Volume of space : 54 m3
Type of combustible : Gasoline
Ventilation openings
Air outlet near ceiling: 0.5 m2
Air inlet centered at 2.1 m below ceiling: 0.5 m2
From Table 5.3.2.2., the minimum CO2 design
concentration can be found.
3
Minimum design CO2
concentration of
gasoline is 34%
4
From NFPA12:2018
6
Material conversion factor can be found from
FIGURE 5.3.4.
7
Because the design concentration is not over 34%,
no conversion is needed.
8
CO2 will be lost through the bottom opening while air
enters through the top opening.
9
17.5 x 4.89 =
85.58
10
From Session 5.3.5.1 Openings that cannot be closed –
any openings that cannot be closed at the time of
extinguishment shall be compensated for by the
addition of a quantity of CO2 equal to the anticipated
loss at the design concentration during a 1-minute
period.
Additional CO2 for openings = 85 x 0.5 = 42.5 kg
Total CO2 required = 48.6 + 42.5 = 91.1 kg
11
Reference: NFPA12 Standard on
Carbon Dioxide Extinguishing Systems (2018)
12
Table 5.3.2.2. for the
minimum CO2