UPS after Sales Services – FOC during Subsequent to inspections, we have seen SEMIANNUAL PACKAGE

warranty period and could be quoted that all the UPS units are neat and clean.
Checking for if there were dead batteries 1,Visually check for liquid contamination from
upon customers request/supplier batteries and capacitors.
which will result in not providing enough
recommendation backup time, visual a sign of corrosion, 2, Clean and vacuum UPS equipment enclosures.
leakage or swelling, as these signs indicate
that the battery needs to be replaced. 3, Check HVAC equipment and performance
related to temperature and humidity.
QUARTERLY PACKAGE 3, Monthly UPS system and room
temperature monitoring: temperature
check using thermal scanning, which uses a
BIANNUALLY PACKAGE
1. Monthly Visual UPS inspection: that
non-contact infrared thermometer to
incorporates a visual test of the UPS,
measure the surface temperature of the 1, A transient load test: a transient load test
plus a physical check of all electrical
chassis have been done in order to make simulates the performance of a UPS with large,
connections using thermal imaging
sure that the temperature around the UPS instantaneous swings in load. The UPS should
technology that can pick up more faults
is within the manufacturer's operating accommodate full-load swings without
than the human eye and touch. Checking
specifications. In fact, comprehensive visual distortion in output voltage or frequency.
for circuit breakers, contactors, fuses,
inspections also include internal 2. A harmonic analysis: a harmonic analysis
cabling, transformers, printed circuit
component inspections such as checking enables technicians to observe the harmonic
boards, capacitors, fans and
whether the AC input & output capacitors content at 0, 50, and 100 percent load, helping
communications-slots. Batteries inspection
and DC filter capacitors are clean to make technicians to determine the effectiveness of
for signs of damage, corrosion or leaks,
sure there are no signs of cracking or the input and output filters. If there is a
with all terminal connections checked to
expansion. However, one may get exposed marked difference in phase currents drawn
ensure they are at the correct torque
to dangerous currents when doing such through a filter assembly, it means one or more
setting. Several mechanical tests on the
inspections. capacitors have degraded.
functionality of the UPS, recording the
system’s operating state and vital electrical 3. A transient load test: a transient load test
measurements. ETHIO-TEBIB HOSPITAL simulates the performance of a UPS with large,
instantaneous swings in load. The UPS should
2, download and full review of the UPS accommodate full-load swings without
performance history logs, as well distortion in output voltage or frequency.
as ensuring the unit has the latest 4. A harmonic analysis: a harmonic analysis enables
firmware installed. Visual inspection to technicians to observe the harmonic content at 0,
identify if there is any accumulation of dust 50, and 100 percent load, helping technicians to
or dirt that can block the ventilation holes determine the effectiveness of
of the device and cause it to overheat.
the input and output filters. If there is a UPS AFTER SALES OFFER
marked difference in phase currents drawn
through a filter assembly, it means one or
more capacitors have degraded.
RIELLO UPS
IMIDIATE SERVICE RESPONSE

5. A battery-rundown test: a battery system


might be subject to failures that go
undetected. A battery-rundown test
enables one to observe temperature,
voltage, and current under load conditions.
Different voltages from battery to battery
or battery set to battery set clearly indicate
battery degradation. While conducting the Annual package
discharge test, technicians should continue
to check battery cell voltages. When the 1. Conduct thermal scans on electrical
battery set provides approximately 80 connections to ensure all are tight and not
percent or less of the rated capacity, it is generating heat, which is the first and
time to consider a full battery replacement. sometimes only indication of a problem. A
non-evasive diagnostic tool helps
technicians identify hot spots invisible to
the human eye. Technicians should
retorque if thermal scan provides evidence
of a loose connection.

2. Provide a complete operational test of


the system, including a monitored battery-
rundown test to determine if any battery
strings or cells are near the end of their
useful lives.