TASK LIST ID KEY DATE COUNT GROUP TEXT Planning Plant
P NO.
ER

8 8 10 2 40 4
TL_ID PLNNR STTAG PLNAL KTEXT WERKS
03/02/2015 17 FIRE PUMP ENGINE WEEKLY TEST 2000
09/14/2014 17 GENERATORS WEEKLY DRY-RUN (AUTOMATIC) 2000
09/15/2014 17 GENERATORS WEEKLY DRY-RUN (MANUAL) 2000
09/21/2014 17 DEEPWELL PUMPS RUNNING INSPECTION 2000
03/05/2015 17 FIRE PUMP VERTICAL RUNNING INSPECTION 2000
SYSTE
Group TASK MAINTENA
STATU M
Work LIST NCE
S STATU
Center USAGE STRATEGY
S
8 1 1 1 6
ARBPL VERWE STATU ANLZU STRAT
2FAC1 4 4 0 WEEKLY 28
2FAC1 4 4 0 WEEKLY 37
2FAC1 4 4 0 WEEKLY 34
2FAC1 4 4 0 MNHTLY 33
2FAC1 4 4 0 WEEKLY 37
OPERATIO WORK CONTRO
TASK LIST ID PLANT OPERATION DESCRIPTION
N NUMBER CENTER L KEY

8 4 8 4 4 40
TL_ID VORNR ARBPL WERKS STEUS LTXA1
1 0010 2FAC1 2000 PM01 Inspect of fuel tank level
1 0020 2FAC1 2000 PM01 Inspect of engine oil level
1 0030 2FAC1 2000 PM01 Inspect for coolant level
1 0040 2FAC1 2000 PM01 Inspect engine external
1 0050 2FAC1 2000 PM01 Operate the generator (manual)
1 0060 2FAC1 2000 PM01 Check for abnormal noises / vibrations
1 0070 2FAC1 2000 PM01 Stop for the engine
2 0010 2FAC1 2000 PM01 Check isolation breaker turnoff position
2 0020 2FAC1 2000 PM01 Inspect of fuel tank level
2 0030 2FAC1 2000 PM01 Inspect of engine oil level
2 0040 2FAC1 2000 PM01 Inspect for coolant level
2 0050 2FAC1 2000 PM01 Inspect engine external
2 0060 2FAC1 2000 PM01 Operate the generator (automatic)
2 0070 2FAC1 2000 PM01 Check for abnormal noises / vibrations
3 0010 2FAC1 2000 PM01 Check isolation breaker turnoff position
3 0020 2FAC1 2000 PM01 Inspect of fuel tank level
3 0030 2FAC1 2000 PM01 Inspect of engine oil level
3 0040 2FAC1 2000 PM01 Inspect for coolant level
3 0050 2FAC1 2000 PM01 Inspect engine external
3 0060 2FAC1 2000 PM01 Operate the generator (manual)
3 0070 2FAC1 2000 PM01 Check for abnormal noises / vibrations
4 0010 2FAC1 2000 PM01 Check & measure ampere readings
4 0020 2FAC1 2000 PM01 Check & measure pumping level capacity
4 0030 2FAC1 2000 PM01 Inspect lightning protection
4 0040 2FAC1 2000 PM01 Housekeeping of area
5 0010 2FAC1 2000 PM01 Test Run the Equipment
5 0020 2FAC1 2000 PM01 Check Pressure
5 0030 2FAC1 2000 PM01 Inspect for abnormal noise / vibration
5 0040 2FAC1 2000 PM01 Shut-off the Equipment
UNIT OF OPERATI Number of
WORK
WORK ON ID Pax

73 4 1
ARBEI ARBEH OP_ID
3 MIN 0010 3 26
3 MIN 0020 3 27
3 MIN 0030 3 25
8 MIN 0040 3 23
8 MIN 0050 3 30
20 MIN 0060 3 38
8 MIN 0070 3 19
1 MIN 0010 2 40
5 MIN 0020 2 26
5 MIN 0030 2 27
5 MIN 0040 2 25
8 MIN 0050 2 23
20 MIN 0060 2 33
8 MIN 0070 2 38
1 MIN 0010 2 40
5 MIN 0020 2 26
5 MIN 0030 2 27
5 MIN 0040 2 25
8 MIN 0050 2 23
20 MIN 0060 2 30
8 MIN 0070 2 38
8 MIN 0010 2 31
25 MIN 0020 2 38
8 MIN 0030 2 28
8 MIN 0040 2 20
30 MIN 0010 2 22
8 MIN 0020 2 14
8 MIN 0030 2 38
8 MIN 0040 2 22
TASK LIST
OPERATION ID TEXT EDITOR TEXT LINE TAG COLUMN
ID
84 40 2
TL_ID OP_ID TXLINE TXPARGRAPH
1 0010 Call Electrical & Safety for 1 28
1 0010 testing the equipment. 2 23
1 0010 Visually inspect for fuel tank, must 3 36
1 0010 contained to the specified level, 4 34
1 0010 Check fuel feed valve into OPEN position 5 40
1 0020 Check for the engine oil level 1 30
1 0020 Pull out the oil level gauge (dipstick) 2 39
1 0020 to visually check the oil level. 3 33
1 0020 The proper oil level is bet. high & low 4 40
1 0020 Check also the oil pan drain plug/valve 5 39
1 0020 must be into CLOSED position 6 29
1 0030 Inspect for the coolant level, 1 31
1 0030 If coolant level is low, add coolant 2 36
1 0030 to the specified full level 3 28
1 0040 Inspect for the engine external parts 1 38
1 0040 be sure to keep combustible material 2 37
1 0040 away from the engine, exhaust manifold, 3 40
1 0040 and the battery. Check to remove 4 33
1 0040 unnecessary object like rags, etc. 5 35
1 0040 from the engine and battery. 6 29
1 0040 Visually inspect bolts & nut looseness, 7 40
1 0040 Inspect electrical wiring, check also 8 38
1 0040 that the valve,plugs or cocks in proper 9 40
1 0040 position and check fuel control link 10 37
1 0040 for the smooth movement like 11 29
1 0040 manual stop lever, movement for rack 12 37
1 0040 cancel spring, and ball joint for 13 34
1 0040 looseness and play. Then after checking 14 40
1 0040 will proceed the operation of engine 15 37
1 0050 Use main pump controller for starting 1 37
1 0050 For manual starting, position MODE 2 34
1 0050 SELECTOR to Manual Run. Lift and 3 33
1 0050 hold Manual Crank #1, until engine 4 35
1 0050 starts, or release after 15seconds. 5 36
1 0050 If unit fail to start,wait for 15seconds 6 40
1 0050 use Manual Crank #2 and repeat step. 7 37
1 0060 During the operation inspect the engine 1 39
1 0060 surrounding area for leaks of fuel, 2 36
1 0060 engine oil or coolant, Check also 3 34
1 0060 the abnormality of noise and vibration. 4 40
1 0060 After the inspection,back to panel board 5 40
1 0060 and check for the engine coolant temp. 6 39
1 0060 Check Pump side for vibration, temp. 7 36
1 0060 and unusual sounds. 8 20
1 0070 To stop the engine, return MODE 1 31
1 0070 SELECTOR switch to Automatic/Manual 2 36
1 0070 Stop position, engine will stop. Close 3 39
1 0070 system manual by-pass valve if opened. 4 39
2 0010 Inform Echo Bravo to perform activities 1 39
2 0010 Check the breaker handle 2 24
2 0010 must be at the TURN-OFF position 3 33
2 0010 Before dry-run the engine, check first 4 38
2 0010 the following generator parts 5 30
2 0020 Visually inspect for fuel tank, must 1 36
2 0020 contained to the specified level, 2 34
2 0020 Check fuel feed valve into OPEN position 3 40
2 0030 Check for the engine oil level 1 30
2 0030 Pull out the oil level gauge (dipstick) 2 39
2 0030 to visually check the oil level. 3 33
2 0030 The proper oil level is bet. high & low 4 40
2 0030 Check also the oil pan drain plug/valve 5 39
2 0030 must be into CLOSED position 6 29
2 0040 Inspect for the coolant level, 1 31
2 0040 If coolant level is low, add coolant 2 36
2 0040 to the specified full level 3 28
2 0050 Inspect for the engine external parts 1 38
2 0050 be sure to keep combustible material 2 37
2 0050 away from the engine, exhaust manifold, 3 40
2 0050 and the battery. Check to remove 4 33
2 0050 unnecessary object like rags, etc. 5 35
2 0050 from the engine and battery. 6 29
2 0050 Visually inspect bolts & nut looseness, 7 40
2 0050 Inspect electrical wiring, including 8 37
2 0050 starters and alternators, check also 9 37
2 0050 that the valve,plugs or cocks in proper 10 40
2 0050 position and check fuel control link 11 37
2 0050 for the smooth movement like 12 29
2 0050 manual stop lever, movement for rack 13 37
2 0050 cancel spring, and ball joint for 14 34
2 0050 looseness and play. Then after checking 15 40
2 0050 will proceed the operation of engine 16 37
2 0060 For the operation of the automatic 1 34
2 0060 Open the panel board box and press ON 2 37
2 0060 the fuse, then get the key to start the 3 40
2 0060 engine. Insert the key then wait until 4 39
2 0060 the generator ready was selected 5 33
2 0060 which is found at the panel board menu 6 39
2 0060 then press the Start button, 7 30
2 0060 Write down at the checklist for the 8 35
2 0060 record of running hours operation 9 34
2 0060 of the engine by pressing the 10 30
2 0060 arrow button at the panel board. 11 33
2 0060 check for the ampere must 260A+, 12 33
2 0060 RPM at 1800, Hz at 60, KVA at 600+ 13 36
2 0060 If the Volts reach 24V+ that means the 14 38
2 0060 alternator is working 15 22
2 0060 Inspect also at the panel board 16 32
2 0060 for filter clogged, and electrical trip 17 40
2 0060 which is found at the panel board menu 18 39
2 0070 During the operation inspect the engine 1 39
2 0070 surrounding area for leaks of fuel, 2 36
2 0070 engine oil or coolant, Check also 3 34
2 0070 the abnormality of noise and vibration. 4 40
2 0070 After the inspection,back to panel board 5 40
2 0070 and check for the engine coolant temp. 6 39
2 0070 If the temperature of coolant reach 7 35
2 0070 70°C (158°F),this can stop the engine 8 38
2 0070 by stopping the engine, press the stop 9 39
2 0070 button / red button to stop the engine. 10 40
2 0070 When the engine cannot stop, 11 28
2 0070 pull the manual stop lever until the 12 37
2 0070 engine stops completely. 13 25
2 0070 After the engine stop, turn off the fuse 14 40
2 0070 and safe keep the key and call 15 31
2 0070 Echo Bravo for the turnover of the genset. 16 42
3 0010 Call Echo Bravo to perform activities 1 38
3 0010 before dry-run the engine, check first 2 39
3 0010 The following generator parts 3 29
3 0010 Check the breaker handle 4 24
3 0010 must be at the TURN-OFF position 5 33
3 0020 Visually check for fuel tank, must 1 34
3 0020 contained to the specified level, 2 34
3 0020 Check fuel feed valve into OPEN position 3 40
3 0030 Inspect for the engine oil level 1 33
3 0030 pull out the oillevel gauge (dipstick) 2 39
3 0030 to visually check the oil level. 3 33
3 0030 The proper oil level is bet. high & low 4 40
3 0030 Inspect the oil pan drain plug/valve 5 36
3 0030 must be into CLOSED position 6 29
3 0040 Inspect for the coolant level, 1 31
3 0040 If coolant level is low, add coolant 2 36
3 0040 to the specified full level 3 28
3 0050 Inspect for the engine external parts 1 38
3 0050 be sure to keep combustible material 2 37
3 0050 away from the engine, exhaust manifold, 3 40
3 0050 and the battery. Also check to remove 4 38
3 0050 unnecessary object like rags, etc. 5 35
3 0050 from the engine and battery. 6 29
3 0050 Visually inspect bolts & nuts looseness, 7 40
3 0050 Inspect electrical wiring, including 8 37
3 0050 starters and alternators, check also 9 37
3 0050 that the valve,plugs or cocks in proper 10 40
3 0050 position and check fuel control link 11 37
3 0050 for the smooth movement like 12 29
3 0050 manual sotp lever, movement for rack 13 37
3 0050 cancel spring, and ball joint for 14 34
3 0050 looseness and play. Then after checking 15 40
3 0050 will proceed for operation of engine 16 37
3 0060 For the operation of the manual 1 31
3 0060 get the key for the genset 2 27
3 0060 insert and 1/4 turn counterclockwise 3 37
3 0060 for the key,to preheat the engine about 4 40
3 0060 20-30seconds, then turn 1/2 clockwise 5 38
3 0060 to start/run the engine at the idle 6 36
3 0060 position, after 1 minute running, 7 34
3 0060 pull the Speed Control Handle and 8 34
3 0060 turn it 1/4 clockwise, and check 9 33
3 0060 for the parameters of the engine 10 33
3 0060 Inspect for Oil Pressure and Water Temp. 11 40
3 0060 Inspect RPM, Ampere, & Volts 12 28
3 0060 then, record to the logsheet 13 29
3 0070 During the operation check the engine 1 37
3 0070 surrounding area for leaks of fuel, 2 36
3 0070 engine oil or coolant, Check also 3 34
3 0070 the abnormality of noise and vibration. 4 40
3 0070 After the inspection,back to panel board 5 40
3 0070 and check for the engine coolant temp. 6 39
3 0070 If the temperature of coolant reach 7 35
3 0070 70°C (158°F),this can stop the engine 8 38
3 0070 by stopping the engine, turn the key 9 37
3 0070 1/4 at counterclockwise, If cannot stop 10 40
3 0070 pull the manual stop lever until the 11 37
3 0070 engine stops completely. 12 25
3 0070 and safe keep the key and call 13 31
3 0070 Echo Bravo for the turnover the genset. 14 39
4 0010 Inspect and measure ampere readings 1 35
4 0010 Inspect to the installed ammeter 2 33
4 0010 Inform Electrical for result of reading 3 39
4 0010 If don’t have installed ammeter, 4 32
4 0010 call electrical to check the ampere 5 36
4 0010 using there clamp meter tools 6 30
4 0020 Inspect &measure deepwell pumping level 1 40
4 0020 Manipulate isolation valve for measuring 2 40
4 0020 the pump capacity 3 18
4 0020 get a drum and measure its volume 4 34
4 0020 then put the drum under the isolation 5 38
4 0020 valve. First set the timer and open the 6 40
4 0020 isolation valve & wait until the drum 7 38
4 0020 is fulled in water. Calculate capacity 8 39
4 0020 divide the volume of drum over the 9 35
4 0020 time get result,in convert it into GPM, 10 40
4 0020 record the result into the logsheet 11 36
4 0030 Inspect for the lightning protection 1 37
4 0030 Visually check for its damage and others 2 40
4 0030 that can be affect the equipment 3 33
4 0040 Clean the area of the deepwell pumps 1 36
4 0040 Carried out all the unnecessary object 2 38
4 0040 like plastics, cans, leaves & others. 3 38
4 0040 Include inspection of areas that it 4 35
4 0040 can be affect the accessories of pumps 5 39
5 0010 Call Electrical & Safety for 1 28
5 0010 testing the equipment. 2 23
5 0010 Open the suction & discharge valve 3 34
5 0010 and close the valve going to the 4 33
5 0010 other area. Look for control panel 5 35
5 0010 board and start to test the pump. 6 34
5 0020 Check for the pressure, the pressure 1 36
5 0020 must around 40psi / 3bars. If pressure 2 39
5 0020 cannot attain, operate the by-pass 3 35
5 0020 valve, adjust into half open until it 4 38
5 0020 reach the required pressure, and 5 33
5 0020 record the result. 6 19
5 0030 Inspect pump & motor for vibration, 1 35
5 0030 unusual sound & vibration, cooling fan 2 39
5 0030 check motor cleanliness & Cable gland 3 39
5 0030 check motor terminal box & Fan cover 4 37
5 0030 measure & record motor 5 24
5 0030 (NDE, DE, Body) temperature. 6 29
5 0030 Report unusual findings ASAP 7 28
5 0040 Operate control panel board and 1 31
5 0040 shut-off the equipment. Reopen the 2 35
5 0040 valve for other area and turnover the 3 38
5 0040 equipment to the area owner. 4 29
0
0
0
0
0
0
0
0
0
0
0
0
0
0
GROUP OPERATION CYCLE SHORT
GROUP NO. TASK LIST ID
COUNTER NUMBER TEXT
8 2 8 4 2
PLNNR PLNAL TL_ID VORNR KTEXTZYK01
17 0010 1W
17 0020 1W
17 0030 1W
17 0040 1W
17 0050 1W
17 0060 1W
17 0070 1W
17 0010 1W
17 0020 1W
17 0030 1W
17 0040 1W
17 0050 1W
17 0060 1W
17 0070 1W
17 0010 1W
17 0020 1W
17 0030 1W
17 0040 1W
17 0050 1W
17 0060 1W
17 0070 1W
17 0010 1M
17 0020 1M
17 0030 1M
17 0040 1M
17 0010 1W
17 0020 1W
17 0030 1W
17 0040 1W