FM-200 Calculation
Based on NFPA 2001
Note:
- Minimum Design Concentration for Electrical Hazard (Fire Class C) is 7% v/v
- Estimated Air Conditioned Room Temperature Ambient is 21.1 °C (70 °F)
OPERATOR ROOM
FM-200 Calculation
- Metric - - Imperial -
Width 12.00 m 39.37 ft
Length 19.80 m 64.96 ft
Height 3.50 m 11.48 ft
Volume (W x L x H) 831.60 m³ 29,367.41 ft³
Temperature ( t ) 21 °C 70 °F
Design Concentration ( C ) 7 % v/v 7 % v/v
Specific Volume ( s ) 0.1374 m³/kg 2.207 ft³/lb
Date:
CARBONDIOXIDE (CO2) Calculation
-- Deep Seated Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 50% (Electrical Hazard - Class C Fire)
SWITCHGEAR ROOM
Width 18.00 m
Length 33.00 m
Height 4.00 m
Volume (W x L x H) 2,376 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Surface Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 34%
(ROOM NAME)
Width m
Length m
Height m
Volume (W x L x H) 0.00 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Deep Seated Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 50% (Electrical Hazard - Class C Fire)
BATERRY ROOM
Width 6.00 m
Length 8.75 m
Height 4.00 m
Volume (W x L x H) 210 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Surface Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 34%
(ROOM NAME)
Width m
Length m
Height m
Volume (W x L x H) 0.00 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Deep Seated Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 50% (Electrical Hazard - Class C Fire)
ELECTRICAL ROOM
Width 12.00 m
Length 13.20 m
Height 2.50 m
Volume (W x L x H) 396 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Surface Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 34%
(ROOM NAME)
Width m
Length m
Height m
Volume (W x L x H) 0.00 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Deep Seated Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 50% (Electrical Hazard - Class C Fire)
BASEMENT
Width 33.00 m
Length 24.00 m
Height 2.50 m
Volume (W x L x H) 1,980 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Surface Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 34%
(ROOM NAME)
Width m
Length m
Height m
Volume (W x L x H) 0.00 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Deep Seated Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 50% (Electrical Hazard - Class C Fire)
BASEMENT
Width 1.00 m
Length 1.00 m
Height 90.00 m
Volume (W x L x H) 90 m³
Date:
CARBONDIOXIDE (CO2) Calculation
-- Surface Fire --
Based on NFPA 12
V = Volume (m³)
C = Minimum Design Concentration (% v/v)
Note:
- Minimum Design Concentration is 34%
(ROOM NAME)
Width m
Length m
Height m
Volume (W x L x H) 0.00 m³