You are on page 1of 28

TRANE TM

BYC-D-3
June 1989

81/2, 11 , 14, 17 Ton Convertible


Cooling/Gas heat Packaged Units
BYC100,130,170,200G

DATA CATALOG

Since The Trane Company has a policy of continuous


22-1308-3
product i mprovement , it reserves the right to change
specif ications and design without notice .T
J O
Cooling/Gas Heat Packaged Units
BYC100-200G

The BYC100-200G gas/electric -- ,


rooftops feature:
• A.G.A. certification
. _ ^
• Aluminized heat exchanger
• Forced combustion
• Electronic ignition
• Sight glass for burner inspection
• Lifting points
• Mounting rails
• Overhanging condenser coil
• Zinc-coated steel, phosphatized,
epoxy resin primer, baked enamel
finish
• Hermetic compressor(s) with
winding thermostat
• Crankcase heaters
• R-22 operating charge
• Filter dryers
Accessories • Time Delay Relay (BYC130-200)
• Dual refrigerant circuits
(BYC130-200) • Manual Changeover • Low Ambient Dampers (BYC100)
Thermostats to 0 F
• Expansion valves 1 H/1 C (BYC100) • Low Ambient Two-Speed Motors
• Access valves 1H/2C (BYC100-200) (BYC130-200) to 0 F
2H/2C (BYC100-200)
• Inherent motor overloads • Oversize Evaporator Fan Motor
• Auto Changeover
• Completely prewired Thermostats • Two-Stage Gas Valve (460/60/3
• Standard operation to 30 F 2H/2C (BYC100-200) high and low heat only; standard
on 208-230/60/3)
• Adjustable belt-drive evaporator • Central Control Panel
fan(s) • LPGas Conversion Kit
• Central Control Panel Thermostat
• Threaded drain connection 1 H/1 C ( BYC100)
• One-inch throwaway filters
2H/2C (BYC100-200) Factory-Installed Options
• Programmable Electronic N ight • Downflow Econo m izer
• Two-stage gas valves, 208-230 volt
Setback Thermostat • Copper Evaporator Coils
units, high and low heat
Single-Stage
• Filter racks convertible to 2-inch Multistage • Copper Condenser Coils
• Programmable Thermostat Remote
Sensor
• Horizontal Conversion Panels
• Roof Curb
• Antishortcycle Timer
• Downflow Economizer with Ultra
Low Leak Dampers and Barometric
Relief

• Horizontal Economizer with


Barometric R elief
Ta ble of Co ntents
• Downflow Manual Outside Air Hood
Model Nomenclature 3
Genera l Data 4
Performance Data 5
Dimen sional Data 11
Field Wiring 19
Mechanical Specifications 26
c A merica n S tandard Inc. 1986 2
Cooling/Gas Heat Packaged Units
BYC100-200G

'.._: Models Available Nominal Tonnage Power Supply


BYC100G3 8.5 208-230/60/3
B YC100G4 8 .5 460/60/3
BYC100GW 8 .5 575/60/3
BYC13OG3 11 208-2 30/60/3
BYC1 30G4 11 460/60/3
BYC 130GW 11 575/60/3
BYC170G3 14 208-230/60/3
BYC1 70G4 14 460/60/3
BYC170GW 14 57 5/60/3
BYC200C3 17 208- 230/60/3
BYC200G4 17 460/60/3
BYC200GW 17 57 5/60/3

Model
Nomenclature

B Y C 1 0 0 G 3 L 0 D

.,
T
Always " B"
^^.

M inor Design Sequence


Product Type
YC = Gas/Electric, Packaged Factory Installed Options
I 0 = N one
Cooling Capacity ( MB h)

100 = 100 MB h Heating Capacity


130 = 130 MB h
170 = 170 MBh L = Low
200 = 200 MB h H = High

Major Development Sequence Electrical Characteristics/Agency Approval


Numeric = U . S . Alpha = Canada &
Domestic I nternational
(Including A . G . A. (Including C . S . A .
Models) Models)

3 = 208-230/60/3 U = 208-230/60/3
4 = 460/60/3 V = 460/60/3
W = 575/60/3

3
General
Data

Table 1 General Data


B YC100G BYC130 G BYC170G BYC200G
N o m inal Data '
Gross Cooling Capacity 97 131 168 200
N om ina l cfm 3 400 4400 5600 6800
C o mp ressor Data
N u mber/Size 1 /7.5 2/5 2/6 .25 2/7.5
U n it C apac ity Steps (%) 100/Off 100/50/Off 100/5 0/Off 100/50/Off
Condenser Fan Data
C y c le/ Phase 60/ 1 60/ 1 60/1 60/ 1
HP/ N u mbe r 1/3 (2) 1 /2 (3 ) 1 /2 (3) 1!2 (3)
Fan D r ive Direc t Direct D irect Di rec t
N o minal Rpm 1100 1 725 1 7 25 1725
Condenser Coil Data
N o./Size 1 /67-3/4x34 1 /78- 1 f4x44 1 178- 1 l4x44 1 /78- 1 /4x48
Face Area (sq. ft .) 16.0 23.91 23.9 26.1
R ows/F in s per In c h 3/ 14 2/15 3/ 1 3 3/ 14

E vaporator F a n Data
N umber Fans/ M otor H P 1/2 1/3 2/3 2/5
R pm R ange 819-12 5 1 78 2-1 0 1 1 7 82- 1011 840- 1066

Evaporato r Coi l D ata


Coil Size (in.) 44x24 55x30 61x30 69x30
Face A rea (sq ft ) 7.33 11 . 46 1 27 1 1 4 .38
R o ws/ F i n s pe rin c h 3/1 5 4/12 4/ 12 4/ 1 2

Efficiency Data2'
E ER 8 .6 8.3 8.4 8 .5
Cf m/ N et MBh 2700/90 .0 3500/ 121 . 0 4 500/ 1 54 .0 51 00/1 80. 0
T ota l kw 10 .5 14. 6 1 8 .3 2 1 .2
Compressor k w at A . R .I. 8.6 1 2.1 14.7 17. 4

Gener al Data
Filt e r- N o. (4) ( 6) ( 6) (6)
Size 1x16x25 1 x 2 0x20 1x1 6x20 1x 2 0x25
(2)
1x20x20
A .R. I . So und Rating ( BELS) 8.0 8. 8 8.8 8.8
Refrig. C ha rge ( R -22) 1 4 lbs. 12 oz. 19 lbs. 8 oz. 27 lbs. 29 Ibs. 4 oz.
NOTES
9, Unit nomi nal c fm is approximat ely 400 c fm per nomin al net to n. No te that A . RJ . rating c fm is n o t t h e s ame a s
nomin a l c im ,

2 BY Ct O0.13QG rated in ac corda nce with A . R I. standard 210 at AR . I . con ditions, 80/67, 95 F a m b ien t
3. BYC176200G rated in accordance w ith A.R I. stan d ard 360 at A RJ. con d it ions 80167, 95 F ambie nt .

4
Performance
Data

Table 2 BYC100G Gross Cooling Capacities


Ambient Temperature
85 95 105 115
Ent .
Cfm Dry Entering Wet Bulb
Std . Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Air (F) MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR

75 88 . 82 98 . 57 109 .36 83 . 84 93 . 58 103 .36 78 . 86 87 . 59 98 . 36 73 .89 82 . 61 91 . 36

80 89 . 95 98 . 70 109 . 48 84 .97 93 . 72 103 .49 80 . 99 87 . 74 97 . 50 75 1 . 00 82 . 76 91 . 50


2400
85 92 1 . 00 98 . 83 109 .60 88 1 . 00 93 .85 103 .61 84 1 . 00 88 . 88 97 . 63 80 1 .00 82 . 90 91 . 64

90 97 1 . 00 99 .94 109 .72 93 1 .00 94 .97 103 . 73 89 1 . 00 89 .99 97 . 76 85 1 .00 85 1 . 00 91 . 78

75 91 . 88 101 . 60 113 .36 86 . 90 96 .61 107 .37 81 . 93 90 .63 100 . 37 76 .95 84 . 64 94 . 37

BO 93 1 . 00 101 . 75 113 . 50 89 1 . 00 96 . 77 107 . 51 85 1 . 00 90 .80 100 . 52 80 1 .00 84 . 82 94 . 53


3000 . 97 94 . 70
85 99 1 .00 102 . 90 113 . 64 95 1 . 00 97 . 92 107 . 66 90 1 . 00 91 .95 100 . 68 85 1 .00 86
90 105 1 . 00 105 1 . 00 113 . 78 100 1 . 00 100 1 .00 107 . 80 95 1 . 00 95 1 .00 101 . 83 90 1 .00 90 1 .00 94 . 85

75 93 . 91 103 . 62 115 . 37 88 . 94 97 . 63 tOB . 37 83 . 96 91 .65 102 . 37 78 . 99 85 67 95 . 37

80 97 1 .00 103 . 79 114 . 52 92 1 . 00 97 .81 108 . 53 87 1 . 00 92 . 84 102 . 54 83 1 . 00 86 86 95 . 55


3400
85 103 1 . 00 104 94 114 .67 98 1 .00 99 . 96 108 . 69 93 1 . 00 94 . 98 102 . 71 88 1 . 00 88 1 .00 95 . 74

90 109 1 . 00 108 1 . 00 115 .82 104 1 .00 104 1 . 00 109 .84 99 1 .00 99 1 .00 102 . 87 94 1 . 00 94 1 . 00 96 .90
75 94 . 93 104 . 63 115 .37 89 . 95 98 . 64 109 .37 84 .98 92 . 66 102 . 37 78 1 .00 86 . 68 96 . 37

80 98 1 . 00 104 .80 115 . 53 94 1 .00 98 . 83 109 . 54 89 1 .00 92 . 85 102 . 55 84 1 . 00 86 . 89 96 . 56


3600
85 104 1 . 00 106 . 95 115 .68 99 1 . 00 100 . 97 109 . 70 94 1 .00 95 . 99 102 . 73 89 1 . 00 89 1 . 00 96 . 75

90 110 1 . 00 110 1 . 00 116 .84 105 1 . 00 105 1 . 00 109 .86 100 1 .00 100 1 . 00 103 . 89 95 1 . 00 95 1 . 00 97 . 92

NOTES :
1 . All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat
2 . MBh = Total Gross Cooling Capacity
SHR = Sensible Heat Ratio
Sens i ble Heat Capacity (SHC) = MBh x SHR

Table 3 BYC130G Gross Cooling Capacities


A m b ient Te m pera ture
85 95 105 115
Ent .
C fm Dry Entering Wet Bulb
Sid. Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Air ( F) MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh S HR MBh SHA MBh SHR MBh SHR MBh SHR

75 1 20 . 83 135 .57 1 51 . 36 114 . 85 128 .58 143 . 36 107 . 87 120 . 59 1 35 .36 100 90 11 3 . 61 127 .36

80 1 21 . 96 1 35 .7 1 1 50 .48 115 . 97 12 8 . 72 143 .49 110 1 . 00 120 .74 135 .50 104 1 .00 1 13 . 76 1 26 .51
3600
85 127 1 . 00 135 . 84 150 . 60 122 1 .00 128 . 86 143 .61 116 1 . 00 1 21 . 88 1 35 .63 11 0 1 .00 1 13 .91 1 26 . 65
90 1 35 1 .00 1 36 . 95 150 .72 129 1 . 00 130 . 97 143 .74 123 1 . 00 1 23 . 98 13 5 .76 117 1 .00 1 17 1 . 00 126 . 79
75 122 .85 1 37 .59 153 . 36 116 .87 130 . 60 145 .36 109 .90 1 22 .6 1 1 37 .36 10 2 .93 1 14 .62 128 .37
80 124 .98 137 .73 153 .4 9 11 9 1 .00 130 .75 1 45 .50 113 1.00 122 .77 137 .51 107 1 .00 11 4 .79 128 .52
4000
85 1 32 1 . 00 1 37 . 87 153 .62 126 1 .00 130 . 89 145 .63 1 20 1 .00 123 . 92 1 37 . 65 1 14 1 .00 11 6 . 94 128 .6 7
90 13 9 1 .00 140 .67 153 .75 134 1 . 00 134 1. 00 145 . 77 128 1 .00 128 1. 00 1 37 . 79 1 21 1 .00 121 1 . 00 128 . 82
75 1 24 . 88 139 .60 155 . 36 118 . 90 131 . 61 147 .36 111 . 93 124 .62 1 39 . 37 104 . 95 1 16 . 64 130 .37
80 12 8 1 . 00 139 .75 1 55 . 50 122 1 .00 131 . 77 147 .51 116 1 . 00 124 . 80 139 .52 110 1 . 00 11 6 . 82 130 .53
44 00
85 135 1 . 00 139 . 90 155 .64 130 1 .00 132 . 92 147 .65 1 24 1 . 00 1 25 . 94 1 38 . 67 1 17 1 . 00 118 . 97 130 .70
90 143 1. 00 143 1 . 00 155 .7 7 137 1.00 13 7 1 . 00 147 .80 131 1 . 00 1 31 1. 00 1 39 . 82 125 1 .OD 125 1 . 00 130 .85
75 1 26 90 140 .61 15 7 . 36 119 . 93 1 33 .62 149 .37 11 2 . 95 125 . 64 140 .37 105 .97 1 17 . 66 131 .37
80 1 31 1. 00 140 .78 1 56 .5 1 125 1 .00 133 . 80 148 .5 2 119 1 . 00 125 .82 140 .53 1 12 1 .00 1 17 . 85 131 .5 4
4800
85 139 1.00 1 42 . 92 156 .66 133 1. 00 134 . 94 1 48 ,68 127 1.00 127 .97 1 40 .70 120 1.00 120 .98 131 .72
90 147 1 . 00 147 1. 00 156 .80 141 1 . 00 141 1 . 00 149 .84 134 1 .00 134 1 . 00 140 .85 128 1. 00 1 28 1 . 00 1 31 .88

NQTES:
1 . Al l capacities sh ow n a re gross and have not considered indoor fan heat . To obtain net cooling capacities subt ract i ndo o r fa n heat .

2. MBh = Tota l Gro ss Coo l ing Capac i ty


SHR = Sens i b l e Heat Ratio
S ensible Heat Capaci t y (S HC ) = MBh x SHR

5
Performance
Data

Table 4 BYC170G Gross Cooling Capacities


Ambient Temperature
85 95 105 115
Ent .
Cfm Dry Entering Wet Bulb
Std . Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Air (F) MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR

75 151 80 169 98 189 37 143 82 160 57 178 37 134 84 150 58 168 36 125 86 140 59 158 36

80 153 93 169 69 189 47 145 94 160 70 178 48 136 97 150 72 168 49 129 100 140 74 157 50
4000
85 159 100 169 81 189 59 151 100 160 83 178 60 144 100 151 85 168 61 137 100 141 88 158 63
90 167 100 171 92 189 70 160 100 162 94 178 71 153 100 153 96 168 73 145 100 145 97 158 75
75 158 85 175 59 195 36 149 87 165 60 184 36 139 91 155 61 173 36 130 93 145 63 162 37
5 80 161 98 175 74 195 49 153 100 165 76 184 50 145 100 155 77 173 51 137 100 145 80 162 52
000
85 170 100 176 89 195 63 162 100 167 89 184 64 154 100 157 92 173 66 146 100 147 95 162 68
90 180 100 180 97 195 75 172 100 172 100 184 78 164 100 164 100 173 80 155 100 155 100 162 83
75 161 BB 178 61 198 36 151 91 168 62 187 36 142 93 157 63 175 37 133 96 147 65 1 64 37
80 166 100 178 76 197 51 158 100 168 79 187 51 150 100 158 81 175 53 142 100 147 84 164 54
5600
85 175 100 180 91 197 65 168 100 170 92 187 66 159 100 160 96 175 69 151 100 151 97 164 71
90 186 100 185 100 198 79 177 100 177 100 187 81 168 100 169 100 176 84 160 100 160 100 165 87
75 162 91 179 62 199 37 153 93 169 63 188 37 144 95 159 64 177 37 135 97 148 66 165 37
80 169 100 180 78 199 52 161 100 169 80 188 53 153 100 159 83 177 54 144 100 148 86 165 55
6000
85 179 100 182 92 199 66 171 100 172 95 188 68 162 100 163 96 176 71 153 100 153 100 165 73

90 190 100 189 100 200 66 181 100 181 100 189 83 172 100 172 100 178 86 163 100 163 100 167 89

NOTES :
t . All capacities shown are gross and have not considered indoor fan heat . To obtain net cooling capacities subtract indoor fan beat
2. MBh = Total Gross Cooling Capacity
SHR = Sensible Heat Ratio
Sensible Heat Capacity (SHC) = MBh x SHR

Table 5 BYC200G Gross Cooling Capabilities


Ambient Temperature
95 105 115
Ent .
Cfm Dry Entering Wet Bulb
Std . Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Air (F) MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR MBh SHR
75 180 81 201 56 224 36 170 82 190 57 212 36 160 84 179 58 200 37 150 87 167 60 187 36
80 182 93 201 69 224 48 172 96 190 71 212 48 163 98 179 72 199 49 154 100 167 74 187 50
4800
85 189 100 201 82 223 59 181 100 190 84 212 60 172 100 179 86 199 62 163 100 169 89 187 63

90 199 100 203 93 223 70 191 100 193 95 212 72 182 100 183 97 199 74 173 100 173 100 187 76

75 187 87 208 59 231 36 177 89 196 60 218 36 166 91 184 62 206 36 156 94 172 63 193 37

80 192 98 207 74 231 50 183 100 196 76 218 50 173 100 185 78 205 52 164 100 173 81 193 53
6000
85 203 100 210 88 231 63 194 100 198 95 218 68 184 100 187 93 205 67 175 100 176 95 193 68
90 214 100 214 98 231 76 205 100 205 100 219 79 195 100 195 100 206 81 185 100 185 100 . 194 84
75 191 90 211 61 235 37 180 93 199 63 222 36 170 95 187 64 209 37 159 97 175 66 195 37
80 198 100 212 77 235 51 189 100 200 80 222 52 179 100 188 82 209 53 170 100 176 85 195 55
6800
85 210 100 214 92 235 66 201 100 203 95 222 68 191 100 191 96 209 70 181 100 181 98 195 72
90 222 100 222 100 235 80 212 100 212 100 223 83 202 100 202 100 210 85 192 100 192 100 197 88
75 193 92 213 62 236 37 182 94 201 63 223 37 171 96 188 65 210 37 161 98 176 67 197 37
80 202 100 213 79 236 52 192 100 201 81 223 53 182 100 189 84 210 54 172 100 177 87 196 56
7200
85 214 100 216 94 236 67 204 100 205 96 223 70 193 100 194 97 210 71 183 100 183 100 196 74

90 226 100 226 100 237 82 216 100 216 100 224 85 205 100 205 100 211 88 195 100 195 100 199 90

NOTES :
1. All capacities shown are gross and have not considered i ndoor tan heat . To obtain net cooling capacities subtract i ndoor fan heat .

2 . MBh = Total Gross Cooling Capacity


SHR = Sensible Heat Ratio
Sensible Heat Capacity ( SHC) = MBh x SHR

6
Performance
Data

Table 6 Unit And Accessory Weights (Lbs.)


Accessories (Net Wts . )

Downflow Low Ambient


Man .
Unit Economizer Horiz . OA Roof Oversize 2-Speed
Model Net Ship Net ^ Ship Economizer Damp Curb Motor Dampers Motor
BYC100G 1120 1340 65 165 120 26 100 65 50
BYC130G 161 5 1890 71 173 165 30 120 65 20
BYC170G 1725 2040 75 179 190 32 130 65 20
B YC200G 1 945 2290 80 1 86 230 36 1 40 85 20
' Th is ne t weig h t should be added to un it weight whe n o rdering facto ry instal led econom izer.

Table 7 Heating Section General Data


Model BYC100G BYC130G BYC170G BYC200G
Heating Input (MBh) 120 250 160 300 160 300 240 400
Number of Burners 6 10 4 6 4 6 6 8
N umber of Heat
Exchanger Elements 6 10
Gas Connection
Pipe Size (in.) 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4
M in. Gas Pipe
Size (in.)*
25 ft. 3/4 1 3/4 1 3/4 1 1 1
50 ft. 1 1-1/4 1 1-1/4 1 1-1/4 1-1/4 1-1/4
100 ft. 1 1-1/4 1-1/4 1-1/4 1-714 1-1/4 1-1/4 1-1/2
For natura l gas, 900-1 1 00 Btu/cu, ft „ 0. 65 speci f ic grav i ty; based on app rox imately 0. 4 i nc h water g auge pi pe l oss.

Table 8 Gas-Fired Heating Capacities


Heating Hea tin g H eati ng Heat i n g
Input Output In p ut Ou tput
A .G. A . A .G. A . C.S.A C.S. A.
M odel Heat MBh MB h MBh MBh
Low 120 97.2 150 1 1 2.5
BXC100G
High 250 18 7.5 250 1 87.5
Low 160 121.6 200 150.0
B YC130G
High 300 225 .0 300 225.0
Low 160 121 . 6 200 150 .0
BYC170G
High 300 225 . 0 300 225.0
Low 240 184 . 5 300 225 . 0
BYC200G
H i gh 400 300 .0 400 300 .0
1000 x MB h O utput = Air Temperature Rise
1 .085 x cfm
Performance
Data

Table 9 Evaporator Fan Performance - Bottom Su pply/Return


aa.
External Static Pressure (inches
80°
of Water) 2 00°
10° 20" aa• 50° 60° 70" ea• i.ar, 1z6° 1.50° i.is..
Unit Cfm RPM BHP RPM BHP RPM BH p RPM BHP RP M 9HP RPM BHP RPM 8liP RPM BHP RPM BHP RPM BliP RPM BHP RPM BH P RPM B HP RPM BHP
2400 797 74 NO 82 880 .90 9 19 17 956 1.05 993 1 .13 1 02 9 1 21 1064 1 30 1 099 1. 39 11 33 1 . 48 1 212 1 . 70 1286 1. 92 1111 :: IL ] 4 1 410 237
2700 886 103 92 5 1. 1 2 962 7.21 997 1 . 29 1 0 31 1_ 38 7 065 1 .46 1098 1. 55 1130 1.64 1 162 1.7 4 1194 1 . 83 ^1 7 041 ,- _N j&,AA1412 2.816
BYC100 G 3000 975 139 1011 1.49 1 04 5 1. 59 1 078 7. 69 1110 iJB 11 4 1 1. 87 1171 1.97 15l 2* - - ---_ 2; 1 -, p^ -;•1^ .- - -
M
330 0 1 066 1. 82 1 099 1. 93 114 7 YA 1-*t 2. 15 11 01 238 5 40 7 xiE 11I-12 75 t. 9
0
3600 4W 23+1 1188 246 qY7 2ft 700 $. 70 1213 F. ffi t=
3200 712 124 761 1 41 793 7.50 827 1_ 67 863 1. 82 898 1. 97 932 2.13 962 2.27 990 241 11014 2 54 1073 2.85 7 ^^
3600 787 171 83 7 1 . 92 870 2 . 08 898 22 1 928 236 960 2-53 992 2 .70 1023 268 . yM -}{0 924 11W .42 1 121112 4.70
1.
B VC 1 30 G 40 00 864 2.29 91 0 2.53 94 7 2.74 974 2. 89 911111 394 1047 327 7 960 233 1[04 - $0 3 1 3?- y^ 9 4.48 t a66 4 .56 - - - -
- e ^ I.
4400 942 299 9!3 31 5_ =S 381 1D^ 3.71 1 0T8 3 .67 1= 4.0i1 i 43422 1148 442 1 TIA t!4 tM -4i3 - - - - - - - -
48 00 142 7 9.84 1068 1. 1t i0¢1 .401E 111y0. 4 .E6 1 162 4 . 116 - - - - - - - - - - - -
4000 752 1 A7 79 2 1 .6 4 837 1 62 868 200 904 2 78 438 237 971 256 100 2 276 1032 295 IM ^T
_^. 11!l 3,63 1 198 4 72 1266 4 .01 - -
4 5 00 836 2. 04 872 2.2 3 907 243 941 263 974 283 tm 6 -38 4 1 907 325 1067 9 .*6 10 925 -.-.1324 493 1109 4.45 1 351 490 - - - -
BYC170G 5000 922 2. 74 954 2.95 ,^'^ 2M 100 301 1077 331 1100 4 .07 1735 430 iM 4.W 31 334. 18 - - - - - - - -
55 00 tM 3, SD _ 1 087 7.88 J06 l^" j6& 1 .91 13 23 4. 55 1151 4 .9Q - - - - - - - - - - - - - - - -
6000 _ tONS 4.0 14R 7 4.87 - - - - - - - - - - - - - - - - - - - - - - -
4800 837 2.25 872 2. 45 905 2. 66 936 2.87 96 7 3_ 09 997 3.3 1 1026 3. 54 1055 3,7 7 1082 4 . 00 1108 4. 23 1170 4 . 82 7910 _ 5w42^, !&M 1338 8 . 67
5400 933 3.13 965 3.37 995 3. 60 7024 1 84 105 2 4 .07 1 079 4. 31 1106 4 . 56 1132 4 . 81 1 ** -LV 1 163 .0 - 4 . Y9 146 W: 7 4 4 - -
svc20oc sooo 1030 4.23 1059 a.so 1007 4.76 1114 5.02 1139 5.2 5 en 5a4 ' *. S.eb 1 2" ItO! 7 a ft *ib-?^ ys # ?wx
ssoo It2r asr ttsa ses 11ea. at5 +20 ex+ izxe 6.72 1262 1.o1 1875 zN - - -- - - - - - - - -
7200 '1?Z4 T V f250 7A9 .
NOT ES
1 . Grey sh aded area in d icat es need for oversize motor.

2. Data includes pressure drop due to wet coil. Data does not include pressure drop due to filters or accessories.
3. A correcti o n factor of 1 .15 must be m u ltipli ed t imes bhp for voltag e o utside of 440-480 , 5 50-600 and 206-2 40 volt ranges.
4 , F a n motor heat ( MBh ) = 3.15 x Fan bhp.
A lso
Kw ( Mechan ical O utpu t ) = HP x .7 4 57
Kw (E lectrica l I n put) = H P x .7 457
M otor E fficiency

M oto r Eff icienc y = 85%

Table 10 Evaporator Fan Performance - End Supply/Return


External Static Pressure (Inches of Water)
.10" 20" W. .40" W" .60" .70" .80" W. 1.00" 125" 1.50" 115" 2.00.•
Unit Cfm RPM BHP RPM BHP RPM 8HP RPM BHP RP M BHP RP M BHP RPM BHP R PM BHP RPM BHP RP M BHP RPM BHP R P M BHP R PM BMP RP M 8HP
2400 775 .78 826 .66 873 . 99 9 17 1 . 09 958 /_1 9 996 1 .30 1 032 1. 39 1 067 1A9 11 0 0 1.58 1132 1 .67 1 208 1. 91 4W&V 1 f
^} tA3 1X 7 2 2.74
1^ ph
2700 859 1.08 906 720 950 137 991 1. 43 1029 1.5 4 1066 1.66 1101 1.78 113 4 1.88 1166 2.00 8Q6 3 :1 1 1 23i - ?.^- 7W- -^^ 2.91 -
BYC10 0G 3000 9 45 1. 46 986 1.5 6 1 028 1.71 1 066 1. 83 11 IX3 1 96 3 1SB 29i 7171 22t- a9B4 , I2 [ M VA4 1Bm 1 2K 4 2ie
330 0 1 0 31 1 .91 1070 204 1109 tllM ll 7 Y 216 1 ;2 2!0 l 7.bi Y.T& -ww t
3600 1117 2 46 ii5/ 2.,D 1109 '215 122 S 2:jj - -
3200 608 1. 0 6 6 49 121 687 1 .35 72 1 / . 49 753 1.6 3 783 1 .75 811 1.8 7 8 38 1 .98 864 2.10 890 221 9 52 2-5 1 11Y 5 28 1 1 5M E .2 19 13 AN
3600 674 1, 47 711 1.63 74 7 1 .79 779 1,9 6 809 2. 1 2 838 227 865 2 .11 8 91 2 . 54 916 2.6 7 940 280 9W .3, 33 1 0 0 3.w 1106 4 ZO 11 65 . 4,19
_ --' - -^ - - - -_ _ .
BVC730G 4000 741 7.98 775 2.15 808 2.33 B^ 2.57 867 2.69 895 2.87 921 3.0 4 5 -8.^1.. o p.. 1^--_ ^8 :^-...- i1b 1ffiD i0.1 1Y8 4J7
4400 808 2.59 839 278 870 2.97 .. _ 17 . 921 2- M 4, 5
,. z : . _.
4800 f1B 5.32 9 0fi 3.52 963 S74 &96 9W 4 17 1^2 4M `• `.-- _- : - - - - - - - - - -
40 0 0 682 1 45 7 33 1.72 776 1.96 813 219 848 2 47 88 1 263 91 2 284 /o '-.. $a M ^,1 1 058 4.15 1 129 1.76 - - - -
asoo 755 196 802 2.28 844 2.5e aeo 285 913 3_13 4" 8;V. 04 aeo Iko SM 100 +M w67 423 iiso 5.00 - - - - - -
evc,7o13 soao 829 2.64 e71 2.97 6112 IM 047 a0 QB4 3.6 7 , M 42+ 10o1 4A9 10e5 4.76 10e sAo - - - - - - - - - -
5500 904 3.44 913 3AQ Z; 6 7 1415 4.S9 1;1A 4I! - - - - - - - - - - - - - - - - - -
8000 M 4-4 2 ifFlB 4.* - - - - - - - - - -
4800 734 2,03 770 2.24 8G5 2.46 839 2.68 870 2.93 900 3.16 928 3.3 8 955 3.80 981 3.82 1007 4 04 1069 4 .57 .. ^^^6 .11 I m
i-- II^n1^ ' ^ --
5400 817 2.82 850 3.06 BBl 3.30 912 3.55 9 42 3.82 970, 4 .08 997 4 .34 1023 4 .60 10 4 7 4 .85 1 071 16 , 111+in.I,U + b a 11 -

BVC200C 6000 900 3.81 931 4 .08 959 4.33 98 7 4 .50 1015 4 89 1052 :6.E6 3 40 1 W^ '-1 }^l _.-j

6600 984 5.00 tO12 SaQ iM.33&_.. 1^ 5$/ 1[1fRk 0:17 itif as i1 ^ & t^ TIi ^4ffi F^I - .•. - - _..:;g - _
^ i -
72 00 10811 312 1045 11.78 1126 1.96 1744 749 .. . -.

OTES: 4. Fan motor heat ( M Bh) = 3.15 x Fan bhp.


N1. Grey shaded area indicates need for oversize moror. Also
2- Data includes pressure drop due to wet coil. Data does not include pressure drop due to filters or accessories. Kw ( Mecha nical Output) = HP x] 457
Kw (Electrical Input) = Hp x .7457
3. A correction factor of 1.15 must be multiplied times bhp for voltage outside of 440-480, 550-600 and 208-240 vott ranges.
Motor Efficiency
8 Motor Efficiency = 85%
Performance
Data

Table 11 Standard Motor Sheave/Fan Speed (Rpm)


Sheave BYC100G BYC130 & 170G BYC200G
Position Fan Speed Fan Speed Fan Speed
6 Turns Open - - 829
5 Turns Open 819 782 866
4 Turns Open 905 828 904
3 Turns Open 99 1 874 941
2 Turns Open 1078 920 978
1 Turn Open 1164 966 1016
Closed 1251 1012 1053

Table 12 Oversized Motor Sheave/Fan Speed (Rpm)


Sheave BYC100G BYC130 8 1 70G BYC200G
Position Fan Speed Fan Sheave Fan Sheave
6 Turns Open - 953 963
5 Turns Open 1073 996 1008
4 Turns Open 1149 1039 1053
3 Turns Open 1226 1082 1098
2 Turns Open 1303 1125 1143
1 Turn Open 1380 1168 1187
Clos ed 145 7 1210 1232

Table 13 Static Pressure Drops Through Accessories


(I nches Water Column)
Economizer With
Filters OA/RA D9mpers
Model Cfm Std . 2- Inch 100%O A 1 00°6 RA
2400 .01 . 03 .08 .00
BYC100 3000 .02 . 04 .09 .00
3600 .03 .06 .10 .00
3200 . 02 . 03 08 . 00
BYC130 4000 .02 . 04 . 09 .00
4800 .03 . 06 . 10 .00
4000 .02 . 04 .OB .00
BYC1 70 5000 .04 . 06 .09 .00
6000 .05 . 09 . 10 .00
4800 .02 . 04 .08 .00
BYC200 6000 .03 . 06 . 09 .00
7200 .05 . 08 . 10 .00

9
Performance
Data

Table 14 Electrical Characteristics of


Standard Motor Sizes
Compressor Motor(s) Condenser Fan Motor(s)
Amps ' q mPs'
Model HP'tNo RPM Volts CYC PH F . L 1 L.R . HP '!No RPM Volts CYC PH F. L . L.R .
BYC 1 00G3, GU 7 . 5/ 1 3450 208- 230 60 3 29. 1 156 1 /3/2 1075 208-2 40 60 1 2. 7 5. 5
8YC 1 00G4, GV 7 . 5/ 1 3450 460 60 3 14. 2 79 1 /3J2 1075 446480 60 1 1.3 2 .6
BYC100GW 7.5/1 3450 575 60 3 1 1 .4 63 1 /3/2 1075 575 60 1 1.1 2.1
BY C1 30G3, GU 512 3450 208-230 60 3 21 .6 115 1 12/3 1 725 208- 240 60 1 4 .1 9.5
B YC130G4 .GV 5/2 3450 460 60 3 9.8 50 1/2/3 1725 440-480 60 1 2 ,1 4,8
BYC130G W 5/2 34 50 575 60 3 7. 8 45 1/2/3 1725 575 60 1 16 3.8
BY C770G3,GU 625/2 3450 208-230 60 3 23. 9 1 42 1/2/3 1725 208-240 60 1 4.1 9.5
BY C1 70G 4, G V 625/2 3450 460 60 3 11 2 71 1 !213 1 72 5 440-480 60 1 2. 1 4,8
BY C 170GW 6.25/2 3450 57 5 60 3 9.0 57 1/2/3 1725 575 60 1 1.6 3. 8
BYC200G3,GU 7.5/2 3450 2((18-230 60 3 29.2 156 11213 1725 208-240 60 1 4.1 9.5
BYC200G4,GV 7 5/2 3450 460 60 3 14.2 79 1f213 1 725 446480 60 1 2.1 4 ,8
BYC200GW 7.5/2 3450 575 60 3 1 1 .4 63 1 /2/3 1725 575 60 1 1. 6 3.8

Table 14 (Continued)
Eva porator Fa n Motor
M i n i mum
A m ps" Ci rc uit Fuse Size
M o del HP/No RPM V o lts CYC PH F.L. L.R. Ampacity M i n .' Max.
BYC100G3.GU 2/1 3450 208-230 60 3 6.3 42.0 53 60 80
BY C10DG 4,G V 21 1 3450 440-480 60 3 3. 1 2 1.3 26 30 35
BYC 100G W 2/ 1 3450 575 60 3 2.3 15.8 21 25 30
BYC 7 30G3, G U 3/ 1 3450 208-230 60 3 8.4 72A 73 80 90
13YC130G4 ,GV 3!7 34 50 440-q80 60 3 4.2 36.0 33 35 40
8YC13 0GW 3/1 3450 575 60 3 3.2 28.8 26 30 30
BYC 1 70G3 , GU 3/ 1 3450 208-230 60 3 8. 4 72. 0 77 90 100
B YC17064 ,GV 3/1 3450 440-480 60 3 42 36.0 37 40 45
BVC 7 706W 3/ 1 3450 575 60 3 32 28 .8 29 35 35
B YC200G3, G U 5/ 1 3450 206 -230 80 3 12.8 1 1 0 .0 95 1 00 120
8Y C20004 , GV 5/ 1 3450 440-480 60 3 6.4 55.0 46 50 60
BYC200G W 5/1 3450 575 60 3 6. 1 44 .0 37 40 45

10
Performance
Data

Ta ble 14 (Contin ued)


Oversize Evaporator Fa n Motor
A m ps'
M odel HP RPM Volts C YC PH F . L. L.R.

BYC100G3,GU 3 3450 206-230 60 3 8.4 72

BYC 1 00G4 , G V 3 3450 440-480 60 3 42 36

BYC100GW 3 3450 575 60 3 3.2 29

BYC130G3, GU 5 3450 208-230 60 3 1 2.8 110

BYC130G4,GV 5 3450 440- 480 60 3 6,4 55


BYC1 30GW 5 3450 575 60 3 6. 1 44

BYC 170G3, GU 5 3450 208-230 60 3 1 22 110

BYC170G 4 ,GV 5 3453 440-480 60 3 6.4 55


BYC1 70GW 5 3450 575 60 3 6.1 44

BYC 200G 3, G U 7.5 3450 208-23 0 60 3 18 .8 127

BYC200G4,GV 7.5 3450 440-480 60 3 9. 4 63.5

BYC200GW 7.5 3450 575 60 3 9.0 50.8

N OTES.
1 . Am p d raws for each Motor, multiply v alue by n umber of motors to determine tota l am ps
2. Rated at UL conditions (i.e., 80 F dry bul b/67 F wet bulb/95 percent relative humidity) for 208 or 460-volt
o perati on_ Am p va l ues a re as st am ped on un i t namepl ate
3. Val ues prov ided in t hese co lu mns are per motor. BYC 7 00 uni ts have 1 com p resso r an d 2 condenser fans; BY C130-
200 units have 2 com pressors a nd 3 cond enser fa ns.
4 . 575-volt units are C.S.A. ce rt i f ied on ly , a nd a re not A .G. A . a pproved.
5. Dual-element (Class K) fuse should be used.

BYCisa2oo
0
N%.,/
T 0 T
26" A
0 I
34 " -^{
B-^

Dimensional
Data

Figure 1 - Unit Center of Gravity


Information
Unit A B
BYC130 35" 37"
BYC170 39" 42"
BYC200 35" 43"

11
D imensional
Data

UNIT

- 6 - 6 '!s
6_2 ---- 4 - 4 7a
-

3 - 3 'la

2-3'; ^
5 3/4
^
16'-3

5-2 'h

BAROMETRIC RELIEF HOOD


WITH ECONOMIZER ONLY

HOOD FOR ECONOMIZER 1 'fe REF


AND FRESH AIR
MANUAL - 3 - 8 r/e
3- 4 3ls
12 3Fa
S 3`fF

' 1 '!a R E F
1 %Ie REF
14

r^z 5- 6

NOTE
ROOFCURB
3- 10 3/8 DUCTWORK ATTACHES
DIRECTLY TO THE
ROQFCURB

RETURN SUPPLY
A I R OPE NI NG AIR OPENI N G

R ET U R N
OPENIN G

Figure 2 - BYC7 00

12
Dimensional
Data

13b DI A. K .O. ?b pA. KO.


ELEC7 CO N N ELEC T CONN FLUE C A P
1 HEIGHT2Ya

3 '!z

6 9. \O, i y
^ 't+ NPT
47z D R0.i N CO NN
R Q6FCU R B
G A S C Ot3N
2 CIA K O. .i... BY Ct OOG -L
ELEC T CONN. B YCtOf}G-H
^r OUT S ID E DIM
OF ROOF C UR6

3-0^ ^
Q 24
3

Q_^^(/ J ^ ^
MAXIM UM M f N f M U M CL EARA NCE
4- 0 R Qp F
OPENING
/ yr

_ l 9k
24ky 52,.
i /

.^^

CENTER OF CONCEN TRIC DUC T

NOT ES
t ROO F OPENING SAME WITH OR WITHOUT CURB .
2 86TfOM SUPPLY AND RETURN DIMENS I ONS W ITHO UT
ROO F CURB .

SUR PLV
AIR O PE N I NG

RE T URN
AI R O PE NIN G

C )"

't 'a

\7^ 7''= 6-2

\\ V

Figure 3 - BYC1 00

13
Dimensional
Data

=F Di a GAS CC
hn NP T DR A I 1 1 GQNN

OU TSI DE OIM
O F R C}Q F C URB

a i

C F. NFE R O F
CONCE NTR kC DUC T

^ ^ MI N IMUM
LLE RRAN CE

Figure 4 - BYC7 30

14
Dimensional
Data

3 -'

HOO D FOR
AN D M ANUAL
FRE SH AIR

rn i -t,v"vrci € -
ON LY 1 ^,re REF y ^ -4.

4-2 3,+

15 ta
14'1^
1 718 REF
, -t 'Fa REF

^
14 'ha

6- 4 74

R ETUR N AIR OPENI N G' N OTE


DUCTWO RK ATTAC H ES
4-63Ia DIRECTLY TO TH E
^ ROOF CU R B

S UPPLY A IR OPE N ING

1 ?F.

3 -1

^N

Figure 5 - BYC130

15
Dimensional
Data

Figure 6 - BYC770, 200


L
7- 0 A Un it Dimensi ons
BYC170 BYC200
^ 51/2 L 8 7- 1 /8 " 9 '5-7/ 16„
M 2 '- 10" 3'-15/ 16"
3 - 1t s^ A 5' 9- 1 /8 " 6' 4- 1 /2 •'
B 5' 1 -5/8 " 5'9- 1 /2"
C 4 ' 9 -1/8 •, 5'5"

HOOD F O R ECON O MIZER


t ^,H
AND MANUA L
FRESH AIR
BAROMETRIC B
RELIEF HOOD
WITH EC O NOMIZE R
O NLY

9 ie 2

t^

3 'z
4t

C \OPTIONA L RE TU FN
O P E NING

OPTIONAL S UPPLY
OPE N I N G

^2
T^
\ 3 o'a1

1 '"e REF

C
B _ _
i ?Fa REF
- - 1 le RE F

E A
RE T UR N A IR OPE NIN G /NOTE
DUCTWORK AlTACHES
F DIRECTLY TO THE
R OOF C URB

SUPPLY AIR O PENING

Figure 7 - Roof Curb


Mode l A B C D E F
BYC170 76-1 /4 14-7/8 1 5-1 /8 57 72- 1 /2 61
BY C2 00 7 6- 1 /4 14 -7/8 1 5-1 /8 65 72- 1 /2 69

16
Dimensional
Data

'!a DIA K O 3DIA K O Figure 8 - BYC1 7Q 200


8YC170 BYC20U
Clearance and Roof Opening Dimens ions'

F 4'9" 5'S"

G 741/2" 2'8-1/2••
N OTES:
t. Roof opening same without or without curb.

^, N PT DRNN C ONN .
BOTH E NDS

?+; [

au7sfaE DIM
QF R C3C3F GU R B

3Q
^ / / ^^ ✓
2^

\ \\

C ^ ^-^ - nnax I nnurn


Roo F aPE rv iN G
^
CEN TER OF
CONCENTRIC DUCT
X
b C

F G .

MIN I MUM
CLEARANCE

Supply and Return Dimensions

BYC170 BYC200

H 5'B-5/8 " 64-1/2"

J 4'5-7/8" 5'1-3l4••

N OTES:
t. Bottom su pply a nd return d imensions without roof
curb.

17
Dimensional
Data

Figure 9 - Horizontal Economizer (Inches)


Un it No. A B C D E
BYC- 100G 48- 1 /32 " 25- 1 /4" 27" 46- 1 /2" 9"
BYC- 1 30G 57- 1 /4" 31 -5/8" 28- 1 /4" 55-5/8" 9-7/8"
BYC- 1 70G 63- 1 /4" 31 -5/8" 28- 1 /4" 61 -5/8" 9-7/8"
BYC-200G 71 -1/8" 31 -5/8" 28-1/4" 69- 1 /2 " 9-7/8"

F R ES H AIR INTAKE

C ONTROL ACCI

RETURN AIR DUCT


COLLAR

Figure 10 - Low Ambient Damper


BYC100
A 2'1/4"
B 1-5/8"
C 2'4"

- ^ - - ,_ ^ ^ ---o - - - -,. -=o..- - .- -.o.: ---- ^

9 ..

1
C

18
Field
Wiring

Field Wiring BYC100

D ISCO NN ECT
S W ITC H
(B Y O THER S)

THERMOSTAT
- - 1 - - -L - - -

- ---
k®l
^ OPTIONAL
L _ CENTRAL CONTROL
P AN EL

A- 1 H/1 C manual changeover - 4 wires


1 H/2C manual changeover - 5 wires
2H/2C manual/auto changeover - 6 wires
1 H/1 C with central control panel - 2 wires
2H/2G with central control panel - 4 wires
B- 3 power wires
C- 3 wires
D- 5 wires
All wiring except power wires is low voltage.
N O T E: All c usto me r su ppl ied wiring to be copper and must conform to N EC or C EC a nd l ocal electrical codes. Wi ring s hown
dotted is to be furnished and installed b y customer.

Field Wiring BYC130-200

DISCONNECT
SWITCH
(BY OTHERS)

A v L
THERMOSTAT

D
---I
C r
1
^ OPTIONAL
L_ E CENTRALCONTROL
PANEL

A - 1 H/2C manual changeover - 5 wires


2H/2C manual/auto changeover - 6 wires
2H/2C with central control panel - 4 wires
B - 3 power wires
C - 3 wi res
D - 5 wi res
All wiring except power wires is low voltage.
NOT E7 All c ustomer suppl ied w i ring to be copper and m ust conform to NEC orCEC a nd local electric al codes. Wiri ng s how n
dotted is to be furnished and installed by customer.

19
Unit
Wiring

r --------------------------------------------
U N IT CO NTROL BOX N USED 1
ONOTSI N GLE I
^ L CI R CUIT J ;
^ U NIT S
T S 1 -Y1 T S1-Y2 T S 1 -G TS 1-E 2 T SI-Et T$1_7

1AP -l 1AP1-2 1AP1 - 3 1M1 -4 AP1 - 5 1AP1 - 6 ^


L-
----------------------------------------------J
YAJI - 1 YA J 1 - 2 YA J 1 - 3 J1 -4 J 1 -5 1 J1-r 6
6T

2 19 TR

10 6
10 9 TR1
10B 0
2Sb
1K 1K ^ MA
C L T ^ ^^ 3 1 1
T 2:2
113
1 66
T1 2200 1K a,1
EC ^ 106 ♦ 6
>> 3 p} P4
2 e --I1/\/V O
1K
tt5 ^ n p 107 P
V 2t8
a

J
4,

i I
b FIELD SU P PLIED
b
I j REMOTE M INI M UM
L___J POSITIO N
POTE N TIOM ETER
JU M PER J4
MUST BE RE M OVED]

Legend
Device
Desig natio n De sc ript i on
AJ Auxi lia ry J ac k Con necto r
EC Enthalpy Co ntrol
J4 M i n . Pot. Ju m per
C LT Co mp ressor Lock out T he rmostat
1K E con o m i zer Rel ay
MA M ixed A ir Sensor
P4 M ini mum Posit ion Poten tiomete r
Ut Acfu ator Moto r

230 6-3557

Fig ure 11 - Eco nom izer Schemat ic

20
YCfTaC[

r i o t

^- n Y Y Y i _3

^ -

00 -

v- Q

-----------------

-----------------

----------------
r "-

^n

^^ -
_ .
a^ -
^
H-

3 s- - __ CP__ ' s^+a


^

T51

A^^>

^t - I ICb - ^

^. ^r L E 55 6irqq ^ 5[ ^q }E P . ^ T 9^'i^C K S ^ E
T 5'C t ^T W S VK I I IC

T E S FUI4 0 OI . N^ @ K i [R
51M1fO MM ! u5 O CC U IN. DL4 m t
t^M01 G lE'CO IVG Y[N T S PPW IfXO B Y T K FFLfO
I Ww E E^ C[OSt w pi W ^i wT[ ^ ttF
. iE -1F7 01 1 IB CE S Y [5 OPtsp1S.

Q M w¢ Ob I C R T
xaovoii .w+'rF . xoe xii'oieR-

]Q i F1 9 V[,J K[ CC^w CCi PI v ITH1 .1.[UP EN Y I ^R S

^ Q p^^41^ E R^ i ^ ^
Sm V r^iCw V x li ^iu5
^[ C5C^^ a II^ fon lpE Wie d .

- TEO THE
EfC M 11ZE
Q Sc°"re ^11 ^:"°
'wc°a:oIXi,Ls 1-otta"a
P ^ T-^rRd1
_-_- - _-_-_- _^
ie

Qr ^e ^^re^ ...^ rn ars s ^+ ao w o-c


^e a^n .c^a e. wE.« e ussrw . r c :a .r

2306-3525
Figure 12 - Electrical Schematic for BYC1 OOG3-GU Units (20 8-230/60/3)

21
10 -----,
, _ ^-y--1--^----^ i

• - ^L ^' _ ^' ^, ^
-----^------,--1

----------------

----- ----------- -

^o-

a,-

„-
,^
•r- aw0.
i Y

TSt-rr

A K
10.1 NS i}95' C^ItT^ f1^0 A F A TI V^[RIC
51
MK SS^I If. 1 1 50 • R [L A ii K M W e 6 iir, •

„_ ^t Q A Jn- ^
Q[ r ^s p M^P1^LeN[
f ^ PSWSS
^ I^^W^C ^
[ u e 1- f -L 5W CM.
^ ^
tCC ^ iED OM ^ 1 [ f ^ON ^ I2F R

f] - -^

]^ R COwi[ial Ir^iN ^Vl f Ex 1^ I P E5


[ M . ^ f ^LIM[ 551
♦. w Cw uxrr ru5 [-12[x [axra0. oPr-
E¢ PaY^IIn

Q ^1 1^^^Li M E SSY ME W S TlLiS US(6^sOp ]


ST N
w.{ C ^ 5 K w^ iwG 4 v iiOn p^ ^.

O P f RA EI W .
^ f a^pvv [rt^p srCq n^ [Ci^V
i0 TE M^ r M L I Q pF f M r15^CYY^ ^it1.

p1 c^n
60 - SM B USSWM 0. 0
Q] V ,1 J O Y FUY

Q CM M f v I R e ^ YO r ^pE.

2306-3527

Figure 1 3 - El ectrical Schematic for BYC100G4-GV, GW Un its (460/60f3 and 575/60/3)

P:K
^

^+

1 5-

21-

d0 -

31-

L'

)J-

]! -

♦) -

16-

SO -

- • ,It - -_^
3FINSf ^NLSR ..•
-_ .._ '. _ -'_ _

^ 6 vM^LN u N l*K M^s fECOn7u^i 2 E A RCO rv^ R0^ ^9c i5 ^ 1

^ Q •^ ^ Q ^`. _v raR Nz
s ^ nc E ws wE^ ri ti c vR -iv ti w ^ ♦
^LEF

u TS y ^n G ^ O ^ ^. ^
^ ] ^100r ^Fy 5;5n
B uSSY^N x t M 20 JJ^V
^ 600v^F W 5^ ^ ^^ ^

2 306-3534

Figure 1 4 - Electrical Schematic for BYC13 0,200G3-GU Units (208-230/60/3)

23
Li wE v O fi ^G F

J1 -

31-

34

S^ -

I^ '^ _ ^ _ .M1'.` _ _.r

TlM^^iEO^-^ N ^SVM[M CA^ „


S ^S^pwr PFSSURE i
•,-_^^ ^ E L^Pi IER t '
^ac [
5, ^ ax ^wr EcanouWtc v . ^ ^ ^ Eru-^r^ws ouulm. a^ T4o im[o
__ - - w ^.e c xcu^: .r nr a ^e c ^s n^ia ws.
I `9 x.

v ca«^eo^ro ]Q vl^ F IWf R^ ^S iS


-_- _ _
@fi M pL
vM fN WL J^ CNA S^CCO Ndi f Iq iM 1i 01 .

; L-
Q Y w l.
Pf KI 1 t
[S 0 f0o 3
S T ^CCG ^S KA iF K a11 o 0M qv

`, ^ ^ I IE SSY^4 L ^ 0 CF GW

2306-3536
Figure 15 - Electrical Schem atic for BYC730,170,200G4 GV, GW Units (460/60/3)

24
IS-

.Y -

^] -

-i
_-
---- - -

7"P"E
L ^
O C iEOV^RyIN[ tCWT/ i F E F .
pEO , e

1-71
• ^9 ^

^fC GwI^EW

^ Yi EC vR Z

.eJ 55u^ Apua oN G u4


^ ^rAiw' ! 0] + n'
Nl^

23063537
Fi gure 16 - Electrical Schematic for BYC7 30,170,200G4-GV, GW Units (575/60/3)

25
Mechanical
Specifications

General Drain Pan - Evaporator pan shall be Forced Combustion Blower - Shall
All units shall be factory assembled , internally sealed and insulated with insure flame stability under varying
piped , internally wired and fully copper drain connection provided for wind cond itions. Shall give higher
charged with R-22 . All units shall be evaporator section. combustion efficiency and unit
designed to operate at outdoor Condenser Coil - BYC130G to location flexibility. Combustion
ambient temperatures as high as BYC200G units shall be dual blower motor shall not be in hot
120 F. Cooling and heating capacities circuited. Outdoor coils shall be airstream.
shall be rated in accordance with 3/8-inch OD seamless copper tubing Electronic Ignition System - Pilot
A . R . I . standards . The heating /cooling mechanically bonded to aluminum shall be lit each time thermostat calls
unit design shall be certified by the fins. Each coil shall be factory for heat . Flame sensor shall prove
American Gas Association (A .G .A. ) or pressure and leak tested at 425 psig. pilot flame and turn on main burners.
Canadian Standards Association Should a loss of pilot flame occur, the
(C . S . A. ) , specifically for outdoor main valve sha ll close and a spark re-
Fa ns
applications using propane or natural occur within 0.8 second. When the
gas . All units shall be designed for Indoor Air Fans - Belt-driven, thermostat is satisfied, both pilot and
outdoor rooftop or ground level forward curved, centrifugal-type fans main burner shall be extinguished.
installation . Exterior surfaces of all equipped with adjustable motor
units shall be phosphatized , zinc- sheaves shall be standard. The motor
coated steel with epozy resin primer shall be thermally overload protected. Accessories
and executive beige, baked enamel Permanently lubricated fan and motor Roof Mounting Curb - The roof curb
finish . bearings. is designed to mate wi th unit and
provide support and complete
Condenser Fans - Direct-drive, weathertig ht installation when
Casings statically and dynamically balanced properly installed. The curb sha l l be
All panels shall be 20-gauge steel, propeller fans. Weatherproof fan constructed of 16-gauge, zinc-clad
gasketed and insulated. One-inch, motors shall be U L listed or C.S. A . steel. Curb shall ship k nocked down
one-pound density foil-faced glass certified for outdoor use. All motors with factory-installed wood nailer
fiber insulation shall be on the heat shall have built-in thermal overload strips. The roof curb design shall
exchanger section. Same composition protection. allow field-fabricated ductwork or
mat-faced insulation shall be in the Filters - One-inch throwaway filters accessory concentric supply/return
evaporator section. shall be standard on BYC100-200. ductwork to be connected directly to
Filter rack shall be field convertible the curb.
R efrigeration System from 1" to 2". Low Ambient Operation - Standard
Refrigeration Controls - refrigeration system operation shall be
Refrigeration controls shall include Heating System to 30 F. Accessory dampers on
condenser fan, evaporator fan and BYC100 and two-speed motor on
Gas-Fired Hesting Section - BYC
compressor contactors, and 24-volt BYC130 to BYC200 models shall
models sha l l provide completely
transformer. Each circuit shall have a provide operation to 0 F.
assembled, wired and piped, gas-fired
separate set of refrigerant controls. heating systems within the unit. Two-Stage Gas Valve - Opt ional
(BYC130 to BYC200 shall have two Design shall be certified by A.G.A. or two-stage gas valve shall allow for 50
independent circuits.) Safety controls C.S.A. specifically for outdoor percent heating input first stage and
shall include high and low pressure application. Threaded gas 100 percent heat i ng input on second
controls and compressor overloads. connections. stage. Shall be standard on some
sizes.
Compressors - All units shall have Heat Exchanger - Shall be
3,600 rpm hermetically sealed embossed, formed and seamed, Accessory Filters - Two-inch
compressors. Compressors shall be 18-gauge aluminized steel. Shall be permanent filters shall be optional.
equipped with over-temperature, over- factory tested for gas leaks. Shall be Time Delay Relay - Shall provide a
current and high pressure controls. stress-relieved, free-floating design. four-minute time delay between
Crankcase heaters shall be standard Heat exchanger shall be located starting of the first and second
on all models. upstream of cooling coil. compressor, used on the BYC130 to
Evaporator Coil - BYC130 to Burners - Shall be stamped and BYC200 models.
BYC200G units shall have two seam welded 20-gauge aluminized Antishortcycle Timer - A lockout
independent circuits. Coils shall be steel. timer shall provide a minimum off
3/8-inch OD seamless copper tubing
time of five minutes between
mechanically bonded to aluminum
compressor cycling.
fins and shall be factory pressure and
leak tested at 225 psig. Thru-the-base Utilitles Package -
Shall accommodate thru-the-base
gas, power wiring and control wiring
connections.

26
Mechanical
Specifications

Copper Coils Horizontal Conversion Panel -


Accessory shall be required for
Copper condenser and evaporator
conversion to horizontal airflow .
coils shall be available as a special .
Units with these coils shall have
extended delivery cycles . Contact Control Options
Trane Clarksville for availability . Central Control Panel - Shall be
combined standard thermostat
O utside Air O ptions subbase with heat, cool, off, fan-auto-
and-on position. Four signal lights
Downflow Manual Outside Air
shall ind icate power, pilot outage,
Dampers -Manually set outside air
clogged filters and reset relay. Power
damper shall provide a fixed outside
signal shall show green indicating
air quantity from 0 to 25 percent of
pow er available to unit. Power signals
total supply air.
shall show red indicating power
Downflow Economizer (Factory U .S . outage. Pilot signal shal l show red
Domestic Units Only or Field - w hen gas service is i nterrupted or
Installed) - Enthalpy-controlled there is an electrical ig n ition
economizer shall be operated through malfunction. Filter signal shal l show
the room thermostat to automatically red when filters clog and need
use outdoor air for free cooling when replacement. Reset signals sha l l show
outdoor air temperature and humidity red if system is out on any cooling
are at acceptable levels.- Automatically safety controls.
modulating outdoor and return air
Programmable Electronic Night
dampers shall maintain proper
Setback Thermostat - Programmable
discharge air temperature into the
electronic thermostat shall provide
conditioned space. Adjustable
heating setback and cooling setup
minimum position control shall be
w ith 7-day, 5-1-1, programming
standard. Shall have spring return
capabi l ity. 1 H/1 C or 2H/2C models
motor. Upon loss of power, dampers
available. Shall have digital display of
shall close shut. Economizers shall
V a.." t ime, day, temperature, program
offer the energy saving "ultra" low-
status and active stage. Shall be
leak economizer dampers. These
continuous or timed override. Shall
dampers reduce damper leakage
have up to 4 tem perature adjustments
down to 10 cfm ft.2, one-inch wg
per day. Shall provide preferential rate
differential static pressure. That's less
control, keyboard disable, setback
than one percent of nominal unit
auto fan, touch-sensitive keyboard,
airflow according to tests completed
choice of automat ic or manual
at The Air M ovement and Control
changeover, minimum on-off times,
Association (A. M .C.A.) Laboratories in
7-day battery backup, low battery
accordance with A. M .C.A. Standard
warning, and 6-minute equipment
575. Barometric relief shall be
lockout for power outages over'1/2
included.
second. Optional remote sensor shall
Horizontal Econom izer ( U.S . be available.
Domestic Models Only) -
Economizer shall be shipped
completely assembled and shall
include outside air dampers, return air
dampers, enthalpy control, and w iring
plug for ease of installation. Spring
return shall be another feature of this
economizer. Horizontal economizer
shall attach directly to the Trane
rooftop unit. Please note that
horizontal conversion panels must be
ordered to complete horizontal
applications. Economizer controls
sha l l be fully modulating to maintain
proper discharge air temperature into
the conditioned space.

27
The Trane Cornpany
Library Product Literature
Light Commercial Group
Product Section Unitary
Guthrie Highway
Product Rooftop Air Cond.-Cooling/Gas Heat
Clarksville, TN 37040
Model BYC- 2-17 Tons
An American-Standard Company Literature Type D
Sequence 3
Date June 1989
File No. PL-UN-RT-BYC-D-3-689
Since The Trans Compan y has a poGcy of continuous Supersedes BYC-D-3 986
product improvement, it reserves the rght to change
desigi and svecificatioi u withart notice.
Ordering No. BYC-D-3