\& Petbow
installation manual for
generating sets -Section H
page H.1
Exhaust systems
No internal combustion engine will operate efficiently
unless its exhaust gases can be discharged easily andit
is stressed that your exhaust system should conform as
closely as possible to the following recommendations.
General
The exhaust system should be as short as site
conditions and local regulations will allow it to be. A
minimum number of bends should be used and those of
the long radius type. Hot exhaust gases travel at high
velocity and become very inflexible if their direction of
flow is changed rapidly, back pressure builds up in the
exhaust system preventing efficient scavenging, with a
resultant loss of engine power. Keep the back pressure
down as low as possible. See data sheet
Where conditions increase the exhaust system length
longer than 9m, the bore will have to be increased.
‘The amount of increase will depend on the total exhaust
pipe length and number of bends. Details of the pro:
posed pipe run, preferably a sketch, should be sent to,
‘our Installation Department for their recommendations.
See Diagram Page H2.
‘The first section of exhaust from the engine manifold
must include a flexible section of pipe or bellows unit.
The next section of exhaust pipe should be supported
to allow the flexible pipe movement without putting
weight on the engine manifold.
“The support bracket on the exhaust must allow for the
pipe to expand or should be of the roller type. A short
flexible or expansion bellows should be incorporated on
long runs between fixing brackets.
All pipework should have a minimum wall thickness:
of 3mm,
Sleeves:
Where the exhaust pipe passes through walls a
sleeve or wall plates should be fitted or allow a
clearance hole otherwise cracking of the wall material
will take place, it is also a’ safeguard against a
fire hazard,
Termination
Care should be taken when deciding on the exhaust
terminating point to atmosphere, that there are no air
inlet grills or opening windows where the exhaust gas.
can re-circulate into the building, also the terminating
point should be so arranged to stop the ingress of rain.
(On long exhaust runs a drain point or condensation trap
should be fitted near the engine.
Multiple Exhaust Systems:
~ Where more than one engine is installed each should
have its own independent exhaust system as running
more than one set into a common pipe can be
dangerous and could cause damage to various parts,
of the engine.
Where the exhaust system is required to go into a
disused boiler chimney this should be checked for gas
tightness before proceeding with the system.
An exhaust should not be discharged into a chimney
that is in use as the engine pulsations will upset the
operation of the boiler draught. Also there is a risk of an,
explosion taking place through the ignition of
unburnt gases.
Silencers:
Exhaust silencers, there are various types, these
are the most common
Normal industrial silencers:
Used where noise is not critical
Residential silencers:
Used where noise is an important factor.
Resonance or absorbtion silencers:
Used at end of long exhaust runs.
Spark arrestor silencers:
Used in explosive gases areas.
The exhaust system should be lagged, especially
the internal pipework, and clad with metal sheeting to
retain the lagging where possible as the exhaust gas
temperature on most engines at full load is in a range
‘of 500-600”, at manifold, and this must be taken into
account, when choosing a suitable lagging. Where
‘any part of the exhaust is in an area where personnel
ean come in contact with it, it must be lagged
or guarded. Do not use asbestos which is a health
hazard.Section H
page H.2
exhaust systems
TYPICAL EXHAUST RUNExhaust Systems
pogeH3
Exhaust pipeline recommendations
Pipe size recommendations*
Exhaust outlet size Upto m to 12m 12m to 18m 18m to 24m
|____ mm finches) 6m (2oft) (2010 40ft) (40 t0 60ft) 60 to Bon)
mm (ins) mm (ins). | mm (ins) | mm (ins). | mm (ins)
50 (2) 80 (2) 63 (2) 78 (3) 76 (3)
7 3) 78 (3) 89 (314) 100 (4) yoo (a)
a9 (3%) 89 (3%) 100 (a) 100 (4) 100 (a)
178) 1275) 160 (6) 150 (6) 200 (8)
150 (6) 150 (6) 150 (6) 200 (8) 200 (8)
200 (8) 200 (8) 200 (8) 254 (10) 254 (10)
254 (10) 254 (10) 254 (10) 305 (12) 305 (12)
‘Note. These sizes are for
nce only. Specification and special silencer applications may affect the actual ine size.
The following formula can be used to calculate the actual back pressure to the exhaust system for a given length and
diameter.
Lxsxa? Pipe length and elbows in fect,
e-ee Q = Exhaust flow (CFM)
Inside diameter of pipe (inches)
S = Specific weight of exhaust gas (lb Jeu. ft.)
Swill vary with the absolute temperature of exhaust gas as follows
a
S~ Geq-¥ exhaust temp.
P = Back pressure (p.si.). Must not exceed max. allowable back pressure as shown in
accompanying table.
Some useful conversions
Millimeters to inches ~ multiply by 0.03937,
Metres to feet ~ multiply by 3.281
Cubie metres to cubic feet multiply by 36.31
Centigrade to Fahrenheit — multiply by (Cx 1.8) + 32
p.sii. to inches of water (H,0) - divide by 0.0361
Inches of water to mm of water ~ multiply by 25.4
Jeesonz eet _| ism [nota] fag | 0H EES eer
175 | 2006TGI | PRAI40A | 127 1 | 690} 625 | 6seTcA2 | Ewsoo | 150 681
227 | NTB55G4 | BNI82A | 150 | 1 1021 750 | KTA38G2 | CO600A | 150 1021
250 | 2006TWG | PRC200A| 127 | 1 690 | 920 | KTTA38G | CW736A} 150 1021
290 | NT855G6 | BM232A | 150 | 1 1021 1000 | KTASOG1 | CKSO0A | 127 1021
gSection!
pagel.1
Cooling and Ventilation
Cooling and ventilation of an engine room is very
important. Provision must be maue for an adequate air
flow through the room, to replace the air consumed by
the engine, and air pushed out by the cooling
radiator fan.
‘There are various types of cooling systems that can
be adopted, the main ones being as follows,
‘Set mounted radiator.
Remotely positioned radiator.
Heat exchanger cooling,
Cooling tower system.
Radiator Cooled Sets:
When a radiator is mounted on the end of the plant
main frame, position the set so that the radiator is as
close to the outlet vent as possible, otherwise recircula-
tion of hot air can take place. The recommended
maximum distance away fromthe outlet ventis 150mm.
If the plant cannot be positioned as above an air duct
‘must be incorporated in the system,
‘The minimum cross sectional area of theducting must
be the same as the cooling area of the radiator. Acanvas,
duct with mating stee! flanges to suit radiator andoutput,
louvres is normally adequate for this purpose.
Ducting bends must be well radiused and where long
runsare required the ducting mustbeenlargedtoredyce
back pressure on the radiator. Sound attenuated ducts,
require long runs and have tobe designed specifically for
each building (see section on sound).
‘The air inlet and outlet apertures in a building are
normally louvred or screened with mesh. The free area
taken up by the louvring slats or mesh mustbetaken into
consideration when calculating size of aperture.
‘The large volume of air required by a diesel engine for
‘cooling and combustion is not always appreciated and it
isrecommended that the total area of incoming air vents
should be at least double that of the engine radiator
outlet. Al vents should be protected against the ingress
of rain. In cold climates where sets are employed on
‘standby duty and only run occasionally, the room should
be kept warm. Air inlets and radiator outlets should be
provided with adjustable louvres that can be closed
when the set is not in use. Thermostatically controlled
immersion heaters are fitted in the engine coolant
system on all Petbow automatic mains failure sets,
as standard
Remote Radiator Cooled Systems:
‘Where space in a below-ground level installation
precludes the use of ducting a number of alternative
‘methods of cooling are available.
‘A.conventional small cooling tower which is reason-
ably cheap, simple to install and maintain or a separate
radiator system which can be constructed as shown in
figure 3/4. The radiator in this system is separated from
the engine and the fan driven by an electric motor.
‘The radiator with an electricdriven fancanbe supplied
‘a8 a totally enclosed unit for outside use, or an open type:
for installation inside a building.
When the radiator is mounted more than 3,0 metres
higher than the set, on most engines abreak tank andan
electric driven water pump is required. The size of the
break tank depends on the capacity of the entire cooling
system, The amount of pipework required, plus a similar
amount of water for cooling.
Water is circulated from the break tank through the
radiator and engine by means of an electrically driven
circulating pump.
As the radiator electricfan motor andwater circulating
pump are powered by the generator, this load
requirement must be added to the total set power.
‘As thewater from the radiator will drain into the break
tank when the setis atrest, the tank musthavesufficient
‘capacity to fill the entire cooling system when the set is
running, and still retain enough coolant for it to
circulate efficiently,
Precautions Required with this System:
1. Against contamination of coolant water by
foreign matter.
2. Water becoming oxygenated through turbulence
in break tank
3. Avoidance of air locks in system, pipes should
have vent points,
4. Carry out suitable water treatment to engine
manufacturers recommendations.
5. Take precautions against freezing,
6, Engine runs virtually unpressurised.
If the radiator is mounted at the same level as the
engine and no break tank is required, an expansion
tank should be fitted just above the radiator to allow for
the expansion of the coolant water.
Heat Exchanger Cooling:
‘Alternatively, a heat exchanger cooled engine can be
‘employed.
This system requires less space than a break tankand
the closed circuit means that replenishment of the
coolant lost through evaporation can be made up
‘automatically with a ball valve in the header tank
Fig. 6.
Heat exchangers can be supplied on most types of
engines, This system is used where the water is likely to
be contaminated or to come fromacooling tower orlarge
storage tank. After the water has been through a heat
exchanger, it has to be treated as contaminated water
and cannot be used for domestic purposes.
Most Water Boards will not allow town mains waterto
be used through the heat exchanger as it must be run to
‘waste after use. The water pressureonaheatexchanger
can be about 20 lbs constant.
Special Note:
‘When using @ remote radiator or heat-exchanger
cooling system, allowance must still be made for
aspiration of engine, ventilation of engine room, and
‘cooling of alternator.cooling and ventilation
Section |
page L2
Coolant Water Treatment:
Its essential that water treatment be employed in all
engine cooling systems as soon as an enginegoesinto
service, irrespective of the quality of the basic water
availabie. The cost is small compared to the cost of,
damage resulting from lack of, or. inadequate
treatment. Some inhibitors provide chemical protection
(on PH control whilst others deposit a protective film on
the waterside surfaces. The PH value of coolant is
lakes precedence e.g. with soluble oil and some other
inhibitors recently introduced where the inhibitor
controls and determines the PH value.
Anti freeze type B to B.S.3151 contains inhibitors,
sodium Benzoate/sodium nitrite, and a minimum 20%,
dosage should be maintained in order that these
inhibitors are present in desirable quantities.
‘The instructions supplied with an inhibitor must be
strictly adhered to, particularly in respect of dosage
and sampling
The following coolants are recommended
For protection against frost and corrosion
Clean drinking water containing inhibited anti-
Ireeze to one of the following specifications
British standards institution — 8.S.3150, 3151
or 3152, 1959,
Proprietary US.
anti-freeze.
2. For protection against corrosion only: Clean
drinking water containing inhibitors similar in
formulation and proportions to those used in
any of the British Standards quoted.
specification — Prestone
Air Cooled Engines:
Generating sets with air cooled diesel engines require
2 different approach to installation than water cooled
engines. For a start, cool air is drawn in directly to the
engine and hot air exhausted out vie a specially
formed duct.
It is recommended that the engine air intake at the
front of the set be positionedas closely as possible to the
fresh air inlet which can be double louvred doors with at
least double the free air area of the engine air intake, or
fitted louvres. Intake ducting is not essential.
Hot air is exhausted at one side of the engine and
specially built ducting fitted directly to the engine should
extend outside the building to avoid any recirculation of
hot air. It is imperative that hot air is prevented from
recirculating within the room as such air if drawn in by
the cooling system will cause engine overheating and
loss of power if absorbed for combustion purposes,
Note: Remote Radiators and Heat Exchanger Cooling
Systems,
Certain engines with turbocharging andair toair charge
cooling are unsuitable for remote radiator installations.
This applies particularly to the Rolls Royce range with
outputs in excess of 160 kW. Engines with air to water
charge cooling, mainly Cummins, M.AN. and Volvo are
normally quite suitable
With heat exchanger cooling some loss of power will
cooling systems of the air to air type.Section |
page 3
coo!
g and ventilation
COOLING WITH SHORT AIR DUCT
ont
aes ee ee
FIG1
FIG2
‘FLOW REQUIREMENTS NOON
Ford airflow in cic feet per minute
pai
mower
tal heat input to room in ST Uimnute
AT. & Permianbleinereacein room temperature in dgreos front
feat contrbuted bythe generar and coral panel in BTUNIN, can be estimated at 424 x gross engine pov
COOLING AND AIR DUCTINGSection |
page L4
cooling and ventilation
REMOTE RADIATOR COOLING
re
ypasunse
rooruve_| fk V5Section J
page J.1
Fuel Oil Systems
Unless otherwise requested, all diesel engines that we
use on our sets are designed to run on Class A fuel tothe
current 8.5.8. 2869
With al fuel oil installations local regulations have to
be checked, most local regulations allow fora storage of
200 litres stored in one room with precautions, The
G.LC. Department of Architecture and Civic Design
approval under the London Bullding Acts 1930-1978
and/or the London Building (construction) by-laws,
1972-74 states as follows:
“Note: no objection will be raised to the inclusion
within the chamber of a diesel oll storage tank or tanks.
having an aggregate capacity not greater than 900 litres
(198 gallons)
Where the storage capacity is between 180 ftres (40
gallons) and 450 litres (100 gallons) foil the encosing
Walls and floors of the chamber shall have a standard of
fire resistance of not less than two hours and the access
doorway shall be fitted with a Class C door.
Where the storage capacity exceeds 450 litres (100
gallons) the enclosing walls and floors shall have a
standard of fie resistance of notless than fourhoursand
the Class Caccessdoor shallbeofatype incorporatingan
insulating material to limit the transmission of heat
In each case a’ suitable catchpit shall be formed
beneath the tank, or tanks, having a capacity not less
than ten per ent greater than the capacity of the tank, or
tanks.”
“The capacity ofthe fuel oil anks must be based on the
size of set etc., as a guide for assessment purposes only
take 0.3 litres of fuel per kilowatt hour, at full load is a
general rough guide for sizing bulk ‘storage tanks.
Actual fuel consumption figures given on request (see
Section A).
Fuol Lift Pumps:
When positioning the daily service tank awayfromthe
set, care must be taken that the engine fuel lft pumps
can supply the fuel pump. Most engine lift pumps will
draw the fuel up 1.2m maximum lift, also the spill return,
from the filters and injectors should not rise more than,
2.4m and return into the bottom of the tank. The above
‘would apply if the fuel was drawn directfrom abulktank
Bulk Storage Tanks:
‘Where bulk storage is required, the most simple and
economical method is to install the tank adjacent to the.
engine room. On gravity feed systems transfer of fuel oil
from the bulk storage tank to the service tank should be
via a float switch and solenoid valve asa safety precau-
tion against the bulk tankbeing commonedtotheservice
tank, The overflow/vent pipe should be taken back tothe
bulk tank ensuring that itis routed back above the height
‘of both tanks with a fall to the bulk tank.
‘Where the bulk tank is lower than the service tank, a
ssemi-rotary hand pump can be used, orifthefuelstorage
tanks are sited t00 far from the service tank for a semi:
rotary pump to operateefficiently anelectricfueltransfer
pump can be used, this can be fully automatic and work
off afloat switch in the service tank. Werecommendihat,
the pump be positioned at the bulk tank, thereby pushing
{as against lifting the fuel oil. Again on this system an,fuel oil systems
overtiow/vent shouldbe installedasasafeguardagainst
‘overflowing and of pressuring the service tank in the
event of float switch failure,
Bulk storage tanks should have a sludge cock at the
lowest point for drawing off sludge and water. The fuel
supply take off shouldbe atleast 75mmabovethe sludge
‘cock preferably at the other end of the tank.
Fitter
Precautions should be taken against the ingressof dirt
‘and water into the tank anda Tiler shouldbe fittedon the
‘draw off line, this should be a mesh type and not coarser
than 120 mesh,
Fire Regulations:
‘Where bulk fuel storage tanksare installedin business
premises, the Local Council fireprotection requirements
usually insist on the fitting of freefall fire shut-off valves
tothe tank outlet pipes andthe erection of anoiltight spill
wall around the tank to retain its contents in a
controllable area should damage to the tank occur.
Insome instances ocalauthoritiesalsorequirethatan
‘automatic warning system be fitted to indicate when the.
tank is full during re-fuelling.
Provision should always be made for cleaning out the
bulk fuel storage tank when necessary.
‘We strongly recommend inall instances that the local
District Surveyors advice be sought before installation
begins.
Section J
page J.2
Typical Specification for Bulk Storage Fuel Tanks
Tanks are manufactured in accordance with B.S,2594
and are fabricated in accordance from good commercial
quality mild steel plate of 6mm thickness. Enddishedand
flanged. electrically welded throughout and spatter
removed,
Fitted with one 450 mm (18") dia raised manhole with
joint and 9mm thick bolted on cover.
BS.PT. connections are provided for:— Fill, Vent,
TYPICAL DIMENSIONS OF BULK
FUEL STORAGE TANKS
{CYLINDRICAL TYPE}
&
sue ry
Note: For standby generators free standing ar set mounted fuel tanks are recommended and should be installed
sufficiently high enough to provide a head at the engine fuel lift pump. This will improve the reliablity of fuel
supply.
SUGGESTED INSTALLATION FOR BULK AND SET TANKS
FIG.1say
Section J
page J.3
fuel oil systems
GRAVITY FEED FUEL TRANSFER SUPPLY SYSTEM
FIG.2
FIG.3
REMOTE FUEL TRANSFER SYSTEM-
|
FL
eitfuel oil systems
Section J
page Ja
STANDARD PETBOW FUEL TANKS
FIG.4
FIG.5
FREE STANDING DAY TANKS.Interconnecting Cables
‘The cross sectional area of interconnecting cables
between the set and the change over (or transfer) cubicle
‘or the customers distribution panel is governed by the
capacity of the set and must be adequate to carry out the
full rated continuous output of the alternator. We
recommend the use of mult-cored P.V.C. SWA. PV.C.
cable between the set and panel, but the final connection
to the altemator terminal box must be in flexible cable.
We recommend that a separate terminal box be mounted
close to the set into which the PV.C. SW.A. PC. cable/s
are terminated, short flexible cable tails are then installed
to the alternator.
\Where trunking or conduit is preferred care should be
taken that a short flexible piece is connected to the
alternator to allow for movement of the set on its
resilient mountings.
Mains failure — set mounted panel (system 2)
(On sets where the control panel is mounted on the set all
control and power cables are cabled in and only require
the customer to supply the mains input and load output
cables to the terminals provided in the panel. The change
‘over contactors and ail the auto start equipment and
batteries are supplied on a standard set. Cable entry is,
through the bottom of the panel and either armoured or
flexible cable can be used.
Mains failure — free standing panel (system 3)
On sets where there is a free standing control panel the
cable work required by the customer is from the terminal
box on the alternator to the control panel
Control cables also originate from this terminal box and,
are normally run in muiti-core cables.
‘Care should be taken not to run A.C. and D.C. in the same
multi-core cable.
The output cable is run from the altemator terminal box to
the control panel terminals.
IfPV.C. SWA. PX.C. armoured cable is to be used a
‘separately mounted load terminal box must be included.
Flexible cable from the alternator box to the load box must
be used and the armoured cable terminated in the same
load box.
‘Mains Failure Sets should have an isolator switch in the
‘company mains supply to the sets control cubicle ingoing
terminals as no maintenance engineer can be expected to
work on a set that is partially live.
By-pass Switches
‘Special By-Pass Switches can be provided that will enable
the mains supply to be isolated from the control cubicle
and connected direct to the protected load, to avoid the
necessity for a shut down during maintenance periods,
The switches are available in two forms. The first is a rotary
three or four pole type housed either in a wall mounting
Flexible cables from alternator box to load
connection boxes on 1.5 m W sets.
Flexible cables feed straight into alternator terminal
box on 200 Kw sets.Interconnecting Cables
Section K
Page K2
sheet steel box or installed in the Petbow mains failure
control cubicle. These are normally used with automatic,
‘mains failure sets with outputs of up to 400 amps.
‘The second is a flush mounted three pole or four pole type
‘switch (or two/three pole with neutral) with interlocks and
housed in a separate free standing sheet steel cubicle
attached to the Petbow mains failure control cubicle.
These are generally used on mains failure sets-of outputs
above 400 amps up to 1200 amps.
Heater and battery charger connections
‘A small and separate terminal box mounted on the side of
the generator houses these connections. A mains supply
of normally 220-230 volts is required.
Cable entry
Except where otherwise shown all cable entries are routed
in through the base of the control cubicles (applicable to
systems 2 & 3). Where underfloor cable runs are
impracticable the cables can be run overhead and brought
‘down to the bottom of the panel. Alternatively special
provision can be made for the top entry but will usually
result in a large control cubicte.
Mains failure free standing control panel and by-pass
switch.
Typical mains failure systems.
ZZ
ieee?
a! —
es seses
O BWBaror
CB faa
besis
Cable mains failure or
: electric start Section K
connections — systems. Page K3
Flexible cable must be used between
Joad box and alternator terminal box. faq
Electric start
or mains
Free standing
Lae mney mains failure
oo control cubicle
with changeover
coneaix 130 0) nce
terminal box. |X’ . customers load
distribution board. System 1:
= Tey 1 Note:
Toad terminal box must bé"| [TESST TT Iflexible cable Is used between
“used if connecting cable Is:-> : aes ‘mains failure contro! cubicle/
PVC swa PVC. & sor distribution board and generator, a
eb load terminal box is un-necessary.
‘Customers distribution board.
‘Aulomatic i
mains failure
contro! system|
with
changeover
cubicle,
= System 2:
Mains failure systems with set
S mounted control and changeover
: cubicles.
Cable can be flexible or armoured.