You are on page 1of 2
Surge Protection Device Combined Class II for Power Supply System AT PCM TT1+1 275 FM No. 910 821 iG * Technical data ‘Type AT PCM TT1+1 275 FM ‘Order No. 910 821 Rated voltage (max. continuous voltage) |_U. | 275V-(L-N) _255V~ (N-PE) Nominal discharge current (8/20) 1 | 20KA (LN) 40KA (N-PE) Max. discharge current (8/20) Toa | 40KA (LN) 65kA (N-PE) Lightning impulse current(10/350) Thy _ | 20KA (N-PE) Voltage protection level at, U,_ |S 1250V (LN) 5 1500V (N-PE) Voltage protection level 5kA U, [5 1000V (LN) Response time ti | /S25ns(L-N) 5 100ns (N-PE) Follow curent extinguishing capabiity at U, |, | 100A... (N-PE) Max. back up fuse 125A gligG (LN) Operating temperature range Ty _[ -40°C..180°C Cross-sectional area 4.5mm ~ 25mm solid / 35mm flexible Mounting on ‘35mm DIN rail Enclosure material Light gray thermoplastic, UL94-VO Dimension 2mods Test standards TEC 61643-11; GB 18802.1; YDIT 1295.1 Certification CE (LVD, EMC) Type of remote signaling contact Switching contact ‘Switching capacity Uvl._| AC:250V10.5A _ DC:250V/I0.1A,125Vi0.2A,75VI0.5A Cross-sectional area for remote signalling contact Max. 1.5mm solid / flexible Design and Engineered by: (GP) sperry Power Pte Ltd « Product introduction 1. Summary ATPCM TT1+1 275 FMis for installation at LPZ 0,-1 ‘or higher, protecting low voltage equipment from surge. Applied in modular SPD Class I! (Class C) for TT and TN power supply system. Designed according to IEC 61643-11; GB 18802.1; YDIT 1235.1 3. Application AT PCM TT1+1 275 FMis applied in TT and TN system (141 circuit). ¢ Installation instruction ‘According to lightning protection zones concept, for installation at LPZ 0,-1 or higher. This surge protective device is usually installed in dstribution-box or feeder bus of UPS, protecting devices or equipment downstream. Fuse must be installed at the upstream of the SPD or the lightning arrester to make sure thatthe protected system has double protection. The value of the fuse used in a SPD system should be conformed to 1. The value of FUSE should not be larger than the max. withstand capacity of the SPD's backup fuse value, 2. Under the status ofthe max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited. 3, Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of SPD. Installation diagram: 2. Main character + Small volume, pluggable * Quick response * Double thermal disconnector devices, providing more reliable protection + Mulifunctional terminal for connecting conductors and busbars + Green window will change to red when fault and also provide remote alarm control at the same time 4, Application environment + Temperature: 40°C...#80°C * Relative humidity: < 95% (25°C) * Installation steps 1. Check the product for integrity ofthe package; make sure the product window indicate green. 2. Mount the SPD on the 35mm DIN rail 3. Connect conductors, the cross-sectional area of cable must be larger than 6mm. The withstand voltage value of cable is not smaller than ACBOOV: ensure wiring reliable. 4, Hfneed remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or2 and 3 (When normal, ‘and 2 open, 2 and 3 close; when faut, the state is reversed) 5. After above, switch on the power supply and tun on the circuit breaker, if the SPD’s window indicates green, tis indicates the uni is operating normally Regularly inspect the operating status, especially after lightning. Once the fuse upstream breaks, or the SPD's window indicates red, electrician should checkireplace the SPD. +) ATP CM 275 Fel 1) ATPOM 255 FM Fis 125aqU93 Remote signalling Babar WARNING: safety regulations. 1. The device must be installed by electrically skilled person, conforming to national standards and 2, tis recommended that installation should be done under power off condition.

You might also like