Professional Documents
Culture Documents
Revision B
April 2012
Operator’s Manual
EN Operator’s Manual
ES Manual Del Operador
FR
Manuel De L’opérateur
PT Manual do Operador
PRINT LANGUAGE
ENGLISH
SPANISH
FRENCH
PORTUGUESES
3.0 WARRANTY
The Company warrants that the equipment manufactured by THE COMPANY MAKES NO OTHER WARRANTY OR
it and delivered hereunder will be free of defects in material REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED
and workmanship for a period of twelve months from the OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED
date of placing the Equipment in operation or eighteen WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
months from the date of shipment from the factory, PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
whichever shall first occur. The Purchaser shall be obligated
Correction by the Company of nonconformities whether
to promptly report any failure to conform to this warranty,
patent or latent, in the manner and for the period of time
in writing to the Company in said period, whereupon the
provided above, shall constitute fulfilment of all liabilities of
Company shall, at its option, correct such nonconformity, by
the Company for such nonconformities whether based on
suitable repair to such equipment or, furnish a replacement
contract, warranty negligence, indemnity, strict liability or
part F.O.B. point of shipment, provided the Purchaser has
otherwise with respect to or arising out of such Equipment.
stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has The Purchaser shall not operate Equipment which is
complied with specific recommendations of the Company. considered to be defective, without first notifying the
Accessories or equipment furnished by the Company, but Company in writing of its intention to do so. Any such use of
manufactured by others, shall carry whatever warranty the Equipment will be at Purchaser’s sole risk and liability.
manufacturers have conveyed to the Company and which
Note that this is Ingersoll Rand standard warranty. Any
can be passed on to the Purchaser. The Company shall not
warranty in force at the time of purchase of the equipment
be liable for any repairs, replacements, or adjustments to the
or negotiated as part of the purchase order may take
Equipment or any costs of labor performed by the Purchaser
precedence over this warranty.
or others without Company’s prior written approval.
The effects of corrosion, erosion and normal wear and tear
are specifically excluded. Performance warranties are limited
to those specifically stated within the Company’s proposal.
Unless responsibility for meeting such performance
warranties are limited to specified tests, the Company’s
obligation shall be to correct in the manner and for the
period of time provided above.
HIGH VOLTAGE
7.1 INTRODUCTION • After running the dryer under full rated flow for
approximately 30 minutes, verify that when the
Ingersoll Rand non-cycling dryers remove moisture from solenoid drain on each module opens, all of the
compressed air by cooing the air to a low temperature. This accumulated liquid is discharged and is then followed
causes water vapor to condense into water droplets that by a small burst of air.
can then be easily removed from the air. The dryer consists
of two (2) or more Air/Refrigeration Modules. All modules • If a small amount of liquid and a large amount of air is
are connected by common Inlet and Outlet Headers. discharged, decrease the on-time setting or increase
The major systems of the dryer are: Air System; Moisture the off-time setting. If there is all liquid and no air is
Removal System; Refrigeration System; Controls System. The discharged, increase the on-time setting or decrease
following sections describe each of the systems in detail. the off-time setting.
550207
550208
Ingersoll Rand Refrigerated Compressed Air Dryers are • Turning the adjustment screw clockwise raises suction
equipped with a Microprocessor Controller. This advanced pressure and exchanger temperature.
microprocessor-based Controller has been engineered by • Turning the adjustment screw counter-clockwise
Ingersoll Rand for use with Ingersoll Rand Compressed Air reduces suction pressure and exchanger temperature.
Dryers.
• All adjustments should be made without air flow
For Non-Cycling dryers, the Controller displays the (load) on the dryer.
temperature of the air at the coldest point in the air stream,
providing an indication of the outlet pressure dew point of ADJUSTMENT SCREW
the dryer. In addition, the Controller permits monitoring of
ADJUSTMENT SCREW
dryer parameters and enunciation of alarm conditions.
LOCKING NUT
The list below summarizes the features of the Controller:
• 2 X 16 Character Backlit LCD Display: Easy-to
read display provides continuous indication of
dryer default parameter. Standard backlight
permits viewing of critical information in low light
environments.
• Electronic Drain with On/Off Time Adjustment:
Included with dryer is a solenoid drain valve. Control
of the open and close time of the valve is set via the
Controller.
• Remote Start / Stop: The Controller offers a unique
remote start / stop feature. This feature allows the Figure 2 - HOT GAS BYPASS VALVE
dryer to be operated via a remote user-supplied D5525IN
switch.
• Remote Alarm Contact: Controller includes a remote
alarm contact to provide indication of any of the
dryers alarms described later in this manual. Contact
rated for 2A / 120V max.
The Controller features three levels of access. The default
level CUSTOMER MODE permits adjustment of dryer
parameters to address seasonal variations for drain. A
protected TECHNICIAN MODE permits access to and
manipulation of additional parameters to address the initial
machine set up. A password protected FACTORY MODE
is also included for use by Factory Service Personnel for
troubleshooting the dryer.
Ingersoll Rand non-cycling dryers include a Hot Gas By-
Pass Valve to maintain suction pressure and temperature.
Refer to Figure 2. This valve is necessary during low load
applications to prevent freeze-up in the chiller section. The ADJUSTMENT SCREW
normal suction pressure for no load conditions should never
drop below 72 psig. This setting may need adjustment to Figure 2 - HOT GAS BYPASS VALVE
match the load/ambient conditions encountered. D6800IN-D13600IN
NOTICE
This adjustment is not a procedure covered under Do not rotate Hot Gas By-Pass Valve adjustment
warranty as it is typically required for application- fully clockwise. Full clockwise rotation may result in
specific conditions. refrigerant compressor damage. Any suction pressure
setting above 90 psig is not recommended.
SELECT
DISPLAY End Cust Set Pts
12 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN
Press SELECT DISPLAY as necessary to display the End
ingersollrandproducts.com
Customer Set points Screen.
ENTER DRN INT:5 min
7.0 PRINCIPLES OF OPERATION
Pressing “ENTER” saves the set point.
PRE-FILTER
FIGURE 5
TYPICAL PIPING ARRANGEMENT
Drain connections should be piped to an appropriate that not more than one device be connected to a single
reservoir or container. It is recommended that a properly- valve due to the pressure differential between the two
sized oil / water separator be installed to comply with EPA devices.
regulations for waster water disposal. It is recommended
8.8 INITIAL START-UP Anti-short cycle delay and crankcase heater delay have
timed out, the refrigeration system will energize.
NOTICE After the alarm delay, provided the Chiller Temperature is
For water cooled models, the water valve must be greater than the HIGH TEMPERATURE ALARM set point, the
manually opened to ensure that the condenser is full dryer will go into HIGH TEMPERATURE ALARM. The LCD panel
of water prior to start-up. will indicate the alarm and the refrigeration system will
continue to operate. Pressing the SELECT DISPLAY button
will permit viewing of the available dryer parameters during
this alarm condition. Note that the alarm condition screen
Allow 8 hours of warm-up time for the crankcase heater will reappear after approximately 30 seconds until the alarm
prior to start up. Crankcase heater is connected directly condition is cleared.
to the incoming power and is energized at all times.
The CHILLER TEMPERATURE will gradually drop as indicated
8.8.1 START- UP SEQUENCE on the display. Once the temperature falls below the HIGH
TEMPERATURE ALARM set point, the alarm will reset and the
Apply power to dryer. LCD Panel will illuminate. The Anti- LCD panel will return to its default display. Air flow may be
Short Cycle delay will commence counting down. Remaining slowly introduced to the dryer.
time on the Crankcase heater will also countdown.
NOTICE
NOTICE If power is removed from the dryer for less than two
After installation or a prolonged shutdown, start the hours, the crankcase heater delay will be automatically
dryer with no air load (no air flow). This enables the bypassed. If, however, the power is removed from
dryer to reach its proper operating temperature in the the dryer for more than two hours, the full crankcase
shortest time possible. heater delay must be observed.
Start Dryer, using one of the following methods, depending
on Start Mode setting:
• Manual Mode - Press the ON pushbutton.
• Auto Restart Mode - No additional action required
• Remote Automatic Mode - Close the remote contact.
For proper operation, it is essential that the air cooled Certain filters contain multiple elements. When replacing
condenser fins are free of dirt and dust. Regular cleaning is filter elements, all elements should be replaced
therefore required. simultaneously. Mixing new and old elements can result in
reduced air quality.
9.3 CONDENSATE DISCHARGE SYSTEM
ABLE
Pressing the “2” and “3” buttons simultaneously enters the
In TECHNICIAN MODE, the following parameters can be TECHNICIANMODE.
viewed but not changed:
WARNING
SELECT
Changing the AUTO RESTART feature to “Y” will permit DISPLAY BEGIN ALARM LIST
the dryer to operate automatically once power is
applied and after a brief delay. Proper warning signs Depressing the SELECT DISPLAY list displays the ALARM
should be affixed to the dryer to alert users and service LIST screen at the top of the ALARM LIST.
personnel that dryer may start without warning.
Failure to do so may result in serious injury.
The Alarm List will repeat as many times as the SELECT
SELECT DISPLAY button is depressed. To EXIT the ALARM LIST,
DISPLAY END TECH SET PTS perform the following:
11.1 INTRODUCTION
Ingersoll Rand multiple module dryers are designed for reliable, trouble-free operation. In the event of any dryer
malfunction, the guide below has been developed to facilitate problem identification and corrective actions.
WARNING WARNING
An air dryer always operates under pressure. Any Prior to working on the unit, make sure that all circuit
maintenance procedure that involves disassembly of breakers or disconnected switches are tagged “Out of
pipe fittings, valves or any other components requires Service.”
the dryer be isolated from the compressed air stream
and fully depressurized. NOTICE
Any in-depth troubleshooting should only be done by
qualified service technicians. Prior to performing any
significant corrective action, consult factory.
More than one condensate source Reroute condensate to eliminate secondary path. Install
connected providing alternative path check valves as required.
for condensate.
Air bleed from conden- Debris trapped under seal. Damage Press and hold the test button to clear (drain valve will
sate drain outlet port to seal. open). Replace seal with Service Kit.
550212A
D5525IN
550213A
D6800IN
550214A
D8160IN
550215A
D10200IN
550215A
D10200IN
550216A
D13600IN
550216A
D13600IN
3.12
2.50
MODULE 1 MODULE 2
100.00
A
90.38
B
72.00
O .62 MTG HOLES 4 PLCS 3.00 TYP 1.62 RIGGING HOLES TYP 3.00 TYP
64.75 5.25 86.00
75.38 91.25
ingersollrandproducts.com
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
LCD DISPLAY
13.0 GENERAL ARRANGEMENT
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
AIR TREATMENT 5) PERCENT SAVINGS
CONTROL SYSTEM 6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
8) CUSTOMER SET POINTS
DRYER ON-OFF
SWITCH
DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT
SWITCH (TYP)
GENERAL ARRANGEMENT
D5525IN-D8160IN
NEMA-1
550197
31
13.0 GENERAL ARRANGEMENT
GENERAL ARRANGEMENT
D5525IN-D8160IN
(2 PLCS)
NEMA-1
550197
REAR VIEW
3.12
2.50
MODULE 1 MODULE 2
100.00
A
90.38
B
72.00
4.75
10.79
O .62 MTG HOLES 4 PLCS 3.00 TYP 1.62 RIGGING HOLES TYP 3.00 TYP 3.00
64.75 86.00
1-1/2" MPT WATER
75.38 INLET CUSTOMER 91.25
ingersollrandproducts.com
CONNECTION
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
LCD DISPLAY
13.0 GENERAL ARRANGEMENT
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
AIR TREATMENT 5) PERCENT SAVINGS
CONTROL SYSTEM 6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
8) CUSTOMER SET POINTS
DRYER ON-OFF
SWITCH
DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT
33
13.0 GENERAL ARRANGEMENT
NEMA-1
550201
REAR VIEW
2.00
101.25
A
90.38
B
72.00
ingersollrandproducts.com
LCD DISPLAY
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
AIR TREATMENT 4) DRAIN ON
5) PERCENT SAVINGS
13.0 GENERAL ARRANGEMENT
CONTROL SYSTEM
6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
DRYER ON-OFF 8) CUSTOMER SET POINTS
SWITCH
DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT
POWER ON LIGHT SWITCH (TYP)
PUSHBUTTONS
DETAIL B 1) ON
DRYER FAULT ALARM LIGHT 2) OFF
GENERAL ARRANGEMENT
D10200IN WATER COOLED
NEMA-1
550202
35
13.0 GENERAL ARRANGEMENT
NEMA-1
550202
REAR VIEW
3.12
2.88
102.25
A
90.38 B
72.00
ingersollrandproducts.com
LCD DISPLAY
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
13.0 GENERAL ARRANGEMENT
DRYER AUTO-MANUAL-REMOTE
SWITCH MODULE DISCONNECT
SWITCH (TYP)
POWER ON LIGHT DETAIL B PUSHBUTTONS
1) ON
2) OFF
GENERAL ARRANGEMENT
D13600IN WATER COOLED
NEMA-1
550203
37
13.0 GENERAL ARRANGEMENT
NEMA-1
550203
REAR VIEW