Professional Documents
Culture Documents
1
VE24 vacuum circuit breaker
Product overview
Application areas • The main circuit is encapsu- Ideal for medium voltage
lated by epoxy resin, whereby control and protection in
• Chemical industry the current-carrying compo- medium voltage power supply
• Petroleum industry nents won’t be exposed to and distribution system
• Piping industry temperature fluctuations or
• Offshore mining • The VE24 is equipped with • The circuit breakers with
oxidization which can result in
• Shipbuilding superior spring charging electric charging operating
the deterioration of heat
• Paper manufacturing mechanism, utilizes modular mechanism have complemen-
dispersion.
• Opencast coal mine design that is offering tary spring charging motor,
• The main circuit is encapsu-
• Substation optimized mechanism main shunt release, trip free relay,
lated by epoxy resin, ensuring
• Cement industry parts distribution, simpler and auxiliary switch for spring
that the connecting compo-
• Automotive industry structure and more reliable charging motor release.
nents won’t loosen due to
• Power plant performance. The whole • The following accessories are
mechanical operations,
• Textile and food industries mechanism is composed by offered as needed: undervolt-
long-time use or temperature
• Metallurgical industry three modules: charging, age releases, overcurrent
changes, thus avoiding
closing, opening. Assembly relays, etc..
overheating issues.
and maintenance of these
• The number of components
three parts are very simple.
VE24 vacuum circuit breaker of the main circuit is only
The spring charging mecha-
requires almost no relevant 40-50% of that of composite
nism composed by ratchet
maintenance insulation type circuit
wheel mechanism, oscillator
breakers, which optimizes the
Simple structure design of VE24 and closing spring is compact
control of phase and polarity
series minimizes fault occur- and smart. The operating
spacing between the contact
rence, simplifies routine mechanism is usually
arms and tulip contacts and
maintenance. Positive indication equipped with manual
improves the contact head
charging device and electric
of the circuit breaker operating centering and contacting.
charging device, enabling
status is provided on the front • The heat dissipating compo-
automatic reclosing function.
panel of the circuit breaker for nents of the large current
• The circuit breakers with
easy visual verification. EPU use epoxy coating
manual charging operating
process to control insulation.
The encapsulated pole unit mechanism are equipped
Thus, larger heat dissipating
(EPU) used in VE24 series with manual opening and
components with a broader
circuit breakers ensures closing operation buttons,
radiating surface are used to
reliability in operation of breaking position indicator
improve heat dispersion.
vacuum interrupter (VI) and and spring mechanism
• The main circuit is encapsu-
other key components. The EPU charging status indicator,
lated by epoxy resin, so as to
switch operations counter,
of VE24 has following features: guard against the possibility
shunt release auxiliary switch,
• A vacuum interrupter with of small parts and other
position and fault signals,
lower contact resistance is foreign material left over from
etc..
used. Main circuit resistance the installation and commis-
is 10-20% lower than for sioning stage and provides
compound insulation, thus protection against the ingress
improves temperature rising of water during operation,
conditions from the heat thus preventing possible
source. short circuit or arcing events.
• The main circuit is protected
by EPU from dust accumula-
tion which can result in the
deterioration of heat dissipa-
tion.
Optional accessories
2
VE24 vacuum circuit breaker
Spring operating mechanism data
3
VE24 vacuum circuit breaker
Technical data
VE24 vacuum circuit breaker technical data (for 210 mm distribution panel)
Name Unit Parameters
Rated voltage kV 24 24
Rated frequency Hz 50 50
Rated short-time power frequency withstand voltage (1 min) kV 65 (phase-to-ground, phase-to-phase); 79 (gap) 65 (phase-to-ground, phase-to-phase); 79 (gap)
Rated lightning impulse withstand voltage kV 125 (phase-to-ground, phase-to-phase); 145 (gap) 125 (phase-to-ground, phase-to-phase); 145 (gap)
Rated current A 630/1250 630/1250
Rated short-time withstand current (4s) kA 25 31.5
Rated peak withstand current kA 63 80
Rated short-circuit breaking current kA 25 31.5
Rated short-circuit making current kA 63 80
Rated short-circuit operating sequence O-0.3s-CO-180s-CO O-0.3s-CO-180s-CO
Conduction circuit resistance per phase μȍ ≤60 (630A) ≤50 (1,250A)
Average closing speed m/s 0.8~1.2 0.8~1.2
Average opening speed m/s 1.1~1.7 1.1~1.7
Closing time ms 35~70 35~70
Opening time ms 20~50 20~50
Contact closing bounce time ms ≤2 ≤2
Three phase opening/closing asynchronism ms ≤2 ≤2
Pole center distance mm 210 210
Permissible wear for movable and fixed contacts mm 3 3
Mechanical lifespan cycles 10000 10000
4
VE24 vacuum circuit breaker
Technical data
VE24 vacuum circuit breaker technical data (for 275mm distribution panel)
Name Unit Parameters
Rated voltage kV 24 24
Rated frequency Hz 50 50
Rated short-time power frequency withstand voltage (1 min) kV 65 (phase-to-ground, phase-to-phase); 79 (gap) 65 (phase-to-ground, phase-to-phase); 79 (gap)
Rated lightning impulse withstand voltage kV 125 (phase-to-ground, phase-to-phase); 145 (gap) 125 (phase-to-ground, phase-to-phase); 145 (gap)
Rated current A 630/1250 630/1250/1600/2000/2500/3150
Rated short-time withstand current (4s) kA 25 31.5
Rated peak withstand current kA 63 80
Rated short-circuit breaking current kA 25 31.5
Rated short-circuit making current kA 63 80
Rated short-circuit operating sequence O-0.3s-CO-180s-CO O-0.3s-CO-180s-CO
Conduction circuit resistance per phase μȍ ≤60 (630A) ≤50 (1,250A)
≤35 (1600-2,000A) ≤25 (above 2500A)
Average closing speed m/s 0.8~1.2 0.8~1.2
Average opening speed m/s 1.1~1.7 1.1~1.7
Closing time ms 35~70 35~70
Opening time ms 20~50 20~50
Contact closing bounce time ms ≤2 ≤2
Three phase opening/closing asynchronism ms ≤2 ≤2
Pole center distance mm 275 275
Permissible wear for movable and fixed contacts mm 3 3
Mechanical lifespan cycles 10000 10000
5
VE24 vacuum circuit breaker
Dimensions
Eaton Power
800 630 25 210 638 652 640 650 685 Ø35 325 745 737 655 277 40
800 630 31.5 210 638 652 640 650 705 Ø35 345 745 757 655 277 40
800 1250 25 210 638 652 640 650 685 Ø49 325 745 737 655 277 40
800 1250 31.5 210 638 652 640 650 705 Ø49 345 745 757 655 277 40
1000 630 25 275 838 852 840 850 685 Ø35 325 745 737 655 377 40
1000 630 31.5 275 838 852 840 850 705 Ø35 345 745 757 655 377 40
1000 1250 25 275 838 852 840 850 685 Ø49 325 745 737 655 377 40
1000 1250 31.5 275 838 852 840 850 705 Ø49 345 745 757 655 377 40
1000 1600~2000 31.5 275 838 852 840 850 705 Ø79 345 735 757 685 377 0
1000 2500~3150 31.5 275 838 852 840 850 781 Ø109 345 735 825 685 377 0
6
7
Motor circuit Closing circuit Locking circuit Opening circuit
Wiring diagram
S9: Auxiliary switch (when circuit breaker is in the service position) HQ: Closing coil
S8: Auxiliary switch (when circuit breaker is in the test position) TQ: Opening coil
S2: Auxiliary switch R0-R1: Resistance
S1: Auxiliary switch (switched on after the closing spring is charged) Y7-Y9: Indirect overcurrent release coil
QF: Auxiliary switch (switched during closing or opening operation) (optional)
Y1: Locking coil (optional)
Note:
1. In the figure, the circuit breaker is in the test position, is open and is not storing energy.
2. For DC power supply, the polarities in the dash box should be consistent.
VE24 vacuum circuit breaker
VE24 vacuum circuit breaker selection guide
Optional configurations (standard option includes trip free device. Please note if the trip free device has to been canceled)
Name Parameters