Professional Documents
Culture Documents
Instruction Manual
Common for 200V/400V Converters
vz7000 SERIES
Throughout this manual, the following notes are used to alert you to safety considerations:
CAUTION: Only qualified electrical personnel familiar with the construction and operation of this
equipment and the hazards involved should install, adjust, operate, or service this equipment.
! Read and understand this instruction manual and all other applicable instruction manuals in their
entirety before proceeding. Failure to observe this precaution could result in destruction of the
equipment, severe bodily injury, or loss of life.
CAUTION: DC bus capacitors retain hazardous voltages after input power has been
disconnected. After disconnecting input power, wait for a while for the DC bus capacitors to
! discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could
result in destruction of the equipment, severe bodily injury, or loss of life.
CAUTION: In order to operate this equipment, the detailed explanation described in the inst- ruc-
tion manual relating to installation and operation of this equipment is required. These information is
! stored in CD-ROM, floppy disk or other devices packed in this equipment. If you need hard copies
of these information, please call +81-(0)45-701-1770.
CAUTION: Burn hazard exists on the upper surface of the converter due to the dangerous
temperature.
!
Reproduction of a part or an entirety of this instruction manual is prohibited without any written approval of REJ
Co., Ltd. in advance.
Table of Contents I
Chapter 7 Spare Parts ............................................................................................ 7-1
7.1 Spare Parts for 200V/400V Series Common Converters ............... 7-1
Chapter 8 Peripheral Devices for Converters....................................................... 8-1
8.1 Cables for I/O Terminal Blocks ....................................................... 8-1
8.2 Recommended AC Reactor............................................................. 8-2
8.3 Recommended DC Reactor ........................................................... 8-2
II VZ7000 Converter
List of Figures
Fig 2-1 - Regulator Board................................................................................... 2-1
Fig 2-2 - Front View of UAZ7055 ..................................................................... 2-2
Fig 2-3 - Front View of UAZ701A...................................................................... 2-2
Fig 2-4 - Front View of UAZ701E...................................................................... 2-2
Pin Arrangement of I/O Connector
Fig 2-5 -
(Viewed from connecting cable) .......................................................... 2-3
Fig 2-6 - Sequence Input and Output Signals.................................................... 2-7
Fig 2-7 - Analog Output Signals......................................................................... 2-8
Fig 2-8 - Timing Flow Chart of Input and Output Signals .................................. 2-9
IV VZ7000 Converter
Chapter 1
Outline
The VZ7000 converter is an equipment that does not need the precharge resistance
by using a thyristor to the rectifier and charging DC bus by controlling a phase.
In addition, this equipment converts three phase AC power, which can break AC
line input when an error is occurred, to DC power. Also, from safety point of view, the
VZ7000 converter equips with a AC line fuse. However, please be noted that the re-
sistance regeneration kit is required to radiate regenerative energy. Read carefully
and understand of the instruction manual for proper operation of the converter.
U AZ7 0 1A A
VERSION
No mark: Initial version
Then, A, B, and C are added in order
when the converter is modified or improved.
POWER VOLTAGE
4: 400V Series 2: 200V Series 0: Common Series
SERIES NAME
AZ7: VZ7000 Converter
NAME
U: Equipment
Note 1: The converter of which capacity is equal or more than 220 kW can construct parallel drive by
connecting UAZ701A and UAZ701E converters in parallel (parallel connection is available
until maximum four units). In practice, rating reduction is required. Please contact REJ Co.,
Ltd. when constructing a parallel drive.
Outline 1-
1- VZ7000 Converter
Chapter 2
Visual Appearance and Major Components
Fig 2-1 shows the regulator board, Fig 2-2, 2-3 and 2-4 show the front view for converters
from UAZ7055 to UAZ701E. The power terminal is covered by the front cover. The front
cover can be dismounted by loosing screws. These screws should be remained on the front
cover so as not to miss them.
CN11 7 1 1 2
14 8
1 3
B A
JP1 3 1
JP1
1
CODE LED
CN6
6
POWER
26
26
STATUS
POWER Lamp
J7
9 0 1 9 0 1
7 8
7 8
2 3
2 3
4 56 4 56
1
ADR Switch RST 1 S3 4
CN8
1
S5
DAT Switch
5
17 18
RED BLU
CN10
2 1
RST Switch
CN9
CN3
S3 Switch
1 3
20
19
2
1
9 1
9
CN4 CN2
PE
TB1 (R/L1)
WARNING!
WARNING!
警告!
感電の恐れあり 。
カバーを外す前に入力
電源を遮断し 、LEDが消
灯するまで待ち、 テスター でバス
電圧が50V以下となっていることを TB1 (T/L3)
TB3 (AC2)
確認してください 。キ ャパシタバン
クを使用しているときは放電する
までに17分以上かかる場合があり
ます。 ME-B7004B
M/N UAZ7*** R
SER No. ***** ********
Volt: 100 - 240Vac
Control Power Freq:
W ARNING ! 50 /60Hz
Supply In put Amps: *.* A
I/ M 39013
Hot surfaces on top.
Do not touch hot 3 PH, *** A (cont)
AC Input 3 80/400/440 /460V
NAME LABEL
surfaces. 5 0/60 Hz
Hot surfaces cause *** A
a burn. DC Output
540 - 620 V
警告 ! ENCLOSURE CHASSIS TYPE
装置上部に高温加熱
部があります。 火傷 Reliance Electric Limited
の危険があるので触 Made in Jap an
らないでください 。
ME-B7021
Unit.Rev. 0.1
D rive REV. 0.1
M8 M8 M8 M8
1
AC1
2
AC2
PE
WARNING!
WARNING!
TB1 (R/L1)
- Risk of electric shock -
Before removing the
cover, disconnect input
power, wait until the lamp is
turned off, and ensure with
voltmeter that DC-BUS voltage
is less than 50 V. Capacitor
discharge time is at least 17
min. when using Capacitor Unit.
警告!
!
TB1 (S/L2)
感電の恐れ あり 。
カバー を外す前に入 力
電源 を遮断し 、LEDが消
TB3 (AC1)
灯す るまで待ち、 テスター でバス
電圧 が50V以 下となっているこ とを
確認 してください 。キャパシタバン
クを使用してい るときは放 電する
までに17分以上かか る場合 があり
ます。 ME-B7004B
WARNING!
Mod el N am e : U AZ 701A
(1 10k W / 400V Seri es)
M1 0 M1 0
M1
0 Unit.Rev.
Dri ve REV . 0.1
0. 1 10
M 10
M
10
M
1
AC 1
AC2
2
3
N C
NC NAME LABEL 1
AC 1
AC 2
3
NC
N C
4 ×8
4 ×8
M
P1 P2 P N
WARNING!
- Risk of electric shock -
Before removing the
cover, disconnect input
power, wait until the lamp is
turned off, and ensure with
voltm eter that DC-BUS voltage
is less than 50 V. Capacitor
discharge time is at least 17
min. when using Capacitor Unit.
警告
警告!!
感電の恐 れあり 。
カバーを外 す前に入力
電源を遮断し 、LEDが消
灯するまで 待ち、 テス ターでバ ス
電圧が50V以下とな っていることを
確認してください 。キャパシタバン
TB2 (P2)
クを使用しているときは放 電す る
までに17分 以上かかる場合があり
ます。 ME-B7004B
W ARNING !
TB2 (P1)
a burn. M/N UAZ7*** R
警告 ! SER No. *** **********
Volt: 10 0 - 240Vac
Control Powe r
Freq: 50/60Hz
Su pplyInpu t Amps: *.* A
装置上部に高温 加熱
部があります 。 火傷 I/ M 390 13
の危険が あるので触 3PH, ** * A (cont)
TB3 (AC2)
らないでください 。 AC Inp ut 380/400/ 440 /460V
50/60 Hz
ME-B7021
DC Ou tput *** A
540 - 620 V
ENCLOSURE CHASSIS TYPE
Unit.Rev. 0.1
Dri ve REV. 0.1 M 12 M1 2 M1 2 M1 2
1 3
AC 1 N C
2 4
AC1 NC
P1 P2 P N
NAME LABEL TB2 (P)
TB2 (N)
The power circuit terminals are used to input and output power on the power circuit.
Table 2-1 Power Circuit Terminals
Terminal Name Terminal Code Description
TB1 AC power Input R/L1 Terminal for supplying power to the converter from
Terminal S/L2 AC power.
T/L3 Three phase AC 380/400/460V +/- 10%, 50/60Hz
Terminal PE Grounding
for Grounding
TB2 DC Reactor P1 Terminal for DC reactor. When connecting DC
Terminal for P2 reactor, remove the jumper bar and connect the
Connecting DC reactor.
Output Terminal P Output terminal for converting AC power to DC
N power and supplying power to the inverter
19 21 23 25 27 29 31 33 35
20 22 24 26 28 30 32 34 36
1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18
Fig 2-5 Pin Arrangement of I/O Connector (Viewed from connecting cable)
Note *: Numbers in parentheses in the column of Pin No mean terminal symbols of the terminal block of the
connector.
The LED indicator shows the operational conditions of the converter including failed state.
0 1 2 3 4 5 6 7 8 9
A(10) b(11) C(12) d(13) E(14) F(15) G(16) H(17) I(18) J(19)
Regarding the standard mode and parameter mode, refer to the “Chapter.4. Standard
Mode and Parameter Mode”.
CAUTION: Regarding the rotary switch and the DIP switch of face plate,
changing of the setting after power supply is invalid at the standard mode.
! Make sure that the setting has been completed properly before power
supply. Re-supply of the power is required when changing the setting.
Sequence input and output signals listed in the Table 2-3 are explained in the fol-
lowing Fig 2-6. The sink source can be changed, and external power supply can be
used with a way of wiring.
+3.3V
+24VI(0.1Amax)
4.7Kohm
0VI
2.2Kohm
RUN1
12V
~24V
RUN2
COM1
COM2
RB1
RB2
The analog output signal listed in the Table 2-3 are explained in the following Fig 2-7.
The common (0V) of analog I/O is the same potential as the terminal ground of the
processor.
When conducting the wiring of analog output, take an enough noise protection.
Otherwise, the converter may make an error.
470ohm 470ohm
Regulator Board
AOUT1
AOUT2
+/-10Vmax
0.1uF
0V
Sequence signals are processed in the converter under the following timing as
shown in the Fig 2-8.
Processing of sequence signals:
1. When power supply for the control circuit is turned on, the POWER LED is light-
ed.
2. The 7-segmented Code LED display with a decimal point flashes when the processor is
properly running.
3. of the processor is complete, and the converter is properly running,
the fault relay (FR) contact gets closed, and the regulator gets ready for operation.
4. When a RUN enable signal is entered, the DC BUS of the main power is charged
(status light blinks in green). When the charge is complete, RDY turns on
(status light turns green).
5. When the protection circuit detects an error, the gate signal of the thyristor gets immediately
disabled, and the error contact output FR opens.
6. The fault condition continues until a reset signal is input, or the unit is turned off and then
back on again. A reset signal can be received as long as RUN input signal is disabled.
7. The RB signal turns on when the DC BUS voltage reaches a level that enables regeneration.
Also, active RB signal enables a DC BUS capacitor to be discharged while the unit is off.
DC Bus Voltage
5sec 5sec
DC BUS Lamp Red
Close
RUN Open
ON
Protection Circuit Fault
OFF
ON
Reset
OFF
Close
Contact Output RDY Close Open Close
Open
2sec *2
RB
Exhaust Air
VZ7000
Converter
UAZ701A
100mm
4. Install the converter on the site having less noises. If the converter is used in
an environment adjacent to a noise source or the environment where noise
problems might be projected, please take sufficient countermeasures on them.
3-2
3.3 Wiring of Converters
Confirm that the input power supply to the converter coincides with the voltage and
frequency printed on the name plate of the converter and the power capacity for
your plant site is sufficient to supply input current necessary for the converter.
CAUTION: If the power source does not satisfy input power necessary
for a line, improper voltage may be supplied to the converter, and various
! instantaneous protection circuits may take action.
CAUTION: Risk of electrical shock exists. Provide one ore more circuit
breaker(s) in the incoming power line enabling to discharge the DC bus
! capacitor before accessing into the converter. Further, in order to avoid
electrical shock, open the circuit breaker in front of AC Input power before
accessing into the converter.
If proper line input voltage (200V for the motor with a cooling fan) can not be obtained,
a transformer is installed between the power source of the plant site and the converter.
Appropriate conducting wires for the converter are connected with the grounding
terminals for the motor frame, the external control station if it is used, the input and
output power transformer if it is used, and the drive. Confirm that this conducting
wires are properly connected, and then, connect it with the grounding pole.
Refer to the Table 3-3 for wires for input and output power supply for more informa-
tion. Select sizes of wires suitable for applied voltage and current in consideration
of types of wires, wiring methods, and length of wires.
Wiring of control and signal circuits is preferably performed in the following proce-
dures.
1 Confirm that all wires should be separated from the power lines. Because in-
duced voltage caused by current of the power lines may be generated in the
wires of the control circuit.
2 Use a separate duct for wires of the signal circuit. A dedicated duct for wires of
the signal circuit is preferably recommended.
3 The wires of the signal circuit must not pass through a junction box or the termi-
nal box prepared for cables for controls.
4 If the wires for the control circuit are crossed with each other, they must be
crossed at right angles.
5 Cables for signals must not pass through in the vicinity of the device generating
externally a magnetic field.
The Fig 3-2A shows the connection diagram when using one unit of the VZ7000
converter and the Fig 3-2B shows the connection diagram when using four units of
the VZ7000 converter in parallel.
When using VZ7000 converters in parallel, the communication is performed among
converters and necessary information is shared. Therefore, the wiring of sequence
signal of the interlock etc. is connected with only the master device.
DC Reactor VZ7000
Converter *3,4 Motor
Drive
R/L1 P1
RUN
S/L2 P2 DIN_COM VCC VCC
RUN 0V 0V
ENC
T/L3 P COM COM
AC Reactor FR1 COM/ COM/
*3 PE N FR2
ON
FR1 AC1
FR2 AC2
COM1(13) RDY1
COM2(14) RDY2
*8 IP1
0VI
P IP2
RUN1
RUN2
DC Reactor
Converter *3,4
R/L1 P1 Cf:-
1: Molded Circuit Breaker (1CB) is preferably installed for safety purpose.
S/L2 P2
2: The molded Circuit Breakers (2CB, 3CB) should be installed.
T/L3 P 3: The reactor has the harmonic restraint capability. Therefore installation of
AC Reactor
*3 PE N AC Reactor or DC Reactor is highly recommended.
FR1 AC1
4: When using the DC reactor, connect it to the P1, P2 terminals
FR2 AC2 by removing the jumper bar.
COM1(13) RDY1
COM2(14) RDY2
5: In case of parallel use, take an interlock signal from the only one converter
*8 IP1 6: Wire the DC BUS wiring as short as possible. When connecting in parallel,
0VI
P IP2
connect DC BUS of all units to become the same DC BUS voltage.
RUN1
RUN2 7. In order to radiate regenerative energy, use the resistance regeneration kit.
DC Reactor 8.To connect the units in parallel operation, use shielded twisted cables.
Converter *3,4
R/L1 P1
S/L2 P2
T/L3 P
AC Reactor
*3
PE N
FR1 AC1
FR2 AC2
COM1(13) RDY1
COM2(14) RDY2
0VI IP1
IP2
RUN1
RUN2
Fig 3-2B Connection Diagram for VZ7000 Converter (Four units in parallel)
Table 3-2 shows setting of switches when using converters in parallel. When
changed the setting, re-supply the control power.
1 Applicable wire sizes of power lines and fastening screws for terminals are listed in
the Tables 3-3. Select appropriate wires and screws in consideration of temperature
rise caused by types of wires, wiring methods, and various wiring lengths.
The Table 3-4 shows fastening torques of terminal block for each model. Fix a wire
to terminal block based on the fastening torque shown in the Table 3-4.
2 Use the twisted pair wire with 0.2 to 0.5 mm2 for the signal wires such as analog
output or sequence signal connected with the I/O connector for control signal.
Table 3-3 Wire Sizes, Terminal Screws for Each Converter Wiring
Model UAZ UAZ UAZ
7055 701A 701E
Applicable Motor (kW) 55 110 150
Power Capacity (kVA) 75 150 200
R/L1, S/L2, Applicable Wire (mm2) 60 150 200
T/L3, PE, Applicable Wire (AWG) 1/0 250/300 MCM 400 MCM
P1, P2, P, N Terminal Screw Size M8 M10 M12
AC1, AC2 Applicable Wire (mm2) 1.25
Applicable Wire (AWG) 16
Terminal Screw Size M4
I/O Connector Applicable Wire (mm2) 0.2
Applicable Wire (AWG) 24
Terminal Screw Size Soldered
Notes:
1. Be sure to use copper wires only of which temperature rating is 75 degree C for the power line (R/L1,
S/L2, T/L3, PE, P1, P2, P, N) wiring.
2. Use proper size pressure terminals for wires to be used, and the UL listed and CSA certified pressure
terminals should be used. When put pressure on the pressure terminal to connect the pressure
terminal with the wire, use the genuine tool (JST Mfg: YPT-60N, YPT-150-1, BCT-860N, BCT-8150, YF-4,
E-4) specified by the terminal manufacturer.
When supplying the control power of the VZ7000 converter, the regulator board starts based
on the standard mode.
Exchange of standard mode and parameter mode can be executed by pushing the RST
button of the faceplate for three seconds or more.
CODE
LED
456 456
RST S3
S2 x10 S1 x1
Switch
RST
1 2 3 4
1) Set up register bank from the #3, #4 of the S3. Set up register address from the ADR
switch. In order to return the setting to the original after changing parameters, take a
memo of the switch setting before changing parameters.
2) Set up register data from the DAT switch. A decimal point of the CODE LED illuminates
when a carry is recognized to the register data being set up from the DAT switch. (From
Unit Rev.#0.3, a carry is executed by turning on the S3-1.)
3) The data set by the DAT switch is registered to the parameter data by pushing the RST
switch and the value is displayed to the CODE LED.
4) When parameters setup is complete, get the switch that was changed in parameter
mode back to the original settings. Turn on #3 and #4 of S3 of the faceplate then
reverse the mode from parameter to standard by pressing and holding the RST switch
for at least three seconds until the STATUS LED goes off. If the RST switch is held less
than three seconds, unintended setting changes may occur. Further, you cannot return
to standard mode from parameter mode with the switch settings changed.
(In Unit Rev.#0.4 or earlier, you can bring it back to standard mode without returning to
the original switch settings. Switch settings get only enabled during the power-on
process. Make sure that you have restored the switch back to its original settings.
setting is executed. Therefore, if the switch setting is not returned, reading of incorrect
switch setting is executed when power is supplied.)
In parallel connection, set up the same parameters of register bank "0" among the converters as
follows: [ 0: Precharge Time ], [ 1: Regenerative Voltage Adjustment] ,
[ 2: OL Setting ], [ 9: Discharge ] and [ 10: Fuse Blow Detection ]
Reset the power supply when you have changed the settings.
0 1 2 3 4 5 6 7 8 9
A(10) b(11) C(12) d(13) E(14) F(15) G(16) H(17) I(18) J(19)
VZ7000 converter has an auxiliary function that records and stores the information of the
errors (fault codes) that occurred during the standard mode.
The stored fault codes can be referred if you set ON to #3 of SW3 and OFF to #4 of SW3
respectively in parameter mode. Also, if a value within range of 0-9 is specified to the ADR
switch, the fault code can be displayed in code LED. The last 10 fault codes are put in order
from what happened most recently and going backwards.
0 displays the latest record and 9 the oldest.
Logs older than 10 records will automatically be deleted. If there have not been any events or
events occurred less than 10 times, error code will not be recorded, so the code LED remains
off.
If the fault code is not stored properly due to some kind of failure, "n" will be displayed in code
LED. Normally, it never appears in the event of a typical failure. Event information recorded in
a log is retained regardless of whether the control power supply is off.
1. Verify that the molded circuit breakers are properly turned on or off depending on
the type of inspection intended to be conducted.
2. We recommend to work together with an assistant to prepare for emergency
cases.
! must not be used. Using the Megger may result in equipment damage.
1 Before power supply is turned off, verify conditions of display lamps listed in the
Tables 2-4 and 5-1.
2 Turn off power supply and wait at least five minutes until the DC bus lamp goes off
then verify that DC bus voltage drops down below 50V by using a multimeter.
If a capacitor "C. UNIT" is implemented, discharging can take longer than nomral
time.
.
3 Verify the following safety items.
• Loose terminals and connections.
• Power supply voltage.
• Grounding for the converter and the motor frame.
• The surge suppressors are properly installed on coils of relays, solenoid
valves, and magnetic brakes which can generate noises in the vicinity of the
converter and motors.
4 Verify that protective functions are suitable. If not, readjust them and power up.
Inspection for Troubles and Countermeasures 5-
5.3 Fault Codes
When the abnormality is occurring or an alarm is issued on abnormality detection, the STATUS
LED and CODE LED behave as follows:
Abnormality: STATUS LED – Red, CODE LED – ON
Alarm : STATUS LED – Off, CODE LED - Blinking
When two or more events are occurring, fault codes are displayed in a sequential manner.
If an alarm is issued during an abnormal event, an alarm code will not be displayed.
In parameter mode, parameter settings indicated in the ADR switch are displayed in code LED
regardless the presence of events. The fault code is displayed when the status indicator is
blinking in orange.
Table 5-1 shows a list of codes and abnormal condition.
Notes:
(*1) When “d” indicating that an error is occurring in the other device is displayed, you can clear the
error by resetting the converter where LED turned on.
(*2) “L” indicating Instantaneous power interruption is not detected unless RUN signal is input.
When the converter is used as a power supply of the inverter, make sure that the full
rated output current and instantaneous maximum output current of the converter are greater
than the total of rated current and overload current of inverters to be connected, respectively.
The dimension diagrams of UAZ7055, UAZ701A and UAZ701E are shown in the Fig
6-1.
W1 D
W2
f dP
V Z7 000
DIGITAL AC SERVO DRIVE
H1
H2
H3
p
W2
Unit: mm
Converter W1 W2 H1 H2 H3 D dP p, f
UAZ7055 200 160 349 390 410 18 9
UAZ701A 344 300 350 20 10
360 430 460
UAZ701E 547 490 24 12
The Table 7-1 shows spare parts for converters. The numbers shown in the table means the
necessary quantity of the part. The blank space means the part is not necessary for the
corresponding converter model. Some parts may be changed by modified standards, integration or
discontinuance of parts in the future. In case any spare parts is required, contact with our local
offices in advance.
Qty to be Used(UAZ)
Standard /
Part Name Part Number 7055 701A 701E 701A 701E 701A 701A 701E 701E
Specifications
*2 *2 *3 *4 *3 *4
ACDC-7
Regulator Board B40829624XXX 1
S-B7040
170M1369 B40286586AXR 3 - - - - - - - -
Fuses 170M4412 B40286582AXR - 3 - 6 - 9 12 - -
170M4415 B40286585AXR - - 3 - 6 - - 9 12
PD130FG160 B40574079AXR 3 - - - - - - - -
Thyristor TD250N16KOF B40574941AXR - 3 - 6 - 9 12 - -
TD285N16KOF B40574942AXR - - 3 - 6 - - 9 12
MB-B7076 B40929027XXR 1 - - - - - - - -
Capacitor MB-B7073 B40929020XXR - 1 - 2 - 3 4 - -
MB-B7074 B40929024XXR - - 1 - 2 - - 3 4
MB-B7075 B40929028XXR 1 - - - - - - - -
Surge Protector
MB-B7071 B40929019XXR - 1 1 2 2 3 4 3 4
Cooling Fans MB-B7062 B40929021XXR 1 2 3 4 6 6 8 9 12
PBA50F-24-CJ B40370545BXR 1 1 - 2 - 3 4 - -
Power Supply
PBA75F-24-CJ B40370546AXR - - 1 - 2 - - 3 4
The following table shows types and connecting methods of cables for the I/O termi-
nal blocks.
Table 8-1 Types and Connecting Method of Cables for I/O Terminal Blocks
Length Approx Weight
Cable for I/O Terminal Block Catalog No. Cable[m] [kg]
MB-B7001-01 B40174013XXR 1 0.2
MB-B7001-xx MB-B7001-02 B40174013AXR 2 0.4
MB-B7001-03 B40174013BXR 3 0.6
Connector Case
Note: When Converters are connected in parallel, the same number of AC reactors is required.
Note: When Converters are connected in parallel, the same number of DC reactors is required.