used of auxiliaries, such as
available for all 5/15 kV VCP-W, VCP-WC VTs or single-phase CPT, or primary fuses
and VCP-WG circuit breakers. Breaker for three-phase or larger than 15 kVA
is fitted with special wheel kit, and single-phase CPTs. When using 3000 A VCP-W Direct Roll-in Breaker with
compartment interface is modified to circuit breaker in the lower compartment, Swivel Wheels on Front
allow circuit breaker to be rolled directly the compartment above the breaker is
from the floor into the switch­gear left blank for ventilation. The design is
compartment, or from switchgear rated for application in IBC/CBC seismic
compartment onto the floor without a environment. It can also be supplied
need for external lifting device or dolly. with UL or CSA label for certain ratings.
The circuit breaker can be supplied with Contact Eaton for ratings available with
all four fixed wheels or can be supplied UL/CSA label. The overall dimensions of
with two swivel-type wheels on the front the 5/15 kV indoor and outdoor walk-in
and two fixed wheels on the rear. In aisle structures with the roll-on-the-floor
2-high construction, the roll-on-the-floor breaker option are the same as the
breaker option is available for breakers in standard structures that use standard non
upper or lower compartments, however, roll-on-the-floor circuit breakers.
removal of upper breaker requires
external lifter and lift pan, which are
optional accessories.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-25

Integral Motorized Remote A microprocessor-based controller card,


located below the drive motor, interfaces
Racking Option (VC-W MR2) with an external hand-held pendant
(standard), discrete external I/O (optional)
or external ModbusT communication
(optional) and controls the breaker/
auxiliary drawer move­ment via the drive
motor. The system is also designed such
that it allows manual racking of the
breaker/auxiliary using the levering
crank accessory if needed. The VC-W
MR2 controller interface is shown in
Figure 5.3-12. The crank safety switch
disables the motor whenever a breaker/
auxiliary is being manually racked in or
out. The connect, test and disconnect
limit switches provide breaker/auxiliary
position inputs to the controller card.
MR2 Hand-Held Pendant In addition to the standard permissive
Breaker Levering Pan Assembly with Test
Position—VC-W MR2 Integral Racking Device switch, two terminals are provided for
VC-W MR2 is an optional motorized connection of the customer’s external
racking device accessory installed interlocking/permissive contact(s). Note
inside a circuit breaker or auxiliary that a single-phase 120 Vac control supply
compartment. It is available for is required for proper operation of the
application in circuit breaker VC-W MR2 controller and the drive motor.
compartments of 5/15/27/38 kV
Type VC-W arc and non-arc, and 5 kV When VC-W MR2 integral racking is
VC-W ND metal-clad switchgear. It is supplied, its controller card is wired to
also available for application in auxiliary the CAT 6 jack installed in the associated
compartments of 5/15 kV Type VC-W breaker/auxiliary compart­ment door,
arc-resistant and standard switchgear. and each switchgear lineup is shipped
This optional accessory allows a user to with one hand-held pendant with 30 feet
safely move a circuit breaker between of CAT 6 cable (lengths up to 100 feet
Connected, Test and Disconnected available). The pendant interfaces with
positions and auxiliary drawer (VT, CPT, the MR2 controller card via the CAT 6
Type VC-W Arc-Resistant Switchgear Auxiliary primary fuse) between Connected and cable through a CAT 6 jack located on the
Drawer with Type MR2 Integral Racking Disconnected positions within their breaker/auxiliary compartment door.It
respective compartments from a safe allows the operator to move away from
distance away from the switchgear. The the switchgear up to 30 feet. The pendant
MR2 controller also allows a user to includes Enable pushbutton for additional
electri­cally open and close the circuit security. It must be pressed in order to
breaker from a safe distance away from activate the pendant functions. By
the switchgear. For switchgear designs/ pressing Enable pushbutton and an
ratings not included above, contact Eaton appropriate function pushbutton together
for availability of MR2 accessory. momentarily, the operator can rack the
breaker between Connected, Test and
Disconnected positions or open or close
the breaker or rack the auxiliary drawer
between Connected and Disconnected
positions. Breaker or auxiliary drawer
positions (Connect, Test, Disconnect)
and breaker opened/closed status are
indicated by appropriate LED lights on
Type VC-W Standard Switchgear Auxiliary the pendant. A blinking light indicates
Drawer with Type MR2 Integral Racking that the breaker/auxiliary is in motion
through the selected position.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-26

A solid (non-blinking) light indicates that The remote LED lights are not included Technical Data
the breaker/auxiliary has reached and with MR2. If the customer needs to
stopped in the selected position. In case operate the MR2 with the hand-held Control Supply Ratings
normal operation fails, the appropriate pendant, the pendant becomes the ■ Nominal control voltage—120 Vac,
error code is displayed in a separate master and will override the customer’s 50 or 60 Hz, single-phase
two-character LED display window on the remote control signals.
pendant. A list of various error codes and ■ Control voltage range—100 to 140 Vac,
their descrip­tions along with suggested The VC-W MR2 controller is also equipped 50 or 60 Hz
corrective actions are printed on the with terminal blocks to allow the customer ■ Time to travel from connect to
back side of the pendant. Examples of to interface with the controller via their disconnect, or disconnect to
error states: motor overcurrent, motor SCADA system using a Modbus interface. connect—50 seconds maximum
overtemperature, motor timed out, Please note that only one of the two
options, discrete I/O interface or Modbus ■ Current draw during the travel—
breaker position unknown, open 15 A maximum for about 3 seconds
permissive, communication error interface, can be used, but not both.
Figure 5.3-13 shows an illustration of a and 3.6 A for about 24 seconds
and no breaker/auxiliary.
typical Modbus control example. ■ Optional dry output contacts when
In addition to pendant, three optional I/O Additional components shown outside included for position indications are
interfaces can be supplied as follows: the MR2 controller in Figure 5.3-13 are not rated for 125 Vac, 2 A
included with the MR2. System-level ■ External permissive contacts, when
1. I/O interface to allow racking of controls can be optionally sup­plied by
breaker (connect, test, disconnect) or used, must be rated for 24 Vdc, 50 mA
Eaton’s Engineering Services & Systems.
auxiliary drawer (connect, disconnect) If the customer needs to operate the MR2
by external hardwired dry contacts with the hand-held pendant, the pendant Requirements for External Contacts
and 24 Vdc output for corresponding becomes the master and will override and LEDs when Interfacing with MR2
remote position indicating LEDs. the Modbus interface. Error codes are ■ External contacts should be rated for
2. I/O board that provided dry contacts displayed on Modbus devices when minimum open circuit voltage of
for remote indication of breaker controlling the MR2 with Modbus and 24 Vdc, and be able to close and
(connect, intermediate, test, on the pendant when controlling with carry 5 mA at 24 Vdc
disconnect)/auxiliary drawer (connect, the pendant. ■ When remote LEDs are used, use
test) position within its compartment. 24 Vdc rated LEDs, current up to 20 mA
■ Optional dry output contacts when
3. I/O interface to allow breaker open/
close functions via external hardwired included for position indications are
dry contacts and 24 Vdc output for rated for 125 Vac, 2 A
corresponding remote open/close ■ External permissive contacts, when
status LEDs. used, must be rated for 24 Vdc, 50 mA
It is the customer’s responsibility to
provide single-phase 120 V, 50 or 60 Hz
nominal supply for the MR2 controller.
It can be derived from within the
switchgear if an appropriate control
power transformer is available within
the switchgear.
Type VC-W MR2 motorized racking
accessory has been endurance tested
and guaranteed for 500 operations as
required by IEEE C37.20.2.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-27

Figure 5.3-12. VC-W MR2 Controller Interface for a VCB with Distinct Test Position and Open/Close Functions

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-28

Figure 5.3-13. VC-W MR2 Typical Modbus Control Example

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-29

Accessories Ground and Test Device


The ground and test device is a drawout
Eaton 5–15 kV switchgear is element that may be inserted into a
provided with the following metal-clad switchgear housing in place of
accessories as standard: a circuit breaker to provide access to the
■ One test jumper primary circuits to permit the temporary
connection of grounds or testing equip­­
■ One levering crank
ment to the high-voltage circuits. High
■ One maintenance tool potential testing of cable or phase
■ One lifting yoke (5–27 kV) checking of circuits are typical tests
which may be performed. The devices
■ One sets of rails (5–27 kV)
are insulated to suit the voltage rating
The following optional accessories of the switchgear and will carry required
are also available. Contact Eaton for level of short-circuit current.
additional information.
Before using ground and test devices, it is
recommended that each user develop
Optional Accessories detailed operating procedures consis­tent
with safe operating practices. Only
■ Transport dolly (5–27 kV), qualified personnel should be authorized
(5–15 kV arc-resistant) to use ground and test devices. 5/15 kV Manual G&T Device shown
■ Portable lifter (5–27 kV) with Upper Terminals Grounded
Manual and electrical ground and test
■ Test cabinet devices are available. These devices
■ Electrical levering device (5–38 kV) include six studs for connection to
■ Ramp for lower breaker (5–27 kV), primary circuits. On the manual device,
(5–15 kV arc-resistant) selection and grounding is accomplished
by cable or bus bars connection. On
■ Manual or electrical ground and electrical-type devices, grounding is
test device accomplished by an electrically
■ Hi-pot tester operated grounding switch.

5/15 kV Manual G&T Device shown


with Lower Terminals Grounded

5/15 kV Manual Type G&T Device

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Devices 5.3-30

System Options

Partial Discharge Sensing and Monitoring for Switchgear

InsulGard Relay RFCT Sensor

Partial Discharge Equipment

InsulGard Relay (PD Monitoring)


Partial Discharge in Switchgear Sensing and Monitoring
Partial discharge is a common name for Eaton’s Type VCP-W metal-clad switch­gear The PD sensing and monitoring system
various forms of electrical discharges (2.4–38 kV) is corona-free by design. is optional. It consists of Eaton’s
such as corona, surface tracking, and Corona emissions within the standard InsulGard™ Relay and PD sensors
discharges internal to the insulation. It VacClad switchgear assemblies have specifically developed for application
partially bridges the insulation between been eliminated or reduced to very low in the switchgear to work with the relay.
the conductors.These discharges are levels by special fabrication and assembly Partial discharges within the switch­gear
essentially small arcs occurring in or techniques, such as rounding and buffing compartment are detected by installation
on the surface of the insulation system of all sharp copper edges at the joints, of a small donut type radio frequency
when voltage stress exceeds a critical employing star washers for bolting current transformer (RFCT) sensor over
value. With time, airborne particles, metal barriers, and using specially floating stress shields of the specially
contaminants and humidity lead to crafted standoff insulators for primary designed bus or line side primary
conditions that result in partial discharges. bus supports. By making switchgear bushings. Partial discharges in customer’s
Partial discharges start at a low level and assemblies corona-free, Eaton has made power cables (external discharges) are
increase as more insulation becomes its standard switchgear more reliable. detected by installation of the RFCT
deteriorated. Examples of partial discharge However, as indicated above, with around ground shields of the incoming
in switchgear are surface tracking across time, airborne particles, contaminants or outgoing power cable terminations.
bus insulation, or discharges in the air gap and humidity lead to conditions that
between the bus and a support, such as cause partial discharges to develop in In 5/15 kV switchgear (refer to
where a bus passes through an insulating switchgear operating at voltages 4000 V Figure 5.3-15), primary epoxy bushings
window between the sections of the and above. Type VC-W switchgear can with stress shield and RFCT sensors
switchgear. If partial discharge activity is be equipped with factory-installed partial for measurement of internal as well as
not detected and corrected, it can develop discharge sensors and partial discharge external partial discharges are all optional.
into a full-scale insulation failure followed sensing relay for continuous monitoring InsulGard relay is also optional. When
by an electrical fault. Most switchgear of the partial discharges under normal specified, one set of primary epoxy
flashover and bus failures are a result of operation. Timely detection of insulation bushings (located on bus side) with
insulation degradation caused by various degradation through increasing partial stress shield and associ­ated RFCT sensor
forms of partial discharges. discharges can identify potential is provided at every two vertical sections.
problems so that corrective actions can An additional RFCT sensor for each
be planned and implemented long before incoming and outgoing power cable
permanent deterioration develops. Partial circuits can be provided as required.The
discharge detection can be the foundation RFCT output signals can be connected
of an effective predictive maintenance directly to InsulGard relay for continuous
program. Trending of partial discharge moni­toring of partial discharges or can be
data over time allows prediction of used for periodic field measurements.
failures, which can be corrected before
catastrophic failure occurs.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-31

Input
Temp Sensor Terminal InsulGard
Block Relay Optional
Humidity Sensor Modem

120 Vac
Auxiliary
Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
RFCT Sensor, RTD Input, etc.) Status

Figure 5.3-14. InsulGard Relay System

RFCT #1 detects partial discharges internal to switchgear compartment.

RFCT #2 detects partial discharges in customer’s cables up to 100 ft


from switchgear.

Figure 5.3-15. Typical Partial Discharge Sensor Connections


(5–15 kV Switchgear)
Note: Use one set of epoxy bottles with ground stress shield on bus side
(either in the top or bottom compartment) at every two vertical sections.
Use standard bottles at all other locations.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-32

Partial Discharge Sensors and Monitoring for Switchgear

Radio Frequency Current Sensor (RFCT) Epoxy Bottles with Stress Shield
(5/15 kV Switchgear)

PD Sensors

PD Sensors
PD Sensors are Installed
in Switchgear Cubicle

Figure 5.3-16. How the Process Works—Sensing and Data Collection

Pulse Repetition Rate (PPC)


5

0
Cub12

Cub13

Cub14

Cub15

Cub16
Cub11
Cub1

Cub2

Cub3

Cub4

Cub5

Cub6

Cub7

Cub8

Cub9

Relatively high Partial Discharge levels indicate problems in


older non-fluidized epoxy insulated MV bus. Problems in cable
terminations and in connected equipment can also be revealed.

Figure 5.3-17. How the Process Works—Data Analysis and Report (Sample)

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-33

Standard
Typical Application Layouts

Figure 5.3-18. Typical Arc-Resistant Switchgear Application Layouts—5 and 15 kV


Notes:
1. Maximum number of CTs: Two sets of 2. Bottom entry is standard for all 3. All lineups shown can be provided in
standard or one set of high accuracy power cables. In breaker over breaker mirrored configuration.
CTs can be installed on each side of arrangement, maximum number of
the circuit breaker. cables is limited to two per phase 4. Refer to Figure 5.3-21 to Figure 5.3-26
for each breaker. for dimensions.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-34

Figure 5.3-19. Typical Arc-Resistant Switchgear Application Layouts—5 and 15 kV


Notes:
1. Maximum number of CTs: Two sets of standard or one set
of high accuracy CTs can be installed on each side of the
circuit breaker.
2. Bottom entry is standard for all power cables. In breaker over
breaker arrangement, maximum number of cables is limited
to two per phase for each breaker.
3. All lineups shown can be provided in mirrored configuration.
4. Refer to Figure 5.3-21 to Figure 5.3-26 for dimensions.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-35

Figure 5.3-20. Typical Arc-Resistant Switchgear Application Layouts—5 and 15 kV


Notes:
1. Maximum number of CTs: Two sets of 2. Bottom entry is standard for all 3. All lineups shown can be provided in
standard or one set of high accuracy power cables. In breaker over breaker mirrored configuration.
CTs can be installed on each side of arrangement, maximum number of
the circuit breaker. cables is limited to two per phase for 4. Refer to Figure 5.3-21 to Figure 5.3-26
each breaker. for dimensions.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-36

Available Configurations

32.00 Arc exhaust


(812.8) plenum

Control 1200 A 1200 A Auxiliary 1200 A


Compartment Breaker Breaker (VT, CPT Breaker
(with relay (with relay or Fuses) (with relay
box) box) box)
(no relays)

Control Control Control Control Control


95.00 Compartment Compartment Compartment Compartment Compartment
(2413.0)

1200 A Control 1200 A 1200 A Auxiliary


Breaker Compartment Breaker Breaker (VT, CPT
(with relay (with relay (with relay or Fuses)
box) box) box)
(no relays)

32.00
(812.8)

Auxiliary 2000 A 1200 A 2000 A 2000 A


(VT, CPT Breaker Breaker Breaker Breaker
or Fuses) (with relay (with relay (with relay (with relay
box) box) box) box)
(no relays)

95.00
(2413.0) Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent

2000 A Auxiliary 2000 A 1200 A 20000A


Breaker (VT, CPT Breaker Breaker Breaker
(with relay or Fuses) (with relay (with relay (with relay
box) box) box) box)
(no relays)

(Note 1) (Notes 1, 2) (Notes 1, 3) (Notes 1, 2, 3) (Notes 1, 3, 4)


36.00
(914.14)

Notes:
1 = Please note that the only control space available for relays and LV devices for this configuration
is the relay box located on the breaker compartment door.
2 = Maximum current through a 2000 A breaker in this location must be limited to 1750 A.
3 = This configuration requires use of a 4000 A main bus.
4 = Maximum current through each 2000 A breaker in this configuration must be limited to 1750 A each.

Figure 5.3-21. Available Arc-Resistant Switchgear Configurations (Front Views)—5 and 15 kV

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-37

32.00 Arc exhaust


(812.8) plenum

Auxiliary Auxiliary
Control (VT, CPT Control (VT, CPT Ampgard Ampgard
Compartment or Fuses) Compartment or Fuses) Transition Transition
Bolted Door Bolted Door
(no relays) (no relays)
(no relays) (no relays)

Control Control Control Control


95.00 Compartment Compartment Compartment Compartment
(2413.0) Dynamic Vent

Auxiliary Auxiliary Control Auxiliary


2000/3000 A (VT, CPT (VT, CPT (VT, CPT
Compartment Bolted Door
Breaker or Fuses) or Fuses) or Fuses) (no relays)
(with relay
box)
(no relays) (no relays) (no relays)

32.00
(812.8)

2000/3000 A 3000 A 3000 A FC 3000 A FC 4000 A FC


Breaker Breaker Breaker Breaker Breaker
(with relay (with relay (with relay (with relay (with relay
box) box) box) box) box)

Fan Fan
Control
95.00 Compartment
(2413.0) Dynamic Vent Dynamic Vent Dynamic Vent Dynamic Vent

Auxiliary Auxiliary Fans located


(VT, CPT (VT, CPT inside this
Control or Fuses) Control or Fuses)
Compartment Compartment compartment

(no relays) (no relays)

Dynamic Vent
(Notes 2, 5) (Notes 1, 5) (Note 6) (Notes 1, 6) (Note 7)
36.00
(914.14)

Notes:
1 = Please note that the only control space available for relays and LV devices for this configuration
is the relay box located on the breaker compartment door.
2 = Maximum current through a 2000 A breaker in this location must be limited to 1750 A.
5 = Maximum current through a 3000 A breaker in this location must be limited to 2500 A.
6 = Maximum current allowed through a 3000 A circuit breaker in this configuration is 3000 A
with fans running, and 2500 A when fans are not running.
7 = Maximum current allowed through a 3000 A circuit breaker in this configuration is 4000 A
with fans running, and 2500 A when fans are not running.

Figure 5.3-21. Available Arc-Resistant Switchgear Configurations (Front Views)—5 and 15 kV (Continued)

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-38

Typical Sectional Side Views

Figure 5.3-22. Typical Arc-Resistant Switchgear (Side Views)—5 and 15 kV

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-39

Figure 5.3-23. Typical Arc-Resistant Switchgear (Side Views)—5 and 15 kV

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-40

Figure 5.3-24. Typical Arc-Resistant Switchgear (Side Views)—5 and 15 kV

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-41

Typical Top Plan—Dimensions in Inches (mm)

36.00 36.00 36.00


End Wall 1.50 1.50 End Wall
(38.1) (914.4) (914.4) (914.4) (38.1)
18.00 18.00 18.00 18.00 18.00 18.00
(457.2) (457.2) (457.2) (457.2) (457.2) (457.2)
Cables for the
Upper Breaker 3.00 3.00
through These (76.2) (76.2)
Conduits 3.00 3.00
(76.2) 7.00 7.00 (76.2) 7.00 1.25
(177.8) (177.8) (177.8) (31.8)

9.00
(228.6)
6.00 6.00 9.00 6.00 6.00
(152.4) (152.4) (228.6) (152.4) (152.4)

81.00 108.00 a
(2057.4) (2743.2)
Plenum

15.25
(387.4)

VS #1 VS #2 VS #3
Front
Top View

Figure 5.3-25. Typical Arc-Resistant Switchgear, Top Entry Cables—Typical Conduit Entrance Locations—5 and 15 kV
Note: For switchgear with enclosure arc ratings of up to 41 kA rms symmetrical, minimum two vertical sections and one arc duct exit are required.
For switchgear with enclosure arc ratings of 50 kA rms symmetrical or higher, minimum three vertical sections and two arc duct exits are required.

a Depth shown is based on use of maximum one 500 kcmil per phase, or two 250 kcmil per phase power cables for each breaker entering from the top;
otherwise, use structures with 121.50-inch (3086.1-mm) depth.

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Layouts and Dimensions 5.3-42

Typical Floor Plan—Dimensions in Inches (mm)

1 These are the locations of 0.75 inch (19.1 mm)


diameter mounting holes for securing an
arc-resistant VacClad-W switchgear assembly
(hereafter referred to as VC-W) vertical section to a
finished foundation. Use of 0.50 inch (12 mm)
Rear diameter SAE Grade 5 hardware tightened to
4 75 ft-lb (101.7 Nm) is recommended. Use of
36.00 7.52 20.96
other post-installed mechanical anchor systems,
7.52 bonded/adhesive type systems, pre-installed
(914.4) (191.0) (532.4) (191.0) cast-in-place systems such as shear lugs, L-bolts
1.61 and J-bolts, or plug welding the VC-W switchgear
(40.9) 3.75 vertical section at the mounting hole locations to
(95.3) cast-in-place structural steel materials or to a steel
house foundation is sole responsibility of others.
Alternative mounting systems must have equal or
greater average ultimate tensile and shear load
1 1 capabilities as SAE Grade 5 hardware. In addition
22.75 to load capabilities of the mounting system, the
28.00 6 (577.9) bearing strength and bearing surface area at each
(711.2) VC-W switchgear vertical section mounting hole
location must be taken into account. Alternative
mounting systems must provide equal or greater
1 1 bearing properties as a Key Bellevilles, Inc.,
K1125-E-125 washer or other manufacturer’s equal
device used with SAE Grade 5 hardware at each
9.00 7 VC-W switchgear anchor location. Consult a
(228.6) licensed structural or civil engineer prior to
96.46 selecting a mounting system if a system other
(2450.1) than that recommended is preferred.
44.50
(1130.3) 8 2 Minimum front clearance required when using
Eaton’s portable lifter to install drawout devices.
0.75 0.75 61.09 If other Eaton devices are used to install drawout
(19.1) (19.1) devices, these devices may require more space,
1 1 3.37 (1550.9)
which will be indicated on an arc-resistant VC-W
(85.6) switchgear assembly specific shop order floor
3.00 0.25 plan. In addition, the local authority having
(76.2) jurisdiction may also require a larger distance.
16.00 19.00 (6.4)
(406.4) (482.6) 5 3 Minimum left-hinged panel clearance.
Minimum clearance to RH side of the
switchgear: 6.00 inches (152.4 mm).
3.88 4 This is the minimum rear clearance required.
4.46 1 1
1.46 (98.6) The local authority having jurisdiction may require
(113.3)
(37.1) 5.80 a larger distance.
0.88 0.88
(22.4) (22.4) (147.3)
5 Location of low-voltage control conduit wiring
openings. Conduits are limited to a projection
of 1.00 inch (25.4 mm) above the finished floor
32.00 Min. 36.00 or inside the top cover when such conduit entry
(812.8) (914.4) is from the top. Maximum conduit size is
70.00 Min. 1.25 inches (31.8 mm).
3 (1778.0)
6 These are the high-voltage cable conduit entry
Front 2 locations when entering from the floor or the top.
See shop order base plan for recommended
conduit locations when bottom entry is being
used. Conduit projection must not exceed
2.00 inches (50.8 mm).

7 This is the location of the cable lug for attaching


the cable from the customer’s ground grid. In the
first and last vertical section in an arc-resistant
VC-W switchgear assembly, the grounding grid
cable should enter through the HV cable conduit
entry area in the floor and be routed to this
Floor Plan Detail terminal lug.

8 Finished foundation surface shall be level within


0.06-inch (1.5 mm) in 36.00 inches (914.4 mm)
left-to-right, front-to-back, and diagonally, as
measured by a laser level.

Figure 5.3-26. Typical Arc-Resistant Switchgear Floor Plan—5 and 15 kV

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-43

Typical Weights
Table 5.3-15. Assemblies (Less Breakers) abc
Type of Main Bus Indoor Structure Indoor Structure Indoor Structure
Vertical Section Rating 36.00-Inch (914.4 mm) W 36.00-Inch (914.4 mm) W 36.00-Inch (914.4 mm) W
97.50-Inch (2476.5 mm) D 109.50-Inch (2781.3 mm) D 121.50-Inch (3086.1 mm) D
Amperes Lb (kg) Lb (kg) Lb (kg)

Breaker/breaker 1200 2800 (1271) 3025 (1374) 3175 (1441)


2000 2900 (1317) 3175 (1441) 3375 (1532)
3000 3000 (1362) 3275 (1487) 3475 (1578)
4000 3100 (1407) 3375 (1532) 3575 (1623)
Blank/breaker or 1200 2700 (1226) 2900 (1317) 3125 (1419)
breaker/blank 2000 2800 (1271) 3125 (1419) 3175 (1441)
3000 2900 (1317) 3150 (1430) 3325 (1510)
4000 3000 (1362) 3275 (1487) 3475 (1578)
Auxiliary/breaker or 1200 2650 (1203) 2850 (1294) 2975 (1351)
breaker/auxiliary 2000 2750 (1248) 2975 (1351) 3225 (1464)
3000 2850 (1294) 3100 (1407) 3275 (1487)
4000 2950 (1339) 3225 (1464) 3450 (1566)
Auxiliary/auxiliary 1200 2600 (1180) 2800 (1271) 2925 (1328)
2000 2700 (1226) 2925 (1328) 3175 (1441)
3000 2800 (1271) 3050 (1385) 3225 (1464)
4000 2900 (1317) 3175 (1441) 3375 (1532)
Blank/auxiliary or 1200 2500 (1135) 2700 (1226) 2825 (1283)
auxiliary/blank 2000 2600 (1180) 2825 (1283) 2975 (1351)
3000 2700 (1226) 2950 (1339) 3125 (1419)
4000 2800 (1271) 3075 (1396) 3275 (1487)
Blank/blank 1200 2500 (1135) 2700 (1226) 2825 (1283)
2000 2600 (1180) 2825 (1283) 2975 (1351)
3000 2700 (1226) 2950 (1339) 3125 (1419)
4000 2800 (1271) 3075 (1396) 3275 (1487)
a Add weights of end-wall to left and right end structures as follows:
350 Lb (159.1 kg) for 97.50-inch (2476.5) D structures.
390 Lb (177.3 kg) for 109.50-inch (2781.3) D structures.
430 Lb (195.4 kg) for 121.50-inch (3086.1) D structures.
b Add plenum weight as follows:
300 Lb (136.4 kg) to left and right end structures.
200 Lb (91.0 kg) to each intermediate structures.
c Add arc duct assembly weight as follows:
200.00 Lb (91.0 kg) for standard 51.00-inch (1295.4 mm) arc exhaust duct assembly.
30.00 Lb (14.0 kg) per foot for additional arc duct.

Control Power Requirements


Table 5.3-16. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated Spring Charging Motor Close or Trip UV Trip Voltage Range Indicating
Control Inrush Run Average Run Amperes mA Close Trip Light
Voltage Amperes Amperes Time, Sec. Maximum Amperes

48 Vdc 36.0 9 6 16 200 38–56 28–56 0.02


125 Vdc 16.0 4 6 7 80 100–140 70–140 0.02
250 Vdc 9.2 2 6 4 40 200–280 140–280 0.02
120 Vac 16.0 4 6 6 — 104–127 104–127 0.02
240 Vac 9.2 2 6 3 — 208–254 208–254 0.02

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-44

Typical Schematics

ANSI Standard VCP-W Breaker dc Control Schematic

P
(+)
CS CS PR
C T

11
Spring

9UV
WL GL RL
Charged
Indicating
Light
UV

10UV
dc Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

12
1 2

9A
4 7 5 6 7 8 9 10 3
3A
3

9
13

61
Y

51

53

55

57
LS1 a
bb a
Y SR

62
ST

52

56

58
54
ST 18 17 16 15 22 2
M b b 1
a
LC a
PS2 LS2 LS2

10A
PS Y
bb 1 bb aa
Not Available when Second 13
14

10
4

24 21 20 19
Trip Coil Option is Chosen
TRCO_51N
TRCS_
TCSSLT
LOCATION

Options
LOCATION
CCBSN CGL
LOCATION LOCATION
TCSSLT
TRCS_
TRCO_51N

N
(-)

ANSI Standard VCP-W Breaker ac Control Schematic

1 S-CPU
S-TRU
FUSE
CAC120
LOCATION
S-MRU

CS
C
CS PR
T
11
Spring

9UV
WL GL RL
Charged
Indicating
Light
UV

9UV
10UV
ac Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

ac (+) 12 UV
1 2
9A

4 5 9 6 7 8 10 3
10UV

7
Cap Trip Dev
3A

9
3

13

55

61

Y
51

57
53

a a
LS1 ac (–)
bb
Y SR
62
52

58

ST
54

ST 2
M 1
18 17 15 22 For ac UV
b b a
LC
a Trip Only
PS2 LS2 LS2 a
10A

bb PS Y
1 bb aa
Not Available when Second 13
14

56

10
4

24 21 20 16 19 Trip Coil Option is Chosen


TRCO_51N
TRCS_
TCSSLT
LOCATION

2
LOCATION
CCBSN CRL
LOCATION LOCATION
TRCS_
TRSS
TRCO_51N

Options

Figure 5.3-27. Typical 5/15/27 kV VCP-W “dc” and “ac” Control Schematics

Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay
PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
Application Details 5.3-45

Breaker dc Control Schematic


P S-CPU
S-TRU
LOCATION
FUSE
CDC0
S-MRU

(+)
CS CS PR
C T
11 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
Spring WL GL RL
Charged

9UV
Indicating
Light U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
UV U24

Auxiliary Switch #2 Optional

10UV
dc Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

12 OPTIONS
1 2 4 7 5 6 7 8 9 10 3

9A
13

57
3

61
3A

51

53

55
Y
LS1 a
bb a

54

62
Y

52

56

58
SR
ST
ST 18 17 16 15 22 2
b
LOCATION

M 1
b

10A
LC a
PS2 PS Y LS2 LS2 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14

10

a
4

24 21 20 19
N
LOCATION
TRCS_
TCSSLT
TRCO_51N

Customer Must Furnish


(-) This ”a“ Contact from
Auxiliary Switch When
Second Trip Coil Option
is Chosen and Make the
Appropriate Connections

Breaker ac Control Schematic


1 LOCATION
S-CPU
S-MRU
FUSE
CAC120
S-TRU

CS
C U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
CS PR
T
11
Spring WL GL RL
Charged
9UV

U24 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
Indicating
Light
Auxiliary Switch #2 Optional
UV
10UV
ac Source

9UV

OPTIONS
TRCO_51N
TRCS_
TCSSLT
LOCATION
14

ac (+) 12 UV
1 2 4 7 5 9 6 7 8 10 3
10UV
9A

CAP TRIP DEV


13

9
3A
3

61
55

51

a
53

57

Y
LS1 ac (-) a
bb
62
52

58
54

Y SR
ST
ST
1
18 17 15 22 2
For ac UV
M b a
LOCATION

b
Trip Only
10A

LC
PS2 PS Y LS2 LS2 a 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14

10

a
56
4

24 21 20 16 19
2
LOCATION
TRCS_
TRSS
TRCO_51N

Customer Must Furnish


This ”a“ Contact from
SACCN
SAACCN
MOTOR
CL_STD
CL_GR
CRL
TRIP
S-MRL
S-TRL
S-MRU
S-TRU
S-CPU
FUSE
CAC120
LOCATION
CONTACT
S-CPL

Auxiliary Switch When


Second Trip Coil Option
is Chosen and Make the
Appropriate Connections

Figure 5.3-28. Typical 38 kV VCP-W “dc” and “ac” Control Schematics

Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>

EATON www.eaton.com
VacClad-W 5–15 kV, Arc-Resistant Design Guide DG022003EN
Metal-Clad Medium-Voltage Switchgear Effective August 2020
5.3-46

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. DG022003EN / Z24265 All other trademarks are property
August 2020 of their respective owners.