You are on page 1of 1

CUSTOMER : M/S. FIRST ESCO INDIA PVT. LTD.

CHEEMA BOILERS LIMITED,


COIMBATORE - 641011 PROJECT : 37 TPH (MCR), 72 BAR(G), 510±5°C (SINGLE DRUM AFBC BOILER)

DOC No. : CB2261-BOILER-BUS-001 REV : NIL


BUSBAR SIZING CALCULATION FOR BOILER MCC PANEL
BOILER No. : CB2261 DATE : 20.07.2022

A) CONTINUOUS CURRENT RATING

BOILER MCC PANEL INCOMER RATING : 1600

SELECTED BUSBAR SIZE : 100x 10 x 2 - PHASE ALUMINIUM, 100 x 10 x 1 - NEUTRAL ALUMINIUM

SELECTED BUSBAR AREA : 2000Sq.mm

RATED CURRENT FOR ALUMINIUM = 1Amps / 1 Sq.mm

DERATING FACTOR FOR TEMP RISE = 0.8A

CURRENT CARRYING CAPACITY (I) = SELECTED BUSBAR AREA x DEAERATING FACTOR FOR TEMP RISE

= 2000 x 0.8

= 1600

THIS IS ABOVE BOILER MCC PANEL INCOMER RATING. HENCE THE SELECTED BUSBAR SIZE (100 x 10 x 2- PH & 100 x 10 x 1 - N) IS SUFFICIENT.

PREPARED AJAY CHECKED PARKASH

Page 1 of 1