• Outdoor Units
Unit Mounting
• Package Units
Dimensions
• Tri-Capacity Units
Condensate and
Safety Tray • Split Ducted Indoor Units
Drainage (SRA SCA SRD SRV SRM Models)
Instructions • Tri-Capacity Split Ducted Indoor Units
(Indoor Unit)
(ELY EVY Models)
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
Installation Section 110308
Copyright © 2011 Actron Engineering Pty. Ltd.
UNIT WEIGHT DISTRIBUTION GUIDE
DISTRIBUTION GUIDE
TOP VIEW RM
RR RF
FAN FAN
CONDENSER COIL
LR LF
LM
SPLIT OUTDOOR UNIT
RM
RR RF
LR LF
LM
SPLIT INDOOR UNIT
RM
RR RF
COIL
EVAP. EVAP.
FAN FAN
COMPRESSOR
CONDENSER COIL
LR LF
LM
PACKAGE UNIT
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
WEIGHT DISTRIBUTION GUIDE - P1 - 100510
Copyright © 2010 Actron Engineering Pty. Ltd.
UNIT WEIGHT DISTRIBUTION GUIDE
DISTRIBUTION GUIDE
WEIGHT POINT DETAILS
CORNER WEIGHT
SPLIT DUCTED OUTDOOR - UNITS
WEIGHT DISTRIBUTION (1)
MODEL LF RF LR RR LM RM TOTAL WEIGHT
(kg) (kg) (kg) (kg) (kg) (kg)
SRE081C 28.0 30.0 18.0 7.0 --- --- 83.0
SRA101C 45.0 39.0 26.0 9.0 --- --- 119.0
SRA120C 45.0 39.0 27.0 9.0 --- --- 120.0
SRA121C 45.0 39.0 29.0 10.0 --- --- 123.0
SRD125C 52.0 45.0 29.0 10.0 --- --- 136.0
SRA140C 52.0 44.5 28.5 10.0 --- --- 135.0
SRA141C 53.0 45.0 29.0 10.0 --- --- 137.0
SRD151C 53.0 46.0 29.0 10.0 --- --- 138.0
SRA160C 50.0 55.0 33.0 7.0 --- --- 145.0
SRD160C 50.0 56.0 33.0 7.0 --- --- 146.0
SRA161C 50.0 56.0 33.0 7.0 --- --- 146.0
SRD175C 66.0 67.0 39.0 8.0 --- --- 180.0
SRA190C 58.5 71.0 34.5 11.0 --- --- 175.0
SRD190C 62.0 75.0 36.5 11.5 --- --- 185.0
SRA230C 73.2 63.4 26.8 17.9 7.1 11.6 200.0
SRD230C 80.5 69.7 29.5 19.6 7.9 12.8 220.0
SRA260C 76.0 81.3 22.5 16.0 24.6 24.6 245.0
SCA290C 90.0 84.1 23.2 33.8 30.9 28.0 290.0
SCA300C 105.6 90.1 33.2 23.7 17.8 29.6 300.0
SCA330C 100.5 100.5 37.0 25.4 17.3 24.3 305.0
SCA340C 107.8 103.1 33.7 43.0 23.7 23.7 335.0
SCA400C 109.7 103.6 33.5 45.0 24.1 24.1 340.0
PACKAGE UNITS
WEIGHT DISTRIBUTION *
MODEL LF RF LR RR LM RM TOTAL WEIGHT
(kg) (kg) (kg) (kg) (kg) (kg)
PCA140U 62.2 71.0 55.2 31.6 --- --- 220
PCA160U 72.9 67.8 50.1 44.2 --- --- 235
PCA190U 100.6 69.3 49.2 55.9 --- --- 275
PCA230U 99.1 68.7 31.5 52.5 24.8 33.4 310
PCA260U 93.4 71.8 35.4 27.5 49.2 77.7 355
PCA290U 120.8 126.6 67.2 53.6 37.0 44.8 450
PCA290S 120.8 126.6 67.2 53.6 37.0 44.8 450
PCA300U 139.7 147.7 44.0 40.6 44.0 44.0 460
PCA300S 142.9 150.9 44.9 41.5 44.9 44.9 470
PCA330U 142.9 150.9 44.9 41.5 44.9 44.9 470
PCA330S 151.8 134.1 54.3 46.6 46.6 46.6 480
PCA340U 149.5 129.3 52.4 62.0 53.4 53.4 500
PCA340S 149.5 129.3 52.4 62.0 53.4 53.4 500
PCA400U 162.7 152.4 51.8 45.6 51.8 45.6 510
PCA400S 162.7 152.4 51.8 45.6 51.8 45.6 510
NOTES:
1. See Unit Weight Distribution Guide drawing for details of weight point locations.
2. --- Indicates Not Applicable.
3. Refer details of Tri-Capacity models corner weight to particular catalogue unit dimensions page. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
WEIGHT DISTRIBUTION GUIDE - P2 - 100721
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
UNIT MOUNTING DIMENSIONS
OUTDOOR UNITS - SRE SRA SRD SCA MODELS
“ A “"A"
CTRS
PLAN VIEW
Detail X
“ B1 “
"B1"
CTRS “"B2"
B2 “ 25
CTRS
“E“
"E" “D“
"D" “C“
"C" “D“ “E“
"E" "D" Ø15
MOUNTING DIMENSION
MODEL A B1 B2 C D E
PLAN VIEW
"“ A “" CTRS
CTRS
Detail X
Detail X
"“ B “"
CTRS
CTRS 25
COMPRESSOR
"E"
“E“ "D"
“D“ "“ C “" "D"
“D“ "E"
“E“ Ø15
MODEL A B C D E
Detail X
Detail X G
COMPRESSOR 1
“"C"
C“
CTRS
CTRS
Ø15
COMPRESSOR 2
(if 2 Stage)
"F"
“F“ "E"
“E“ "D"
“D“ "E"
“E“ "D"
“D“ "E"
“E“ "F"
“F“
MODEL A B C D E F G
SRA230C SRD230C SRA260C 673.5 673.5 616.0 555.5 118.0 110.0 25.0
NOTES:
1. ALL DIMENSIONS ARE IN MM. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice, Please check prior to purchase. MTG DIM OUTDOOR - 100916
®
"A" CTRS
PLAN VIEW
Detail X
CONDENSER SECTION
Detail X
MOUNTING DIMENSION
COMPRESSOR
"B"
CTRS
25
Ø15
EVAPORATOR SECTION
MODEL A B C D E
PLAN VIEW
"B" CTRS "A" CTRS
Detail X
CONDENSER SECTION
COMPRESSOR 1 Detail X
G
"C"
CTRS COMPRESSOR 2 (if 2 Stage)
Ø15
EVAPORATOR SECTION
MODEL A B C D E F G
NOTES:
1. ALL DIMENSIONS ARE IN MM. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice, Please check prior to purchase. MTG DIM PACKAGE - 100506
®
MOUNTING DIMENSION
30 (MTG C-C DIST 1115) (MTG C-C DIST 1115) 30 40 (MTG C-C DIST 1115) 40
33 33
65 785 524 785 65
65
1065
65
MODELS
PACKAGE UNIT
40.5 (MTG C-C DISTANCE 1127) (MTG C-C DISTANCE 1127) 40.5 30 (MTG C-C DIST 1115) (MTG C-C DIST 1115) 30
65 1066 45 1094 65
65
785
33
NOTES:
524
MODELS
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice, Please check prior to purchase.
®
MTG DIM TRI-CAPACITY - 100608
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
SERVICE AREA & AIRFLOW SPACES
SPLIT DUCTED UNITS
B D (ELECTRICAL BOX /
PIPING END)
(ELECTRICAL BOX /
PIPING END)
A
A D
MODEL SRA140E SHOWN
AIRFLOW CLEARANCES
DUCT DUCT
SRA190E SRD190E SRV190E SRM190E 800 800 410 800
WORK WORK
SERVICE AREAS
DUCT DUCT
SRA230E SRV230E SRM230E SRA260E 890 890 410 890
WORK WORK
DUCT DUCT
SCA290E SCA300E SCA330E SCA340E SCA400E 1200 1200 430 1200
WORK WORK
* Space Clearance “B” can be 10mm minimum if Space Clearance “D” is applicable. ALL DIMENSIONS ARE IN mm
** Space Clearance “D” can be 600mm minimum if Space Clearance “B” is applicable. DO NOT SCALE DRAWING.
*** Space Clearance “E” can be 10mm minimum if Space Clearance “D” is applicable.
(COMPRESSOR END)
(OUTDOOR COIL SIDE)
A A
(OUTDOOR COIL SIDE) D
MODEL SRA140C SHOWN
SRD160C SRD175C SRA190C SRD190C 400 300 NIL 600 1500 600
SCA290C SCA300C SCA330C SCA340C SCA400C 750 300 NIL 800 1500 1000
* Space Clearance “A” is applicable provided walkway passage is available on either “B” or “D” side ALL DIMENSIONS ARE IN mm
DO NOT SCALE DRAWING.
to allow coil replacement without lifting coil over the top of condensing unit.
NOTES:
1. Minimum service access areas and spaces for airf ow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airf ow.
2. Suggested minimum clearance for fan discharge side. Clearance should be free from any obstructions from
sides to allow proper air circulation. ®
R
3. Refer Tri-Capacity units service area & airf ow spaces to corresponding unit dimensional drawing.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
Gen. Info. Acess/Airf ow 100916
Copyright © 2010 Actron Engineering Pty. Ltd.
SERVICE AREAS & AIRFLOW SPACES
PACKAGE UNITS
C
PLAN VIEW (OUTDOOR COIL SIDE)
CONDENSER COIL
(COMPRESSOR END)
COMPRESSOR
B D
EVAP. EVAP.
FAN FAN
COIL
A
AIRFLOW CLEARANCES
See Note 2.
E
SERVICE AREAS
ISOMETRIC VIEW
C
D
(OUTDOOR COIL SIDE)
B A
PCA140U MODEL SHOWN
DUCT
PCA140U PCA160U PCA200U 600 300 300 1500 600
WORK
DUCT
PCA230U PCA260U 800 600 300 1500 1000
WORK
* Space Clearance “C” is applicable provided walkway passage is available on either “B” or “D” side ALL DIMENSIONS ARE IN mm
to allow coil replacement without lifting coil over the top of the unit. DO NOT SCALE DRAWING.
NOTES:
1. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
2. Suggested minimum clearance for fan discharge side. Clearance should be free from any obstructions from ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
GI SERV PACKAGE - 100512
Copyright © 2010 Actron Engineering Pty. Ltd.
SERVICE AREAS & AIRFLOW SPACES
HORIZONTAL DISCHARGE OUTDOOR UNITS
See Note 2.
PLAN VIEW C
(COMPRESSOR END)
CONDENSER FANS
B COMP.
D
CONDENSER COIL
AIRFLOW CLEARANCES
SRA120C-H SRA121C-H
SRA140C-H SRA141C-H
SERVICE AREAS
SRA160C-H SRA161C-H 300 300 1500 600 300 600
SRA190C-H
SRD151C-H SRD175C-H
* Space Clearance “A” is applicable provided walkway passage is available on either “B” or “D” side ALL DIMENSIONS ARE IN mm
DO NOT SCALE DRAWING.
to allow coil replacement without lifting coil over the top of condensing unit.
See Note 2.
PLAN VIEW C
B COMP.
D
CONDENSER COIL
SRA230C - H SRA260C - H
600 300 1500 800 300 1000
SRD190C - H SRD230C - H
* Space Clearance “A” is applicable provided walkway passage is available on either “B” or “D” side ALL DIMENSIONS ARE IN mm
to allow coil replacement without lifting coil over the top of condensing unit. DO NOT SCALE DRAWING.
NOTES:
1. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
2. Suggested minimum clearance for fan discharge side. Clearance should be free from any obstructions from
sides and top to allow proper air circulation.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SERV SRA120-230C-H - 100510
Copyright © 2010 Actron Engineering Pty. Ltd.
SERVICE AREAS & AIRFLOW SPACES
ESP VERTICAL PACKAGE UNITS
PLAN VIEW
PLAN VIEW C (CONDENSER COIL SIDE)
DEPTH
B D
(COMPRESSOR END)
A
MODEL VARIATION SERIES SHOWN:
XA & HXA
WIDTH
ISOMETRIC VIEW
X Series R Series
XA & HXA SERIES RA & HRA SERIES
B D
A
MODEL VARIATION SERIES SHOWN:
RA & HRA
XA & HXA
SIDE BY SIDE
MODEL A B C D E STACKING OF UNITS
WIDTH DEPTH
(HEIGHT CLEARANCE) (DISTANCE BETWEEN B & D)
PMD120R & PMD120HR SERIES 3200 --- --- --- DUCT WORK 1200 825 ---
PMD160R & PMD160HR SERIES 3200 --- --- --- DUCT WORK 1400 870 ---
PMD160X SERIES 3200 200 200 600 DUCT WORK 1400 870 600
PMD190HR SERIES 3200 --- --- --- DUCT WORK 1600 1078 ---
PMD190HX SERIES 3200 200 200 600 DUCT WORK 1600 1078 600
NOTES:
1. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
2. Suggested minimum clearances should be free from any obstructions to allow proper air circulation.
3. Airflow space “B” and service access “D” for X & HX Series are interchangeable, depending on the location of
electrical cable access point.
4. “C” will be DUCT WORK clearance for “E” & “F” Series variations.
5. For units fitted with Surge Protection Device, leave minimum 600mm clearance on transformer access side,
depending on the handing of the unit. Please check prior to purchase.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SERV MINING - 100831
Copyright © 2010 Actron Engineering Pty. Ltd.
SERVICE AREA & AIRFLOW SPACES FOR MULITPLE UNITS
PKY470T-6Q1 PKY540T-6Q1 PKY620T-6Q1 PKY700T-6Q1
END-TO-END CONFIGURATION
UNIT 1 UNIT 2
DUCT 1000 mm DUCT 1000 mm
WORK FILTER WORK FILTER 500 mm
ACCESS DUCT ACCESS DUCT AIRFLOW ALLOWANCE
WORK WORK
AIRFLOW ALLOWANCE
UNIT 1 OUTDOOR COIL
1000 mm
SERVICE
OUTDOOR COIL
INDOOR COIL
INDOOR COIL
500 mm
CLEARANCE
UNIT 1 PLUG
FAN (PLUG FAN)
UNIT 2 PLUG
FAN UNIT 2 & 3
+ 1000 mm
SERVICE
AIRFLOW ALLOWANCE
UNIT 1 CLEARANCE
1000 mm (PLUG FAN)
SERVICE +
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
500 mm
CLUSTER CONFIGURATION
UNIT 1 UNIT 1
1000 mm 1000 mm
SERVICE SERVICE
CLEARANCE CLEARANCE 500 mm 500 mm
(PLUG FAN) (COMP. & ELEC.) AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE
WORK
DUCT
UNIT 2
OUTDOOR COIL
PLUG
1000 mm
AIRFLOW ALLOWANCE
FAN
SERVICE
UNIT 2
UNIT 2 & UNIT 3
CLEARANCE
OUTDOOR COIL
1000 mm
ACCESS
500 mm
1000 mm
+ ACCESS
FILTER
UNIT 3
UNIT 1
UNIT 1
WORK
PLUG
UNIT 2
DUCT
WORK
PLUG
DUCT
OUTDOOR COIL
NOTES :
1. Service Clearance and Airf ow Allowances given above are suggested minimum based on the condition that
the spaces around the units are free from any obstractions and walkway passage of 1000mm between the units
or between the unit and the outside perimeter is available.
2. Minimum service access areas and spaces for airf ow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airf ow.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
Tri-Capacity PKY Multi-Unit Serv. Areas 100901
Copyright © 2010 Actron Engineering Pty. Ltd. Page 1
SERVICE AREA & AIRFLOW SPACES FOR MULITPLE UNITS
PKY470T-6Q1 PKY540T-6Q1 PKY620T-6Q1 PKY700T-6Q1
SIDE-BY-SIDE CONFIGURATION
OUTDOOR COIL
WORK
WORK
DUCT
DUCT
WORK
DUCT
PLUG PLUG
AIRFLOW ALLOWANCE
FAN FAN UNIT 3
UNIT 2
1000 mm
ACCESS
OUTDOOR COIL
FILTER
UNIT 1
500 mm
1000 mm
1000 mm
ACCESS
FILTER
UNIT 3
INDOOR COIL FILTER INDOOR COIL INDOOR COIL
ACCESS
500mm AIRFLOW ALLOWANCE
AIRFLOW
UNIT 1 UNIT 2
WORK
WORK
DUCT
DUCT
WORK
PLUG
DUCT
FAN
UNIT 3 UNIT 3
500 mm 500 mm 1000 mm 1000 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE SERVICE SERVICE
CLEARANCE CLEARANCE
(PLUG FAN) (COMP. & ELEC.)
UNIT 1 UNIT 1
1000 mm DUCT 1000 mm
DUCT
FILTER WORK FILTER
WORK
ACCESS DUCT ACCESS DUCT
WORK WORK
SPACE CLEARANCE
SPACE CLEARANCE
300 mm
300 mm
INDOOR COIL
INDOOR COIL
UNIT 2
AIRFLOW ALLOWANCE
+
CLEARANCE
(COMP. & ELEC.)
(COMP. & ELEC.)
500 mm
+
UNIT 2
OUTDOOR COIL
AIRFLOW OUTDOOR COIL
ALLOWANCE
500 mm 500 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE
* For Reverse Handing, service clearance for Plug Fan and airf ow clearance for Hood will be reversed. HEIGHT CLEARANCE FOR ALL THE UNITS = 1500mm
** Remove Optional Hood when service is required for the Plug Fan of the opposite unit.
*** Conf guration shown above is a sample only of the many possibilities of unit banking conf gurations with
Optional Hood application. Provide a 300mm Space Clearance for the Optional Hood as shown.
NOTES :
1. Service Clearance and Airf ow Allowances given above are suggested minimum based on the condition that
the spaces around the units are free from any obstractions and walkway passage of 1000mm between the units
or between the unit and the outside perimeter is available.
2. Minimum service access areas and spaces for airf ow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airf ow.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
Tri-Capacity PKY Multi-Unit Serv. Areas 100901
Copyright © 2010 Actron Engineering Pty. Ltd. Page 2
SERVICE AREA & AIRFLOW SPACES FOR MULITPLE UNITS
PKY820T-3Q1 PKY960T-3Q1
END-TO-END CONFIGURATION
OUTDOOR COIL
1000 mm
AIRFLOW ALLOWANCE
SERVICE
INDOOR COIL
INDOOR COIL
PLUG CLEARANCE PLUG
UNIT 1 FAN (PLUG FAN)
UNIT 2 FAN UNIT 2 & 3
500 mm
+ 1000 mm
SERVICE
UNIT 1 CLEARANCE
1000 mm (PLUG FAN)
SERVICE +
AIRFLOW ALLOWANCE
INDOOR COIL
(COMP. & ELEC.)
OUTDOOR COIL
OUTDOOR COIL
ELEC.) PLUG
UNIT 3
500 mm
FAN
+
UNIT 2
AIRFLOW
ALLOWANCE
OUTDOOR COIL OUTDOOR COIL OUTDOOR COIL OUTDOOR COIL
CLUSTER CONFIGURATION
UNIT 1 UNIT 1
1000 mm 1000 mm
SERVICE SERVICE
CLEARANCE CLEARANCE 500 mm 500 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE
(PLUG FAN) (COMP. & ELEC.)
AIRFLOW ALLOWANCE
OUTDOOR COIL
1000 mm
WORK
WORK
DUCT
DUCT
OUTDOOR COIL
PLUG SERVICE
FAN
CLEARANCE UNIT 3
500 mm
(COMP. &
ELEC.)
1000 mm
1000 mm
ACCESS
ACCESS
FILTER
FILTER
UNIT 1
UNIT 3
INDOOR COIL
+
INDOOR COIL
(PLUG FAN)
OUTDOOR COIL
OUTDOOR COIL
+
WORK
WORK
UNIT 1
DUCT
DUCT
PLUG
UNIT 1
INDOOR COIL
FAN
UNIT 2 & UNIT 3
AIRFLOW
PLUG
OUTDOOR COIL ALLOWANCE FAN UNIT 2
UNIT 3 UNIT 3
500 mm
AIRFLOW ALLOWANCE 1000 mm 1000 mm
SERVICE SERVICE
CLEARANCE CLEARANCE
(COMP. & ELEC.) (PLUG FAN)
DUCT UNIT 2
WORK 1000 mm
FILTER DUCT HEIGHT CLEARANCE FOR ALL THE UNITS = 1500mm
ACCESS WORK
NOTES :
1. Service Clearance and Airflow Allowances given above are suggested minimum based on the condition that
the spaces around the units are free from any obstractions and a walkway passage of 1000mm between the units
or between the unit and the outside perimeter is available.
2. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
3. Do not scale drawing.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
PKY820T - 960T Multi-Unit Serv. Areas 100927
Copyright © 2010 Actron Engineering Pty. Ltd. Page 1
SERVICE AREA & AIRFLOW SPACES FOR MULITPLE UNITS
PKY820T-3Q1 PKY960T-3Q1
SIDE-BY-SIDE CONFIGURATION
500 mm
(PLUG FAN) (COMP. & ELEC.) (PLUG FAN) (COMP. & ELEC.)
OUTDOOR COIL
AIRFLOW ALLOWANCE
OUTDOOR COIL
OUTDOOR COIL
WORK
WORK
WORK
DUCT
DUCT
DUCT
OUTDOOR COIL
PLUG PLUG
FAN FAN
UNIT 3
500 mm
1000 mm
1000 mm
1000 mm
ACCESS
ACCESS
ACCESS
FILTER
FILTER
FILTER
UNIT 1
UNIT 3
INDOOR COIL INDOOR COIL INDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
WORK
WORK
WORK
UNIT 1 UNIT 2
DUCT
DUCT
DUCT
PLUG
UNIT 3 UNIT 3
500 mm 500 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE 1000 mm 1000 mm
SERVICE SERVICE
CLEARANCE CLEARANCE
(COMP. & ELEC.) (PLUG FAN)
SPACE CLEARANCE
300 mm *
300 mm *
INDOOR COIL
INDOOR COIL
OPTIONAL OPTIONAL
HOOD
UNIT 1 PLUG
FAN HOOD **
UNIT 2 PLUG
FAN UNIT 2
1000mm
SERVICE
CLEARANCE
(COMP. &
UNIT 1 ELEC.)
AIRFLOW ALLOWANCE
1000mm
SERVICE +
OUTDOOR COIL
OUTDOOR COIL
(PLUG FAN *
COMP. & ELEC.)
+
OUTDOOR COIL OUTDOOR COIL UNIT 2 OUTDOOR COIL OUTDOOR COIL
AIRFLOW
500 mm ALLOWANCE 500 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE
* For Reverse Handing, Plug Fan service clearance and Optional Hood space clearance will be reversed.
** Remove Optional Hood when service is required for the Plug Fan of the opposite unit.
*** Configuration shown above is a sample only of the many possibilities of unit banking configurations with
Optional Hood application. Provide a 300mm Space Clearance for the Optional Hood as shown.
NOTES :
1. Service Clearance and Airflow Allowances given above are suggested minimum based on the condition that
the spaces around the units are free from any obstractions and a walkway passage of 1000mm between the units
or between the unit and the outside perimeter is available.
2. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
3. Do not scale drawing.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
PKY820T - 960T Multi-Unit Serv. Areas 100927
Copyright © 2010 Actron Engineering Pty. Ltd. Page 2
SERVICE AREA & AIRFLOW SPACES FOR MULITPLE UNITS
CAY470T-6Q1 CAY540T-6Q1 CAY620T-6Q1 CAY700T-6Q1
END-TO-END CONFIGURATION
500 mm
AIRFLOW ALLOWANCE
300 mm 300 mm
SPACE CLEARANCE SPACE CLEARANCE
AIRFLOW ALLOWANCE
UNIT 1
AIRFLOW ALLOWANCE
UNIT 1 1000 mm UNIT 2 UNIT 2 & UNIT 3
OUTDOOR COIL OUTDOOR COIL
SERVICE
1000 mm
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
CLEARANCE
500 mm
500 mm
(COMP. & ELEC.) SERVICE
+ CLEARANCE
UNIT 2 (COMP. & ELEC.)
OUTDOOR COIL OUTDOOR COIL AIRFLOW OUTDOOR COIL OUTDOOR COIL UNIT 3
ALLOWANCE
300 mm
SPACE CLEARANCE
500 mm 500 mm
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE
CLUSTER CONFIGURATION
UNIT 1
1000 mm
SERVICE
CLEARANCE 500 mm
(COMP. & ELECT.) 300 mm AIRFLOW ALLOWANCE
SPACE CLEARANCE
UNIT 2
AIRFLOW ALLOWANCE
UNIT 2 1000 mm
OUTDOOR COIL
OUTDOOR COIL
SERVICE
OUTDOOR COIL
OUTDOOR COIL
CLEARANCE
500 mm
SPACE CLEARANCE
SPACE CLEARANCE
(COMP. & ELEC.)
+
UNIT 3
UNIT 1
300 mm
300 mm
UNIT 3
OUTDOOR COIL OUTDOOR COIL
AIRFLOW
ALLOWANCE
OUTDOOR COIL
OUTDOOR COIL
500 mm
AIRFLOW ALLOWANCE
OUTDOOR COIL
500 mm UNIT 3
AIRFLOW ALLOWANCE 1000 mm
SERVICE
CLEARANCE
(COMP. & ELECT.)
SIDE-BY-SIDE CONFIGURATION
UNIT 3
1000 mm
500 mm 500 mm SERVICE
AIRFLOW ALLOWANCE AIRFLOW ALLOWANCE CLEARANCE
(COMP. & ELECT.)
OUTDOOR COIL
SPACE CLEARANCE
UNIT 1
UNIT 2
UNIT 3
300 mm
UNIT 1
UNIT 2
UNIT 3
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
UNIT 1 UNIT 2
1000 mm 1000 mm 500 mm
SERVICE SERVICE AIRFLOW ALLOWANCE
CLEARANCE CLEARANCE
(COMP. & ELECT.) (COMP. & ELECT.) HEIGHT CLEARANCE FOR ALL THE UNITS = 1500mm
NOTES :
1. Service Clearance and Airf ow Allowances given above are suggested minimum based on the condition that
the spaces around the units are free from any obstractions and walkway passage of 1000mm between the units
or between the unit and the outside perimeter is available.
2. Minimum service access areas and spaces for airf ow are responsibilities of the installer, ®
R
ActronAir® will not be held responsible for any extra charges incurred due to lack of access and space for airf ow.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specif cations are subject to change without notice. Please check prior to purchase.
®
Tri-Capacity CAY Multi-Unit Serv. Areas 100901
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
CONDENSATE AND SAFETY TRAY DRAINAGE INSTRUCTIONS
SPLIT DUCTED INDOOR UNITS - 190 MODELS AND BELOW
SUGGESTED MINIMUM SLOPE TO ENSURE CORRECT DRAINAGE
RETURN AIR
CONDENSATE DRAIN
INDOOR COIL
CONNECTION
INTERNAL CONDENSATE TRAY
CONDENSATE DRAINAGE
SAFETY TRAY DRAIN
DIAGRAM
SUPPLY AIR CONNECTION
INSTALL A T-PIECE AS AN
AIR VENT FOR LONG DRAIN RUNS.
NOTES:
1. REFER TO UNIT DIMENSIONS PAGE OF THE TECHNICAL CATALOGUE FOR
SPECIFICATIONS OF DRAIN CONNECTORS.
®
R
2. STANDARD SPLIT DUCTED MODEL SHOWN. CONDENSATE DRAINAGE
INSTRUCTIONS ALSO APPLICABLE TO ESP, ESP PLUS AND ULTIMA MODELS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
DF DRAIN 100505
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
CONDENSATE AND SAFETY TRAY DRAINAGE INSTRUCTIONS
SPLIT DUCTED INDOOR UNITS - ABOVE 190 MODELS
25mm 15mm
FRONT VIEW
"A"
SIDE VIEW
RETURN AIR
CONDENSATE DRAIN
CONNECTION
INDOOR COIL
CONDENSATE DRAINAGE
FAN COIL AT A MINIMUM
OF 10MM PER METRE
TOP VIEW
DIAGRAM
SUGGESTED DRAIN TRAP DETAILS
50mm
150mm
CONDENSATE CLEAR OR HIGH ENOUGH TO
DRAIN PLASTIC MAINTAIN POSITIVE AIR SEAL
CONNECTION INSPECTION
TUBE
4 x P.V.C INSTALL A T-PIECE
ELBOW AS AN AIR VENT
TRAP FOR LONG DRAIN RUNS
DETAIL - “A”
NOTES:
1. REFER TO UNIT DIMENSIONS PAGE OF THE TECHNICAL CATALOGUE FOR
SPECIFICATIONS OF DRAIN CONNECTORS.
2. LOW PROFILE (ELY) TRI-CAPACITY MODEL SHOWN. CONDENSATE
DRAINAGE INSTRUCTIONS ALSO APPLICABLE TO STANDARD PROFILE
(CAY, SRA & SCA) AND MODELS.
3. PARTS FOR THE CONDENSATE TRAP ARE NOT SUPPLIED WITH THE UNIT. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
DF DRAIN TRI-CAPACITY 100525
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
CONDENSATE AND SAFETY TRAY DRAINAGE INSTRUCTIONS
PKY470T-6Q1 PKY540T-6Q1 PKY620T-6Q1 PKY700T-6Q1
SUGGESTED MINIMUM SLOPE TO ENSURE CORRECT DRAINAGE
TOP VIEW
SIDE VIEW
CONDENSATE DRAINAGE
FRONT VIEW "A"
DIAGRAM
SEAL WITH
SILICONE
ENSURE DRAIN PIPE SEALANT
SLOPE DOWN FROM THE
UNIT AT A MINIMUM
OF 10MM PER METRE
CLAMP
BANDS
50mm
150mm
CONDENSATE CLEAR OR HIGH ENOUGH TO
DRAIN PLASTIC MAINTAIN POSITIVE AIR SEAL
CONNECTION INSPECTION
TUBE
4 x P.V.C INSTALL A T-PIECE
ELBOW AS AN AIR VENT
TRAP FOR LONG DRAIN RUNS
DETAIL - "A"
NOTES:
1. REFER TO UNIT DIMENSIONS PAGE OF THE TECHNICAL CATALOGUE FOR
SPECIFICATIONS OF DRAIN CONNECTORS. ®
R
2. PARTS FOR THE CONDENSATE TRAP ARE NOT SUPPLIED WITH THE UNIT.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
DF DRAIN TRI-CAPACITY PACKAGE 101018
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
CONDENSATE AND SAFETY TRAY DRAINAGE INSTRUCTIONS
PKY820T-3Q1 PKY900T-3Q1
CONDENSER DRAIN
MUST BE RUN
SEPERATELY FROM THE
EVAPORATOR DRAIN MUST BE
EVAPORATOR DRAIN RETURN RUN SEPERATLY FROM THE
AIR CONDENSER DRAIN
TOP VIEW
SIDE VIEW
CONDENSATE DRAINAGE
DIAGRAM
"A"
FRONT VIEW
SEAL WITH
SILICONE
SEALANT
CLAMP
BANDS
50mm
150mm
CONDENSATE CLEAR OR HIGH ENOUGH TO
DRAIN PLASTIC MAINTAIN POSITIVE AIR SEAL
CONNECTION INSPECTION
TUBE
4 x P.V.C INSTALL A T-PIECE
ELBOW AS AN AIR VENT
TRAP FOR LONG DRAIN RUNS
DETAIL - "A"
NOTE:
1. Parts for the condensate trap are not supplied with the unit. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®
DF DRAIN PKY820T-PKY900T-3Q1
Copyright © 2011 Actron Engineering Pty. Ltd. All rights reserved. 110628
THIS PAGE WAS INTENTIONALLY LEFT BLANK
INSTALLATION GUIDE
SRE091C SRA101C SRA121C SRA141C SRA161C
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SRE091C SRA101C SRA121C SRA141C SRA161C
REFRIGERANT TYPE R-410A
R-410A R-410A R-410A R-410A
REFRIGERANT CHARGE grams 3175 **
4000 4500 5300 6500 * Included in Maximum Field Pipe Length.
PRE-CHARGED LENGTH m 0 10 20 20 20
ADDITIONAL REFRIGERANT /m grams 50 50 50 50 50 ** SRE091C is NOT pre-charged with
MAX. EQUIV. PIPE LENGTH RANGE m 0 - 25
0 - 60 0 - 60 0 - 60 0 - 60 refrigerant. ADD Base Charge of 3175
MAX. VERTICAL HEIGHT DIFF. * m 20 20 20 20 20 grams in the field, this excludes
LIQ. In(mm) 3/8 (9.5)
3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) additional refrigerant charge for the
FIELD PIPE SIZING field pipe length more than 10m.
GAS In.(mm) 5/8 (15.9)
5/8 (15.9) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Additional 50 grams per meter of pipe
LIQ. In(mm) 3/8 (9.5)**** length is required.
swaged swaged swaged swaged
OUTDOOR UNIT CONNECTION
5/8 (15.9) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
GAS In.(mm) *** Swaged End to be cut-off in the field to
swaged swaged *** swaged swaged swaged
fit field pipe.
3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
LIQ. In(mm)
swaged swaged swaged swaged swaged **** Factory fitted with Schrader valve.
INDOOR UNIT CONNECTION
5/8 (15.9) 5/8 (15.9) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) To be cut-off and swaged in the field
GAS In.(mm)
swaged swaged swaged swaged swaged to fit field pipe.
CLOSED
5) REFRIGERANT CHARGE
5.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
5.2 Check operating pressures and temperatures, if required adjust charge.
5.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD083 111011
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SRA120C SRA140C SRA160C SRA190C
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SRA120C SRA140C SRA160C SRA190C
REFRIGERANT TYPE R-410A R-410A R-410A R410A
REFRIGERANT CHARGE grams 4900 5400 6400 6950
PRE-CHARGED LENGTH m 20 20 20 15
ADDITIONAL REFRIGERANT /m grams 50 50 50 50 100
MAX. FIELD PIPE LENGTH RANGE m 0 - 60 0 - 60 0 - 60 0 - 20 20 - 60
MAX. VERTICAL HEIGHT DIFF. * m 20 20 20 20
LIQ. In(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 1/2 (12.7) ***
FIELD PIPE SIZING
GAS In.(mm) 3/4 (19.05) 3/4 (19.05) 3/4 (19.05) 7/8 (22.22) 7/8 (22.22)
3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
LIQ. In(mm)
swaged swaged swaged swaged swaged ****
OUTDOOR UNIT CONNECTION
3/4 (19.05) 3/4 (19.05) 3/4 (19.05) 7/8 (22.22) 7/8 (22.22)
GAS In.(mm)
swaged swaged swaged swaged swaged
3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
LIQ. In(mm)
swaged swaged swaged swaged swaged ****
INDOOR UNIT CONNECTION
3/4 (19.05) 3/4 (19.05) 3/4 (19.05) 7/8 (22.22) 7/8 (22.22)
GAS In.(mm)
swaged swaged swaged swaged swaged
* Included in Maximum Field Pipe Length. *** Run 1/2” (12.7mm) field pipe the whole distance.
**** Swaged End to be cut-off in the field to fit field pipe.
5) REFRIGERANT CHARGE
5.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
5.2 Check operating pressures and temperatures, if required adjust charge.
5.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
MUST BE INSTALLED BY A
ELECTRICAL SAFETY REGULATIONS 2002
LICENSED ELECTRICIAN
6.1 Make sure all wiring is in accordance with local electricity authority wiring regulations. This refers to electrical works only
6.2 Check indoor fan amps DO NOT EXCEED rated amps (see indoor rating label).
6.3 THREE PHASE MODEL A) Check all three phases have 415 Volts (-6% to +10%) between all phases.
B) Check all single phases have 240 Volts (-6% to +10%) between active to neutral.
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No.,
then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD070 110419
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SRA230C SRA260C
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SRA230C ** SRA260C **
REFRIGERANT TYPE R410A R-410A
REFRIGERANT CHARGE grams 8050 10100
PRE-CHARGED LENGTH m 10 10
ADDITIONAL REFRIGERANT /m grams 100 100
MAX. FIELD PIPE LENGTH RANGE m 0 - 60 0 - 60
MAX. VERTICAL HEIGHT DIFF. * m 20 20
LIQ. In(mm) 1/2 (12.7) 5/8 (15.9)
FIELD PIPE SIZING
GAS In.(mm) 1 (25.4) 1 (25.4)
1/2 (12.7) 5/8 (15.9)
LIQ. In(mm)
swaged swaged
OUTDOOR UNIT CONNECTION
7/8 (22.2) swaged 1-1/8 (28.6) ID to
GAS In.(mm)
to fit 1 (25.4) fit field pipe
1/2 (12.7) 5/8 (15.9)
LIQ. In.(mm)
swaged swaged
INDOOR UNIT CONNECTION
1 (25.4) swage in 1 (25.4)
GAS In.(mm)
field to fit 1 (25.4) swaged
* Included in Maximum Field Pipe Length. ** Crankcase Heater is to be disconnected for pipe lengths 8m or less.
5) REFRIGERANT CHARGE
5.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
5.2 Check operating pressures and temperatures, if required adjust charge.
5.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
MUST BE INSTALLED BY A
ELECTRICAL SAFETY REGULATIONS 2002
LICENSED ELECTRICIAN
6.1 Make sure all wiring is in accordance with local electricity authority wiring regulations. This refers to electrical works only
6.2 Check indoor fan amps DO NOT EXCEED rated amps (see indoor rating label).
6.3 THREE PHASE MODEL A) Check all three phases have 400 Volts (-6% to +10%) between all phases.
B) Check all single phases have 230 Volts (-6% to +10%) between active to neutral.
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No.,
then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD087 110823
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SRD125C SRD151C
● ACTRONAIR ESP R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
This ESP air-conditioner is fitted with the latest MODEL SRD125C SRD151C
PERFECT-TEMP logic and digital scroll compressor REFRIGERANT TYPE R-410A R-410A
technology that provides superior comfort control REFRIGERANT CHARGE grams 5,400 5,000
and highier seasonal energy efficiencies. PRE-CHARGED LENGTH m 20 20
ADDITIONAL REFRIGERANT /m grams 50 50
1) ESP OPERATION MAX. EQUIV. PIPE LENGTH RANGE m 0 - 60 0 - 60
1.1 Modulation / Capacity range is 10 - 100%. MAX. VERTICAL HEIGHT DIFF. * m 20 20
1.2 When running at 100% capacity the compressor LIQ. In(mm) 3/8 (9.52) 3/8 (9.52)
FIELD PIPE SIZING
operation is the same as standard Copeland scroll GAS In.(mm) 3/4 (19.05) 3/4 (19.05)
compressors. 3/8 (9.52) 3/8 (9.52)
1.3 The compressor modulates when full capacity is LIQ. In(mm)
swaged swaged
not required. OUTDOOR UNIT CONNECTION
3/4 (19.05) 3/4 (19.05)
1.4 When modulating, the compressor operates in GAS In.(mm)
swaged swaged
the loaded and unloaded states. The modulation
3/8 (9.52) 3/8 (9.52)
is controlled by the PWM valve, which makes a LIQ. In(mm)
swaged swaged
clicking sound whilst operating. INDOOR UNIT CONNECTION
1.5 During modulation, it is normal for the discharge 3/4 (19.05) 3/4 (19.05)
GAS In.(mm)
and suction pressures to increase and decrease. swaged swaged
* Included in Max. Field Pipe Length. ** Cut Swaged End in the field to fit field Pipe.
2) OPERATION OF SHUT - OFF VALVES
(A) LIQUID (B) GAS
OPEN
CLOSE TO OPEN TURN ANTI-CLOCK WISE (1/4 TURN)
Wrench Key
CLOSED ( As Shipped Position )
4. Phase error will be indicated by a red light on the 3 phase sequence relay.
5. Phase correction must be applied to the incoming supply side.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD084 100716
Copyright © 2010 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SRD175C SRD190C
● ACTRONAIR ESP R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
This ESP air-conditioner is fitted with the latest MODEL SRD175C SRD190C
PERFECT-TEMP logic and digital scroll compressor REFRIGERANT TYPE R-410A R410A
technology that provides superior comfort control REFRIGERANT CHARGE grams 7100 7950
and highier seasonal energy efficiencies. PRE-CHARGED LENGTH m 15 15
ADDITIONAL REFRIGERANT /m grams 50 50 100
1) ESP OPERATION MAX. EQUIV. PIPE LENGTH RANGE m 0 - 60 0 - 20 20 - 60
1.1 Modulation / Capacity range is 10 - 100%. MAX. VERTICAL HEIGHT DIFF. * m 20 20
1.2 When running at 100% capacity the compressor LIQ. In(mm) 3/8 (9.52) 3/8 (9.52) 1/2 (12.7)
FIELD PIPE SIZING
operation is the same as standard Copeland scroll GAS In.(mm) 3/4 (19.05) 7/8 (22.22) 7/8 (22.22)
compressors. 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
1.3 The compressor modulates when full capacity is LIQ. In(mm)
swaged swaged cut swage **
not required. OUTDOOR UNIT CONNECTION
3/4 (19.05) 7/8 (22.22) 7/8 (22.22)
1.4 When modulating, the compressor operates in GAS In.(mm)
swaged swaged swaged
the loaded and unloaded states. The modulation
3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
is controlled by the PWM valve, which makes a LIQ. In(mm)
swaged swaged cut swage **
clicking sound whilst operating. INDOOR UNIT CONNECTION
1.5 During modulation, it is normal for the discharge 7/8 (22.22) 7/8 (22.22) 7/8 (22.22)
GAS In.(mm)
and suction pressures to increase and decrease. cut swage ** swaged swaged
* Included in Max. Field Pipe Length. ** Cut Swaged End in the field to fit field Pipe.
2) OPERATION OF SHUT - OFF VALVES
(A) LIQUID (B) GAS
OPEN CLOSE TO OPEN TURN ANTI-CLOCK WISE (1/4 TURN)
Wrench Key
( As Shipped Position )
CLOSED
4. Phase error will be indicated by a red light on the 3 phase sequence relay.
5. Phase correction must be applied to the incoming supply side.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD080 100716
Copyright © 2010 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SRD230C
● ACTRONAIR ESP R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SRD230C
This ESP air-conditioner is fitted with the latest
REFRIGERANT TYPE R-410A
PERFECT-TEMP logic and digital scroll compressor
REFRIGERANT CHARGE grams 9700
technology that provides superior comfort control
and highier seasonal energy efficiencies. PRE-CHARGED LENGTH m 10
ADDITIONAL REFRIGERANT /m grams 100
1) MAX. EQUIV. PIPE LENGTH RANGE m 0 - 60
ESP OPERATION MAX. VERTICAL HEIGHT DIFF. * m 20
1.1 Modulation / Capacity range is 10 - 100%.
LIQ. In(mm) 1/2 (12.7)
1.2 When running at 100% capacity the compressor FIELD PIPE SIZING
GAS In.(mm) 1 (25.4)
operation is the same as standard Copeland scroll
compressors. 1/2 (12.7)
LIQ. In(mm)
1.3 The compressor modulates when full capacity is swaged
OUTDOOR UNIT CONNECTION
not required. 7/8 (22.2)
GAS In.(mm)
1.4 When modulating, the compressor operates in swaged to 1 (25.4)
the loaded and unloaded states. The modulation 1/2 (12.7)
is controlled by the PWM valve, which makes a LIQ. In(mm)
swaged
clicking sound whilst operating. INDOOR UNIT CONNECTION
1 (25.4)
1.5 During modulation, it is normal for the discharge GAS In.(mm)
swaged
and suction pressures to increase and decrease. * Included in Max. Field Pipe Length.
2) OPERATION OF SHUT - OFF VALVES
(A) LIQUID (B) GAS
OPEN CLOSE TO OPEN TURN ANTI-CLOCK WISE (1/4 TURN)
Wrench Key
( As Shipped Position )
CLOSED
INSTALLATION GUIDE
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No.,
then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times.
3. ** E9 can also indicate a phase error (incorrect phase rotation or phase loss). ®
R
4. Phase error will be indicated by a red light on the 3 phase sequence relay.
5. Phase correction must be applied to the incoming supply side.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD066 110419
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SCA290C SCA330C
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SCA290C SCA330C
REFRIGERANT TYPE R-410A R-410A
REFRIGERANT CHARGE grams 11050 12800
PRE-CHARGED LENGTH m 5 5
ADDITIONAL REFRIGERANT /m grams 165 165
MAX. FIELD PIPE LENGTH RANGE m 0 - 60 0 - 60
MAX. VERTICAL HEIGHT DIFF. * m 20 20
LIQ. In(mm) 5/8 (15.9) 5/8 (15.9)
FIELD PIPE SIZING
GAS In.(mm) 1-1/8 (28.6) 1-1/8 (28.6)
5/8 (15.9) 5/8 (15.9)
LIQ. In(mm)
swaged swaged
OUTDOOR UNIT CONNECTION
1-1/8 (28.6) 1-1/8 (28.6)
GAS In.(mm)
swaged swaged
5/8 (15.9) 5/8 (15.9)
LIQ. In(mm)
swaged swaged
INDOOR UNIT CONNECTION
1-1/8 (28.6) 1-1/8 (28.6)
GAS In.(mm)
swaged swaged
( As Shipped Position )
( Operating Position )
5) REFRIGERANT CHARGE
5.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
5.2 Check operating pressures and temperatures, if required adjust charge.
5.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No., ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD068 110910
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
SCA300C SCA340C SCA400C
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL SCA300C SCA340C SCA400C
REFRIGERANT TYPE R-410A R-410A R-410A
REFRIGERANT CHARGE grams 2 x 4725 2 x 7050 2 x 7850
PRE-CHARGED LENGTH m 5 5 5
ADDITIONAL REFRIGERANT /m grams 50 (per stage) 50 (per stage) 100 (per stage)
MAX. FIELD PIPE LENGTH RANGE m 0 - 60 0 - 60 0 - 60
MAX. VERTICAL HEIGHT DIFF. * m 20 20 20
LIQ. In(mm) 3/8 (9.52) 3/8 (9.52) 1/2 (12.78)
FIELD PIPE SIZING
GAS In.(mm) 3/4 (19.05) 3/4 (19.05) 7/8 (22.2)
3/8 (9.52) 3/8 (9.52) 1/2 (12.7)
LIQ. In(mm)
swaged swaged swaged
OUTDOOR UNIT CONNECTION
3/4 (19.05) 3/4 (19.05) 7/8 (22.2)
GAS In.(mm)
swaged swaged swaged
3/8 (9.52) 3/8 (9.52) 1/2 (12.7)
LIQ. In(mm)
swaged swaged swaged
INDOOR UNIT CONNECTION
7/8 (22.2) 7/8 (22.2) 7/8 (22.2)
GAS In.(mm)
cut-off swage cut-off swage swaged
5) REFRIGERANT CHARGE
5.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
5.2 Check operating pressures and temperatures, if required adjust charge.
5.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
6.2 Check indoor fan amps DO NOT EXCEED rated amps (see indoor rating label).
6.3 THREE PHASE MODEL A) Check all three phases have 400 - 415 Volts (-6% to +10%) between all phases.
B) Check all single phases have 230 - 240 Volts (-6% to +10%) between active to neutral.
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No.,
then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times. ®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD069 110910
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
PACKAGE UNITS
1.1 Make sure all wiring is in accordance with local electricity authority wiring regulations.
1.2 Check indoor fan amps DO NOT EXCEED rated amps (see indoor rating label).
1.3 THREE PHASE MODEL A) Check all three phases have 400 - 415 Volts (-6% to +10%) between all phases.
B) Check all single phases have 230 - 240 Volts (-6% to +10%) between active to neutral.
2.1 A drain line trap must be fitted to prevent air movement in the drain pipe.
2.2 The trap height should be not less than 40mm.
2.3 Adjust the level of the unit to ensure that the condensate water drains from the drip tray.
3) MAINTENANCE
3.1 The refrigeration components and pipe work must be inspected periodically for leaks to minimise refrigerant emissions.
3.2 Drain traps and drain trays must be cleaned and/or cleared periodically to prevent drain blockages and ensure system cleanliness.
3.3 Electricals must be periodically checked to prevent hot joints that may cause system failure.
3.4 Ensure air filters are cleaned and/or replaced periodically to ensure system cleanliness and performance.
4) SYSTEM CHARGE
Temperatures listed below are a guideline for correct system charge. Values may vary under
different operating conditions and are to be taken after a 15 minutes system’s continuous
operation.
Note: Periodic maintenance inspections must be carried out to minimise possible refrigerant emissions.
INSTALLATION GUIDE
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No.,
then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD067 110419
Copyright © 2011 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
CAY470T-6Q1 CAY540T-6Q1 CAY620T-6Q1 CAY700T-6Q1
1) R410A REFRIGERATION PIPING AND REFRIGERANT CHARGE
MODEL CAY470T-6Q1 CAY540T-6Q1 CAY620T-6Q1 CAY700T-6Q1
COMPRESSOR NUMBER (Circuit) 1 2 1 2 1 2 1 2
REFRIGERANT TYPE R-410A
REFRIGERANT CHARGE grams 5,200 10,900 7,100 13,600 7,900 15,400 9,200 15,500
PRE-CHARGED LENGTH m 5 5 5 5 5 5 5 5
ADDITIONAL REFRIGERANT / m grams 50 165 50 165 100 165 100 165
MAX. EQUIV. PIPE LENGTH RANGE m 0 - 75 0 - 75 0 - 75 0 - 75 0 - 75 0 - 75 0 - 75 0 - 75
MAX. VERTICAL HEIGHT DIFF. † m 20 20 20 20 20 20 20 20
FIELD PIPE SIZING - liquid 9.5 (3/8) 15.9 (5/8) 9.5 (3/8) 15.9 (5/8) 12.7 (1/2) 15.9 (5/8) 12.7 (1/2) 15.9 (5/8)
In(mm) gas 19.1 (3/4) 28.6 (1-1/8) 22.2 (7/8) 28.6 (1-1/8) 25.4 (1) 28.6 (1-1/8) 25.4 (1) 28.6 (1-1/8)
OUTDOOR UNIT CONNECTION liquid 9.5 (3/8)* 15.9 (5/8)* 9.5 (3/8)* 15.9 (5/8)* 12.7 (1/2)* 15.9 (5/8)* 12.7 (1/2)* 15.9 (5/8)*
- In (mm) gas 19.1 (3/4)* 28.6 (1-1/8)* 22.2 (7/8)* 28.6 (1-1/8)* 25.4 (1)* 28.6 (1-1/8)* 25.4 (1)* 28.6 (1-1/8)*
INDOOR UNIT CONNECTION liquid 9.5 (3/8)* 15.9 (5/8)* 9.5 (3/8)* 15.9 (5/8)* 12.7 (1/2)* 15.9 (5/8)* 12.7 (1/2)* 15.9 (5/8)*
- In(mm) gas 19.1 (3/4)* 28.6 (1-1/8)* 22.2 (7/8)* 28.6 (1-1/8)* 25.4 (1)* 28.6 (1-1/8)* 25.4 (1)* 28.6 (1-1/8)*
† Included in Maximum Field Pipe Length
* Factory swaged
4) REFRIGERANT CHARGE
4.1 No additional refrigerant is required for pipe lengths less than the pre-charged length, as shown on the chart above.
4.2 Check operating pressures and temperatures, if required, adjust charge using subcool and superheat methods.
4.3 Must be liquid charged when adding refrigerant.
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for R410A only.
5) ELECTRICAL
5.1 Make sure all wiring is in accordance with local electricity authority wiring regulations.
5.2 Check indoor fan amps DO NOT EXCEED maximum amps (see indoor rating label).
INSTALLATION GUIDE
5.3 Supply voltage should be within 415 Volts ±5% . Voltage of all three phases must not exceed ±2% between them.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD085 100716
Copyright © 2010 Actron Engineering Pty. Ltd.
INSTALLATION GUIDE
PKY470T-6Q1 PKY540T-6Q1 PKY620T-6Q1 PKY700T-6Q1
ELECTRICAL
Make sure all wiring is in accordance with local electricity authority wiring regulations.
Check indoor fan amps DO NOT EXCEED maximum amps (see indoor rating label).
Supply voltage should be within 415 Volts ±5% . Voltage of all three phases must not exceed ±2% between them.
MAINTENANCE
The refrigeration components and pipe work should be inspected periodically for leaks to minimise refrigerant emissions
Drain traps and rain trays should be cleared periodically to prevent drain blockages and ensure system cleanliness.
Electrical must be periodically checked to prevent hot joints and or system failures. Ensure air filters are cleaned and or
replaced periodically to ensure system cleanliness and performance.
SYSTEM CHARGE
Record operating temperature and pressure and check subcool and superheat.
where:
SCT = Saturated Condensing Temperature at the given discharge pressure (from R410a Pressure Temperature Chart), oC
LLT = Liquid Line Temperature, oC
SST = Saturated Suction Temperature at the given suction pressure ((from R410a Pressure Temperature Chart), oC
SLT = Suction Line Temperature, oC
Subcool and Superheat must be within the range in the table shown below. If not, it is necessary to adjust refrigerant charge using subcool and
superheat method.
Subcool Superheat
COOL 5-8k 4-8k
HEAT 15-25k 3-8k
NOTE: Periodic Maintenance inspections should be carried out to minimise possible refrigerant emissions.
It is important to work with absolute system’s cleanliness.
WARNING: It is an offense to vent/release R410A into the atmosphere. Reclaim the refrigerant into a container dedicated for
R410A only.
NOTES:
1. When unit is powered up, the first LED display will be the software version number (first three number), compressor
number (1 or 2), then “8” (means outdoor coil sensor has not finished its readings) and finally “0” (means default for cooling
operation). And then it will be followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times.
3. When Phase Protection Relay Option is fitted.
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SD086 100506
Copyright © 2010 Actron Engineering Pty. Ltd.
THIS PAGE WAS INTENTIONALLY LEFT BLANK
INSTALLATION GUIDE
REFRIGERANT FILTER DRIER SPECIFICATIONS
Background
Liquid line filter driers in air-conditioning system are highly recommended in order to remove harmful elements
from the circulating refrigerants and lubricants that may cause damage to the unit. No matter how much precau-
tions are taken during assembly and installation or servicing of a system, contaminants can still end up into the
system. These contaminants can be solid, such as metal swarf, flux, dust and dirt. Equally menacing are soluble
contaminants, such as water, acid and wax. Organic acids, which are severely harmful contaminants, can form
or generate inside the circuit through decomposition, chemical reaction and hydrolysis of the refrigerants, lubri-
cants and foreign substances in air-conditioning system. Excessive temperatures are the major factor that can
accelerate the process of acid generation. It is important that any generated acid is adsorbed as soon as it is
formed in the system. Likewise, solid contaminants need to be filtered and contained within the circuit.
Technical Data
Max. Working Pressure 44.8 bar (650psi)
Desiccant Type Solid Block, 75% Molecular Sieve / 25% Activated Alumina
Shell Material / Finish 1.0mm Steel / Powder Paint Coated to withstand 500 hours Salt Spray
* Refer to Emerson Climate Technologies Flow Controls brochure for exact Unit Size and Filter Drier model
®
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
CS-03-001 100503
Copyright © 2010 Actron Engineering Pty. Ltd. REVISION 1