Total Cooling
Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 12 70 1 è 840.00 840.00 2,866.20
Total Cooling
Area (m2) Density (W/m )
2 CLF Factor Load (W) Load (W) Load (Btu/hr)
Internal sources
Light 64 18 1 1.2 1,382.40 1,382.40 4,716.94
Power 64 30 1 1 1,920.00 1,920.00 6,551.31
Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δt Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 12 2.5 30 10 369.00 369.00 1,259.08
Infilteration (base on ACH = 0.3) 18 10 216.29 216.29 738.02
Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δw Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 12 2.5 30 0.01295 1,169.39 1,169.39 3,990.11
Infilteration (base on ACH = 0.3) 18 0.01295 685.44 685.44 2,338.83
= 101
1,224
= 8.23
say 8%
= 33 x 0.08 = 2.64
23 x 0.92 = 21.16
Mixture 23.8
o
say 23.8 C