You are on page 1of 1

5.

5.44
Ø31.62

140 140 150 140 L(Length of Insulators 420kN) 200 140 370-580 76 715
(2071~2281)+L ACSR Curlew

457
1 1 2 3 4 5 6 7 8 9 10

Note:
1.Minimum breaking load:380kN,except slip strength
of tension clamp 95% RTS of conductor;
2.The ball & socket size according to IEC 60120:28;
3.Galvanized to ASTM A153;
10 Tension Clamp NY-525/68 Al & Galv.steel 2 4.Insulators not covered in our supply;
5.All dimensions are in millimetres;
9 U Shackle AS-210 Galv.steel 2 210kN
8 Adjuster Plate 6.Marking on the fittings: Manufacturer logo (JD) & Product Type.
PT-21370-580A Galv.steel 2 210kN
7 Yoke Plate L-42J-140/457 Galv.steel 2 420kN Single Tension String
General Tolerance
6 Socket Clevis WSJ-42200 Galv.steel 1 420kN
Arcing Ring <=30 ±1.5mm ANGLE: Insulator Set 380kN for
5 FJY-60/700/300 Aluminium 1 中天
>30 ±5% ± 2×ACSR Curlew 中天科技
4 Arcing Horn ZH1-3826 Galv.steel 1
3 Ball Eye QS-42140 Galv.steel 1 420kN Weight ±15% (cota 4500~5200m) Brand JD-LinefitTM
2 Plate SZ-42J-150 Galv.steel 1 420kN Drawing Harvey 2023/04/10 Mass(kg) Scale NTS
Jiangsu Zhongtian
1 U Shackle U-42140 Galv.steel 2 420kN Checked Victor 2023/04/10
Technology Co., Ltd. JSH-XJ17720-12 REV E
Item Description Cat. No. Material Quantity U.T.S. Approved Rachal 2023/04/10