24 kV VE24 encapsulated pole vacuum circuit breaker

Proven, durable circuit


protection and control
VE24 vacuum circuit breaker
Product overview

VE24 vacuum circuit breaker Contents


Description Page
VE24 vacuum circuit breaker
Product overview ................................................................ 1
Spring operating mechanism data .......................................... 3
Technical data .......................................................................... 4
Dimensions ............................................................................. 6
Wiring diagram ........................................................................ 7
VE24 vacuum circuit breaker models ...................................... 8

VE24 vacuum circuit breaker


Product description Certificates Features
Built upon Eaton's heritage of • GB 1984-2003 High-voltage • APG process used in VE24 • Type tests are conducted-ac-
vacuum technology, the VE24 AC circuit breakers series to seal the vacuum cording to GB standard:
vacuum circuit breaker series is • JB 3855-1996 3.6-40.5 kV interrupter and circuit into the electrical endurance: E2;
24kV 3-phase indoor vacuum Indoor AC HV vacuum circuit insulation cylinder enhances Mechanical endurance: M2;
circuit breakers integrated with breaker dielectric strength greatly, breaking capacitive current:
an encapsulated pole, from • DL/T 403-2000 HV vacuum makes the VE24 perfect choice C2.
630A to 3150A and 25kA to circuit breaker, rated voltage for harsh environment. • Consistency in dimension and
31.5kA with rated frequency 50 12kV to 40.5kV • Highly reliable vacuum circuit pre-engineering tests in
- 60Hz. • IEC 62271-100:2008 High-volt- breaker with superior breaking switchgear in plants guaran-
VE24 series is designed to age switchgear and control- capability. No maintenance tees interchangeability.
achieve control and protection gear – Part 100: Alternat- needed for key components. • Mechanical operation in
for medium voltage equipment ing-current circuit-breakers • The proven spring operating routine tests ensure the
and applications in industrial, mechanism provides stable stability of product perfor-
mining and utility industries. By Operating conditions performance and excellent mance.
adopting APG technology, the anti-corrosion performance,
encapsulated pole unit protects • Ambient temperature: -40°C therefore needing less
to +40°C maintenance within its life
the VI and other components of
the main circuit from physical • Ambient humidity: cycle.
Daily average relative
impact, dust and condensation, humidity: ≤95%
thereby making it ideal for Monthly average relative
operation less than ideal humidity: ≤90%
ambient conditions. The Daily average vapor
draw-out design equipped with pressure: ≤2.2×103Mpa
dedicated cassette is also Monthly average vapor
available. pressure: ≤1.8×103Mpa
• Altitude: <1000 m
• Seismic intensity: < Magni-
tude 8

1
VE24 vacuum circuit breaker
Product overview

Application areas • The main circuit is encapsu- Ideal for medium voltage
lated by epoxy resin, whereby control and protection in
• Chemical industry the current-carrying compo- medium voltage power supply
• Petroleum industry nents won’t be exposed to and distribution system
• Piping industry temperature fluctuations or
• Offshore mining • The VE24 is equipped with • The circuit breakers with
oxidization which can result in
• Shipbuilding superior spring charging electric charging operating
the deterioration of heat
• Paper manufacturing mechanism, utilizes modular mechanism have complemen-
dispersion.
• Opencast coal mine design that is offering tary spring charging motor,
• The main circuit is encapsu-
• Substation optimized mechanism main shunt release, trip free relay,
lated by epoxy resin, ensuring
• Cement industry parts distribution, simpler and auxiliary switch for spring
that the connecting compo-
• Automotive industry structure and more reliable charging motor release.
nents won’t loosen due to
• Power plant performance. The whole • The following accessories are
mechanical operations,
• Textile and food industries mechanism is composed by offered as needed: undervolt-
long-time use or temperature
• Metallurgical industry three modules: charging, age releases, overcurrent
changes, thus avoiding
closing, opening. Assembly relays, etc..
overheating issues.
and maintenance of these
• The number of components
three parts are very simple.
VE24 vacuum circuit breaker of the main circuit is only
The spring charging mecha-
requires almost no relevant 40-50% of that of composite
nism composed by ratchet
maintenance insulation type circuit
wheel mechanism, oscillator
breakers, which optimizes the
Simple structure design of VE24 and closing spring is compact
control of phase and polarity
series minimizes fault occur- and smart. The operating
spacing between the contact
rence, simplifies routine mechanism is usually
arms and tulip contacts and
maintenance. Positive indication equipped with manual
improves the contact head
charging device and electric
of the circuit breaker operating centering and contacting.
charging device, enabling
status is provided on the front • The heat dissipating compo-
automatic reclosing function.
panel of the circuit breaker for nents of the large current
• The circuit breakers with
easy visual verification. EPU use epoxy coating
manual charging operating
process to control insulation.
The encapsulated pole unit mechanism are equipped
Thus, larger heat dissipating
(EPU) used in VE24 series with manual opening and
components with a broader
circuit breakers ensures closing operation buttons,
radiating surface are used to
reliability in operation of breaking position indicator
improve heat dispersion.
vacuum interrupter (VI) and and spring mechanism
• The main circuit is encapsu-
other key components. The EPU charging status indicator,
lated by epoxy resin, so as to
switch operations counter,
of VE24 has following features: guard against the possibility
shunt release auxiliary switch,
• A vacuum interrupter with of small parts and other
position and fault signals,
lower contact resistance is foreign material left over from
etc..
used. Main circuit resistance the installation and commis-
is 10-20% lower than for sioning stage and provides
compound insulation, thus protection against the ingress
improves temperature rising of water during operation,
conditions from the heat thus preventing possible
source. short circuit or arcing events.
• The main circuit is protected
by EPU from dust accumula-
tion which can result in the
deterioration of heat dissipa-
tion.

Optional accessories

Charging handle Trolly handle Lifter

2
VE24 vacuum circuit breaker
Spring operating mechanism data

Spring operating mechanism data


Technical data of stored energy motor
Name Specification
Rated operating voltage (V) AC, DC110 AC, DC220
Motor rated input power (W) 65 (80 above 2500A) 65 (80 above 2500A)
Normal operating voltage range 85%-110% of rated operating voltage 85%-110% of rated operating voltage
Stored energy time at rated operating voltage (s) ≤ 15 ≤ 15

Technical data of closing coil


Name Specification
Rated operating voltage (V) AC, DC110 AC, DC220
Closing coil rated operating current (A) 2.0 1.0
Opening coil rated operating current (A) 1.8 0.9
Normal operating voltage range Closing: 80%-110% of rated operating voltage
Opening: 65%-120% of rated operating voltage. Will not open when below 30% rated operating voltage

3
VE24 vacuum circuit breaker
Technical data

VE24 vacuum circuit breaker technical data (for 210 mm distribution panel)
Name Unit Parameters

Rated voltage kV 24 24
Rated frequency Hz 50 50
Rated short-time power frequency withstand voltage (1 min) kV 65 (phase-to-ground, phase-to-phase); 79 (gap) 65 (phase-to-ground, phase-to-phase); 79 (gap)
Rated lightning impulse withstand voltage kV 125 (phase-to-ground, phase-to-phase); 145 (gap) 125 (phase-to-ground, phase-to-phase); 145 (gap)
Rated current A 630/1250 630/1250
Rated short-time withstand current (4s) kA 25 31.5
Rated peak withstand current kA 63 80
Rated short-circuit breaking current kA 25 31.5
Rated short-circuit making current kA 63 80
Rated short-circuit operating sequence O-0.3s-CO-180s-CO O-0.3s-CO-180s-CO
Conduction circuit resistance per phase μȍ ≤60 (630A) ≤50 (1,250A)
Average closing speed m/s 0.8~1.2 0.8~1.2
Average opening speed m/s 1.1~1.7 1.1~1.7
Closing time ms 35~70 35~70
Opening time ms 20~50 20~50
Contact closing bounce time ms ≤2 ≤2
Three phase opening/closing asynchronism ms ≤2 ≤2
Pole center distance mm 210 210
Permissible wear for movable and fixed contacts mm 3 3
Mechanical lifespan cycles 10000 10000

4
VE24 vacuum circuit breaker
Technical data

VE24 vacuum circuit breaker technical data (for 275mm distribution panel)
Name Unit Parameters

Rated voltage kV 24 24
Rated frequency Hz 50 50
Rated short-time power frequency withstand voltage (1 min) kV 65 (phase-to-ground, phase-to-phase); 79 (gap) 65 (phase-to-ground, phase-to-phase); 79 (gap)
Rated lightning impulse withstand voltage kV 125 (phase-to-ground, phase-to-phase); 145 (gap) 125 (phase-to-ground, phase-to-phase); 145 (gap)
Rated current A 630/1250 630/1250/1600/2000/2500/3150
Rated short-time withstand current (4s) kA 25 31.5
Rated peak withstand current kA 63 80
Rated short-circuit breaking current kA 25 31.5
Rated short-circuit making current kA 63 80
Rated short-circuit operating sequence O-0.3s-CO-180s-CO O-0.3s-CO-180s-CO
Conduction circuit resistance per phase μȍ ≤60 (630A) ≤50 (1,250A)
≤35 (1600-2,000A) ≤25 (above 2500A)
Average closing speed m/s 0.8~1.2 0.8~1.2
Average opening speed m/s 1.1~1.7 1.1~1.7
Closing time ms 35~70 35~70
Opening time ms 20~50 20~50
Contact closing bounce time ms ≤2 ≤2
Three phase opening/closing asynchronism ms ≤2 ≤2
Pole center distance mm 275 275
Permissible wear for movable and fixed contacts mm 3 3
Mechanical lifespan cycles 10000 10000

5
VE24 vacuum circuit breaker
Dimensions

VE24 vacuum circuit breaker dimensions

Eaton Power

Distribution panel Rated short-circuit breaking


width(mm) Rated current (A) current (kA) P A B C D F G J K N R S T

800 630 25 210 638 652 640 650 685 Ø35 325 745 737 655 277 40
800 630 31.5 210 638 652 640 650 705 Ø35 345 745 757 655 277 40
800 1250 25 210 638 652 640 650 685 Ø49 325 745 737 655 277 40
800 1250 31.5 210 638 652 640 650 705 Ø49 345 745 757 655 277 40
1000 630 25 275 838 852 840 850 685 Ø35 325 745 737 655 377 40
1000 630 31.5 275 838 852 840 850 705 Ø35 345 745 757 655 377 40
1000 1250 25 275 838 852 840 850 685 Ø49 325 745 737 655 377 40
1000 1250 31.5 275 838 852 840 850 705 Ø49 345 745 757 655 377 40
1000 1600~2000 31.5 275 838 852 840 850 705 Ø79 345 735 757 685 377 0
1000 2500~3150 31.5 275 838 852 840 850 781 Ø109 345 735 825 685 377 0

6
7
Motor circuit Closing circuit Locking circuit Opening circuit

Wiring diagram

VE24 vacuum circuit breaker wiring diagram


VE24 vacuum circuit breaker

Overcurrent trip (phase A) Overcurrent trip (phase C) Overcurrent trip (phase B)

S9: Auxiliary switch (when circuit breaker is in the service position) HQ: Closing coil
S8: Auxiliary switch (when circuit breaker is in the test position) TQ: Opening coil
S2: Auxiliary switch R0-R1: Resistance
S1: Auxiliary switch (switched on after the closing spring is charged) Y7-Y9: Indirect overcurrent release coil
QF: Auxiliary switch (switched during closing or opening operation) (optional)
Y1: Locking coil (optional)

V2-V4: Bridge rectifier (off for DC)


M: Spring charging motor
JP1-JP11: Jumper
K0: Anti-pumping relay (optional)

Note:
1. In the figure, the circuit breaker is in the test position, is open and is not storing energy.
2. For DC power supply, the polarities in the dash box should be consistent.
VE24 vacuum circuit breaker
VE24 vacuum circuit breaker selection guide

VE24 vacuum circuit breaker selection guide


Distribution panel width (mm) Breaker phase spacing (mm) Rated short-circuit breaking current (kA) Rated operating current (A)
800 210 25 □630 □1250
31.5 □630 □1250
1000 275 25 □630 □1250
31.5 □630 □1250 □1600 □2000 □2500 □3150

Spring operating mechanism parameters


Name Parameters

Opening power supply (V) □ DC110 □ AC110 □ DC220 □ AC220


Closing power supply (V) □ DC110 □ AC110 □ DC220 □ AC220
Stored energy motor power supply (V) □ DC110 □ AC110 □ DC220 □ AC220

Optional configurations (standard option includes trip free device. Please note if the trip free device has to been canceled)