You are on page 1of 44

80446115

Revision B
April 2012

Non-cycling Refrigerated Dryer


Models D5525IN - D13600IN

Operator’s Manual

EN Operator’s Manual
ES Manual Del Operador
FR
Manuel De L’opérateur
PT Manual do Operador

PRINT LANGUAGE

ENGLISH

SPANISH

FRENCH

PORTUGUESES

Save These Instructions


1.0 contents
contents page contents page

1.0 contents 3 9.0 MAINTENANCE AND SYSTEM CHECK 20


2.0 INTRODUCTION 4 9.1 INTRODUCTION 20
3.0 WARRANTY 4 9.2 REFRIGERANT CONDENSER 20
4.0 REFRIGERATED DRYER NOMENCLATURE 4 9.3 CONDENSATE DISCHARGE
5.0 RECEIVING AND INSPECTION 5 SYSTEM 20
5.1 INSPECTION 5 9.4 PRE-FILTERS AND POST-FILTERS 20
5.2 HANDLING 5 10.0 TECHNICIAN MODE 21
6.0 SAFETY AND OPERATION PRECAUTIONS 5 10.1 ENTERING TECHNICIAN MODE 21
7.0 PRINCIPLES OF OPERATION 7 10.2 ALARM LIST 22
7.1 INTRODUCTION 7 11.0 TROUBLESHOOTING 23
7.2 AIR SYSTEM 7 11.1 INTRODUCTION 23
7.3 MOISTURE REMOVAL SYSTEM 7 12.0 WIRING DIAGRAMS 25
7.4 REFRIGERATION SYSTEM 7 13.0 GENERAL ARRANGEMENT 32
7.5 CONTROLS 11 14.0 REPLACEMENT PARTS 40
7.5.1 BASIC USER INTERFACE 12 14.0 REPLACEMENT PARTS 42
7.5.2 DISPLAY PARAMETERS 13 15.0 ENGINEERING SPECIFICATIONS 42
7.5.3 DRYER SET POINTS AND ALARMS 13
7.5.4 ADJUSTING SET POINTS 13
7.5.5 ALARMS AND THEIR FUNCTIONS 14
7.5.6 START MODES 14
7.5.6.1 Manual Mode 14
7.5.6.2 Auto Restart Mode 15
7.5.6.3 Remote Automatic Mode 15
8.0 INSTALLATION AND INITIAL START-UP 16
8.1 LOCATING EQUIPMENT 16
8.2 OFFLOADING / LIFTING THE DRYER 16
8.3 INSTALLATION OF AIR PIPING 17
8.4 PIPING AND VALVES 17
8.5 FILTRATION 18
8.6 ELECTRICAL CONNECTION 18
8.7 PRE START-UP AND SYSTEM
LEAK CHECK 18
8.8 INITIAL START-UP 19
8.8.1 START- UP SEQUENCE 19

 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
2.0 INTRODUCTION
The Ingersoll Rand refrigerated air dryer removes moisture, installed into various pneumatic systems in which dry air is
oil vapor, and other contaminants from compressed air. required or desired. Please refer to Principles of Operation for
These contaminants are detrimental to pneumatically complete operating details.
operated appliances, controls, instruments, machinery
Ingersoll Rand recommends that this technical manual be
and tools. This is accomplished by cooling the air with a
thoroughly reviewed prior to start up.
refrigeration unit to a temperature at which moisture in
the air is condensed and separated from the airstream. Original instructions are in English. Other languages are a
The temperature the air is cooled to, normally between 36 translation of the original instructions.
and 40°F, is known as dew point. This dryer can be easily

3.0 WARRANTY
The Company warrants that the equipment manufactured by THE COMPANY MAKES NO OTHER WARRANTY OR
it and delivered hereunder will be free of defects in material REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED
and workmanship for a period of twelve months from the OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED
date of placing the Equipment in operation or eighteen WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
months from the date of shipment from the factory, PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
whichever shall first occur. The Purchaser shall be obligated
Correction by the Company of nonconformities whether
to promptly report any failure to conform to this warranty,
patent or latent, in the manner and for the period of time
in writing to the Company in said period, whereupon the
provided above, shall constitute fulfilment of all liabilities of
Company shall, at its option, correct such nonconformity, by
the Company for such nonconformities whether based on
suitable repair to such equipment or, furnish a replacement
contract, warranty negligence, indemnity, strict liability or
part F.O.B. point of shipment, provided the Purchaser has
otherwise with respect to or arising out of such Equipment.
stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has The Purchaser shall not operate Equipment which is
complied with specific recommendations of the Company. considered to be defective, without first notifying the
Accessories or equipment furnished by the Company, but Company in writing of its intention to do so. Any such use of
manufactured by others, shall carry whatever warranty the Equipment will be at Purchaser’s sole risk and liability.
manufacturers have conveyed to the Company and which
Note that this is Ingersoll Rand standard warranty. Any
can be passed on to the Purchaser. The Company shall not
warranty in force at the time of purchase of the equipment
be liable for any repairs, replacements, or adjustments to the
or negotiated as part of the purchase order may take
Equipment or any costs of labor performed by the Purchaser
precedence over this warranty.
or others without Company’s prior written approval.
The effects of corrosion, erosion and normal wear and tear
are specifically excluded. Performance warranties are limited
to those specifically stated within the Company’s proposal.
Unless responsibility for meeting such performance
warranties are limited to specified tests, the Company’s
obligation shall be to correct in the manner and for the
period of time provided above.

4.0 REFRIGERATED DRYER NOMENCLATURE


DRYER NOMINAL* Ingersoll Rand CONDENSER POWER RATING CONVERSION CHART
FLOW (m³/hr) NON-CYCLING TYPE
D 5525-13,600 IN A = AIR 4 = 460-3-60 1 = NEMA 1 5525 Nm³/hr = 3250 SCFM
W = WATER 6 = 575-3-60 H = NEMA 4 6800 Nm³/hr = 4000 SCFM
8160 Nm³/hr = 4800 SCFM
10,200 Nm³/hr = 6000 SCFM
13,600 Nm³/hr = 8000 SCFM

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 


ingersollrandproducts.com
5.0 RECEIVING AND INSPECTION
The unit should be thoroughly inspected immediately upon 5.2 HANDLING
delivery by the carrier. The unit should be placed in an open
area to allow inspection from all sides. Examine the unit All uncrated multiple module refrigerated air dryer units
for physical signs of damage or mishandling such as bent should be moved with great care. Be sure the lifting
support members, misaligned piping or control components. equipment and hoists are rated to lift and move such
Report all discrepancies on shipping documents. weight. Slings can be used as long as those safety features
mentioned above are abided by. Rigging holes are provided
Any indication of potentially rough handling by the carrier for hoist and spreader bar transporting as well as crane
should be noted on the delivery receipt especially if the movement. Do not allow chains and slings to bear on sheet
dryer will not be immediately uncrated. Obtaining the metal.
delivery man’s signed agreement to any noted damages will
facilitate any future insurance claims. WARNING
5.1 INSPECTION Multiple module refrigerated air dryers require
specific offloading procedures to avoid damage to the
All models are wrapped in protective plastic to protect dryer or personal injury. Before offloading dryer, refer
fragile components. Carefully remove the protective wrap to Section 8.2.
from the dryer, paying particular attention not to damage
dryer components during the removal process.
WARNING
Under no circumstances should any person attempt
to lift heavy objects without proper lifting equipment
(i.e., crane, hoist, slings or fork truck). Lifting any unit
without proper lifting equipment, can cause serious
injury.

6.0 SAFETY AND OPERATION PRECAUTIONS


Because an air dryer is pressurized and contains rotating
OSHA
parts, the same precautions should be observed as with
Heading Descriptions
any piece of machinery of this type where carelessness in
operation or maintenance could be hazardous to personnel.
In addition to obvious safety rules that should be followed WARNING
with this type of machinery, safety precautions as listed “Warning” is used to indicate a hazardous situation which has some
below must be observed: probability of death or severe injury. Warning should not be considered
for property damage accidents unless personal injury risk is present.

1. Only qualified personnel shall be permitted to adjust, CAUTION


perform maintenance or repair this air dryer. “Caution” is used to indicate a hazardous situation which may result in
minor or moderate injury.
2. Read all instructions completely before operating
unit. NOTICE
3. Pull main electrical disconnect switch and disconnect “Notice” is used to indicate a statement of company policy as the
message relates directly or indirectly to the safety of personnel or
any separate control lines, if used, before attempting protection of property. Notice should not be associated directly with a
to work or perform maintenance on the unit. hazard or hazardous situation and must not be used in place of
“Danger,” “Warning,” or “Caution.”
4. Do not attempt to service any part while machine is in
an operational mode. NOTICE
The user of any air dryer manufactured by Ingersoll Rand, is hereby
5. Do not attempt to remove any parts without first
warned that failure to follow the above Safety and Operation
relieving the entire air system of pressure. Precautions may result in personal injury or equipment damage.
However, Ingersoll Rand does not state as fact, nor does it mean to
6. Do not operate the dryer at pressures in excess of its imply, that the preceding list of Safety and Operating Precautions is all
rating. inclusive, and further, that the observance of this list will prevent all
personal injury or equipment damage.
7. Do not operate the dryer without guards, shields and
screen in place.
8. Inspect unit daily to observe and correct any unsafe
operating conditions.

 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
6.0 SAFETY AND OPERATION PRECAUTIONS

Removing fuses will not disconnect


power from dryer. Always disconnect
power from ALL sources before
performing service.
READ TECHNICAL MANUAL

Air Under Pressure Will Cause


Injury, Death Or Property Damage.
• Do Not Exceed Pressure Rating.
• Relieve Press. Before Servicing. FAN MAY AUTOMATICALLY
• Do Not Modify/Repair/Rework START AT ANY TIME
ASME Coded Pressure Vessels
As Insurance Rating Affected.

READ TECHNICAL MANUAL

HIGH VOLTAGE

This unit is charged with


refrigerant under high pressure.

Air Under Pressure Will Cause


Injury, Death Or Property Damage.
• Relieve Press. Before Servicing.
• Condensate Drain Discharges
Under Pressure.
• Drain Requires Periodic
Cleaning (Service).

READ TECHNICAL MANUAL

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION

7.1 INTRODUCTION • After running the dryer under full rated flow for
approximately 30 minutes, verify that when the
Ingersoll Rand non-cycling dryers remove moisture from solenoid drain on each module opens, all of the
compressed air by cooing the air to a low temperature. This accumulated liquid is discharged and is then followed
causes water vapor to condense into water droplets that by a small burst of air.
can then be easily removed from the air. The dryer consists
of two (2) or more Air/Refrigeration Modules. All modules • If a small amount of liquid and a large amount of air is
are connected by common Inlet and Outlet Headers. discharged, decrease the on-time setting or increase
The major systems of the dryer are: Air System; Moisture the off-time setting. If there is all liquid and no air is
Removal System; Refrigeration System; Controls System. The discharged, increase the on-time setting or decrease
following sections describe each of the systems in detail. the off-time setting.

7.2 AIR SYSTEM


• The on/off-time settings will vary accordingly to
seasonal conditions. During the summer when more
The Air System for each module consists of the dryer moisture is present in the air system, a shorter on-
components that are in contact with the compressed time that increases the valve opening frequency is
air. Referring to the PROCESS AND INSTRUMENTATION required. A longer off-time may be used during the
DIAGRAMS and following the bold “PROCESS AIR” path winter months when moisture levels are lower. Adjust
indication, hot saturated air from the air compressor enters drain valve timing on each module accordingly.
the common inlet header and is distributed among the
7.4 REFRIGERATION SYSTEM
precooler/reheaters in the modules. Here, cool air exiting
the air/moisture separator cools the incoming air prior The Refrigeration System consists of all the components
to it entering the evaporator. The air then goes into the which handle refrigerant R-404A in each module. These
evaporator section where it is further cooled through are hermetically sealed closed-loop systems. Referring
direct heat transfer with evaporating refrigerant. The air to the PROCESS AND INSTRUMENTATION DIAGRAMS and
continues to the separator where the moisture is removed, following the dot-dash “REFRIGERANT” path indication
thereby allowing cool, dry air to return to the precooler/ for each module, refrigerant is shown leaving the chiller
reheater where the temperature is elevated by the warm, evaporator section, which in the process of removing heat
incoming process air. Air exiting the reheater portion of each is changed from a low pressure liquid to a low pressure gas.
module should be approximately 15-20 deg. F lower than This gas enters the suction side of the compressor where it
the incoming process air temperature based on standard is compressed into a high pressure gas. The high pressure
conditions at full rated flow. Dry air from each module is gas is cooled in the condenser section to become a high
collected in the common outlet header before leaving the pressure liquid. It then goes through a permanent filter-dryer
dryer. that ensures the refrigerant system is free of contaminants. A
thermostatic expansion valve meters the refrigerant into the
7.3 MOISTURE REMOVAL SYSTEM chiller’s evaporator. The pressure is reduced upon entering
Liquid droplets are removed from the air stream in the the chiller evaporator where it removes heat from the air
separator located in each module. As the air and liquid system. When there are low loads (low air flow rate or low
mixture passes through the separator it spins, slows down inlet temperature), a hot gas valve by-passes the condenser
and then changes direction. This causes condensate to and the thermostatic expansion valve on each module. This
fall out of the air stream and collect in the bottom of the valve maintains a minimum evaporator pressure of 76 psig,
separator. The collected liquid is removed from the separator which corresponds to a chiller temperature of 34 °F, thus
by the solenoid valve that is located on each module and is preventing freeze-up.
controlled by the Microprocessor Controller on each module.
For adjustment please note the following:
• To obtain the optimum time values for operation
of the electric drain valve located on each module,
set the drain closed time to five minutes and the
open time to five seconds. Refer to Section 7.5.4 for
details about accessing CUSTOMER MODE in the
Microprocessor Control System to adjust Drain Set
Points.

 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION

PROCESS AND INSTRUMENTATION DIAGRAM


D3250IN, D6800IN, D8160IN
AIR & WATER COOLED
550206

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION

PROCESS & INSTRUMENTATION DIAGRAM

AIR & WATER COOLED


D10200IN

550207

 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION

PROCESS & INSTRUMENTATION DIAGRAM

AIR & WATER COOLED


D13600IN

550208

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION
7.5 CONTROLS For Hot Gas By-Pass Valve adjustment, note the following:

Ingersoll Rand Refrigerated Compressed Air Dryers are • Turning the adjustment screw clockwise raises suction
equipped with a Microprocessor Controller. This advanced pressure and exchanger temperature.
microprocessor-based Controller has been engineered by • Turning the adjustment screw counter-clockwise
Ingersoll Rand for use with Ingersoll Rand Compressed Air reduces suction pressure and exchanger temperature.
Dryers.
• All adjustments should be made without air flow
For Non-Cycling dryers, the Controller displays the (load) on the dryer.
temperature of the air at the coldest point in the air stream,
providing an indication of the outlet pressure dew point of ADJUSTMENT SCREW
the dryer. In addition, the Controller permits monitoring of
ADJUSTMENT SCREW
dryer parameters and enunciation of alarm conditions.
LOCKING NUT
The list below summarizes the features of the Controller:
• 2 X 16 Character Backlit LCD Display: Easy-to
read display provides continuous indication of
dryer default parameter. Standard backlight
permits viewing of critical information in low light
environments.
• Electronic Drain with On/Off Time Adjustment:
Included with dryer is a solenoid drain valve. Control
of the open and close time of the valve is set via the
Controller.
• Remote Start / Stop: The Controller offers a unique
remote start / stop feature. This feature allows the Figure 2 - HOT GAS BYPASS VALVE
dryer to be operated via a remote user-supplied D5525IN
switch.
• Remote Alarm Contact: Controller includes a remote
alarm contact to provide indication of any of the
dryers alarms described later in this manual. Contact
rated for 2A / 120V max.
The Controller features three levels of access. The default
level CUSTOMER MODE permits adjustment of dryer
parameters to address seasonal variations for drain. A
protected TECHNICIAN MODE permits access to and
manipulation of additional parameters to address the initial
machine set up. A password protected FACTORY MODE
is also included for use by Factory Service Personnel for
troubleshooting the dryer.
Ingersoll Rand non-cycling dryers include a Hot Gas By-
Pass Valve to maintain suction pressure and temperature.
Refer to Figure 2. This valve is necessary during low load
applications to prevent freeze-up in the chiller section. The ADJUSTMENT SCREW
normal suction pressure for no load conditions should never
drop below 72 psig. This setting may need adjustment to Figure 2 - HOT GAS BYPASS VALVE
match the load/ambient conditions encountered. D6800IN-D13600IN

NOTICE
This adjustment is not a procedure covered under Do not rotate Hot Gas By-Pass Valve adjustment
warranty as it is typically required for application- fully clockwise. Full clockwise rotation may result in
specific conditions. refrigerant compressor damage. Any suction pressure
setting above 90 psig is not recommended.

10 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION
Ingersoll Rand air cooled models utilize a microprocessor-
NOTICE
controlled fan contactor to control the condensing
temperature. This contactor controls the condensing Verify that there is an adequate volume of water for
temperature by cycling the fan based on refrigerant dryer demand.
discharge pressure. When the unit reaches 275 psig, the
microprocessor energizes the fan contactor that will run the 7.5.1 BASIC USER INTERFACE
primary fan until the discharge pressure is reduced to 195 The Microprocessor Control display provides the user with
psig. Should the discharge pressure continue to rise, the the operating parameters and their corresponding values.
remaining fan(s) will energize at 335 psig and continue to When power is supplied to the dryer, the Microprocessor
operate until the discharge pressure has been reduced to Control will illuminate and default to the “Standby” mode,
235 psig. displaying the “Press ON” prompt.
For water cooled models, a high pressure cut out switch The following illustration summarizes the keypad functions.
is positioned near the water regulating valve. The switch
is designed to open at 320 psig and close at 270 psig. The
DPC™ controller includes a digital readout for monitoring
the discharge pressure of the refrigerant gas exiting
the compressor. This reading will vary depending upon
CHLLR TEMP: 37
condenser type as indicated below:
Air Cooled condensers with ambient temperatures between
80°F and 100°F, the refrigerant discharge gauge should read
between 230 - 355 psig.
Water cooled condensers utilize a water regulating valve
(Refer to Figure 3). The water regulating valve comes pre-
adjusted from the factory at 260 psig discharge pressure.
To compensate for water temperature variation, it may be
necessary to adjust the water regulating valve to maintain
a 260 psig discharge pressure. Adjustment can be done
by rotating the adjusting screw counterclockwise for an
increase in discharge pressure. For conditions where low
water temperature and/or high water pressure are expected
it is advisable to install a water pressure regulator ahead of BUTTONS
the condenser. ON
Places the dryer “On Line”;
OFF
Places the dryer “Off Line”; Stops all automatic functions.
SELECT DISPLAY
ADJUSTMENT
SCREW Allows the user to cycle through the available displays. The
last display selected will remain displayed as the default
display.
+/-
Allows user to modify set point values. Set point values
cycle through a fixed range. Also allows entering negative
numbers in FACTORY MODE.
Figure 3 - WATER REGULATING VALVE
TEST
NOTICE Allows user to manually activate the drain valve.
For conditions where low water temperature and/or
RESET
high water pressure are expected, it is advisable
to install a water pressure regulator ahead of the Pressing once clears the local alarm indication and de-
condenser. energizes the remote alarm contact. Should the alarm
condition persist, the alarm will return after the alarm inhibit
time has expired.
NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 11
ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION
SET 7.5.3 DRYER SET POINTS AND ALARMS
Permits the adjustment of parameters in TECHNICIAN and The Microprocessor Control has several user adjustable set
FACTORY MODES. In CUSTOMER MODE, allows user to back points that are displayed at the end of the display parameter
through displays, list. These set points allow the user to configure the dryer
ENTER to operate according to site conditions. The controller is
shipped from the factory with each parameter having its
Used to accept changed parameters and set point values. own default value.
i
7.5.4 ADJUSTING SET POINTS
Restricted Level access for factory use only. Not used for
basic dryer functions. Not to be used by customer or service Accessing and manipulating each of the set points in
technician. the CUSTOMER MODE is accomplished as follows. The
parameter is selected using the SELECT DISPLAY button.
7.5.2 DISPLAY PARAMETERS After scrolling through the displays, the “Cust Set Points”
screen is displayed. The parameters after this screen may
The Microprocessor Control is capable of displaying a be adjusted by the user. Once the desired parameter is
number of system parameters. The following summarizes displayed, depressing the “+/-” button changes the set
the parameters that can be accessed by the user from the point. Once the new set point is displayed, depressing
Microprocessor Control: ENTER saves the set point. Exiting the Customer Set Point
• Chiller Temperature (CHLLR TEMP): The Chiller routine is accomplished by depressing the SELECT DISPLAY
Temperature is the temperature, in degrees button until the END CUST SET PTS screen is displayed. The
Fahrenheit, of the compressed air after the separator. following example illustrates the keystrokes required to
change the Drain Closed Time from the default value of 3
• Compressor Status (CMPRSSR): Displays whether the minutes to 5 minutes:
refrigeration compressor is “ON” or “OFF”.
• Discharge Pressure (P disch): Displays the discharge SELECT
DISPLAY CHLLR TEMP: 36
pressure of the refrigeration system.
• Suction Temperature (T suction): Displays the suction Pressing SELECT DISPLAY will increment the display through the
temperature, in deg. F, of the refrigeration system. available display parameters.
This value is useful in determining superheat of the
refrigerant.
SELECT
• Suction Pressure (P suction): Displays the suction DISPLAY Cust Set Points
pressure, in psig, of the refrigeration system.
Continue pressing SELECT DISPLAY until the Customer Set point
• Drain Interval (DRN INT): Displays the length of time, screen is displayed. The parameters that follow are the User
in minutes, between operation of the solenoid drain. Adjustable Parameters for the controller.

• Drain On (DRN ON): Displays the length of time, in


seconds, that the solenoid drain is open. SELECT
DRN INT:3 min
DISPLAY
• Cumulative Dryer Hours (CUM DRYER HR): Displays
the length of time, in hours, that the dryer has been Press SELECT DISPLAY until “DRN INT” is displayed.
operational.
• Depressing the SELECT DISPLAY button repeatedly +
scrolls through the above non-adjustable displays. -
DRN INT:5 min
The Customer Set Points appear at the end of the
list and may be adjusted by the end user to match Depress “ + / -“ as required to change the DRN INT to 5 minutes.
seasonal refrigeration and drain operation. These
settings are as follows:
• Drain Interval (DRN INT) ENTER DRN INT:5 min
• Drain On (DRN ON) Pressing “ENTER” saves the set point.

SELECT
DISPLAY End Cust Set Pts
12 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN
Press SELECT DISPLAY as necessary to display the End
ingersollrandproducts.com
Customer Set points Screen.
ENTER DRN INT:5 min
7.0 PRINCIPLES OF OPERATION
Pressing “ENTER” saves the set point.

HIGH PRESSURE CUTOUT ALARM (HPCO ALARM)


SELECT If the discharge pressure of the refrigerant is determined
DISPLAY End Cust Set Pts to be above the set point, the alarm routine will activate.
This alarm condition may cause damage to the dryer when
Press SELECT DISPLAY as necessary to display the End subjected to continuous or long-term exposure. Note that
Customer Set points Screen. this alarm will shut down the dryer after a response time
delay. The operator must depress the RESET button in order
SELECT to clear the alarm and restart the refrigeration system.
DISPLAY CHLLR TEMP: 36
LOW PRESSURE CUTOUT ALARM (LO PRESS CO)
If the suction pressure of the refrigerant is determined to be
Press SELECT DISPLAY as necessary to return the Microprocessor
below the set point of the LPCO alarm, the Microprocessor
Control to the desired display parameter.
Control alarm routine will activate. This alarm condition may
cause damage to the dryer when subjected to continuous or
7.5.5 ALARMS AND THEIR FUNCTIONS
long-term exposure. Note that once cleared, the compressor
There are several alarms detected by the Microprocessor will restart automatically. However, if two successive low
Control to alert the user of an out of tolerance condition. pressure conditions are determined, this alarm will shut
Once each alarm is detected, a description of the alarm down the dryer after a response time delay and will display
will appear in the screen and the remote alarm contact will the alarm condition. The operator must depress the RESET
close. Note that during the alarm condition, the SELECT button in order to reinstate the compressor.
DISPLAY button may be depressed to scroll through the
Parameter R-404A
available parameters. After approximately 30 seconds, the
alarm screen will reappear, provided the alarm condition FAN 1 ON 275 psig
persists. The alarm names and a brief description of each are FAN 1 OFF 195 psig
described in detail below. FAN 2 ON 335 psig
Alarm Display Alarm Set Point FAN 2 OFF 235 psig
HIGH PRESSURE HI PRESS CO See Table 1 HPCO (Air Cooled) 450 psig
CUTOUT HPCO (Water Cooled) 320 psig
LOW PRESSURE LO PRESS CO See Table 1 LPCO 20 psig
CUTOUT
HIGH TEMPERATURE HITEMP ALRM 55 °F 7.5.6 START MODES
ALARM
Ingersoll Rand dryers are capable of starting in one of
LOW TEMPERATURE LOTEMP ALRM 30 °F
three start modes. Note that to protect the refrigeration
ALARM
compressor from repeated rapid starts, the Microprocessor
HIGH TEMPERATURE ALARM (HITEMP ALARM) Control is equipped with an anti-short cycle (ASC) delay.
When the exchanger temperature reaches the alarm set The ASC delay will countdown from the factory set point.
point, the alarm will be activated. This alarm condition may Only after the ASC delay has timed out will the refrigeration
not necessarily damage the dryer when subjected to long system operate. Below are brief descriptions of these various
term exposure. It may, however, have a significant impact start modes.
on downstream processes and thus should be investigated
7.5.6.1 Manual Mode
upon detection. Note that this alarm will not shut down the
dryer. This alarm will activate the remote alarm contact and Ingersoll Rand dryers are shipped from the factory in the
reset automatically once the alarm condition is rectified. Manual Mode. After power is supplied to the dryer and once
LOW TEMPERATURE SAFETY ALARM (LOWTEMP ALARM) the Crankcase Heater Delay has timed out, the user will be
If the dryer chiller temperature falls to or below the factory presented with the ASC delay, followed by the “PRESS ON
set point and remains at or below this set point for the BUTTON” display. After the ASC delay has timed out, the
factory delay time, the alarm routine will activate. This alarm dryer will only start once the ON button is depressed. In this
condition may cause damage to the dryer when subjected configuration, to restart the dryer, the user must manually
to continuous or long-term exposure. Note that this alarm depress the ON button on the dryer’s control panel.
will shut down the dryer after a response time delay. This
alarm will activate the remote alarm contact and reset
automatically once the alarm condition is rectified.

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 13


ingersollrandproducts.com
7.0 PRINCIPLES OF OPERATION

7.5.6.2 Auto Restart Mode 7.5.6.3 Remote Automatic Mode


After power is applied to the dryer, and once the Crankcase This mode of operation allows the user to control the
Heater and ASC delays have timed out, the dryer will start dryer remotely and requires the installation of a customer-
automatically. In addition, this mode of operation allows supplied contact. With power applied to the dryer and once
manual control of the dryer via the ON & OFF pushbuttons. the Crankcase Heater and ASC delays have timed out, the
This is useful for applications where automatic restarting of dryer will start automatically once the switch is closed. In
the dryer is desired after a power failure has occurred. addition, this mode of operation allows manual control of
the dryer via the ON & OFF pushbuttons. Note that the signal
to the remote contact must be 110V.

14 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
8.0 INSTALLATION AND INITIAL START-UP
8.1 LOCATING EQUIPMENT
WARNING
The dryer should not be located in an area where the Prior to attempting to remove the dryer from the
ambient temperature is likely to exceed 113°F (45°C). The delivery vehicle, read the following section in its
dryer should be located where the ambient temperatures entirety. Failure to do so may result in damage to the
will not be less than 50°F (10° C) unless equipped with dryer or personal injury.
provisions for low ambient operation. If loads fluctuate
significantly, then the dryer should be placed ahead of the WARNING
receiver and sufficient storage capacity downstream of the
Refer to Engineering Specifications Sheet for
dryer should then be available to prevent excessive air flow
estimated weight of dryer prior to lifting.
through the dryer.
The dryer must be located in an area that provides sufficient To offload the dryer:
clearance from walls and other adjoining equipment to allow
easy access for servicing and maintenance requirements. • Install lifting chains through the eyes in the lifting
A minimum of three feet is required to allow free flow of lugs on headers.
air to the condenser inlets, access for drain maintenance
and access to control panels. Refer to the multiple module
• If using two-point lifting, use a spreader bar (not
included) as shown in Figure 4. Be sure that chains /
refrigerated dryer GENERAL ARRANGEMENT drawing for slings do not bear on sheet metal.
condenser air flow requirements.
• Adjust chains as required to keep equipment level
NOTICE during offloading.
Failure to comply to the above instructions may result • Carefully raise dryer from vehicle and locate according
in equipment malfunction and will void warranty. to criteria described in Section 8.1.

8.2 OFFLOADING / LIFTING THE DRYER • Secure dryer in place


The headers are constructed with lifting lugs to enable the
dryer to be offloaded and moved. Figure 4 illustrates two
methods of using the lifting lugs for offloading or moving
the dryer.

FIGURE 4 - LIFTING / OFFLOADING DIAGRAMS

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 15


ingersollrandproducts.com
8.0 INSTALLATION AND INITIAL START-UP
8.3 INSTALLATION OF AIR PIPING NOTICE
Multiple module dryers are equipped with one blind flange Verify that compressor vibration and vibration from
on each of the Inlet and Outlet Headers. Either side of the any process air equipment has been isolated from air
header can be used to connect to the process air piping. system piping. Failure to do so may damage dryer.
•Connect the inlet and outlet piping to the inlet and
outlet headers
8.4 PIPING AND VALVES
• Relocate, if needed, the blind flange on the inlet
header to the remaining flange of the inlet air header. Install piping, fittings and accessory items as indicated in
Figure 4. For bypass and isolating purposes, valves (A), (B),
• Relocate, if needed, the blind flange on the outlet and (C) must be installed (not furnished). In order to test and
header to the remaining flange of the outlet air isolate each drain without depressurizing the dryer, drain
header. isolation valve (D), has been provided for your convenience.
NOTICE
Insure that adequate piping supports are in place to
prevent loading on the Inlet and Outlet Headers. Do
not allow piping loads to be exerted on dryer.

PRE-FILTER

FIGURE 5
TYPICAL PIPING ARRANGEMENT

Drain connections should be piped to an appropriate that not more than one device be connected to a single
reservoir or container. It is recommended that a properly- valve due to the pressure differential between the two
sized oil / water separator be installed to comply with EPA devices.
regulations for waster water disposal. It is recommended

16 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
8.0 INSTALLATION AND INITIAL START-UP
8.5 FILTRATION • For units equipped with water-cooled condensers,
check that water supply lines and dryer water
To protect the air dryer from residual compressor oil and connections are leak free. Be sure to manually open
insure maximum dryer performance, a coalescing pre-filter is water regulating valves to fill condensers prior to
recommended. Filters should be located as close to the dryer starting dryer.
as possible and positioned to allow for ease of access for
element replacement. Highly efficient pre-filters and post-
• For all compressors, verify that oil is present in sight
glass.
filters sized to your drying application can be provided by
Ingersoll Rand. Contact your local distributor to select the After the checks described above have been performed
filter that best suits your filtration requirements. Note that all and prior to the initial starting of the dryer, perform the
filters should be individually supported such that no loads following:
are transmitted to the dryer inlet and outlet connections. • Energize Crankcase Heaters
Ensure that dryer is energized for a minimum of (8)
8.6 ELECTRICAL CONNECTION hours prior to startup.
Equipment is available in various electrical configurations. • On the Main Power Enclosure, turn the Compressor
All customer connections can be made at the main Controller Switch to MANUAL
electrical box located at the side of the dryer. All three phase
electrical configurations L1, L2 and L3 can be wired in any • On the Main Power Enclosure, turn the Dryer On/Off
configuration and not affect compressor performance. Switch to the ON position.
For all Ingersoll Rand equipment, a suitable fused • Supply power to dryer Main Power Enclosure and
disconnect switch in accordance with national and local engage each individual Module Disconnect Switch for
code requirements is recommended. a minimum of (8) hours prior to dryer startup.
All Ingersoll Rand Multiple Module dryers are equipped • The Microprocessor Control boards on each Module
with module disconnects for safety during maintenance or will indicate the modules are energized and the
repair. With this Multi-disconnect feature, each individual crankcase heater delay time remaining.
module can be isolated from the power source by using its
own dedicated switch. NOTICE
WARNING For water cooled models the water valve must be
manually opened to ensure the condenser is full of water
Crankcase heaters are disconnected through the prior to start up.
disconnect switch. Note that the position of the Dryer
On/Off Switch does not affect Crank Case Heater Verify Proper Refrigerant Pressure
operation. Refer to wiring diagram supplied with your • Check refrigerant pressure readings on the
dryer. Microprocessor Control digital display based on the
following general guidelines (refrigeration pressure
NOTICE will vary with ambient temperature):
Never wire directly or connect any additional wires to
Ambient Temperature Approximate Refrigerant
the compressor junction box. This will cause severe
Pressure (R-404A)
system malfunction.
50°F 105 psig
8.7 PRE START-UP AND SYSTEM LEAK CHECK
60°F 125 psig
Once dryer has been installed and prior to initial start-up, all 70°F 150 psig
dryer systems should be checked for proper installation and 80°F 175 psig
leaks. Be sure to check, as a minimum, the following:
90°F 205 psig
• Verify that all air system distribution piping is
reasonably leak free.
• Note that due to site conditions, it may not be
practical to make the air system completely leak-free.
• Check air connections on dryer to insure there are no
leaks present.
• Check drain lines for air or liquid leaks.
• Check all flange connections, if applicable, for gasket
compression.

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 17


ingersollrandproducts.com
8.0 INSTALLATION AND INITIAL START-UP

8.8 INITIAL START-UP Anti-short cycle delay and crankcase heater delay have
timed out, the refrigeration system will energize.
NOTICE After the alarm delay, provided the Chiller Temperature is
For water cooled models, the water valve must be greater than the HIGH TEMPERATURE ALARM set point, the
manually opened to ensure that the condenser is full dryer will go into HIGH TEMPERATURE ALARM. The LCD panel
of water prior to start-up. will indicate the alarm and the refrigeration system will
continue to operate. Pressing the SELECT DISPLAY button
will permit viewing of the available dryer parameters during
this alarm condition. Note that the alarm condition screen
Allow 8 hours of warm-up time for the crankcase heater will reappear after approximately 30 seconds until the alarm
prior to start up. Crankcase heater is connected directly condition is cleared.
to the incoming power and is energized at all times.
The CHILLER TEMPERATURE will gradually drop as indicated
8.8.1 START- UP SEQUENCE on the display. Once the temperature falls below the HIGH
TEMPERATURE ALARM set point, the alarm will reset and the
Apply power to dryer. LCD Panel will illuminate. The Anti- LCD panel will return to its default display. Air flow may be
Short Cycle delay will commence counting down. Remaining slowly introduced to the dryer.
time on the Crankcase heater will also countdown.
NOTICE
NOTICE If power is removed from the dryer for less than two
After installation or a prolonged shutdown, start the hours, the crankcase heater delay will be automatically
dryer with no air load (no air flow). This enables the bypassed. If, however, the power is removed from
dryer to reach its proper operating temperature in the the dryer for more than two hours, the full crankcase
shortest time possible. heater delay must be observed.
Start Dryer, using one of the following methods, depending
on Start Mode setting:
• Manual Mode - Press the ON pushbutton.
• Auto Restart Mode - No additional action required
• Remote Automatic Mode - Close the remote contact.

18 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
9.0 MAINTENANCE AND SYSTEM CHECK
9.1 INTRODUCTION 9.4 PRE-FILTERS AND POST-FILTERS

Ingersoll Rand multiple module refrigerated air dryers


WARNING
require little maintenance. These dryers utilize hermetically
sealed compressors which do not require any lubrication. Depressurize the system before disassembling filters.
Ingersoll Rand recommends component inspection and Failure to do so may result in injury or death.
service at regular intervals to obtain maximum performance
Filter elements should be changed semi-annually. Change
from your dryer.
carbon elements when hydrocarbons are first detected
9.2 REFRIGERANT CONDENSER downstream or every six months, whichever comes first.

For proper operation, it is essential that the air cooled Certain filters contain multiple elements. When replacing
condenser fins are free of dirt and dust. Regular cleaning is filter elements, all elements should be replaced
therefore required. simultaneously. Mixing new and old elements can result in
reduced air quality.
9.3 CONDENSATE DISCHARGE SYSTEM

Operation of the automatic drains should be checked at least


once each month. Drains should be removed and cleaned to
ensure no debris is trapped inside.

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 19


ingersollrandproducts.com
10.0 TECHNICIAN MODE

The Microprocessor Control provides a protected 10.1 ENTERING TECHNICIAN MODE


TECHNICIAN MODE to manipulate several parameters not
accessible by the typical operator. This mode also permits WARNING
viewing of the factory settings to aid in troubleshooting of
the dryer. Below is a list of parameters that can be accessed TECHNICIAN MODE should only be entered by
and manipulated by the technician in the TECHNICIAN qualified service personnel. Altering the set points in
MODE: TECHNICIAN MODE will have a significant effect on
the operation of the dryer. Incorrect set points may
Parameter Display Set Point damage dryer and cause potential serious injury.
DRAIN VALVE ENABLE DRAIN ENABLE OFF (For NO LOSS
To enter the TECHNICIAN MODE, perform the following
DRAIN)
keystrokes:
CRANKCASE HEATER CCH DLY 8 (or 0,2,4,12
DELAY hours)
TECH SET MODE
AUTO RESTART EN- AUTO RESTART N (or Y) 2 3

ABLE
Pressing the “2” and “3” buttons simultaneously enters the
In TECHNICIAN MODE, the following parameters can be TECHNICIANMODE.
viewed but not changed:

Parameter Display Set Point SELECT


DISPLAY DRAIN ENABLE: OFF
CONFIGURATION (# of CONFIG #: 1, 2, 4, 8
sensors)
Depressing SELECT DISPLAY scrolls through the available
OPERATING MODE OP MODE: HS or NC parameters. The first three parameters viewed are adjustable
REFRIGERANT REFRIG: 404 in TECHNICIAN MODE.
CONDENSER TYPE COND: AC OR WC
OPERATING T OP DIFF: 3 The DRAIN ENABLE parameter determines whether the
TEMPERATURE Microprocessor Control shall control an electronic no-loss
DIFFERENTIAL drain valve. A value of “ON” will permit the Microprocessor
Control to control the drain valve. A value of “OFF” will
SHORT CYCLE DELAY SHT CYC DLY: 3 disable this feature. Ingersoll Rand dryers are equipped with
HIGH PRESSURE HPCO: See Table-1 a no air loss drain as standard equipment. As such, DRAIN
CUTOUT ENABLE must remain “OFF”:
HIGH PRESSURE HPCO DLY: 10
CUTOUT DELAY
SELECT CCH DELAY: 4
LOW PRESSURE LPCO: See Table-1 DISPLAY
CUTOUT
LOW PRESSURE LPCO DLY: 10
CUTOUT DELAY Depressing the SELECT DISPLAY button advances to
the next adjustable parameter for the Crankcase
HIGH TEMPERATURE HITEMP ALRM: 55
Heater Delay. This parameter must not be altered
ALARM
unless instructed by Ingersoll Rand Service personnel.
LOW TEMPERATURE LOWTEMP ALRM: 30
ALARM NOTICE
LOW TEMPERATURE LOTEMP DLY: 2:00 The Crankcase Heater Delay set point must not be
ALARM DELAY altered unless directed by Ingersoll Rand Service
FAN 1 ON PRESSURE FAN1 ON: See Table-1 Personnel. Improperly altering the set point may
FAN 1 OFF PRESSURE FAN1 OFF: See Table-1 result in damage to the dryer. Contact Ingersoll Rand
Compressed Air Solutions before altering the default
FAN 2 ON PRESSURE FAN2 ON: See Table-1
set point.
FAN 2 OFF PRESSURE FAN2 OFF: See Table-1
ALARM LIST BEGIN ALARM N/A
LIST

20 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
10.0 TECHNICIAN MODE
The AUTO RESTART feature permits the dryer to operate once 10.2 ALARM LIST
power is applied to the dryer without requiring operator
intervention. This would be desirable should the user wish At the end of the list of non-adjustable parameters, the
to have the dryer restart automatically after a power outage. Microprocessor Control displays a list of the most recent 20
Note that the refrigeration system will operate once the alarm conditions. This list can facilitate troubleshooting the
ASC or CCH delay times out. To change the AUTO RESTART dryer.
set point from “N” (NO) to “Y” (YES), perform the following.
Otherwise, depress the SELECT DISPLAY button to advance
SELECT
to the next display: DISPLAY BEGIN ALARM LIST
SELECT
DISPLAY AUTO RESTART: N At the end of the list of parameters, depressing the SELECT
DISPLAY button displays the beginning of the ALARM LIST.
Depressing the SELECT DISPLAY button advances to the
next adjustable parameter for the Auto Restart feature. SELECT
DISPLAY HPCO

Depressing the SELECT DISPLAY button displays the alarms


SET AUTO RESTART: Y that the dryer has experienced, with the most recent alarm
displayed first. The actual display will depend on the most
Depressing the SET button changes the AUTO RESTART recent alarm detected by the Microprocessor Control.
parameter from “N” to “Y”.
SELECT
DISPLAY END ALARM LIST
ENTER AUTO RESTART: Y
The list of alarms can be scrolled by depressing the SELECT
DISPLAY button as needed. At the end of the alarm list, the
Depressing ENTER saves the selected set point. END ALARM LIST screen is displayed.

WARNING
SELECT
Changing the AUTO RESTART feature to “Y” will permit DISPLAY BEGIN ALARM LIST
the dryer to operate automatically once power is
applied and after a brief delay. Proper warning signs Depressing the SELECT DISPLAY list displays the ALARM
should be affixed to the dryer to alert users and service LIST screen at the top of the ALARM LIST.
personnel that dryer may start without warning.
Failure to do so may result in serious injury.
The Alarm List will repeat as many times as the SELECT
SELECT DISPLAY button is depressed. To EXIT the ALARM LIST,
DISPLAY END TECH SET PTS perform the following:

Depressing the SELECT DISPLAY button displays the


END TECH SET PTS display. TECH SET MODE
The remaining non-adjustable parameters may be viewed by
depressing the SELECT DISPLAY button as required to arrive Depressing the BLANK button (located above the SET
at the desired display. button) returns the controller to the top of the TECHNICIAN
MODE.
NOTICE
To exit the TECHNICIAN MODE at any time, depress the CHLLR TEMP: 37
 button to return to the CUSTOMER MODE.
Depressing the BLANK button again returns the controller to
the default display of the CUSTOMER MODE.

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 21


ingersollrandproducts.com
11.0 TROUBLESHOOTING

11.1 INTRODUCTION
Ingersoll Rand multiple module dryers are designed for reliable, trouble-free operation. In the event of any dryer
malfunction, the guide below has been developed to facilitate problem identification and corrective actions.

WARNING WARNING
An air dryer always operates under pressure. Any Prior to working on the unit, make sure that all circuit
maintenance procedure that involves disassembly of breakers or disconnected switches are tagged “Out of
pipe fittings, valves or any other components requires Service.”
the dryer be isolated from the compressed air stream
and fully depressurized. NOTICE
Any in-depth troubleshooting should only be done by
qualified service technicians. Prior to performing any
significant corrective action, consult factory.

PROBLEM PROBABLE CAUSE CORRECTIVE ACTION


Compressor will not start 1. Line disconnect switch open 1. Close start or disconnect
(no hum)
2. Fuse removed or blown 2. Inspect and replace fuse
3. Overload protector tripped 3. Allow internal overload to cool and reset. Check
motor windings and starting amps.
4. Control stuck in open position 4. Repair or replace control
5. Wiring improper or loose 5. Close start or disconnect
Compressor will not 1. Improperly wired 1. Check wiring
start hums but trips on
2. Low voltage to unit 2. Determine reason and correct
overload protector
3. Compressor motor has a winding 3. Replace compressor
open or shorted
4. Internal trouble in compressor 4. Replace compressor
Compressor starts and 1. Excessive discharge pressure 1. Check condenser for dirt
runs, but short cycles on
2. Compressor hot - return gas hot 2. Check refrigerant charge (fix charge)
overload protector
3. Compressor has shorted winding 3. Replace compressor
Compressor starts and 1. High pressure cut-out due to: 1. High pressure cut-out
runs, but short cycles on
a. Insufficient air flow across a. Check condenser for dirt and proper fan operation.
high or low pressure cut
condenser
out.
b. Overcharge b. Reduce refrigerant charge
c. Insufficient water flow across c. Check complete water circuit make necessary
condenser adjustment
2. Low pressure cut-out due to: 2. Low pressure cut-out
a. Undercharge a. Fix leak, add refrigerant
b. Restriction in or faulty expansion b. Consult factory prior to replacing valve.
valve
Liquid line frosted or 1. Restriction in filter dryer or 1. Replace part
sweating condenser

22 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
11.0 TROUBLESHOOTING
PROBLEM PROBABLE CAUSE CORRECTIVE ACTION
Unit operates long or 1. Shortage of refrigerant 1. Fix leak then charge
continuously
2. Control contacts stuck 2. Clean contacts or replace control
3. System inadequate to handle load. 3. Review air system parameters.
4. Restriction in refrigerant system 4. Determine location and correct.
5. Dirty condenser 5. Clean condenser
Suction line frosted or 1. Expansion valve passing excess 1. Check super heat and adjust valve if required.
sweating refrigerant Adjustment is rarely required. Consult factory.
2. Overcharge of refrigerant 2. Correct charge as per manual
3. Expansion valve stuck open 3. Clean valve of foreign particles, replace if necessary.
Unit noisy 1. Loose parts or mountings 1. Find parts and tighten
2. Tubing rattle 2. Reform, to be free of contact
3. Bent fan blade 3. Replace blade
4. Fan motor bearings worn 4. Replace motor
Moisture down stream. Drain failure or adjustment is Manually activate drain and determine functionality. If
Dryer is properly cooling required drain does not discharge properly, service drain.
air stream (Check Chllr
Temp on controller)
Apparent controller Blown Fuse Check Fuses
display malfunction. Board Failure Contact your local distributor for further assistance.
Display Blank
Apparent controller Probe loose, off connection or Inspect probe cable and terminal connection Replace
display malfunction. defective probe probe
Unrealistic temperature
displayed
Apparent controller Probe not completely in thermal well Inspect probe and check readings against independent
display malfunction. source (eg. temperature analyzer/pyrometer/ice bath)
Erratic or inaccurate both in temperature well and to ambient
temperature readings Defective probe Replace probe
Apparent controller Transducer loose, off connection or Inspect transducer cable and terminal connection
display malfunction. defective transducer Replace transducer
Unrealistic pressure
displayed
Condensate drain does Check installation is in accordance with this manual.
not fire Revise installation accordingly.
Inlet / outlet pipe internal diameter Replace with larger diameter piping.
too small causing air-lock or back
pressure.
Excessive use of bends / elbows in Reduce the amount of bends and elbows.
inlet / outlet pipe work causing air-
lock/ back pressure.
Outlet pipe too long / too high Reconfigure condensate piping.
causing back pressure.

More than one condensate source Reroute condensate to eliminate secondary path. Install
connected providing alternative path check valves as required.
for condensate.
Air bleed from conden- Debris trapped under seal. Damage Press and hold the test button to clear (drain valve will
sate drain outlet port to seal. open). Replace seal with Service Kit.

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 23


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550212A
D5525IN

24 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550213A
D6800IN

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 25


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550214A
D8160IN

26 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550215A
D10200IN

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 27


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550215A
D10200IN

28 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550216A
D13600IN

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 29


ingersollrandproducts.com
12.0 WIRING DIAGRAMS

AIR & WATER COOLED, 460/3/60


WIRING DIAGRAM

550216A
D13600IN

30 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
6.31 73.50 70.75
8"-150# AIR OUTLET 8"-150# AIR INLET 17.50 35.75 CONDENSER AIR CONDENSER AIR
HEADER CUSTOMER HEADER CUSTOMER DISCHARGE DISCHARGE
CONNECTION AT CONNECTION AT
EITHER END EITHER END
MAIN POWER ELECTRICAL
ENCLOSURE

3.12

2.50

MODULE 1 MODULE 2

100.00
A
90.38
B
72.00

CONDENSER AIR CONDENSER AIR


INLET INLET

O .62 MTG HOLES 4 PLCS 3.00 TYP 1.62 RIGGING HOLES TYP 3.00 TYP
64.75 5.25 86.00
75.38 91.25

ingersollrandproducts.com
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW

LCD DISPLAY
13.0 GENERAL ARRANGEMENT

1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
AIR TREATMENT 5) PERCENT SAVINGS
CONTROL SYSTEM 6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
8) CUSTOMER SET POINTS
DRYER ON-OFF
SWITCH

DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT
SWITCH (TYP)

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


POWER ON
LIGHT
PUSHBUTTONS
DRYER FAULT DETAIL B 1) ON
ALARM LIGHT 2) OFF
3) RESET
4) TEST
5) SET
6) SELECT DISPLAY
7) ENTER
8) +/-
DETAIL A

GENERAL ARRANGEMENT
D5525IN-D8160IN
NEMA-1
550197

31
13.0 GENERAL ARRANGEMENT

1/4" OD NYLON DRAIN TUBE

GENERAL ARRANGEMENT
D5525IN-D8160IN
(2 PLCS)

NEMA-1
550197
REAR VIEW

32 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
6.31 73.50 70.75
8"-150# AIR OUTLET 8"-150# AIR INLET 17.50 35.75
HEADER CUSTOMER HEADER CUSTOMER
CONNECTION AT CONNECTION AT
EITHER END EITHER END

MAIN POWER ELECTRICAL


ENCLOSURE

3.12

2.50

MODULE 1 MODULE 2

100.00
A
90.38
B
72.00

1-1/2" MPT WATER


OUTLET CUSTOMER
CONNECTION

4.75

10.79

O .62 MTG HOLES 4 PLCS 3.00 TYP 1.62 RIGGING HOLES TYP 3.00 TYP 3.00
64.75 86.00
1-1/2" MPT WATER
75.38 INLET CUSTOMER 91.25

ingersollrandproducts.com
CONNECTION
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW

LCD DISPLAY
13.0 GENERAL ARRANGEMENT

1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
AIR TREATMENT 5) PERCENT SAVINGS
CONTROL SYSTEM 6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
8) CUSTOMER SET POINTS
DRYER ON-OFF
SWITCH

DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


POWER ON SWITCH (TYP)
LIGHT
PUSHBUTTONS
DRYER FAULT DETAIL B 1) ON
ALARM LIGHT 2) OFF
3) RESET
4) TEST
5) SET
6) SELECT DISPLAY
7) ENTER
8) +/-
DETAIL A
GENERAL ARRANGEMENT
D5525IN-D8160IN WATER COOLED
NEMA-1
550201

33
13.0 GENERAL ARRANGEMENT

1/4" OD NYLON DRAIN TUBE

D5525IN-D8160IN WATER COOLED


GENERAL ARRANGEMENT
(2 PLCS)

NEMA-1
550201
REAR VIEW

34 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
6.31 73.50 101.50
10"-150# R.F.S.O. AIR OUTLET 24.00 53.50
HEADER CUSTOMER CONN. 10"-150# R.F.S.O. AIR INLET
AT EITHER END HEADER CUSTOMER CONN.
AT EITHER END

MAIN POWER ELECTRICAL 3.12


ENCLOSURE

2.00

MODULE 1 MODULE 2 MODULE 3

101.25
A
90.38
B
72.00

2" MPT WATER


OUTLET CUSTOMER
CONN.
4.75

2" MPT WATER


INLET CUSTOMER 10.75
CONN.

O .62 MTG HOLES 4 PLCS 1.62 RIGGGING HOLES TYP 1.38


3.00 TYP 3.00 TYP
3.00
86.00 5.50 7.50 97.50 3.00
91.50 108.00
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW

ingersollrandproducts.com
LCD DISPLAY
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
AIR TREATMENT 4) DRAIN ON
5) PERCENT SAVINGS
13.0 GENERAL ARRANGEMENT

CONTROL SYSTEM
6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
DRYER ON-OFF 8) CUSTOMER SET POINTS
SWITCH

DRYER AUTO-MANUAL-REMOTE
SWITCH
MODULE DISCONNECT
POWER ON LIGHT SWITCH (TYP)

PUSHBUTTONS
DETAIL B 1) ON
DRYER FAULT ALARM LIGHT 2) OFF

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


3) RESET
4) TEST
5) SET
6) SELECT DISPLAY
7) ENTER
DETAIL A 8 +/-

GENERAL ARRANGEMENT
D10200IN WATER COOLED
NEMA-1
550202

35
13.0 GENERAL ARRANGEMENT

1/4" OD NYLON DRAIN TUBE

D10200IN WATER COOLED


GENERAL ARRANGEMENT
(3 PLCS)

NEMA-1
550202
REAR VIEW

36 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
6.31 73.50 136.00
12-150# R.F. FLANGED 12"-150# R.F. FLANGED 34.50 67.00
AIR OUTLET HEADER AIR INLET HEADER
CUSTOMER CONN. AT CUSTOMER CONN. AT
EITHER END EITHER END

MAIN POWER ELECTRICAL


ENCLOSURE

3.12
2.88

MODULE 1 MODULE 2 MODULE 3 MODULE 4

102.25
A
90.38 B

72.00

2-1/2" MPT OUTLET


WATER CUSTOMER
CONNECTION
10.00

2-1/2" MPT INLET 10.62


WATER CUSTOMER
CONNECTION
O .62 MTG HOLES 4 PLCS 1.62 RIGGING HOLES (TYP) 1.75 2.38
3.00 (TYP) 3.00 (TYP)
86.00 5.50 7.50 130.25
91.50 140.75
LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW

ingersollrandproducts.com
LCD DISPLAY
1) CHILLER TEMP
2) COMPRESSOR ON/OFF
3) DRAIN INTERVAL
4) DRAIN ON
13.0 GENERAL ARRANGEMENT

AIR TREATMENT 5) PERCENT SAVINGS


CONTROL SYSTEM (TYP) 6) CUMULATIVE DRYER HOURS
7) CUMULATIVE COMPRESSOR HOURS
8) CUSTOMER SET POINTS
DRYER ON-OFF
SWITCH

DRYER AUTO-MANUAL-REMOTE
SWITCH MODULE DISCONNECT
SWITCH (TYP)
POWER ON LIGHT DETAIL B PUSHBUTTONS
1) ON
2) OFF

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


DRYER FAULT 3) RESET
ALARM LIGHT 4) TEST
5) SET
6) SELECT DISPLAY
DETAIL A 7) ENTER
8) +/-

GENERAL ARRANGEMENT
D13600IN WATER COOLED
NEMA-1
550203

37
13.0 GENERAL ARRANGEMENT

1/4" OD DRAIN TUBE


(4 PLCS)

D13600IN WATER COOLED


GENERAL ARRANGEMENT

NEMA-1
550203
REAR VIEW

38 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
14.0 REPLACEMENT PARTS

Qty/ Qty/ Spares


Description D5525INA D5525INW D6800INA D6800INW D8160INA
Mod. Unit 1 2 3
ADAPTER, EXPANSION MODULE 683953 683953 683953 683953 683953 1 1 1 1
BLOCK, CONTACT 1NO/1NC 630612 630612 630612 630612 630612 1
BLOCK, CUSTOMER CONNECTION 699350 699350 699350 699350 699350 1
CABLE, AIR PRESSURE TRANSDUCER 682946 682946 682946 682946 682946 2
CABLE, REFRIGERANT TRANSDUCER 682945 682945 682945 682945 682945 2
CAPACITOR, CONDENSER FAN MOTOR 683618 - 683618 - 683618 2
COMPRESSOR, REFRIGERATION 682248 684300 682346 682248 684296 1 1 1 1
CONDENSER, REFRIGERANT 683587 698202 684310 683652 684310 1
CONTACTOR, COMPRESSOR 698343 698343 698343 698343 698343 1 1 1 1
CONTACTOR, CONDENSER FAN 699621 - 699621 - 699621 2 1 1 1
DRYER CONTROLLER, TYPE 4 WITH
REFRIGERATED PROGRAM ( Dryer model and
800029 800029 800029 800029 800029 1 1 1 1
serial number must be provided with order to
ensure proper configuration.)
DRAIN VALVE, CONDENSATE 22612931 22612931 22612931 22612931 22612931 1
DRYER, REFRIGERANT FILTER 600388 600388 600388 600388 600388 1
FUSE, CONTROL TRANSFORMER PRIMARY 699808 699808 699808 699808 699808 2 2 2 4
FUSE, CONTROL TRANSFORMER SECONDARY 632043 632043 632043 632043 632043 1 2 2 4
FUSE, MODULE POWER DISTRIBUTION - - - - - 3 2 2 4
FUSE, POWER BOX TRANSFORMER PRIMARY 699807 699807 699807 699807 699807 2 2 2 4
FUSE, POWER BOX TRANSFORMER
699391 699391 699391 699391 699391 1 2 2 4
SECONDARY
HEATER, COMPRESSOR CRANKCASE 682245 682245 682245 682245 682245 1
LAMPS, POWER BOX 632207 632207 632207 632207 632207 2
LENS, POWER BOX GREEN 632208 632208 632208 632208 632208 1
LENS, POWER BOX RED 632210 632210 632210 632210 632210 1
MODULE, PLC EXPANSION 683955 683955 683955 683955 683955 1 1 1 1
MOTOR, CONDENSER FAN 683617 - 683617 - 683617 2 1 1 1
POWER SUPPLY 24V DC 683956-SP 683956-SP 683956-SP 683956-SP 683956-SP 1 1 1 1
PROBE, EXCHANGER TEMPERATURE 682955L 682955L 682955L 682955L 682955L 1 1 1 1
PROBE, TEMPERATURE 6FT LEAD INLET/OUT
682955C 682955C 682955C 682955C 682955C 2 2 2 2
TEMPERATURE
RECEIVER, REFRIGERANT - 684026 - 684026 - 1
RELAY, DPDT 698262 698262 698262 698262 698262 1
RESISTOR, CONTROL PANEL DUMMY LOAD 683968 683968 683968 683968 683968 1
STRAINER, CONDENSATE DRAIN 683739 683739 683739 683739 683739 1
SWITCH, MOTOR DISCONNECT 683619 683619 683619 683619 683619 1
SWITCH, ROTARY DISCONNECT 632358 632358 632358 632358 632358 1
SWITCH, SELECTOR - POWER ON/POWER BOX 630611 630611 630611 630611 630611 1
SWITCH, SELECTOR 3 POSITION -ON/OFF/
633378 633378 633378 633378 633378 1
REMOTE POWER BOX
TRANSDUCER, REFRIGERANT DISCHARGE
682943 682943 682943 682943 682943 1 1 1 1
PRESSURE
TRANSDUCER, REFRIGERANT SUCTION
682942 682942 682942 682942 682942 2 1 1 1
PRESSURE/AIR PRESSURE

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 39


ingersollrandproducts.com
14.0 REPLACEMENT PARTS

Qty/ Qty/ Spares


Description D5525INA D5525INW D6800INA D6800INW D8160INA
Mod. Unit 1 2 3
TRANSFORMER, 0.15 KVA CONTROL 600191 600191 600191 600191 600191 1
TRANSFORMER, POWER BOX CONTROL 681861 681861 681861 681861 681861 1
VALVE, CONDENSATE BLOCK 683244 683244 683244 683244 683244 1
VALVE, EXPANSION 684273 684273 684273 684273 684273 1
VALVE, SOLENOID, 5/8” REFRIGERANT LIQUID
683338 683338 683338 683338 683338 1
LINE
VALVE, REFRIGERANT HOT GAS BYPASS 684590 684590 683853 683853 683853 1
VALVE, WATER CONTROL 1 1/4 “ - 698204 - 698204 - 1

Qty/ Qty/ Spares


Description D8160INW D10200INA D10200INW D13600INA D13600INW
Mod. Unit 1 2 3
ADAPTER, EXPANSION MODULE 683953 683953 683953 683953 683953 1 1 1 1
BLOCK, CONTACT 1NO/1NC 630612 630612 630612 630612 630612 1
BLOCK, CUSTOMER CONNECTION 699350 699350 699350 699350 699350 1
CABLE, AIR PRESSURE TRANSDUCER 682946 682946 682946 682946 682946 2
CABLE, REFRIGERANT TRANSDUCER 682945 682945 682945 682945 682945 2
CAPACITOR, CONDENSER FAN MOTOR - 683618 - 683618 - 2
COMPRESSOR, REFRIGERATION 682346 682346 682248 682346 682248 1 1 1 1
CONDENSER, REFRIGERANT 683596 684310 683652 694310 683652 1
CONTACTOR, COMPRESSOR 698343 698343 698343 698343 698343 1 1 1 1
CONTACTOR, CONDENSER FAN - 699621 - 699621 - 2 1 1 1
DRYER CONTROLLER, TYPE 4 WITH
REFRIGERATED PROGRAM ( Dryer model
800029 800029 800029 800029 800029 1 1 1 1
and serial number must be provided with
order to ensure proper configuration.)
DRAIN VALVE, CONDENSATE 22612931 22612931 22612931 22612931 22612931 1
DRYER, REFRIGERANT FILTER 600388 600388 600388 600388 600388 1
FUSE, CONTROL TRANSFORMER PRIMARY 699808 699808 699808 699808 699808 2 2 2 4
FUSE, CONTROL TRANSFORMER
632043 632043 632043 632043 632043 1 2 2 4
SECONDARY
FUSE, MODULE POWER DISTRIBUTION - 632904 632331 632904 632331 3 2 2 4
FUSE, POWER BOX TRANSFORMER
699807 699807 699807 699807 699807 2 2 2 4
PRIMARY
FUSE, POWER BOX TRANSFORMER
699391 699391 699391 699391 699391 1 2 2 4
SECONDARY
HEATER, COMPRESSOR CRANKCASE 682245 682245 682245 682245 682245 1
LAMPS, POWER BOX 632207 632207 632207 632207 632207 2
LENS, POWER BOX GREEN 632208 632208 632208 632208 632208 1
LENS, POWER BOX RED 632210 632210 632210 632210 632210 1
MODULE, PLC EXPANSION 683955 683955 683955 683955 683955 1 1 1 1
MOTOR, CONDENSER FAN - 683617 - 683617 - 2 1 1 1
POWER SUPPLY 24V DC 683956-SP 683956-SP 683956-SP 683956-SP 683956-SP 1 1 1 1
PROBE, EXCHANGER TEMPERATURE 682955L 682955L 682955L 682955L 682955L 1 1 1 1
PROBE, TEMPERATURE 6FT LEAD INLET/
682955C 682955C 682955C 682955C 682955C 2 2 2 2
OUT TEMPERATURE

40 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
14.0 REPLACEMENT PARTS

Qty/ Qty/ Spares


Description D8160INW D10200INA D10200INW D13600INA D13600INW
Mod. Unit 1 2 3
RECEIVER, REFRIGERANT 683742 - 683742 - 683742 1
RELAY, DPDT 698262 698262 698262 698262 698262 1
RESISTOR, CONTROL PANEL DUMMY
683968 683968 683968 683968 683968 1
LOAD
STRAINER, CONDENSATE DRAIN 683739 683739 683739 683739 683739 1
SWITCH, MOTOR DISCONNECT 683619 683619 683619 683619 683619 1
SWITCH, ROTARY DISCONNECT 632358 632358 632358 632358 632358 1
SWITCH, SELECTOR - POWER ON/POWER
630611 630611 630611 630611 630611 1
BOX
SWITCH, SELECTOR 3 POSITION -ON/OFF/
633378 633378 633378 633378 633378 1
REMOTE POWER BOX
TRANSDUCER, REFRIGERANT DISCHARGE
682943 682943 682943 682943 682943 1 1 1 1
PRESSURE
TRANSDUCER, REFRIGERANT SUCTION
682942 682942 682942 682942 682942 2 1 1 1
PRESSURE/AIR PRESSURE
TRANSFORMER, 0.15 KVA CONTROL 600191 600191 600191 600191 600191 1
TRANSFORMER, POWER BOX CONTROL 681861 681861 681861 681861 681861 1
VALVE, CONDENSATE BLOCK 683244 683244 683244 683244 683244 1
VALVE, EXPANSION 684346 683840 683840 683840 683840 1
VALVE, SOLENOID, 5/8” REFRIGERANT
683338 683338 683338 683338 683338 1
LIQUID LINE
VALVE, REFRIGERANT HOT GAS BYPASS 683853 683853 683853 683853 683853 1
VALVE, WATER CONTROL 1 1/4 “ 680181 - 698204 - 698204 1

NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN 41


ingersollrandproducts.com
15.0 ENGINEERING SPECIFICATIONS

Overall dimensions indicated.


Air INLET and OUTLET header centerline
remains consistent throughout the
model range.
Module number varies depending on model.
See last column in chart to indentify modules
per model. 3-module model depicted in this
Illustration.

Pressure Operating Shipping Air


Capacity W D H
Model Drop Power Weight In/Out
scfm m³/min psid barg kW in mm in mm in mm lb kg in
D5525IN 3,250 92.1 3.4 0.23 22.6 77 1956 92 2337 100 2540 4800 2177 8 FLG
D6800IN 4,000 113.3 3.5 0.24 27.6 77 1956 92 2337 100 2540 5000 2268 8 FLG
D8160IN 4,800 136.0 4.8 0.33 32.4 77 1956 92 2337 100 2540 5500 2495 8 FLG
D10200IN 6,000 170.0 2.6 0.18 41.4 110 2794 92 2337 101 2565 7500 3402 10 FLG
D13600IN 8,000 226.7 3.5 0.24 55.2 141 3581 92 2337 102 2591 9000 4082 12 FLG

42 NON-CYCLING REFRIGERATED DRYER MODELS D5525IN - D13600IN


ingersollrandproducts.com
ingersollrandproducts.com
© 2012 Ingersoll-Rand Company

You might also like