You are on page 1of 1

Discipline : C&I

REV:-00

C&I Comments on Vendor Document for Compressor

S.No. ISGEC Comment Vendor Reply

1 Microprocessor based control panel to be provided. Noted & Confirmed

2 Provision for Start/Stop through hardwire from DCS to be Provision shall be provided, All cabling in customer scope
provided.

Compressor ON, Compressor TRIP, Compressor OFF & Confirmed for Remote Load Enable, Remote Load/Unload &
3 Local/remote selction feedback signals are to be provided Remote Start/Stop, Trip Signal is confirmed - Compressor on
for DCS. Local/remote feedback through Modbus…RS485 Port provided

4 230 VAC timer operated automatic drain tap to be Noted & Confirmed
provided.

5 Oil content should be <=0.003 ppm for compressed air, Noted & Confirmed
vendor to confirm