You are on page 1of 1

Project: Istana Negara

Schedule of Technical Requirement - Desiccant Dehumidifier

Description Serving Area Quantity Process Air React Air Estimated Electrical Estimated Type Dessicant
Moisture Characteristic Total Power
Removal
(Nos) (CMH) (CMH) (Kg/Hr) (V/Ph/Hz) (KW)
DEH-1A & 1B Store 1 2 3000 1000 25 415/3/50 35 Ceilling Type EcoDry Metal Silicate
DEH-2 Store 2 1 1500 500 12.5 415/3/50 20.3 Ceilling Type EcoDry Metal Silicate
DEH-3 Store 3 1 2000 666 16.7 415/3/50 26.5 Ceilling Type EcoDry Metal Silicate
DEH-4 Store 4 1 2000 666 16.7 415/3/50 26.5 Ceilling Type EcoDry Metal Silicate