01 EPC DI HD 007 - C Cajas de Conexiones
01 EPC DI HD 007 - C Cajas de Conexiones
REV. C
PANEL
TAG Equipment 0300-JB-002
Location 300 area (colector de polvos)
Dimensions (H x W x D) mm 800 x 600 x 250 (Note 1)
Weight VTS (Note 2)
Installation Outdoor
Enclosure NEMA 4X
Material Sheet steel
Colour RAL 7035
Panel Arragement Single front wall
Cable entry Bottom
Insulation class 600 V
Approval NEMA
INLET
Digital 9 units 1x3C#14 AWG - Multiconductor &
Armored Cable (Outer Diameter Jacket = 0.7")
at bottom (Note 3)
OUTLET
Digital 2 units 1x40C#14 AWG - Multiconductor &
Armored Cable (Outer Diameter Jacket =
1.48") at bottom (Note 3)
TERMINAL BLOCK
Type Terminal Block Din Rail Mounting,
Connections for 12AWG - 16AWG conductor,
Vibration testing
NOTES
1. Vendor must confirm the final dimensions.
2. VTS: Vendor to Specify.
3. O.D: Outer Diameter of Shielded or multiconductor armored cable.
4. Vendor shall define all the accessories to use in panel.
- All wiring shall be properly identified with TAG at both ends of cable.
- The vendor shall include the equipment test protocol and cable routing drawings.
- The panel will included support structure to facilitate erection on side.
Página 1 de 1
33910565-01-EPC-DI-HD-007
INSTRUMENTACIÓN Revisión :C
Hoja de Datos - Cajas de conexiones (señales discretas) Fecha : 13-01-19
PANEL
TAG Equipment 0300-JB-001
Location 300 area (horno rotativo)
Dimensions (H x W x D) mm 800 x 600 x 250 (Note 1)
Weight VTS (Note 2)
Installation Outdoor
Enclosure NEMA 4X
Material Sheet steel
Colour RAL 7035
Panel Arragement Single front wall
Cable entry Bottom
Insulation class 600 V
Approval NEMA
INLET
Digital 7 units 1x3C#14 AWG - Multiconductor &
Armored Cable (Outer Diameter Jacket = 0.7")
at bottom (Note 3)
OUTLET
Digital 2 units 1x30C#14 AWG - Multiconductor &
Armored Cable (Outer Diameter Jacket =
1.36") at bottom (Note 3)
TERMINAL BLOCK
Type Terminal Block Din Rail Mounting,
Connections for 12AWG - 16AWG conductor,
Vibration testing
NOTES
1. Vendor must confirm the final dimensions.
2. VTS: Vendor to Specify.
3. O.D: Outer Diameter of Shielded or multiconductor armored cable.
4. Vendor shall define all the accessories to use in panel.
- All wiring shall be properly identified with TAG at both ends of cable.
- The vendor shall include the equipment test protocol and cable routing drawings.
- The panel will included support structure to facilitate erection on side.
Página 1 de 1
33910565-01-EPC-DI-HD-007
INSTRUMENTACIÓN Revisión :C
Hoja de Datos - Cajas de conexiones Fecha : 13-01-19
INDEX
Página 1 de 1