Model: ADB 40 - 750B

Cooling Capacity: 35,000 - 750,000 BTU/h


Static Pressure: 0.4 - 1.8 in Wg
Refrigerant: R22

D U CT E D S P L I T SYST E M / P 1
Common Features

Flexibility Of Air Supply Convertible Discharge


Air can be distribute evenly to every corner of room through Air discharge can be converted from horizontal to vertical discharge
ducting. or vice versa which provides flexibility in installation at site.
Belt driven blower is utilized which allows for air volume and
static pressure adjustment. This flexibility allows wider range * Applicable for certain unit

of application.

Vertical Blow
*Applicable for ADB 125B / A5DB125H / ADSB125B / A5DSB125H and above.

ADB
Horizontal
Partial Loading Return Air
Blow

Acson Ducted Split System is designed with two or more separate


refrigerant circuits with multiple individual compressors. By doing
so, the unit has part load capabilities. This will improve the reliability
and energy efficiency especially during low loading operations. Ducted Supply Ducted Return

*Applicable for multiple outdoor set. ADB

Air Discharge Return Air


ON

ON
DAY TIME
Required capacity: 250,000 BTU/h

Easy Maintenance
Easy to access from the service panel by loosening few screws.
ON

OFF
NIGHT TIME
Required capacity: 150,000 BTU/h Fresh Air Intake ( Optional )
Fresh air can be introduced into the building through the design of
fresh air intakes which help to improve the indoor air quality. Adding
fresh air to the system accomplishes 2 primary Indoor Air Quality
Safety Features (IAQ) goals:

High pressure and low pressure protection. i. It controls building pressure that help to keep pollutants out.
ii. it increases IAQ by diluting polluted or stale indoor air.
Phase sequencer is implemented to detect any wrong phase
and phase loss during installation or operation.
Adding fresh air inlet to the system is relatively simple and
Built-in internal overload proctection for compressor. inexpensive solution.

D U C T E D S P L I T SYST E M / P 2
DUCTED BLOWER SYSTEM (ADB-B/AMC)
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 40B ADB 50B ADB 60B


Model
Outdoor Unit ALC 35D ALC 40D ALC 50D ALC 61D
BTU/h 35,000 40,000 50,000 61,000
Nominal Capacity
W 10,255 11,720 14,650 17,873
Nominal Total Input Power W 3,155 3,942 5,608 5,954
Nominal Running Current A 15.10 6.50 9.30 10.00
BTU/h/W 11.09 10.14 8.91 10.24
EER
W/W 3.25 2.97 2.61 3.00
Power Source V/Ph/Hz 220 ~ 240 / 1 / 50 IDU: 220 ~ 240 / 1 / 50, ODU: 380 ~ 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL ONLY
Air Flow High l/s / CFM 590 / 1,250 756 / 1,600 1,132 / 2,400
External Static Pressure
Pa / in.wg 100 / 0.4
Without Filter
Sound Pressure Level dBA 53 61
Indoor Unit Height mm/in 572 / 22.6
Unit Dimension Width mm / in 892 / 35.1 1,402 / 55.2
Depth mm / in 761 / 30.0 605 / 23.8
Height mm / in 762 / 30.1 700 / 27.6
Packing Dimension Width mm / in 995 / 39.2 1,562 / 61.5
Depth mm / in 880 / 34.7 845 / 33.3
Unit Weight kg / lb 50 / 111 85 / 188
Air Flow l/s / CFM 1,605 / 3,400 1,793 / 3,800
Sound Pressure Level dBA 58 61
Height mm / in 852 / 33.5
Unit Dimension Width mm / in 1,030 / 40.6
Depth mm / in 400 / 15.8
Height mm / in 1,010 / 39.8
Outdoor Packing Dimension Width mm / in 1,180 / 46.5
Unit Depth mm / in 514 / 20.2
Unit Weight kg / lb 78 / 172 85 / 187 88 / 194 105 / 231
Type FLARE
Pipe
Liquid mm / in 9.52 / 3/8 12.7 / 1/2
Connection Size
Gas mm / in 19.05 / 3/4
Type R22
Refrigerant
Charge kg / lb 2 / 4.4 2.48 / 5.46 2.55 / 5.61 5 / 11.00

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U C T E D S P L I T SYST E M / P 3
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 80B ADB 100B ADB 125B


Model
Outdoor Unit AMC 72C AMC 80C AMC 100B AMC 125B
BTU/h 70,000 80,000 100,000 125,000
Nominal Capacity
W 20,515 23,440 29,300 36,625
Nominal Total Input Power W 7,109 8,760 10,334 12,344
Nominal Running Current A 13.60 15.20 19.40 21.40
BTU/h/W 9.85 9.13 9.67 10.12
EER
W/W 2.89 2.68 2.84 2.97
Power Source V/Ph/Hz IDU: 220 ~ 240/1/50, ODU: 380 ~ 415/3/50 380 ~ 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control HORIZONTAL &
Air Discharge HORIZONTAL
CONVERTIBLE
Air Flow High l/s / CFM 1,180 / 2,500 1,510 / 3,200 1,982 / 4,200
External Static Pressure
Pa / in.wg 100 / 0.4 230 / 0.92
Without Filter
Sound Pressure Level dBA 50 53 58
Indoor Unit Height mm/in 572 / 22.6 885 / 34.8
Unit Dimension Width mm / in 1,402 / 55.2 1,540 / 60.7
Depth mm / in 605 / 23.8 850 / 33.5
Height mm / in 700 / 27.6 1,154 / 45.4
Packing Dimension Width mm / in 1,562 / 61.5 1,787 / 70.4
Depth mm / in 845 / 33.3 1,188 / 46.8
Unit Weight kg / lb 89 / 196 93 / 205 173 / 381
Air Flow l/s / CFM 2,832 / 6,000 2,926 / 6,200
Sound Pressure Level dBA 70 74 65
Height mm / in 946 / 37.2
Unit Dimension Width mm / in 1,300 / 51.18 939 / 37.0
Depth mm / in 500 / 19.68 1,116 / 43.9
Height mm / in 1,132 / 44.56
Outdoor Packing Dimension Width mm / in 1,414 / 55.66 1,112 / 43.8
Unit Depth mm / in 664 / 26.14 1,312 / 51.7
Unit Weight kg / lb 145 / 320 164 / 361 169 / 373
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 25.4 / 1.0 28.58 / 1 1/8 34.92 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 6.4 / 14.08 6.8 / 14.96 7.6 / 16.72 7.95 / 17.49

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U C T E D S P L I T SYST E M / P 4
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 150B ADB 150B2 ADB 200B2 ADB 250B2 ADB 300B2 ADB 300B3
Model
Outdoor Unit AMC 150C AMC 80C x 2 AMC 100B x 2 AMC 125B x 2 AMC 150C x 2 AMC 100B x 3
BTU/h 150,000 200,000 250,000 300,000
Nominal Capacity
W 43,950 43,960 58,600 73,250 87,900
Nominal Total Input Power W 16,200 17,343 20,118 25,658 34,190 30,832
Nominal Running Current A 31.80 34.53 39.30 44.50 66.40 59.80
BTU/h/W 9.26 8.65 9.94 9.74 8.77 9.72
EER
W/W 2.71 2.53 2.91 2.85 2.57 2.85
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & CONVERTIBLE VERTICAL & CONVERTIBLE
Air Flow High l/s / CFM 2,171 / 4,600 3,021 / 6,400 3,776 / 8,000 4,248 / 9,000
External Static Pressure
Pa / in.wg 230 / 0.92 265 / 1.06 280 / 1.12 300 / 1.20
Without Filter
Sound Pressure Level dBA 60 61 63 66
Indoor Height mm/in 885 / 34.8 1,231 / 48.5
Unit
Unit Dimension Width mm / in 1,540 / 60.7 1,794 / 70.7 1,766 / 69.5
Depth mm / in 850 / 33.5 1,069 / 42.0
Height mm / in 1,154 / 45.4 1,506 / 59.3
Packing Dimension Width mm / in 1,787 / 70.4 2,052 / 80.8 2,034 / 80.0
Depth mm / in 1,188 / 46.8 1,412 / 55.6
Unit Weight kg / lb 180 / 397 220 / 486 343 / 757
Air Flow l/s / CFM 5,475 / 11,600 2,832 / 6,000 2,926 / 6,200 5,475 / 11,600 2,926 / 6,200
Sound Pressure Level dBA 74 74 65 74 65
Height mm / in 1,041 / 41.0 946 / 37.2 946 / 37.2 1,041 / 41.0 946 / 37.2
Unit Dimension Width mm / in 939 / 37.0 1,300 / 51.2 939 / 37.0
Depth mm / in 1,116 / 43.9 500 / 19.7 1,116 / 43.9
Height mm / in 1,227 / 48.3 1,132 / 44.6 1,132 / 44.6 1,227 / 48.3 1,132 / 44.6
Packing Dimension Width mm / in 1,112 / 43.8 1,414 / 55.7 1,112 / 43.8
Outdoor
Unit Depth mm / in 1,312 / 51.7 664 / 26.1 1,312 / 51.7
Unit Weight kg / lb 227 / 500 145 / 320 164 / 361 169 / 372 227 / 500 164 / 361
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8 12.7 / 1/2 15.9 / 5/8
Connection Size
Gas mm / in 34.92 / 1 3/8 25.4 / 1.0 28.58 / 1 1/8 34.92 / 1 3/8 28.58 / 1 1/8
Type R22
Refrigerant 7.6 x 2 / 7.95 x 2 / 9.9 x 2 / 7.6 x 3 /
Charge kg / lb 9.90 / 21.78 6.8 / 14.96
16.8 x 2 17.49 x 2 21.78 x 2 16.8 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 5
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 350B3 ADB 400B4 ADB 450B3


Model
Outdoor Unit AMC 100B x 1 AMC 125B x 2 AMC 100B x 4 AMC 150C x 3
BTU/h 350,000 400,000 450,000
Nominal Capacity
W 102,550 117,200 131,850
Nominal Total Input Power W 36,621 39,773 50,236
Nominal Running Current A 65.00 77.40 97.30
BTU/h/W 9.55 10.05 8.96
EER
W/W 2.80 2.95 2.62
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL
Control
Air Discharge VERTICAL & CONVERTIBLE
Air Flow High l/s / CFM 4,956 / 10,500 5,664 / 12,000 6,372 / 13,500
External Static Pressure
Pa / in.wg 285 / 1.14 310 / 1.24 350 / 1.41
Without Filter
Sound Pressure Level dBA 66 68
Indoor Unit Height mm/in 1,486 / 58.5
Unit Dimension Width mm / in 2,022 / 79.6 2,174 / 85.6
Depth mm / in 1,069 / 42.0 1,336 / 52.6
Height mm / in 1,766 / 69.5
Packing Dimension Width mm / in 2,279 / 89.7 2,431 / 95.7
Depth mm / in 1,412 / 55.6 1,684 / 66.3
Unit Weight kg / lb 440 / 970 513 / 1,131 564 / 1,244
Air Flow l/s / CFM 2,926 / 6,200 5,475 / 11,600
Sound Pressure Level dBA 65 73
Height mm / in 946 / 37.2 1,041 / 41.0
Unit Dimension Width mm / in 939 / 37.0
Depth mm / in 1,116 / 43.9
Height mm / in 1,132 / 44.6 1,227 / 48.3
Outdoor Packing Dimension Width mm / in 1,112 / 43.8
Unit Depth mm / in 1,312 / 51.7
Unit Weight kg / lb 164 / 361 169 / 372 164 / 361 227 / 500
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8
Connection Size
Gas mm / in 28.58 / 1 1/8 34.92 / 1 3/8 28.58 / 1 1/8 34.9 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 7.6 / 16.8 7.95 x 2 / 17.49 x 2 7.6 x 4 / 16.8 x 4 9.9 x 3 / 21.78 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U C T E D S P L I T SYST E M / P 6
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 500B4 ADB 500B4 ADB 600B4


Model
Outdoor Unit AMC 100B x 2 AMC 125B x 2 AMC 125B x 4 AMC 150C x 4
BTU/h 450,000 500,000 600,000
Nominal Capacity
W 131,850 146,500 175,800
Nominal Total Input Power W 47,234 51,734 67,577
Nominal Running Current A 86.82 89.70 131.90
BTU/h/W 9.52 9.66 8.88
EER
W/W 2.79 2.83 2.60
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL

Control VERTICAL
VERTICAL & VERTICAL & VERTICAL &
Air Discharge & FACTORY
CONVERTIBLE CONVERTIBLE CONVERTIBLE
CONVERTIBLE
Air Flow High l/s / CFM 7,080 / 15,000 8,496 / 18,000
External Static Pressure
Pa / in.wg 380 / 1.53 405 / 1.63
Without Filter
Sound Pressure Level dBA 68 70
Indoor Unit
Height mm/in 1,486 / 58.5 1,918 / 75.5
Unit Dimension Width mm / in 2,174 / 85.6 2,174 / 85.6
Depth mm / in 1,336 / 52.6 1,775 / 69.9
Height mm / in 1,766 / 69.5 2,062 / 81.2
Packing Dimension Width mm / in 2,431 / 95.7 2,399 / 94.4
Depth mm / in 1,684 / 66.3 2,005 / 78.9
Unit Weight kg / lb 606 / 1,336 991 / 2185
Air Flow l/s / CFM 2,926 / 6,200 5,475 / 11,600
Sound Pressure Level dBA 65 74
Height mm / in 946 / 37.2 1,041 / 41.0
Unit Dimension Width mm / in 939 / 37.0 939 / 37.0
Depth mm / in 1,116 / 43.9 1,116 / 43.9
Height mm / in 1,132 / 44.6 1,227 / 48.3
Outdoor Packing Dimension Width mm / in 1,112 / 43.8 1,112 / 43.8
Unit Depth mm / in 1,312 / 51.7 1,312 / 51.7
Unit Weight kg / lb 164 / 361 169 / 372 169 / 372 227 / 500
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8
Connection Size
Gas mm / in 28.58 / 1 1/8 34.9 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 7.6 x 4 / 16.8 x 4 7.95 x 4 / 17.49 x 4 9.9 x 4 / 21.78 x 4

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 7
Specifications
Ducted Blower System (ADB-B/AMC)

Indoor Unit ADB 600B5 ADB 750B5


Model
Outdoor Unit AMC 100B AMC 125B x 4 AMC 150C x 5
BTU/h 600,000 750,000
Nominal Capacity
W 175,800 219,750
Nominal Total Input Power W 61,497 85,981
Nominal Running Current A 107.69 166.90
BTU/h/W 9.75 8.72
EER
W/W 2.86 2.56
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL
Control
Air Discharge VERTICAL & FACTORY CONVERTIBLE
Air Flow High l/s / CFM 8,496 / 18,000 10,619 / 22,500
External Static Pressure Without
Pa / in.wg 405 / 1.63 455 / 1.83
Filter
Sound Pressure Level dBA 70 71
Indoor Unit Height mm/in 1,918 / 75.5 2,197 / 86.5
Unit Dimension Width mm / in 2,174 / 85.6
Depth mm / in 1,775 / 69.9
Height mm / in 2,062 / 81.2 2,341 / 92.2
Packing Dimension Width mm / in 2,399 / 94.4
Depth mm / in 2,005 / 78.9
Unit Weight kg / lb 991 / 2,185 1,051 / 2318
Air Flow l/s / CFM 2,926 / 6,200 5,475 / 11,600
Sound Pressure Level dBA 65 73
Height mm / in 946 / 37.2 1,041 / 41.0
Unit Dimension Width mm / in 939 / 37.0
Depth mm / in 1,116 / 43.9
Height mm / in 1,132 / 44.6 1,227 / 48.3
Outdoor Packing Dimension Width mm / in 1,112 / 43.8
Unit Depth mm / in 1,312 / 51.7
Unit Weight kg / lb 164 / 361 169 / 372 227 / 500
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8
Connection Size
Gas mm / in 28.58 / 1 1/8 34.9 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 7.6 / 16.8 7.95 / 17.49 x 4 9.9 x 5 / 21.78 x 5

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U C T E D S P L I T SYST E M / P 8
Ducted Blower with Microchannel Heat Exchanger
(MCHE) System (A5DB-H / A5MC-H)

Features

Longer Pipping
Applications
Total Piping Length up to
Total piping length allowed is longer when 75 meters
Height difference
oil trap is included.
Maximum Elevation 30 meters
Easily accommodate various building 30 meters
design with less restriction

*Oil trap is required

Microchannel Heat Exchanger (MCHE)

i Compact design iv Greater air-side heat transfer efficiency


Smaller coil is used compared with conventional coil of Higher heat transfer area per unit volume compared to
equivalent performance which leads to reduced footprint and conventional heat exchangers (consistent contact between
smarter logistics solutions. the microchannel tube surface and ambient air).

Microchannel Coil Construction Typical Coil Construction

Heat transfer is maximized via microchannel


Aluminium fins protrude past the
tubes which provide increased contact
edge of copper tube making it
All aluminium construction surface without large pressure drop.
susceptible to damage

Louvered fins for


cooling efficiency Greater air-side heat
transfer efficiency -
higher heat transfer
area per unit volume

Brazed tube to fin joint where heat


transfer is improved without air gaps.

Microchannels deliver
a solid construction
with dynamic airflow v Brazed tube to fin joint
Copper tube
Air gaps reduce heat transfer. Given all parts are brazed
together in MCHE, there are no air gaps in the joint between the
fins and the tube. Hence, heat transfer is improved.

ii Light Weight vi Easy Cleaning


MCHE weigh less than conventional coils which enables to Easy to clean by using high pressurized water as compared
produce smaller, lighter units with equal performance. to conventional coil.

iii All aluminium vii Low Noise Levels


More rigid and better resistance against galvanic corrosion. An unobstructed airflow that reduces noise

D U CT E D S P L I T SYST E M / P 9
Specifications
Ducted Blower System (A5DB-H/A5MC-H)

Indoor Unit A5DB 80H A5DB 100H A5DB 125H A5DB 150H
Model
Outdoor Unit A5MC 80H A5MC 100H A5MC 125H A5MC 150H
BTU/h 80,000 100,000 125,000 150,000
Nominal Capacity
W 23,400 29,300 36,600 44,000
Nominal Total Input Power W 7,100 10,000 11,350 14,800
Nominal Running Current A 12.50 17.10 19.70 28.70
BTU/h/W 11.27 10.00 11.01 10.14
EER
W/W 3.30 2.93 3.22 2.97
IDU: 220 - 240 / 1 / 50
Power Source V/Ph/Hz 380 - 415 / 3 / 50
ODU: 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & NON - CONVERTIBLE HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 1,085 / 2,300 1,416 / 3,000 1,770 / 3,750 2,124 / 4,500
External Static Pressure With
Pa / in.wg 100 / 0.4 150 / 0.6
Filter
Sound Pressure Level dBA 52 55 53 56
Indoor Unit Height mm/in 553 / 21.77 776 / 30.55
Unit Dimension Width mm / in 1,402 / 55.2 1,540 / 60.63
Depth mm / in 605 / 23.82 850 / 33.46
Height mm / in 700 / 27.56 920 / 36.22
Packing Dimension Width mm / in 1,522 / 59.92 1,783 / 70.2
Depth mm / in 880 / 34.65 1,184 / 46.61
Unit Weight kg / lb 83 / 182.98 84 / 185.19 159 / 350.53
Air Flow l/s / CFM 2,077 / 4,400 3,020 / 6,400 3,256 / 6,900 4,908 / 10,400
Sound Pressure Level dBA 69 65 70
Height mm / in 929 / 36.57 1,067 / 42 1,166 / 45.91
Unit Dimension Width mm / in 1,235 / 48.62 880 / 34.65 980 / 38.58
Depth mm / in 496 / 19.53 880 / 34.65 980 / 38.58
Height mm / in 1,085 / 42.72 1,231 / 48.46 1,321 / 52.01
Outdoor Packing Dimension Width mm / in 1,385 / 54.53 1,030 / 40.55 1,130 / 44.49
Unit Depth mm / in 684 / 26.93 1,058 / 41.65 1,158 / 45.59
Unit Weight kg / lb 111 / 244.71 135 / 297.62 157 / 346.13 177 / 390.22
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 22.23 / 7/8 25.4 / 1 28.58 / 1 1/8 34.92 / 1 3/8
Type R410A
Refrigerant
Charge kg / lb 2.5 / 5.51 3.4 / 7.5 4.8 / 10.58 5.2 / 11.46

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 0
Specifications
Ducted Blower System (A5DB-H/A5MC-H)

Indoor Unit A5DB 200H2 A5DB 250H2 A5DB 300H2 A5DB 300H3
Model
Outdoor Unit A5MC 100H x 2 A5MC 125H x 2 A5MC 150H x 2 A5MC 100H x 3
BTU/h 200,000 250,000 300,000
Nominal Capacity
W 58,600 73,200 88,000
Nominal Total Input Power W 19,700 23,880 30,520 29,710
Nominal Running Current A 35.10 40.60 58.70 52.60
BTU/h/W 10.15 10.47 9.83 10.10
EER
W/W 2.97 3.07 2.88 2.96
Power Source V/Ph/Hz 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control HORIZONTAL &
Air Discharge VERTICAL & CONVERTIBLE
CONVERTIBLE
Air Flow High l/s / CFM 2,832 / 6,000 3,540 / 7,500 4,248 / 9,000
External Static Pressure With
Pa / in.wg 200 / 0.8
Filter
Sound Pressure Level dBA 61 63 66 66
Indoor Unit Height mm/in 885 / 34.84 1,231 / 48.43
Unit Dimension Width mm / in 1,794 / 70.63 1,766 / 69.53
Depth mm / in 850 / 33.46 1,069 / 42.09
Height mm / in 1,154 / 45.43 1,506 / 59.29
Packing Dimension Width mm / in 2,052 / 80.79 2,034 / 80.08
Depth mm / in 1,188 / 46.77 1,412 / 55.59
Unit Weight kg / lb 196 / 432.11 323 / 712.09 337 / 742.96
Air Flow l/s / CFM 3,020 / 6,400 3,256 / 6,900 4,908 / 10,400 3,020 / 6,400
Sound Pressure Level dBA 67 65 70 65
Height mm / in 1,067 / 42 1,166 / 43.94 1,067 / 42
Unit Dimension Width mm / in 880 / 34.65 980 / 38.58 880 / 34.65
Depth mm / in 880 / 34.65 980 / 38.58 880 / 34.65
Height mm / in 1,231 / 48.46 1,231 / 48.46 1,321 / 52.01 1,231 / 48.46
Outdoor Packing Dimension Width mm / in 1,030 / 40.55 1,130 / 44.49 1,030 / 40.55
Unit Depth mm / in 1,058 / 41.65 1,158 / 45.59 1,058 / 41.65
Unit Weight kg / lb 135 / 297.62 157 / 346.13 177 / 390.22 135 / 297.62
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8 12.7 / 1/2
Connection Size
Gas mm / in 25.4 / 1 28.58 / 1 1/8 34.92 / 1 3/8 25.4 / 1
Type R410A
Refrigerant
Charge kg / lb 3.6 x 2 / 7.94 x 2 4.0 x 2 / 8.82 x 2 4.7 x 2 / 10.36 x 2 3.2 x 3 / 7.05 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 1
Specifications
Ducted Blower System (A5DB-H/A5MC-H)

Indoor Unit A5DB 350H3 A5DB 400H4 A5DB 450H3


Model
Outdoor Unit A5MC 100H A5MC 125H x 2 A5MC 100H x 4 A5MC 150H x 3
BTU/h 350,000 400,000 450,000
Nominal Capacity
W 102,500 117,200 131,900
Nominal Total Input Power W 34,550 39,330 45,930
Nominal Running Current A 60.4 70.20 89.30
BTU/h/W 10.13 10.17 9.80
EER
W/W 2.97 2.98 2.87
Power Source V/Ph/Hz 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge VERTICAL & CONVERTIBLE
Air Flow High l/s / CFM 4,955 / 10,500 5,710 / 12,000 6,420 / 13,500
External Static Pressure With
Pa / in.wg 200 / 0.8 250 / 1.0
Filter
Sound Pressure Level dBA 66 68
Indoor Unit Height mm/in 1,486 / 58.50
Unit Dimension Width mm / in 2,022 / 79.61 2,174 / 85.59
Depth mm / in 1,069 / 42.09 1,336 / 52.6
Height mm / in 1,766 / 69.53 1,766 / 69.53
Packing Dimension Width mm / in 2,279 / 89.72 2,431 / 95.71
Depth mm / in 1,412 / 55.59 1,684 / 66.3
Unit Weight kg / lb 431 / 950.19 488 / 1,075.86 533 / 1,175.06
Air Flow l/s / CFM 3,020 / 6,400 3,256 / 6,900 3,020 / 6,400 4,908 / 10,400
Sound Pressure Level dBA 65 70
Height mm / in 1,067 / 42.00 1,166 / 43.94
Unit Dimension Width mm / in 880 / 34.65 980 / 38.58 880 / 34.65 980 / 38.58
Depth mm / in 880 / 34.65 980 / 38.58 880 / 34.65 980 / 38.58
Height mm / in 1,231 / 48.46 1,321 / 52.01
Outdoor Packing Dimension Width mm / in 1,030 / 40.55 1,130 / 44.49 1,030 / 40.55 1,130 / 44.49
Unit Depth mm / in 1,058 / 41.65 1,158 / 45.59 1,058 / 41.65 1,158 / 45.59
Unit Weight kg / lb 135 / 297.62 157 / 346.13 135 / 297.62 177 / 390.22
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 25.4 / 1 28.58 / 1 1/8 25.4 / 1 34.92 / 1 3/8
Type R410A
Refrigerant
Charge kg / lb 3.1 / 6.83 4.7 x 2 / 10.36 x 2 3.4 x 4 / 7.50 x 4 4.6 x 3 / 10.14 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 2
Specifications
Ducted Blower System (A5DB-H/A5MC-H)

Indoor Unit A5DB 500H4 A5DB 600H4 A5DB 750H5


Model
Outdoor Unit A5MC 125H x 4 A5MC 150H x 4 A5MC 150H x 5
BTU/h 500,000 600,000 750,000
Nominal Capacity
W 146,500 175,850 219,900
Nominal Total Input Power W 49,990 61,620 78,640
Nominal Running Current A 85.60 118.90 152.10
BTU/h/W 10.00 9.74 9.54
EER
W/W 2.93 2.85 2.80
Power Source V/Ph/Hz 380 - 415 / 3 / 50
Operation WIRED CONTROL
Control VERTICAL & VERTICAL & FACTORY VERTICAL & FACTORY
Air Discharge
CONVERTIBLE CONVERTIBLE CONVERTIBLE
Air Flow High l/s / CFM 7,135 / 15,000 8,560 / 18,000 10,700 / 22,500
External Static Pressure With
Pa / in.wg 250 / 1.0 300 / 1.2 350 / 1.4
Filter
Sound Pressure Level dBA 68 70 71
Indoor Unit Height mm/in 1,486 / 58.50 1,918 / 75.51 2,197 / 86.5
Unit Dimension Width mm / in 2,174 / 85.59
Depth mm / in 1,336 / 52.6 1,775 / 69.88
Height mm / in 1,766 / 69.53 2,122 / 83.54 2,401 / 94.53
Packing Dimension Width mm / in 2,431 / 95.71 2,399 / 94.45
Depth mm / in 1,684 / 66.3 2,005 / 78.94
Unit Weight kg / lb 580 / 1,278.68 899 / 1,981.96 946 / 2,085.57
Air Flow l/s / CFM 3,256 / 6,900 4,908 / 10,400 4,908 / 10,400
Sound Pressure Level dBA 65 70
Height mm / in 1,067 / 42 1,166 / 45.91
Unit Dimension Width mm / in 980 / 38.58 980 / 38.58
Depth mm / in 980 / 38.58 980 / 38.58
Height mm / in 1,231 / 48.46 1,321 / 52.01
Outdoor Packing Dimension Width mm / in 1,130 / 44.49 1,130 / 44.49
Unit Depth mm / in 1,158 / 45.59 1,158 / 45.59
Unit Weight kg / lb 157 / 346.13 177 / 390.22
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 28.58 / 1 1/8 34.92 / 1 3/8
Type R410A
Refrigerant
Charge kg / lb 4.5 x 4 / 9.92 x 4 4.7 x 4 / 10.36 x 4 4.5 x 5 / 9.92 x 5

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 3
Indoor & Outdoor Units
R22 Ducted Blower B Series

Capacity Indoor Unit Outdoor Unit Capacity Indoor Unit Outdoor Unit
(BTU/h) (BTU/h)

35,000 250,000

ADB 40B ALC 35D ADB 250B2 AMC 125B x 2

40,000

ADB 40B ALC 40D ADB 300B2 AMC150C x 2


300,000

50,000

ADB 50B ALC 50D ADB 300B3 AMC 100B x 3

61,000 350,000

ADB 60B ALC 61D ADB 350B3 AMC 100B + AMC 125B x 2

70,000 400,000

ADB 80B AMC 72C ADB 400B4 AMC 100B x 4

80,000

ADB 80B AMC 80C ADB450B3 AMC 150Cx3


450,000

100,000

ADB 100B AMC 100B ADB 500B4 AMC 100B x 2 + AMC 125B x 2

125,000 500,000

ADB 125B AMC 125B ADB 500B4 AMC 125B x 4

ADB 150B AMC 150C ADB 600B4 AMC 150Cx4


150,000 600,000

ADB 150B2 AMC 80C x 2 ADB 600B5 AMC 100B + AMC 125B x 4

200,000 750,000

ADB 200B2 AMC 100B x 2 ADB 750B5 AMC 150C x 5

D U CT E D S P L I T SYST E M / P 1 4
Indoor & Outdoor Units
R410A Ducted Blower H Series with Microchannel Heat Exchanger (MCHE) System

Capacity Capacity
Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit
(BTU/h) (BTU/h)

80,000 300,000

A5DB 80H A5MC 80H A5DB 300H3 A5MC 100H x 3

100,000 350,000

A5DB 100H A5MC 100H A5DB 350H3 A5MC 100H + A5MC 125H x 2

125,000 400,000

A5DB 125H A5MC 125H A5DB 400H4 A5MC 100H x 4

150,000 450,000

A5DB 150H A5MC 150H A5DB 450H3 A5MC 150H x 3

200,000 500,000

A5DB 200H2 A5MC 100H x 2 A5DB 500H4 A5MC 125H x 4

250,000 600,000

A5DB 250H2 A5MC 125H x 2 A5DB 600H4 A5MC 150H x 4

300,000 750,000

A5DB 300H2 A5MC 150H x 2 A5DB 750H5 A5MC 150H x 5

Ducted Split System Unit Line-up

Capacity Range ('000 BTU/h)


Model
40 50 60 70 100 125 200 250 300 350 400 450 500 600 750

B-series • • • • • • • • • • • • • • •

H-series • • • • • • • • • • • •

Convertible Discharge • • • • • • • •

Note:
A5DB 125H - 500H4 have convertible discharge.
A5DB 600H4 - 750H5 is upon request, and not field convertible. Default is vertical.

D U CT E D S P L I T SYST E M / P 1 5
(ADSB/AMC) (A5DSB-H/A5MC-H)

Acson Double Skin Ducted Blower are ideal for light commercial applications
with large or open spaces. It is designed in order to fulfill the indoor air quality
requirement where the cooling capacity is within range of 80,000 to 500,000
BTU/h and up to a static pressure of 1.0 in Wg.

Common Features:
All the framework is insulated with 1 inch double skin Polyurethane (PU) insulation
panel and all frames are insulated with Polyethylene (PE) that is chemical resistant.
PE is a resilient type closed-cell foam that ideal for shock absorbing, vibration
dampening, minimize heat loss and avoid condensation to take place. Adding double
skin PU insulation panel accomplishes few benefits:
Excellent Thermal Barrier (prevent heat lost and sweating)
Condensation Control
Superior Silent Operation
(lined with 1 inch sound-proof insulation to avoid transmission of vibration)
Air Tightness

Double Skin Ducted Blower System (ADSB)


Indoor Air Throw Direction
convertible discharge which provides flexibility in installation at site.

Double Skin Ducted Blower System (A5DSB-H)


Microchannel Heat Exchanger (MCHE)
Simple, thin profile, all-aluminium design that is lightweight
and prevents galvanic corrosion.

Anti-corrosion evaporator
Standard configured with hydrophilic coating.

*50 mm double skin PU insulation panel is available upon request.

6 X Double Skin
Insulation Panel

GI Sheet
Layer

PU Foam

D U CT E D S P L I T SYST E M / P 1 6
Specifications
Double Skin Ducted Blower System (ADSB/AMC)

Indoor Unit ADSB 75B ADSB 100B ADSB 125B ADSB 150B
Model
Outdoor Unit AMC 80C AMC 100B AMC 125B AMC 150C
BTU/h 80,000 100,000 125,000 150,000
Nominal Capacity
W 23,440 29,300 36,625 43,950
Nominal Total Input Power W 8,769 10,790 11,478 16,211
Nominal Running Current A 20.90 24.40 20.80 31.80
BTU/h/W 9.12 9.27 10.89 9.25
EER
W/W 2.67 2.72 3.19 2.71
IDU: 220 ~ 240/1/50
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
ODU: 380 ~ 415/3/50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL ONLY HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 1,180 / 2,500 1,510 / 3,200 1,982 / 4,200 2,171 / 4,600
External Static Pressure
Pa / in.wg 100 / 0.4 149 / 0.6
Without Filter
Sound Pressure Level dBA 53 54 55 57
Indoor Unit Height mm/in 648 / 25.51 963 / 37.91
Unit Dimension Width mm / in 1,410 / 55.51 1,560 / 61.42
Depth mm / in 794 / 31.26 1,036 / 40.79
Height mm / in 817 / 32.2 765 / 30.1 1,204 / 47.4
Packing Dimension Width mm / in 1,606 / 63.2 1,650 / 65.0 1,787 / 70.35
Depth mm / in 880 / 34.65 1,188 / 46.77
Unit Weight kg / lb 105 / 231 109 / 240 194 / 428 201 / 443
Air Flow l/s / CFM 2,832 / 6,000 2,926 / 6,200 5,475 / 11,600
Sound Pressure Level dBA 74 65 73
Height mm / in 946 / 37.2 1,041 / 41.0
Unit Dimension Width mm / in 1,300 / 51.18 939 / 37.0
Depth mm / in 500 / 19.7 1,116 / 43.9
Height mm / in 1,132 / 44.56 1,132 / 44.6 1,227 / 48.3
Outdoor Packing Dimension Width mm / in 1,414 / 55.66 1,112 / 43.8
Unit Depth mm / in 664 / 26.14 1,312 / 51.7
Unit Weight kg / lb 145 / 320 164 / 361 169 / 373 227 / 500
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 25.4 / 1.0 28.58 / 1 1/8 34.92 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 6.8 / 14.96 7.6 / 16.72 7.95 / 17.49 9.90 / 21.78

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 7
Specifications
Double Skin Ducted Blower System (ADSB/AMC)

Indoor Unit ADSB 200B2 ADSB 250B2 ADSB 300B2 ADSB 300B3
Model
Outdoor Unit AMC 100B x 2 AMC 125B x 2 AMC 150C x 2 AMC 100B x 3
BTU/h 200,000 250,000 300,000
Nominal Capacity
W 58,600 73,250 87,900
Nominal Total Input Power W 21,605 23,646 34,688 31,850
Nominal Running Current A 39.80 42.80 66.70 59.50
BTU/h/W 9.25 10.57 8.65 9.42
EER
W/W 2.71 3.10 2.53 2.76
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 3,021 / 6,400 3,776 / 8,000 4,248 / 9000
External Static Pressure
Pa / in.wg 158 / 0.6 200 / 0.8
Without Filter
Sound Pressure Level dBA 58 60 63
Indoor Unit Height mm/in 967 / 38.07 1,318 / 51.89
Unit Dimension Width mm / in 1,792 / 70.55 1,770 / 69.69
Depth mm / in 1,028 / 40.47 1,244 / 48.98
Height mm / in 1,206 / 47.48 1,590 / 62.6
Packing Dimension Width mm / in 2,090 / 82.28 2,134 / 84.02
Depth mm / in 1,188 / 46.77 1,438 / 56.61
Unit Weight kg / lb 208 / 459 278 / 613 298 / 657
Air Flow l/s / CFM 3304 / 7000 5,475 / 11,600 3304 / 7000
Sound Pressure Level dBA 65 74 65
Height mm / in 946 / 37.2 946 / 37.2 1,041 / 41.0 946 / 37.2
Unit Dimension Width mm / in 939 / 37.0 939 / 37.0
Depth mm / in 1,116 / 43.9 1,116 / 43.9
Height mm / in 1,132 / 44.6 1,132 / 44.6 1,227 / 48.3 1,132 / 44.6
Outdoor Packing Dimension Width mm / in 1,112 / 43.8
Unit Depth mm / in 1,312 / 51.7
Unit Weight kg / lb 164 / 361 169 / 372 227 / 500 164 / 361
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8
Connection Size
Gas mm / in 28.58 / 1 1/8 34.92 / 1 3/8 28.58 / 1 1/8
Type R22
Refrigerant
Charge kg / lb 7.6 x 2 / 16.8 x 2 8.0 x 2 / 17.5 x 2 10.1 x 2 / 22.3 x 2 7.6 x 3 / 16.8 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 8
Specifications
Double Skin Ducted Blower System (ADSB/AMC)

Indoor Unit ADSB 350B3 ADSB 400B4 ADSB 500B4


Model
Outdoor Unit AMC 100B x 1 AMC 125B x 2 AMC 100B x 4 AMC 125B x 4
BTU/h 350,000 400,000 500,000
Nominal Capacity
W 102,550 117,200 146,500
Nominal Total Input Power W 35,416 42,373 52,447
Nominal Running Current A 63.90 79.00 94.50
BTU/h/W 9.88 9.44 9.53
EER
W/W 2.90 2.77 2.79
Power Source V/Ph/Hz 380 ~ 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 4,956 / 10,500 5,664 / 12,000 7,080 / 15,000
External Static Pressure
Pa / in.wg 200 / 0.8 250 / 1.0
Without Filter
Sound Pressure Level dBA 63 64 65
Indoor Unit Height mm/in 1,592 / 62.7 1,585 / 62.4
Unit Dimension Width mm / in 2,050 / 80.7 2,212 / 87.09
Depth mm / in 1,275 / 50.2 1,562 / 61.50
Height mm / in 1,868 / 73.54 1,850 / 72.83
Packing Dimension Width mm / in 2,370 / 93.31 2,431 / 95.71
Depth mm / in 1,538 / 60.55 1,738 / 68.43
Unit Weight kg / lb 352 / 776 364 / 802 386 / 851
Air Flow l/s / CFM 3,304 / 7,000
Sound Pressure Level dBA 65
Height mm / in 946 / 37.2
Unit Dimension Width mm / in 939 / 37.0
Depth mm / in 1,116 / 43.9
Height mm / in 1,132 / 44.6
Outdoor Packing Dimension Width mm / in 1,112 / 43.8
Unit Depth mm / in 1,312 / 51.7
Unit Weight kg / lb 164 / 361 169 / 372 164 / 361 169 / 372
Type BRAZED
Pipe
Liquid mm / in 15.9 / 5/8
Connection Size
Gas mm / in 28.6 / 1 1/8 34.9 / 1 3/8 28.6 / 1 1/8 34.9 / 1 3/8
Type R22
Refrigerant
Charge kg / lb 7.6 / 16.8 8.0 x 2 / 17.5 x 2 7.6 x 4 / 16.8 x 4 8.0 x 4 / 17.5 x 4

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 1 9
Specifications
Double Skin Ducted Blower System (A5DSB-H/A5MC-H)

Indoor Unit A5DSB 80H A5DSB 100H A5DSB 125H A5DSB 150H
Model
Outdoor Unit A5MC 80H A5MC 100H A5MC 125H A5MC 150H
BTU/h 80,000 100,000 125,000 150,000
Nominal Capacity
W 23,400 29,300 36,600 44,000
Nominal Total Input Power W 7,100 10,000 11,350 14,800
Nominal Running Current A 12.50 17.10 19.70 28.70
BTU/h/W 11.27 10.00 11.01 10.14
EER
W/W 3.30 2.93 3.22 2.97
IDU: 220 - 240 / 1 / 50
Power Source V/Ph/Hz 380 - 415 / 3 / 50
ODU: 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & NON - CONVERTIBLE HORIZONTAL & CONVERTIBLE

Air Flow High l/s / CFM 1,085 / 2,300 1,416 / 3,000 1,770 / 3,750 2,124 / 4,500
External Static Pressure With
Pa / in.wg 100 / 0.4 150 / 0.6
Filter
Sound Pressure Level dBA 52 55 53 56
Indoor Unit Height mm/in 632 / 24.88 842 / 33.15
Unit Dimension Width mm / in 1,438 / 56.61 1,588 / 62.52
Depth mm / in 730 / 28.74 973 / 38.31
Height mm / in 844 / 33.23 1,190 / 46.85
Packing Dimension Width mm / in 1,782 / 70.16 1,878 / 73.94
Depth mm / in 1,040 / 40.94 1,275 / 50.20
Unit Weight kg / lb 99 / 218 180 / 397
Air Flow l/s / CFM 2,077 / 4,400 3,020 / 6,400 3,256 / 6,900 4.908 / 10,400
Sound Pressure Level dBA 69 65 65 70
Height mm / in 929 / 36.57 1,067 / 42 1,166/ 45.91
Unit Dimension Width mm / in 1,235 / 48.62 880 / 34.65 980 / 38.58
Depth mm / in 496 / 19.53 880 / 34.65 980 / 38.58
Height mm / in 1,085 / 42.72 1,231 / 48.46 1,321 / 52.01
Outdoor Packing Dimension Width mm / in 1,385 / 54.53 1,030 / 40.55 1,130 / 44.49
Unit Depth mm / in 684 / 26.93 1,058 / 41.65 1,158 / 45.59
Unit Weight kg / lb 111 / 244.71 135 / 297.62 157 / 346.13 177 / 390.22
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8
Connection Size
Gas mm / in 22.23 / 7/8 25.4 / 1 28.58 / 1 1/8 34.92 / 1 3/8
Type R410A
Refrigerant
Charge kg / lb 2.5 / 5.51 3.4 / 7.5 4.8 / 10.58 5.2 / 11.46

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 2 0
Specifications
Double Skin Ducted Blower System (A5DSB-H/A5MC-H)

Indoor Unit A5DSB 200H2 A5DSB 250H2 A5DSB 300H2 A5DSB 300H3
Model
Outdoor Unit A5MC 100H x 2 A5MC 125H x 2 A5MC 150H x 2 A5MC 100H x 3
BTU/h 200,000 250,000 300,000
Nominal Capacity
W 58,600 73,200 88,000
Nominal Total Input Power W 19,700 23,880 30,520 29,710
Nominal Running Current A 35.10 40.60 58.70 52.60
BTU/h/W 10.15 10.47 9.83 10.1
EER
W/W 2.97 3.07 2.88 2.96
Power Source V/Ph/Hz 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 2,832 / 6,000 3,540 / 7,500 4,248 / 9,000
External Static Pressure With
Pa / in.wg 150 / 0.6 200 / 0.8
Filter
Sound Pressure Level dBA 61 63 66 66
Indoor Unit Height mm / in 932 / 36.69 1,282 / 50.47
Unit Dimension Width mm / in 1,770 / 69.69
Depth mm / in 950 / 37.4 1,170 / 46.06
Height mm / in 1,190 / 46.85 1,490 / 58.66
Packing Dimension Width mm / in 2,060 / 81.10 2,032 / 80.00
Depth mm / in 1,275 / 50.20 1,482 / 58.35
Unit Weight kg / lb 218 / 481 350 / 772 364 / 802
Air Flow l/s / CFM 3,020 / 6,400 3,256 / 6,900 4,908 / 10,400 3,020 / 6,400
Sound Pressure Level dBA 65 65 70 65
Height mm / in 1,067 / 42 1,067 / 42 1,166 / 45.91 1,067 / 42
Unit Dimension Width mm / in 880 / 34.65 980 / 38.58 880 / 34.65
Depth mm / in 880 / 34.65 980 / 38.58 880 / 34.65
Height mm / in 1,231 / 48.46 1,321 / 52.01 1,231 / 48.46
Outdoor Packing Dimension Width mm / in 1,030 / 40.55 1,130 / 44.49 1,030 / 40.55
Unit Depth mm / in 1,058 / 41.65 1,158 / 45.59 1,058 / 41.65
Unit Weight kg / lb 135 / 297.62 157 / 346.13 177 / 390.22 135 / 297.62
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2 15.88 / 5/8 12.7 / 1/2
Connection Size
Gas mm / in 25.4 / 1 28.58 / 1 1/8 34.92 / 1 3/8 25.4 / 1
Type R410A
Refrigerant
Charge kg / lb 3.6 x 2 / 7.94 x 2 4.0 x 2 / 8.82 x 2 4.7 x 2 / 10.36 x 2 3.2 x 3 / 7.05 x 3

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 2 1
Specifications
Double Skin Ducted Blower System (A5DSB-H/A5MC-H)

Indoor Unit A5DSB 350H3 A5DSB 400H4 A5DB 500H4


Model
Outdoor Unit A5MC 100H A5MC 125H x 2 A5MC 100H x 4 A5MC 125H x 4
BTU/h 350,000 400,000 500,000
Nominal Capacity
W 102,500 117,200 146,500
Nominal Total Input Power W 34,630 39,401 49,990
Nominal Running Current A 60.4 70.20 85.60
BTU/h/W 10.11 10.15 10.00
EER
W/W 2.96 2.97 2.93
Power Source V/Ph/Hz 380 - 415 / 3 / 50
Operation WIRED CONTROL (FIELD SUPPLY)
Control
Air Discharge HORIZONTAL & CONVERTIBLE
Air Flow High l/s / CFM 4,955 / 10,500 5,710 / 12,000 7,135 / 15,000
External Static Pressure With
Pa / in.wg 200 / 0.8 250 / 1.0
Filter
Sound Pressure Level dBA 66 68
Indoor Unit Height mm/in 1,540 / 60.63 1,540 / 60.63
Unit Dimension Width mm / in 2,020 / 79.53 2,170 / 85.43
Depth mm / in 1,170 / 46.06 1,370 / 53.94
Height mm / in 1,790 / 70.47 1,856 / 73.07
Packing Dimension Width mm / in 2,282 / 89.84 2,432 / 95.75
Depth mm / in 1,532 / 60.31 1,732 / 68.19
Unit Weight kg / lb 462 / 1,019 523 / 1,153 614 / 1,354
Air Flow l/s / CFM 3,020 / 6,400 3,256 / 6,900 3,020 / 6,400 3,256 / 6,900
Sound Pressure Level dBA 65
Height mm / in 1,067 / 42
Unit Dimension Width mm / in 880 / 34.65 980 / 38.58 880 / 34.65 980 / 38.58
Depth mm / in 880 / 34.65 980 / 38.58 880 / 34.65 980 / 38.58
Height mm / in 1,231 / 48.46
Outdoor Packing Dimension Width mm / in 1,030 / 40.55 1,130 / 44.49 1,030 / 40.55 1,130 / 44.49
Unit Depth mm / in 1,058 / 41.65 1,158 / 45.59 1,058 / 41.65 1,158 / 45.59
Unit Weight kg / lb 135 / 297.62 157 / 346.13 135 / 297.62 157 / 346.13
Type BRAZED
Pipe
Liquid mm / in 12.7 / 1/2
Connection Size
Gas mm / in 25.4 / 1 28.58 / 1 1/8 25.4 / 1 28.58 / 1 1/8
Type R410A
Refrigerant
Charge kg / lb 3.1 / 6.83 4.7 x 2 / 10.36 x 2 3.4 x 4 / 7.50 x 4 4.5 x 4 / 9.92 x 4

Note:
1. All specifications are subjected to change by the manufacturer without prior notice.
2. All units are being tested and comply to ISO 13253.
3. Nominal cooling capacity are based on the conditions below:

Cooling
Indoor 27˚C DB / 19˚C WB
Outdoor 35˚C DB / 24˚C WB

4. Indoor sound pressure level are according to JIS B 8615 standard.


Horizontal Discharge : Position of the measurement point 1.5m below the unit.
(With 1m duct connect to the inlet and 2m duct connect to the outlet)
Vertical Discharge : Position of the measurement point is 1m away from every side of the unit and 1m above floor level.
(With Tested with 2m length duct at discharge only)

D U CT E D S P L I T SYST E M / P 2 2