CO2 Gas Suppression System design calculation refer to NFPA 12 (1989 Editio n)-
Carbon Dioxide Requirements For Deep Seated Fire:
Design Parameters
Design Concentration: 50%
Ambient Temperature: 30°C
Volume Factor for Total Flooding: 1.33 kg CO2/m3
Design Calculations
Thus,
Quantity of CO2 Gases Required
For Total Flooding of the Room: 1833.79 m3 x 1.33 kg CO2/m3 = 2438.941 kg
Design Parameters
Design Concentration: 50%
Ambient Temperature: 30°C
Volume Factor for Total Flooding: 1.33 kg CO2/m3
Design Calculations
Thus,
Quantity of CO2 Gases Required
For Total Flooding of the Room: 430.144 m3 x 1.33 kg CO2/m3 = 572.0915 kg