This document provides calculations for CO2 fire protection requirements for a project. It lists the input data used, including an area of 30 square meters, a height of 3.5 meters, a ventilation area of 12 square meters, a volumes factor of 1.35 kg/m3, a time of discharge of 2 minutes, and a forced ventilation rate of 5 kg/min. The output data calculated is a required CO2 mass of 201.75 kg and a required flow rate of 100.875 kg/min.
This document provides calculations for CO2 fire protection requirements for a project. It lists the input data used, including an area of 30 square meters, a height of 3.5 meters, a ventilation area of 12 square meters, a volumes factor of 1.35 kg/m3, a time of discharge of 2 minutes, and a forced ventilation rate of 5 kg/min. The output data calculated is a required CO2 mass of 201.75 kg and a required flow rate of 100.875 kg/min.
This document provides calculations for CO2 fire protection requirements for a project. It lists the input data used, including an area of 30 square meters, a height of 3.5 meters, a ventilation area of 12 square meters, a volumes factor of 1.35 kg/m3, a time of discharge of 2 minutes, and a forced ventilation rate of 5 kg/min. The output data calculated is a required CO2 mass of 201.75 kg and a required flow rate of 100.875 kg/min.