Protection Relays

NA011
FEEDER PROTECTION RELAY
THE ECONOMICAL SOLUTION FOR THE PROTECTION OF LINES
AND TRANSFORMERS WITH AUTOMATIC RECLOSER

— Application
The relay type NA011 can be used in radial networks as feeder or power transformer protection.
In solidly grounded systems the residual overcurrent protection can be used on feeders of any length, while in
ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be
used on feeders of small length in order to avoid unwanted trippings due to the capacitive current contribution
of the feeder on external ground fault.
The NA011 protection relay may be shipped with traditional CTs or low power (LPCT) current inputs; for both ver-
sions, the residual overcurrent protection can use the measured (CTs or balanced transformer) or the calculated
residual current.

52

79 BF

Control functions
Phase CTs - Protective & control functions
50 51
METERING
- I L1..I L3,I E 50/51 Phase overcurrent
Alternative - Oscillography 50N/51N Residual overcurrent
Low power
- Events & Faults log 79 Automatic recloser
CTs (LPCT)
50 51 - Data Logger BF Breaker failure
COMMUNICATION
- RS232
50N 51N - Modbus RS485

NA011 - Flyer - 10 - 2021


— Phase current inputs — Programming and settings
Traditional CTs All relay programming and adjustment operations may be per-
Three phase current inputs with secondary nominal currents formed through MMI (Keyboard and display) or using a Personal
independently selectable at 1 A or 5 A through DIP-switches. Computer with the aid of the ThyVisor software.
Low power CTs The same PC setup software is required to set, monitor and con-
Three phase current inputs with primary nominal currents in- figure all Pro_N devices.
dependently selectable through DIP-switches and software.
— Control and monitoring
— Residual current input Several predefined functions are implemented:
Measured residual current • Cold load pickup (CLP) with block or setting change
One residual current input with secondary nominal current se- • Circuit Breaker diagnostic.
lectable at 1 A or 5 A through DIP-switches.
Calculated residual current Cold Load Pickup (CLP)
Residual current is calculated by the vector sum of the three Cold load pickup element prevents unwanted tripping in case of
phase currents, measured by three 1A or 5A CTs or by three temporary overcurrents produced when a feeder is being con-
LPCT type sensors. nected after an extended outage (e.g. motor starting).
Two different operating modes are provided:
— Binary inputs • Each protective element can be blocked for a programmable
Three binary inputs are available with predefined functions: time
• IN1 - 52b acquisition or external trip • Each threshold can be increased for a programmable time.
• IN2 - 52a acquisition, external trip or CB Open command
• IN3 - 79 (Enable or Remote), external trip or CB Close command — Firmware updating
The use of flash memory units allows on-site firmware updating.
— Output relays
Four output relays are available (one changeover contact); each — Communication
relay may be individually programmed as normal state (normally en- Two communication interfaces are implemented:
ergized or de-energized) and reset mode (manual or automatic). • One RS232 local communication front-end interface for com-
A programmable timer is provided for each relay (minimum pulse munication with ThyVisor setup software
width). The user may program the function of each relay in ac- • One RS485 port using ModBus® RTU or IEC 60870-5-103 for
cordance with a matrix (tripping matrix) structure. communication with remote monitoring and control systems.

— Self diagnostics
— Construction All hardware and software functions are repeatedly checked
The NA011 protection relay case is suitable for flush or rack and any anomalies reported via display messages, communica-
mounting. tion interfaces, LEDs and output relays.
Anomalies may refer to:
— MMI (Man Machine Interface) • Hw faults (auxiliary power supply, output relay coil, ...).
The user interface comprises a membrane keyboard, a backlight • Sw faults (boot and run time tests for data base, EEPROM
LCD alphanumeric display and eight LEDs. memory checksum failure, data BUS,...).
• The green ON LED indicates auxiliary power supply and self
diagnostics, — Metering
• The yellow LED START, no-latched, indicates Start of the I>, NA011 provides metering values for phase and residual currents,
I>>, I>>>, IE>, IE>> elements making them available for reading on a display or to communica-
• The red LED TRIP, no-latched, indicates Trip of the I>, I>>, I>>>, tion interfaces.
IE>, IE>> elements Input signals are sampled 64 times per period and the RMS value
• The red LED 1, latched, indicates Trip of the I>, I>>, I>>> ele- of the fundamental component is measured using the DFT (Dis-
ments crete Fourier Transform) algorithm and digital filtering.
• The red LED 2, latched, indicates Trip of the IE>, IE>> elements The measured signals can be displayed with reference to nomi-
• The red LED 3, no-latched, indicates the CB state (CB open) nal values or directly expressed in amperes.
• The red LED 4, no-latched, indicates the CB state (CB closed)
• The red LED 5, no-latched, indicates the 79 (Reclosure) state: — Data storage
- LED off = 79 disabled Several useful data are stored into a non volatile memory.
- LED on = 79 enabled • Sequence of Event Recorder
- LED slow blink = cycle in progress The event recorder runs continuously capturing in circular
- LED fast blink = reclosure fail mode the last one hundred events upon trigger of binary in-
By means of the (Open) and (Close) keys, the circuit put/output.
breaker commands may be issued. • Sequence of Fault Recorder
The fault recorder runs continuously capturing in circular
mode the last twenty faults upon trigger of binary input/output
and/or element pickup (start-trip).
• Counters

— Digital Fault Recorder (Oscillography)[1]


Upon trigger of tripping/starting of each function or external sig-
nals, the relay records in COMTRADE format:
• Oscillography with instantaneous values for transient analysis.
• RMS values for long time periods analysis.
• Logic states (binary inputs and output relays).
Note 1- A licence for the digital fault recorder function is required.
The oscillography records are stored in non-volatile memory.

2 NA011 - Flyer - 10 - 2021


SPECIF ICAT IONS
GENERAL INPUT CIRCUITS
— Mechanical data — Auxiliary power supply Uaux
Mounting: flush, rack Nominal value (range) 24...230 Vac/dc
Mass (flush mounting case) 1.2 kg Operative range 19...265 Vac / 19...300 Vdc
Power consumption (max) 6 W (9 VA)
— Insulation tests
Reference standards EN 60255-5 — Phase current inputs
High voltage test 50Hz 2 kV 60 s Traditional CTs:
Impulse voltage withstand (1.2/50 ms) 5 kV • Nominal current I n 1 A or 5 A selectable by DIP Switches
Insulation resistance >100 MW • Permanent overload 25 A
• Thermal overload (1 s) 500 A
— Voltage dip and interruption • Rated consumption (for any phase) ≤ 0.002 VA (In = 1 A)
Reference standards EN 61000-4-29 ≤ 0.04 VA (In = 5 A)
• Connections 4 mm ring lugs suitable for M4 screws
— EMC tests for interference immunity Low power CTs (according to IEC 60044-8 standard):
1 MHz damped oscillatory wave EN 60255-22-1 1 kV-2.5 kV • Nominal primary current I pn 100 A
Electrostatic discharge EN 60255-22-2 8 kV • Extended primary current (selectable via DIP Switches and sw)
Fast transient burst (5/50 ns) EN 60255-22-4 4 kV 50...1250 A
Conducted radio-frequency fields EN 60255-22-6 10 V • Maximum primary current 12.5 kA
Radiated radio-frequency fields EN 60255-4-3 10 V/m • Nominal secondary voltage (I np = 100 A) 22.5 mV
High energy pulse EN 61000-4-5 2 kV • Connections RJ45 plug
Magnetic field 50 Hz EN 61000-4-8 1 kA/m
Damped oscillatory wave EN 61000-4-12 2.5 kV — Residual current input
Ring wave EN 61000-4-12 2 kV Nominal current IEn 1 A or 5 A selectable by DIP Switch
Conducted common mode (0...150 kHz) EN 61000-4-16 10 V Permanent overload 25 A
Thermal overload (1s) 500 A
— Emission Rated consumption ≤ 0.006 VA (IEn = 1 A)
Reference standards EN 61000-6-4 (ex EN 50081-2) ≤ 0.012 VA (IEn = 5 A)
Conducted emission 0.15...30 MHz Class A Binary inputs
Radiated emission 30...1000 MHz Class A Quantity 3
Type dry inputs
— Climatic tests Max permissible voltage 19...265 Vac/19...300 Vdc
Reference standards IEC 60068-x, ENEL R CLI 01, CEI 50 Max consumption, energized 3 mA

— Mechanical tests OUTPUT CIRCUITS


Reference standards EN 60255-21-1, 21-2, 21-3
— Output relays K1...K4
— Safety requirements Quantity 4
Reference standards EN 61010-1 Command relays K1, K2, K4
Pollution degree 3 Type of contacts changeover (SPDT, type C)
Reference voltage 250 V Nominal current 8A
Overvoltage III Nominal voltage/max switching voltage 250 Vac/400 Vac
Pulse voltage 5 kV Breaking capacity:
Reference standards EN 60529 • Direct current (L/R = 40 ms) 50 W
Protection degree: • Alternating current (l = 0,4) 1250 VA
• Front side IP52 Make 1000 W/VA
• Rear side, connection terminals IP20 Short duration current (0,5 s) 30 A
Signalling relays K3
— Environmental conditions Type of contacts changeover (SPDT, type C)
Ambient temperature -25...+70 °C Nominal current 8A
Storage temperature -40...+85 °C Nominal voltage/max switching voltage 250 Vac/400 Vac
Relative humidity 10...95 %
Atmospheric pressure 70...110 kPa — LEDs
Quantity 8
— Certifications • ON/fail (green) 1
Product standard for measuring relays EN 50263 • Start (yellow) 1
CE conformity • Trip (red) 1
• EMC Directive 2004/108/EC • Trip I>, I>>, I>>> (red) 1
• Low Voltage Directive 2006/95/EC • Trip IE>, IE>> (red) 1
Type tests IEC 60255-6 • 52a - CB position (red) 1
• 52b - CB position (red) 1
COMMUNICATION INTERFACES • 79 - Auto recloser (red) 1
Local PC RS232 19200 bps GENERAL SETTINGS
RS485 port 1200...57600 bps
Protocol ModBus® RTU/IEC 60870-5-103 — Rated values
Phase CT nominal primary current (Inp) 1 A...5000 A
Residual CT nominal primary current (IEnp) 1 A...5000 A
Reading Direct / Relative

— Relay output timers


Minimum pulse width (K1t TR ... K4t TR) 0.01...0.50 s
NA011 - Flyer - 10 - 2021 3
PROTECTIVE FUNCTIONS — Digital inputs
• IN1 OFF - 52b -Trip EXT
— Phase overcurrent - 50/51 • IN2 OFF - 52a - Trip EXT - CB Open
I> Element • IN3 OFF - 79 Enable - 79 Remote - Trip EXT - CB Close
• I> Curve type (I>Curve) DEFINITE,
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, I2T — AutoReclose - 79
• CLP activation time (t CLP >) 0.00...100.0 s • 79 ActiveMode On - Off
• I> Reset time (t >RES) 0.00...100.0 s • 79 CycleState Reset - On - Off
Definite time • 79 Run On - Off
• 50/51 First threshold definite time (I> def ) 0.100...20.0 In • 79 Residual-time
• I> def within CLP (ICLP>def ) 0.100...20.0 In • 79 LastEvent
• I> def Operating time (t > def ) 0.03...10.00 s
Inverse time
— Counters
• Counter Start I>, Counter Start I>>, Counter Start I>>>
• 50/51 First threshold inverse time (I>inv) 0.100...2.50 In
• Counter Start IE>,Counter Start IE>>
• I>inv within CLP (ICLP>inv) 0.100...10.0 In
• Counter Trip I>, Counter Trip I>>, Counter Trip I>>>
• I>inv Operating time (t >inv) 0.02...60.0 s
• Counter Trip IE>, Counter Trip IE>>
I>> Element • Counter 79 RR
• CLP activation time (t CLP >>) 0.00...100.0 s • Counter 79 SR
• I>> Reset time (t >>RES) 0.00...100.0 s • Counter 79 RDR
Definite time • Counter 79 FR P
• 50/51 Second threshold definite time (I>> def ) 0.100...20.0 In • Counter 79 FR E
• I>> def within CLP (ICLP>>def ) 0.100...20.0 In • Counter 79 FR X
• I>> def Operating time (t >> def ) 0.03...10.00 s
I>>> Element
— Events recorder
Number of events 100
• CLP activation time (t CLP >>>def ) 0.00...100.0 s
Trigger: K1...K4, IN1, IN2, IN3 switching
• I>>> Reset time (t >>>RES) 0.00...100.0 s
Data recorded:
Definite time • Event counter 0...10 9
• 50/51 Third threshold definite time (I>>> def ) 0.100...20.0 In • Event cause info (operating phase) L1, L2, L3
• I>>> def within CLP (ICLP>>>def ) 0.100...20.0 In • Time stamp Date and time
• I>>>def Operating time (t >>> def ) 0.03...10.00 s
— Faults recorder
— Residual overcurrent - 50N/51N Number of faults 20
IE> Element Trigger:
• IE> Curve type (IE>Curve) DEFINITE, • Output relays activation (OFF-ON transition) K1...K4
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, I2T • External trigger (binary inputs) IN1, IN2, IN3
• CLP activation time (t ECLP>) 0.00...100.0 s • Element pickup (OFF-ON transition) Start/Trip
• IE> Reset time delay (t E> RES) 0.00...1.00 s Data recorded:
Definite time • Fault counter (F-Number) 0...10 9
• 50N/51N First threshold definite time (I E>def) 0.005...5.00 IEn • Fundamental RMS phase currents I L1, I L 2 , I L 3
• IE>def within CLP (IECLP>def ) 0.005...5.00 IEn • Fundamental RMS residual current IE
• IE>def Operating time (t E> def) 0.03...10.00 s • Fault cause (F-Cause) start, trip
Inverse time • Time stamp Date and time
• 50N/51N First threshold inverse time (I E>inv) 0.005...2.00 IEn
• IE>inv within CLP (IECLP>inv) 0.005...2.00 IEn — Digital Fault Recorder (Oscillography) [1]
• IE>inv Operating time (t E>inv) 0.02...60.0 s File format COMTRADE
Number of records 2 [2]
IE>> Element Recording mode circular
• IE>> Curve type (IE>>Curve) DEFINITE, Sampling rate 16 per power frequency cycle
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, I2T
• CLP activation time (t ECLP >>def ) 0.00...100.0 s Trigger setup
• IE>> Reset time delay (t E>> RES) 0.00...1.00 s • Pre-trigger time 0...63 T [3]
• Trigger from inputs IN1, IN2, IN3
Definite time • Trigger from outputs K1...K4
• 50N/51N Second threshold definite time (IE>>def) 0.005...5.00 IEn • General trigger from start / trip Start, Trip
• IE>>def within CLP (IECLP>>def ) 0.005...5.00 IEn • Manual trigger ThyVisor
• IE >>def Operating time (t E>> def ) 0.03...10.00 s • Trigger from start / trip Start I>, I>>, ...Trip I>...
Inverse time
Data recorded on analog channels (Analog channel 1...4)
• 50N/51N First threshold inverse time (I E>inv) 0.005...2.00 IEn
• Instantaneous currents i L1, i L2, i L3, i E
• IE>>inv within CLP (IECLP >>inv) 0.005...2.00 IEn
• Fundamental RMS phase currents I L1, I L 2 , I L 3
• IE>>inv Operating time (t E>>inv) 0.02...60.0 s
• Fundamental RMS residual current IE
— AutoReclose - 79 Data recorded on digital channel
79 Function mode (79 Mode) Rapid/Rapid+Slow • Binary inputs state IN1, IN2, IN3
Number of delayed reclosures (N.DAR) 0...5 • Output relays state K1...K4
Rapid reclosure dead time (t rdt) 0.1...60 s • General trigger from start / trip General Start, General Trip
Slow reclosure dead time (t sdt) 1...200 s Note 1 - The oscillography records are stored in non-volatile memory
Reclaim time (t r) 1...200 s Note 2 - The time duration of the two records is dependent of settings;
Slow reclosure fault discrimination time (t d) 0...10 s e.g. the record duration with f = 50 Hz is 240 ms with following settings:
• Instantaneous i L1 current into “Analog channel 1” i L1
METERING & RECORDING • Instantaneous i L2 current into “Analog channel 2” i L2
• Instantaneous i L3 current into “Analog channel 3” i L3
— Measured parameters • Instantaneous i E current into “ Analog channel 4” iE
• Fundamental RMS phase currents I L1, I L 2 , I L 3 • Digital channels K1
• Fundamental RMS residual current IE
Note 3 - T = number of power cycles
Example, with settings T= 4 the pre-trigger time is 80 ms with f = 50 Hz
4 NA011 - Flyer - 10 - 2021
— Example of connection diagram with traditional CT inputs and acquisition of CB states and Auto Reclose enable/start

+UAUX

DG 52a 52b

NA011
A2
K1
A1
A3
P1 C1
A4

CTs CURRENT INPUTS


S1 K2

OUTPUT RELAYS
IL1
S2 C2 A6
P2 C3 A5
C4 IL2
K3 A9
C5 A8
A7
IL3
C6
K4 A11
A12
A10
P1 C7
S1 Note [1]
IE [1] In versions NA011#xxx2
S2 C8 (with measured residual current)
P2

A13
A14 IN1
CB position
A15

-UAUX A16 IN2

79 Enable/79 External trip

+UAUX
A17
A18 IN3 79 IN3 Select
-UAUX

UAUX
A19 ≅
A20 UAUX
UAUX

FRONT PANEL
A+ 3
B-
RS232

RS485

2 E1
120Ω
1
A21
A22

NA011 - Flyer - 10 - 2021 5


— Example of connection diagram with low power CT inputs and acquisition of CB states and Auto Reclose enable/start

+UAUX

DG 52a 52b

NA011
K1 A5
A4
A6
P1
S1 4 + LPCT Setting
A9
K2

OUTPUT RELAYS
IL1

LPCTs CURRENT INPUTS


S2 6 -
P2
L1
A8
L2 A7
4 +
IL2
K3 A3
6 - L3

50 A
100 A
A2
200 A

4 +
400 A
800 A A1
IL3 In=50...1250A
6 - A11
K4
A12
A10
P1 C7
Note [1]
S1
IE [1] In versions NA011#xxx3
S2 C8 (with measured residual current)
P2

A13
A14 IN1
CB position
A15

-UAUX A16 IN2

79 Enable/79 External trip

+UAUX
A17
A18 IN3 79 IN3 Select
-UAUX

UAUX A19 ≅
A20 UAUX
UAUX

FRONT PANEL A+ 3
B-
RS485

2 E1
RS232

120Ω
1
A21
A22

6 NA011 - Flyer - 10 - 2021


DIMENSIONS

FRONT VIEW REAR VIEW


107 101 101

D1

A1 A1 L1
A2 A2 LPCT
C1 C2
Setting
A3 F1 A3
L2
A4 RX F2 A4
A5 F3 A5
1 2 3 4 5
A6 TX F4 A6
A7 F5 A7 L3
1 2 3 4 5
A8 C3 C4 A8

A9 B1 A9 1 2 3 4 5
A10 B2 A10

171

171
149

149
A11 A11
177

B3
A12 B4 A12 50
100
ON 1 2 3 4 5 A13 B5 A13 200
START 400
A14 C5 C6 B6 A14 800
TRIP
A15 B7 A15
A16 B8 A16 EX. In =
300A
(100+200)
A17 A17
A18 A18
A19 A19
A20 C7 C8 A20 C7 C8

A21 A21

3
A22 A22

2
1

1
E1 E1

Traditional CT inputs Low power CT inputs


SIDE VIEW FLUSH MOUNTING CUTOUT
102.5 ±0.3
75 30 75 30 70
161
154
3

3
2

2
1

Traditional CT inputs Low power CT inputs N.4 holes ø 3.5

IDENTIFICATION LABEL LEDS


ON & Diagnostic

In 5A 1A 5A In 5A 1A 5A
IEn 1A 1A 5A
UAUX 24-230 Vac/dc UAUX 24-230 Vac/dc
1 50-51 1 50-51 Start
2 50N-51N 2 50N-51N Trip
3 CB OPEN 3 CB OPEN
4 CB CLOSED 4 CB CLOSED
5 79 5 79

NA011#xxx0 NA011#xxx2

In Rated 50...500A In Rated 50...500A


In Extended 50...1250A In Extended 50...1250A
UAUX 24-230 V IEn 1A 1A 5A UAUX 24-230 V
1 50-51 1 50-51
2 50N-51N 2 50N-51N
3 CB OPEN 3 CB OPEN
Keys (CB open) and (CB close)
4 CB CLOSED 4 CB CLOSED are enabled
5 79 5 79

NA011#xxx1 NA011#xxx3
NA011 - Flyer - 10 - 2021 7
A PERSONALISED SERVICE OF THE PRODUCTION,
A RAPID DELIVERY, A COMPETITIVE PRICE
AND AN ATTENTIVE EVALUATION OF OUR
CUSTOMERS NEEDS, HAVE ALL CONTRIBUTED
IN MAKING US ONE OF THE BEST AND MOST
RELIABLE PRODUCERS OF PROTECTIVE RELAYS.
FORTY YEARS OF EXPERIENCE HAS MADE
STANDARD THESE ADVANTAGES THAT ARE
GREATLY APPRECIATED BY LARGE COMPANIES
THAT DEAL ON THE INTERNATIONAL MARKET.
A HIGHLY QUALIFIED AND MOTIVATED STAFF
PERMITS US TO OFFER AN AVANT-GARDE
PRODUCT AND SERVICE WHICH MEET ALL
SAFETY AND CONTINUITY DEMANDS, VITAL
IN THE GENERATION OF ELECTRIC POWER. OUR
COMPANY PHILOSOPHY HAS HAD A POSITIVE
REACTION FROM THE MARKET BY BACKING
OUR COMMITMENT AND HENCE STIMULATING
OUR GROWTH.

www.thytronic.it