FIXED INSTALLATION CARBON DIOXIDE (CO2) EXTINGUISHING SYSTEM

A) BILIK TNB

1. Room Dimension

Room Name : Bilik TNB


Room Dimensions : Area x Height
: 16.6 m² x 4.5 m

2. Design Criteria

Design Code : NFPA 12 : 1985


Hazard Type : Total Flooding –Deep Seated
Design Concentration : 50%
Rate of Application : 70% discharge in 2 minutes.
Room Temperature : 77oF (25 oC)

3. Agent Discharge

Volume of Space (V) : 74.7 m3


Flooding Factor (F) : 1.33 kg/ m3 (Refer Table 104 as per attachment)
Basic CO2 Quantity (W) : 74.7 (V) x 1.33 (F) = 99.4 kg

4. Total Agent Quantity

Basic CO2 Quantity (W) : 99.4 kg


Add Safety Factor (25%) : 124.3 kg
Agent weight per cylinder : 45 kg
No. of cylinders : 124.3/45
= 2.8
≈ 3.

No. of cylinders provided : 3 (nos.) x 45 (kg) each

CO2/1
CO2
5. Pipe Sizing (Refer Table 105 as per attachment)

Total mass flow rate = 3 x 45 kg x 70%


2 min.
= 47.3 kg/min.

Section Flow Rate (kg/min) Pipe Size (mm)


A-B 47.3 20
B-C, B-D 23.7 15

3 nos. CO2 cylinder


(45 kg each)

CO2/2
CO2
B) BILIK TRANSFORMER 1

1. Room Dimension

Room Name : Bilik Transfrormer 1


Room Dimensions : Area x Height
: 10.6 m² x 4.5 m

2. Design Criteria

Design Code : NFPA 12 : 1985


Hazard Type : Total Flooding –Deep Seated
Design Concentration : 50%
Rate of Application : 70% discharge in 2 minutes.
Room Temperature : 77oF (25 oC)

3. Agent Discharge

Volume of Space (V) : 47.7 m3


Flooding Factor (F) : 1.33 kg/ m3 (Refer Table 104 as per attachment)
Basic CO2 Quantity (W) : 47.7 (V) x 1.33 (F) = 63.5 kg

4. Total Agent Quantity

Basic CO2 Quantity (W) : 63.5 kg


Add Safety Factor (25%) : 79.4 kg
Agent weight per cylinder : 45 kg
No. of cylinders : 79.4/45
= 1.8
≈2

No. of cylinders provided : 2 (nos.) x 45 (kg) each

CO2/3
CO2
5. Pipe Sizing (Refer Table 105 as per attachment)

Total mass flow rate = 2 x 45 kg x 70%


2 min.
= 31.5 kg/min.

Section Flow Rate (kg/min) Pipe Size (mm)


A-B 31.5 15
B-C, B-D 15.8 15

2 nos. CO2 cylinder


(45 kg each)