INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Power cables with extruded insulation and their accessories for rated voltages
above 150 kV (Um= 170 kV) up to 500 kV (Um= 550 kV)-Test methods and
requirements
"'
c
Q)
:;:;:-
9
N
N
0
"'
,._
CD
0
N
CD
u
�
Copyright lnterna ional Electrotechnical Commission
� THIS PUBLI CATION IS COPYRIGHT P ROTE CTED
Ln Copyrig ht© 2022 I EC, Geneva, Switze rland
All rights reserved. U n less otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IE C's member National Committee in the country of the requester. If you have any questions about I EC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local I EC member National Committee for further information.
Droits de reproduction reserves. Sauf indication contraire, aucune partie de cette publication ne peut etre reproduite ni
utilisee sous quelque forme que ce soit et par aucun procede, electronique ou mecanique, y compris la photocopie et
les microfilms, sans l'accord ecrit de l'IEC ou du Camile national de l'IEC du pays du demandeur. Si vous avez des
q uestions sur le copyright de l'IEC ou si vous desi rez obtenir des d roits supplementaires sur cette publ ication, utilisez
les coordonnees ci-apres ou contactez le Cam ile national de l'IEC de votre pays de residence.
A propos de l'IEC
La Commission Electrotech nique I nternationale (I EC) est la premiere organisation mondiale qui elabore et publie des
Normes internationales pour tout ce qui a trait a l'electricite, a l'electronique et aux technologies apparentees.
A propos des publications IEC
Le contenu technique des publications I EC est constamment revu. Veuil lez vous assurer que vous possedez !'edition la
plus recente, un corrigendum ou amendement peut avoir ete publie.
Recherche de publications IEC - Decouvrez noire puissant moteur de recherche et consultez
webstore.iec.ch/advsearchform gratuitement taus les aperi;us des publications. Avec un
La recherche avancee permet de trouver des publications IEC abonnement, vous aurez toujours acces a un contenu a jour
en utilisant differents criteres (numero de reference, texte, adapte a VOS besoins.
comite d'etudes, . . . ). Elle donne aussi des informations sur les
projets et les publications remplacees ou retirees. Electropedia - www.electropedia.org
Le premier dictionnaire d'electrotechnologie en ligne au monde,
IEC Just Published - webstore.iec.ch/justpublished avec plus de 22 300 articles terminologiques en anglais et en
Restez informe sur les nouvelles publications I EC. Just frani;ais, ainsi que les termes equivalents dans 19 langues
Published detaille les nouvelles publications parues. additionnelles. Egalement appele Vocabulaire
Disponible en ligne et une fois par mois par email. Electrotechnique I nternational (IEV) en ligne.
Service Clients - webstore.iec.ch/csc
Si vous desirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
IEC Products & Services Portal - products.iec.ch
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Power cables with extruded insulation and their accessories for rated voltages
above 150 kV (Um= 170 kV) up to 500 kV (Um= 550 kV)-Test methods and
requirements
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
Warni ng! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distri buteur ag ree.
CONTENTS
F O R EW O R D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ?
I NT R O D U C T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Normative refe re n ces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Terms and d efi n itions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1 Defi n itions of d i m e n s i o n a l val ues (th icknesses, cross-sections , etc . ) . . . . . . . . . . . . . . . . . . . . 12
3.2 Defi n itions re lating t o tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 Other d efi n itions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Voltage designations, m ate rials and rou n d i n g of n u m be rs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Rated voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 4
4.2 C a b l e i n s u lating compou nds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 4
4.3 C ab l e metal scree ns/sh eaths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4 C ab l e overs heath i n g compounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.5 Rou n d i n g of n u mbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5 Precautions ag ai nst water penetration i n cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 Ca b l e characte ristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 Accessories c h aracteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.1 Gas i m mersed cable term i n ations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.2 I n su lato rs fo r outdoor c a b l e term i n at i ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7. 3 Accessory characte ristics to be declared 17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8
8.1 A m b i ent te m pe rature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8
8.2 H i g h voltage tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8
8.3 Waveform of i m pu lse test voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8
8.4 Relations h i p o f test voltages t o rated volta ges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8
8.5 Dete r m i nation o f t h e ca b l e conductor te m p e rature 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 2.5. 1 3 Measurement of carbon black content for black P E overs heaths (ST 3
a n d ST 7 ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1 2.5. 1 4 Test u n d e r fi re co nd itions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1 2 . 5. 1 5 Water penetration test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1 2 . 5. 1 6 Tests for co m p o n e n ts of cables with a l o n g itud i na l ly a p p l ied metal tape
or foi l , bonded to the oversheath . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
13 Preq u a l ification test of the cable system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1 3. 1 General a n d rang e of p req u a l ification test a p p rova l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1 3.2 P req u a l ification test o n com p l ete cable syste m . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 9
1 3.2. 1 S u m m a ry of p re q u a l ification tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1 3.2.2 Test voltage val ues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1 3.2.3 Test arra n g e m e n t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1 3.2.4 Heati n g cycl e vo ltage test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1 3.2.5 Lig htn i n g i m p u lse voltage test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1
1 3.2.6 Exam i n ation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1
1 3.3 Tests for the exte nsion of t h e preq ual ification o f a cable system . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1
1 3.3. 1 S u m m a ry of the exte nsion of preq ua l ification test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1
1 3.3.2 E l ectrical part o f t h e exte nsion o f pre q ual ification tests on complete
cable system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1
14 Type test o n cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
15 Type test o n accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
16 E l ectrical test afte r installation (on-site tests) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1 6. 1 Genera l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1 6.2 DC vo ltage test o f the overs heath . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1 6.3 Tests u s i n g A C voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1 6.3. 1 AC voltage test of the i n s u lation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1 6.3.2 Partial d ischarge test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A n nex A ( i nformative) Determ i n ation of the cable conductor te m pe rature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
A. 1 P u rpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
A.2 C a l i b ration of t h e te m pe rature o f the m a i n test l o o p . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2
A.2 . 1 Gene ra l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
A.2.2 I nsta l l ation of cable and tem pe ratu re se nsors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
A.2.3 C a l i bration method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
A.3 Heati ng for the test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
A. 3 . 1 Method 1 - Test u s i n g a refe re nce ca b l e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
A.3.2 Method 2 - Test u s i n g conductor te m p e rature calculations a n d
measurement o f the surface temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
A n nex B ( normative) Ro u n d i ng of n u m bers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
A n nex C ( i nformative) Li st of type , p req ual ificat i on a n d exte nsion of p req u a l ification
tests fo r cable syste m s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
A n nex D ( n ormative) M easure m e n t m ethod for resi stiv ity of sem i-cond u cti ng scree ns . . . . . . . . . 59
A n nex E ( normative) Water penetration test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
E.1 Test pi ece . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
E.2 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
E.3 Req u i re m e nts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
A n nex F ( n ormative) Test for water penetration i n the conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
F.1 Test pi ece . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
F.2 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
F i g u re 1 - Exa m p l e of E Q test a rra ngement for the p req u a l ification of a syste m with
another j o i nt, d es i g ned for rig i d as we l l as for flex i b le i n sta l lation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
F i g u re A. 1 - Schem atic d iagram of test set-up for the refere nce loop and the ma i n test loop . . . 53
F i g u re A.2 - Example of an a rra ngement of the temperature se nsors on the cond u ctor
of the reference loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
F i g u re D . 1 - Di mensions fo r p re p aration of sample s fo r measurement of resistiv ity of
cond uctor scree n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
F i g u re D . 2 - Di mensions fo r p re paration of sample s fo r measurement of resistivity of
i n sulation scree n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
F i g u re E . 1 - Schem atic d i a g ra m o f a p paratus for water penetration test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
F i g u re F . 1 - Schematic d i agram of a p pa ratus for water penetration test in the
cond uctor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
F i g u re G . 1 - Ad hesion of metal tape or fo i l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
F i g u re G . 2 - Exa m ple of ove rlapped metal foi l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
F i g u re G . 3 - Peel strength of ove rlap ped meta l foi l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
F i g u re G.4 - Typ ical stre ngth versus g r i p spacing curve ( 1 ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
F i g u re G . 5 - Typ ical stre ngth versus grip spacing curve ( 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
FOREWORD
1 ) The I nternati onal Electrotech n i cal Co mm ission (I EC) is a worldwide org anization for standard ization comprising
all national electrotechnical comm ittees ( I E C National Co mmittees). The object of I EC is to promote i nternational
co-operation on all q uestions concern i n g standard izati on i n the el ectrical and e lectronic fields. To this end and
i n addition to other activities, I E C pub lishes I nternational Stand ards, Tech nical Specificati ons, Techn ical Reports ,
Publ icly Available Specifications ( PAS) and G u ides (hereafter referred to as "IEC Publ ication (s )"). Their
prepa ration is entrusted to tech nical comm ittees; any I E C National Com mittee i nterested i n the s u bject dealt with
may partici pate i n this preparatory work. I nternational, govern mental and no n-gove rnmental orga nizations liaising
with the I E C also partici pate i n this preparation. I E C co llaborates closely with the I nternational Organ ization fo r
Standard ization ( I SO) i n accordance with conditions dete rmined by agreement between the two organizations.
2 ) The fo rmal decisions o r agreements of I EC on tech nical matters express , as nearly as possible, a n i nternational
consensus of opinion on the releva nt subjects s i nce each tech nical comm ittee has representation from all
i nterested I E C National Committees.
3) I EC Publ ications have the fo rm of recommendations for i nternational use and are accepted by IEC National
Comm ittees i n that sense. While all reasonable efforts are made to ensure that the technical content of I EC
Publ ications is accu rate , IEC can not be held res ponsible for the way i n which they are used o r fo r any
misi nterpretation by any end user.
4) In o rder to promote i ntern ational u n iform ity, I EC National Comm ittees und ertake to apply I EC Publ ications
transparently to the maximum extent possible i n their national and regional publ ications. Any divergence between
any I EC Publ ication and the corres pond ing national or reg ional publ ication shall be clearly i n dicated in the latter.
5) I EC itself d oes not provid e any attestation of conformity. I ndependent certification bodies provide conformity
assessment services and, in some areas, access to I EC marks of conformity. I E C is not respons i ble fo r any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publ icati o n .
7) N o liability shall attach t o I E C or its d i rectors, employees, servants or agents i n c l u d i n g individual experts and
members of its tech n ical comm ittees and I E C Nati onal Comm ittees for any personal i nj u ry, property damage or
other damage of any nature whatsoever, whether di rect o r indirect, or for costs (including legal fees) and
expenses arising out of the publ ication, use of, o r reliance upon, this IEC P u blication o r any other IEC
Publ ications.
8) Attention is d rawn to the N ormative refe rences cited i n this publ icati o n . Use of the referen ced publ ications is
indispensable fo r the correct appl ication of this publ ication.
9) Attention is d rawn to the possibility that some of the e leme nts of this I EC Publ ication may be the subject of patent
rights. IEC shall n ot be held respon sible for ide ntifying any or a l l such patent rights.
I E C 62067 has been prepared by I E C tech nical co m m i ttee 20: E l ectric cables. It is a n
I n ternational Stand ard .
This edition i n c l udes the fol l owi n g s i g n ificant tech n i ca l changes with respect to the p rev ious
edition:
a ) A n ew materi al class (ST 1 2 ) is i ntrod uced which h a s fire performance req u i rements .
b ) A fu l l ra n g e of fire perform ance tests is ava i l a b l e w h i c h can b e sel ected o n the basis of
cl a im ed cable perform a n ce c h aracteristics .
c) The ra nge of cable metal screen d e s i g n s and the b e n d i n g test has been revised i n l i n e with
IEC T R 6 1 9 0 1 [ 1 ] 1 .
d ) Req u i rem ents a re i ntro d uced for outdoor term i n ation i n s u l ators .
e ) Des i g n a n d testing req u i re ments for gas i m m e rsed termi nations ( and t h e i r separati n g
i n su lati n g barriers ) a re coord i n ated with I EC 6227 1 -209 . An a d d ition a l type test i s req u i red
where the separating i n su lating barrier is i n sta l le d by the switchgear m a n ufacturer.
f) A separate water penetration test for the cable co n d u ctor is req u i re d .
g ) A C voltage test i n g o f t h e i n s u lation after i n sta l l ation h a s b e e n revised i n l i n e with rece ntly
p u b l ished C I G R E recom mendations .
h ) Tests have been added for a change i n the type of i n s u l ating gas used i n the cable
con nection enclosure of a gas i m m e rsed term i n ati o n .
F u l l i nformation on the voting for its a p proval can be fo u n d in the re port on voti ng i n d icated i n
the above tab l e .
The comm ittee has decided that the conte n ts of t h i s document w i l l rem a i n u n changed u n t i l the
sta b i l ity d ate i nd icated o n the I E C webs ite u n d e r webstore . iec.ch i n the d ata rel ated to the
s pecific doc u m e n t . At this date, the docu m ent will b e
• re confi rmed ,
• withdrawn ,
• re p laced by a rev ised editio n , or
• a m e n d ed .
INTRODUCTION
As a res u lt of maj o r deve l o p me nts i n cable syste ms with extruded i n s u lation fo r voltages a bove
1 50 kV , C I G R E Study C o m m ittee ( S C ) 2 1 set up Work i n g G ro u p (WG) 2 1 .03 in 1 99 0 . The terms
of refe rence of WG 2 1 . 03 were "to prepare recomme n dations for electrical type tests, sample
and routine tests, based on exten ding /EC 60840: 1 9 8 8 up to 400 kV and to make proposals for
prequalification/development tests which, as a minimum, sho uld b e performe d" .
WG 2 1 . 03 re ported that the exte nsion of I EC 60840 [2] to voltages a bove 1 50 kV needed extra
cons i deration because of the fol lowi n g factors :
1 ) such cab les form part of the backbone of the tra n s m ission system a n d , therefore , re l i a b i l ity
cons iderations a re of the hi g hest pri ority ;
2 ) these cab les and t h e i r accessories operate with h i g h e r e l ectrical stresses t han cables u p to
1 50 kV a n d , as a res u lt, have a s m a l l e r safety m a rg i n with respect to the i ntri nsic
perform ance bound aries of the cable syste m ;
3 ) such cables a n d accessories have a t h i cker i n su lation wa l l than those u p t o 1 50 kV a n d , as
a res u l t , a re s u bj ected to g reater thermo-me chanical effects ;
4) the d e s i g n and coord i n ation of the cables a n d accessories become more d iffi c u l t with
i n creas i ng syste m voltage leve l s .
On the advice of C I G R E , a long term acce le rated a g e i n g test was i ntrod uced i n the first e d i t i o n ,
i n o r d e r t o g a i n s o m e i n d ication o f the long term rel i a b i l i ty o f a c a b l e system . This test, known
as the "preq u a l ification test", was to be performed on the com p l ete system comprising the cab l e ,
joi nts a n d term i n ations i n ord e r t o demonstrate t h e p e rforma nce o f the system .
At its meet i n g i n November 2004 , T C 2 0 concluded that the next rev i s i o n of I EC 62067 s h o u l d
i n cl u de the reco m m endation for test i n g o f HV a n d E H V extruded cables t hat w a s u nd e r
preparation by the C I G R E S C B 1 ( previously S C 2 1 ) WG B 1 . 0 6 . T h i s was made ava i l able as a
C I G R E Tec h n i ca l B roch u re 303 [6] before the meeting of TC 20 i n O ctober 2006, wh ich
confi rmed this view. Therefore , Tec h n ical B roch u re 303 has been considered by TC 20 and
m aj o r pa rts have been i m p le m ented i n this sta n d a rd . This has resu lted i n some mod ifications
to the p req u a l ifi cation test req u i rements, a major change b e i n g the addition of the exte nsion of
the preq u a l ifi cation test. Th e l atte r test req u i res a pproxim ate ly one q u a rter of the time to
com p l ete w h e n compared with the fu l l preq ual ificati o n test.
This t h i rd edition of I E C 62067 has been prod uced as part of the normal period i c rev iew a n d
u p d ati ng p roced u res o f I E C t a k i n g i nto acco u n t p rog ress and developme nts w i t h i n the e n e rg y
i n d u stry .
1 Sco p e
This docu ment specifies test methods and req u i re m e nts for power ca b l e syste ms, cables with
extruded i n s u l ation and their accessories for fixed i n sta l l at i ons, for rated voltages a bove 1 50 kV
( Um = 1 70 kV) u p to and i nc l u d i n g 500 kV ( Um = 550 kV) .
T h i s document does not cover transition j o i nts between cables with extruded i n s u lation and
paper i n s u l ated cables.
The following docu m ents a re refe rred to in the text in s u c h a way that some or a l l of t h e i r content
constitutes req u i re m e nts of this document. For dated refe rences , only the edition cited a p pl i es .
For u n d ated references , the latest ed ition of the refe renced document ( i n c l u d i n g a n y
a m e n d m e nts ) a p p l ie s.
I EC 60060- 1 , High-voltage test techniques - Part 1 : Gen eral definitions a n d test requirements
I E C 60060-3, High-voltage test techniques - Part 3: Definitions and requirements for on-site
testing
IEC 601 37, Insulated b ushings for alterna ting voltages above 1 000 V
I E C 602 2 9 : 2 0 0 7 , Electric cables - Tests on extruded oversh eaths with a special protective
function
I E C 60287- 1 - 1 , Electric cables - Calculation of the current rating - Part 1 - 1 : C urrent rating
equations ( 1 00 % load fa ctor) a n d calculation of losses - General
I E C 60332- 1 -2 , Tests on electric and optical fibre cables under fire conditions - Part 1 -2: Test
for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre
mixed flame
I E C 60332- 1 - 3, Tests on electric and optical fibre cables under fire conditions - Part 1 -3: Test
for vertical flame propagation for a single insulated wire or cable - Procedure for determination
of flaming droplets/particles
I E C 60332-3-24, Tests on electric a n d optical fibre cables under fire con ditions - Part 3-24:
Test for vertical flame spread of vertically-mounte d bunched wires or cables - Category C
I E C 60754-2, Test on gases e volved during combustion of materials from cables - Part 2:
Determination of acidity (by pH measurement) a n d conductivity
I E C 60754-3, Test on gases e volved during combustion of materials from cables - Part 3:
Measurement of low level of halogen content by ion chroma tography
I E C 608 1 1 -2 0 1 , Electric and optical fibre cables - Test m ethods for n on-metallic ma terials -
Part 2 0 1 : General tests - Measurement of insulation thickness
I E C 608 1 1 -2 02: 2 0 1 2 , Electric and optical fibre cables - Test methods for non-metallic materials
- Part 202: Gen eral tests - Measurement of thickn ess of non-metallic sheath
I E C 608 1 1 -202 : 2 0 1 2/AM D 1 : 20 1 7
I E C 608 1 1 -203, Electric and optical fibre cables - Test methods for non-metallic ma terials -
Part 203: Gen eral tests - Measurement of o verall dimensions
I E C 608 1 1 -40 1 , Electric and optical fibre cables - Test meth ods for n on-metallic ma terials -
Part 4 0 1 : Miscellaneous tests - Thermal ageing methods - Ageing in an air oven
I E C 608 1 1 -4 03, Electric and optical fibre cables - Test meth ods for n on-metallic ma terials -
Part 4 03: Miscellan eo us tests - Ozone resistance test on cross-linked compounds
I E C 608 1 1 -4 0 9 , Electric and optical fibre cables - Test methods for non-metallic ma terials -
Part 409: Miscellaneous tests - Loss of mass test for therm oplastic insulations and sheaths
I EC 6 0 8 1 1 -5 0 1 : 2 0 1 2 , Electric and optical fibre cables - Test meth ods for n on-metallic materials
- Part 50 1 : Mechanical tests - Tests for determining th e mechanical properties of insulation
a n d sheathing compounds
I E C 6 0 8 1 1 -5 0 1 : 2 0 1 2/AM D 1 : 20 1 8
I E C 608 1 1 -505, Electric and optical fibre cables - Test meth ods for n on-metallic ma terials -
Part 505: Mechanical tests - Elongation at l o w temperature for insulations a n d sheaths
I E C 608 1 1 -506, Electric and optical fibre cables - Test methods for non-metallic ma terials -
Part 506: Mechanical tests - Impact test at l o w temp erature for insulations a n d sheaths
I E C 608 1 1 -507, Electric and optical fibre cables - Test methods for non-metallic ma terials -
Part 5 0 7: Mechanical tests - Hot set test for cross-linked materials
I E C 6 0 8 1 1 -5 0 8 : 2 0 1 2 , Electric and optical fibre cables - Test meth ods for n on-metallic ma terials
- Part 508: Mechanical tests - Pressure test at high temperature for insulations and sheaths
I E C 608 1 1 -50 8 : 2 0 1 2/AM D 1 : 20 1 7
I E C 608 1 1 -509 , Electric and optical fibre cables - Test methods for non-metallic materials -
Part 509: Mechanical tests - Tests for resistance of insulations a n d sh eaths to cracking (h eat
shock test)
I E C 608 1 1 - 6 05: 20 1 2 , Electric a n d optical fibre cables - Test m e th o ds for n on-metallic ma terials
- Part 605: Physical tests - Measurement of carbon black and/or min eral filler in polyethylene
compounds
I E C 6 0 8 1 1 -606, Electric a n d optical fibre cables - Test m ethods for n on-metallic ma terials -
Part 606: Physical tests - Methods for determining the density
IEC 60885-3, Electrical test m eth ods for electric cables - Part 3: Test meth o ds for partial
discharge measurements on lengths of extruded p o wer cables
IEC 621 55, Hollo w pressurized and unpressurized ceramic and glass insulators for use in
electrical equipment with rated voltages greater than 1 000 V
3 Terms a n d defi n it i o n s
For the p u rposes o f t h i s docu ment t h e fol l owi n g te rms a n d defi n itions a p p l y .
3. 1 . 1
n o m i n a l val u e
va l u e b y w h i c h a q u a ntity i s d es i g n ated a n d w h i ch is often u s e d i n tables
N ote 1 to entry: Usua lly, in this document, nominal values give rise to values to be checked by measurements
taking i nto account s pecified tolerances.
3.1 .2
median va l u e
w h e n several test res u lts have b e e n obtained a n d orde red i n a n i n cre a s i n g ( o r decreas i n g )
s u ccess i o n , m id d l e va l u e i f t h e n u mber o f ava i l a b l e va l u es i s o d d , a n d mean o f t h e two m i d d l e
v a l u e s i f the n u mber i s even
3.2.1
ro u t i n e test
test made by the m a n ufacturer on each m a n ufact ured component ( length of cable or accessory)
to check that the component m eets the specified req u i re me nts
3.2.2
s a m p l e test
test made by the m a n ufact u re r on s a m p les of co m p l eted ca b l e , or com pone nts take n fro m a
com p l eted cable or accessory, at a specified freq ue ncy , so as to verify t hat the fi n ished prod uct
meets the s pecified req u i re m e nts
3.2.3
type test
test made before s u p p lying , o n a g e n e ra l com mercial basis, a type of cable system covered by
t h i s document, i n ord e r to demonstrate satisfactory perform ance characteristics to meet the
i nten ded a p p l ication
N ote 1 to entry: Type tests are of such a nature that, after they have been made, they need not be repeated u nless
changes are made i n the materials, design o r type of man ufactu ring process of cable or accessory which might
change the performance characteristics.
3.2.4
p req u a l ification test
PQ test
test m ade before s u pplying , on a g e n e ra l com me rcia l basis, a type of cable system covered by
t h i s document, in order to demonstrate satisfactory long term perform a n ce of the complete cable
system
3.2.5
exte n s i o n o f p re q u a l ificat i o n test
EQ test
test m ade before s u pplying , on a g e n e ra l com me rcia l basis, a type of cable system covered by
t h i s document, in order to demonstrate satisfactory long term perform a n ce of the complete cable
system , taking i nto acco u n t a n a l ready p req u a l ifi ed c a b l e system
3.2.6
e l e ctrical test after i nstal lation
test made to demonstrate the i nteg rity of the cable system as insta l led
N ote 1 to entry: I nteg rated optical e lements, if prese nt, will be tested upon purchaser req uest. Tests to be defi ned
on agreement between p u rchaser and man ufacturer.
3.3.1
cable system
cable with i nsta l led accessories i n c l u d i ng components used for thermo-mecha n i cal restra i nt of
system s l i m ited to those used for term i n ations a n d j o i nts o n l y
3.3.2
n o m i n a l e l ectrical stress
e l ectrical stress calcu la ted at u0 u s i n g n o m i n a l d i me nsions
N ote 1 to entry: The equations for calculation of the stresses are g iven i n Clause 6 , item n).
3.3.3
combined d es i g n
CD
metal screen d e s i g n that com b i nes rad i a l watertig htn ess a n d e lectrical prope rties
3.3.4
separate d e s i g n
SD
meta l screen d es i g n t h at use s differe nt meta l co mponents fo r rad i a l watertig htness a n d
e l ectrical properties
3.3.5
separate se m i -co n d u ctive d es i g n
SscD
meta l screen design that has separated e lectrical a n d rad i a l watertig htness p rope rties and uses
sem i-cond uctive p lasti c-coated fo i l
3.3.6
n o m i n a l cond u ctor c ross-sect i o n a l a rea
size of the cable co n d u ctor in accorda nce with I EC 60228
3.3.7
maxi m u m mechanical load
MML
h i g h est mecha n i ca l canti lever load which i s expected to be a p p l ied t o a com posite outdoor
term i nation i ns u l ator i n serv i ce and fo r w h i c h it i s de signed
3.3.8
maxi m u m s e rvice p res s u re
MSP
h i g h est di fference between t h e max i m u m absolute i nternal p ress u re , w h e n t h e e q u i pment (of
w h i c h a composite hol low i n s u l ator is a pa rt) is carry i n g its rated normal cu rrent at max i m u m
operati o n a l temperature a n d the normal outside p res s u re
3.3.9
c a b l e a ccessory w i t h screen o r m etal sheath i nterru ption
cable accessory w h e re the metal screen/sheath and i n s u lation scree n of the cable are
e l ectrica l l y i nte rru pted
3.3. 1 0
j o i n t with screen o r m etal s heath i n terru ption
j o i nt where the meta l scree n/sheath a n d i n s u l at i on screen of the cable a re e l ectrica l ly
i nterru pted
3.3. 1 1
term i nation with a n i ns u l ated screen
term i nation w h e re the m etal screen/s h eath and i n s u l at i on screen of the cable a re e l ectri ca l ly
i nterrupted to the g ro u n d
In this docu me nt, the sym bols u0 , U and Um a re used to designate the rated voltages of cables
and accessories w h e re these sym bols have the mea n i ngs g iven in I E C 6 0 1 83 [7].
It is reco m m e n d ed that cable cores with a cross- l i n ked i n s u lation syste m s h o u l d have been
degasse d .
This document a p p l ies to the various designs i n use . I t covers des i g n s prov i d i n g a rad i a l
watertig htness a n d d e s i g n s that do n o t provi de rad i a l watertig htness.
I n all cases the m eta l scree n/sheath s h a l l be able to meet the screen short c i rcuit rati n g .
NOTE Defi nitions of CD, S D , and SscD a re given in 3.3.3, 3.3.4 and 3.3.5
com pos ite scree ns, i nvolvi ng a layer of wi res and either a metal s heath o r a metal tape or
fo i l bonded to the oversheath , acti ng as a ra d i a l water i m permeable barrier (see C l a use 5 ) ,
D u ri n g develop m e n t o f t h e cable a n d c a b l e syste m , with a long itud i na l l y a p pl ie d metal tape
or foi l bonded to the oversh eath , the tests as s pec ified in I E C T R 6 1 9 0 1 [ 1 ] a re
reco m mended .
4.4 C a b l e oversheath i n g co m p o u n ds
I f there i s concern that the oversheath w i l l be deteriorated b y U V ra d i atio n , the overs heath s h a l l
b e p rotected agai nst UV rad iati o n , w h i c h w i l l b e m utually agreed w i t h t h e p u rchaser.
B lack P E oversheaths conta i n i n g the req u i red a m o u nt of a su ita b l e a n d well-dis persed g rade
of carbon black (see Table 5 ) a re protected a g a i nst UV rad iati o n .
NOTE 1 F o r i nstal lation i n a i r a s fo r exa m ple i n tunnels or buildings, i t is p referable for the cable t o have some fire
performa nce and low smoke and ha logen free properties. For such appl ications, an ST 12 (LSHF) overs heath can be
applied.
NOTE 2 For some appl ications the oversheath can be covered by a fu nctional layer (e.g. semi-conductive).
4 .5 Ro u n d i n g of n u m be rs
When cable system s a re i n sta l led in the gro u n d , in locatio n s with a risk of water i ng ress or
corrosion or i n water, a rad i a l water i m permeable barri e r is reco m me nded .
Longitud i n a l water barriers can a lso be a p p l ie d i n order to avoid the need to re p lace long
secti ons of cable i n case of d a mage i n the p resence of wate r.
6 C a b l e c h a racterist i cs
For the p u rpose of carry i n g out the cable syste m or cable tests described i n this document and
record i n g the res u lts , the cable shall be i d entified .
NOTE F i re performance is dependent on the cable design as well as the oversheath materi a l .
d ) type o f cond uctor, its material and n o m i n a l cross-secti o n a l a re a , i n sq uare m m ; conductor
constructi on ; p resence , if a n y , and nature of measures taken to red u ce skin effect;
presence, if any, and n at u re of measures take n to a c h i eve long itud i n a l watertig htness; if the
n o m i n a l cross-sectio n a l area is not in acco rda n ce with I EC 60228, the m a x i m u m
DC conductor res istance , corrected t o 1 km l e n g t h a n d t o 20 ° C ;
e ) com pound ( as d efi ned i n Ta b l e 1 ) a n d n o m i n a l th ic kness o f insu lation ( t n ) (see 4 . 2 ) ;
where
u0 is the v a l u e declared i n item b) above i n kV;
Dia = di i +
2 tn ;
Dia is the cal c u l ated n o m i n a l outer d ia m eter of the i n s u lati o n , i n m m ;
di i is the declared n o m i nal i n n er d i a meter of t h e i n su lati o n , i n m m ;
7 Accessories c h a racte r i s t i cs
I n s u lators for outdoor cable term i n ations shall com p l y with the req u i re me nts g iven i n Table 1 1
for Leve l I or I I m ax i m u m canti lever operating load i n serv i ce (or M M L i n the case of com posite
i n s u lators ) . Level I refers to a normal load and s h a l l be ge ne ra l ly a p p l i e d , u n less a p u rchaser
specifies a heavy load of Level I I . Altern atively, a d iffe rent v a l u e of m axi m u m canti lever
operati ng load or M M L can be agreed between the p u rchaser a n d m a n ufact urer.
For the pu rpose of carry i n g out the cable syste m or accessory tests descri bed i n this docu m ent
a n d record i n g the resu lts , the accessory s h a l l be identified .
8 Test c o n d i t i o n s
U n l ess otherwise s pecified i n the deta i l s for the particu l a r test, tests s h a l l be carried out at a n
a m bi ent tem peratu re o f (20 ± 1 5 ) ° C .
Where test voltages are spec ified i n this document as mu lt i ples of the rated voltage u0 , the
value of u0 for the d eterm i n ation of the test voltages sha l l be as s pecified in Table 4 .
For cables and accessories of rated voltages n ot s hown i n the ta b l e , the value of u0 for the
determi nation of test voltages can be the same as fo r the nearest rated voltage which i s g i v e n ,
provided t h a t the va l u e o f Um for the ca b l e and accessory is n o t h i g h e r t han the co rrespond i n g
value i n t h e ta b l e . Otherwise, a n d particularly i f t h e rated voltage is n o t close t o o n e of the
values in the table, the value of u0 on w h i c h the test voltages are based shall be the rated
va l u e , i . e . U d ivided by '13 . The associated test voltages s h a l l be esta blished by c a l c u l ation
u s i n g the m u lt i p l ie rs g iven i n Table 4 or i nterpolation whe re no m u lti p l i e r i s give n .
T h e test voltages i n this document a re based o n t h e assu m ption t hat t h e cables a n d accessories
are used on a system of category A, as defi ned in I E C 601 83 [7] .
It is recom mended that one of the test methods described i n An nex A is used to determ i n e the
actual con d u ctor te m pe rature.
E lectrical tests on gas i m mersed term i n ations s h a l l be carried out i n a cab l e con nection
en clos u re with the d i a meter specified i n I EC 622 7 1 -209 fo r the re levant value of rated volta g e .
The gas p ress u re req u i re m e nts fo r e l ectrical type tests g iven i n I EC 62271 -209 s h a l l a l s o b e
com p l ied with .
9 Ro u t i n e tests o n ca b l es a n d access o r i es
9.1 G e n e ra l
I n cases 2 ) and 3 ) , the test voltage sh al l be selected s o as t o obta i n at le ast the same e l ectrical
stresses as those on the com ponent i n a com p lete accessory when s u bj ected to the test
voltages specified in 9 . 2 a n d 9 . 3 .
O utdoor term i nation i ns u l ators , which w i l l be s u bj ected t o i nternal gas press u re i n service, s h a l l
b e s u bjected t o t h e routine press u re test accord i n g t o I EC 6 1 462 for com pos i te insu lators , o r
I E C 6 2 1 55 fo r cera m i c i ns u l ators . N o fa i l u re s ha l l occ u r .
NOTE The main insulation of prefabricated accessories cons ists of the components that come i n d i rect contact with
the cable insu lation or are necessary to control the electric stress d istri bution in the accessory. Exam p les a re pre
moulded or precast elastomer or fi l l ed epoxy res i n insu lating com ponents that ca n be used s i ngly o r jointly to provid e
t h e necessary insu lation or screening o f accessories.
The pa rti al d i sc h arge test s h a l l be ca rried out in accorda nce with I EC 60885-3 for ca bles and
the sensitivity as d efi ned i n I E C 60885-3 s h a l l be 1 0 p C or bette r. Testi n g of accessories fol lows
the same princi p l es , but the sensitivity s h a l l be 5 pC or better.
There s h a l l b e no d etectab l e d isc h arg e excee d i n g t h e declared sensitivity from t h e test obj ect
at 1 , 5 u0 .
The voltage test sha l l be made at a m bie nt te m pe rat ure u s i n g an a l ternating test voltage at
power freque ncy.
The test voltage s h a l l be ra ised g rad ually to the s pecified value wh ich s h a l l then be held for the
specified time betwe e n the conductor and metal scree n/sheath accord ing to Table 4, co l u m n 4.
S u bject to agree ment between p u rc haser a n d m a n ufacturer, the cable overs heath sha l l be
s u bjected to the e lectrical test specified i n C l a use 3 of I EC 60229:2007.
1 0 Sa m p l e tests o n c a b l es
1 0. 1 G e n e ra l
The fo l lowi ng tests s h a l l be carried out o n s a m p les whi ch, for t he tests i n i t e ms b ) a n d g ) below,
s h a l l be co m p lete d rum l e ngths o f ca b l e , taken t o re p resent batches:
The s a m pl e tests in items a) to h) and k) of 1 0 . 1 s h a l l be carried out on one l e ngth fro m each
batch ( m an ufacturi ng series) of the same type a n d cross-section of cable but sha l l be l i m ited to
not more than 1 0 % of the n u m be r of lengths in any contract, rou nded to the nearest whole
n u mber.
The fre q u e ncy of the tests i n items i) and j) of 1 0 . 1 s ha l l be in accord ance with ag reed q u a l ity
control p roced u re s. I n the a bsence of s uch an a g ree m e nt, one test s h a l l be made for con tracts
with a ca b l e length between 4 km a n d 20 km a n d two tests for contracts with longer cable
lengths.
If the s a m p l e from any length selected for the tests fa i l s in any of the tests in C l ause 1 0 , fu rth e r
s a m p les s hal l be t ake n fro m two further lengths of the same batch a n d s u bjected to the same
tests as those in w h i c h the ori g i n a l sample fa i l ed . If both add itio n al s a m p les pass the tests , the
other cables i n the batch fro m w h i c h they were ta ken shall be regarded as having complied with
the req u i reme nts of t h i s docu m e nt. I f either fa i l s , this batch of cables shall be regarded as
having fa i l ed to co m p l y .
1 0 .4 C o n d u ctor e xa m ination
Co m p l i a nce with the req u i re m ents of I E C 60228 for conductor constructio n , or the declared
constructi o n , s h a l l be checked by i n s p ection and me asurement when p racti cable.
1 0.5 Meas u re m ent o f e l ectrical resi sta nce o f co n d u ctor a n d o f metal s c ree n/s heath
The DC resistance of the co n d u ctor or meta l scree n/s heath sha l l be corrected to a te mperature
of 20 ° C a n d a 1 km l e ngth i n accord a nce with the fo rm u l a g iven i n I EC 60228 :
u s i n g the te m p e rature coeffi cients g iven in I EC 60228 for a cond uctor or meta l
screen/sheath of copper or a l u m i n i u m or
- fo r a m eta l screen/s h eath othe r than copper or a l u m i n i u m , u s i ng temperature coeffi cie nts
g i ve n in I E C 60287- 1 - 1 .
The corrected DC res i sta nce of the conductor at 20 °C s h a l l not exceed either the a p propri ate
m ax i m u m value specified in I E C 60228 or, when a va l u e for m ax i m u m DC con d u ctor resistance
is declared in Clause 6 , item d ) , then the corrected DC res i sta nce of the co n d u ctor at 20 °C
sha l l not exceed the declared v a l u e .
T h e corrected D C resista n ce o f the meta l scree n/s he ath at 20 °C s h a l l not exceed t h e declared
va l u e .
1 0.6. 1 G e n e ra l
The test method sh al l be i n accorda nce with IE C 608 1 1 -2 0 1 for the i n su l ati o n . For t h e
overs heath the test method in accorda nce with I EC 608 1 1 -202 : 2 0 1 2 and
I E C 6 0 8 1 1 -2 02 : 2 0 1 2/AM D 1 : 20 1 7 s h a l l be a p p l i e d , except t hat for s h eaths whe re the u n derlying
su rfa ce is n ot i rreg u l a r the measurement can be m a d e with a m i cromete r h a v i n g a ball nose
rad i u s of 2,5 m m to 3 m m . Th e accu racy of the m i crometer shall be ± 0 , 0 1 m m .
Each cable le ngth se lected for the test s ha l l be re p resented by a p iece taken fro m o n e e nd after
having d iscard e d , if necessary , a n y portio n that can h ave suffered d a m a g e .
tn is the n o m i n a l t h ickness , i n m m .
The m i n i m u m measure d th ickness shall not be less t han 9 0 % of the nom i n a l th ickness:
tmi n 2: 0 , 90 tn
$; 0, 1 0
The thickness of the sem i-co n d u cti n g screens on the co n d u ctor a n d over the i n su lation s h a l l
n o t be i n cluded i n the th i ckness o f the i n s u l ati o n .
The m i n i m u m m e asu red thickness s h a l l not be less than 85 % of the nom i n a l t hi ckn ess m i n us
0,1 mm:
t min 2: 0 , 8 5 tn - 0 , 1
I n additi o n , for overs h eaths a p p l ied onto a s u bstantially smooth s u rface , the average of the
measured val u e s rounded to 0 , 1 m m shall not be less th a n the n o m i n a l th ickness.
The l atte r req u i rement does not apply to oversheaths a p p l ied onto an i rreg u l ar s u rface , such
as one fo rmed by metal screens of wires an d/or tapes or corrugated metal sheath .
1 0.7.1 G e n e ra l
The fol l owi ng tests a p p l y if t he cable has a me t al s h eath of lead , le ad a l loy, coppe r or a l u m i n i u m .
F o i l s w h i c h a re a p p l ied for ra d i a l watertig htness p u rposes o n l y a re excl uded fro m these tests .
tn is the n o m i n a l t h i ckness, i n m m .
1 0.7.2.1 G e n e ra l
tm i n ;:::: 0 , 9 5 t n - 0,1
The t h i ckn ess of the sh eath s h a l l be measure d by o n e of the fol l ow i n g method s , at the d iscretion
of the m a n ufact u rer.
The measurement s h a l l be made with a micro m eter with plane fa ces of 4 m m to 8 m m d i a meter.
The accu racy of the m i crometer s h a l l be ± 0 , 0 1 m m .
1 0.7.2.3 R i n g method
The measure m e n ts shall be made with a m icro m eter h aving either one flat nose and o n e b a l l
nose , or one flat nose a n d a flat recta n g u l a r nose 0 , 8 m m w i d e a n d 2 , 4 m m l o n g . T h e b a l l nose
or the flat recta n g u l a r nose s h a l l be a p pl ied to the i n s i d e of the ri ng . The accuracy of the
m i cro m eter s h a l l be ± 0 , 0 1 m m .
T h e measure m e nts s h a l l be made on a ring of t h e s h eath carefu lly cut fro m the s a m p l e . The
t h i ckness shall be d eterm i ne d at a sufficient n u mber of points aro u n d the circumference of the
ring to e n s u re that the m i n i m u m th ickness is measure d .
1 0.7.3 C o p p e r o r a l u m i n i u m s heath
tm i n ;:::: 0 , 9 tn - 0,1
tm i n ;:::: 0 , 8 5 tn - 0,1
The measure m e nts sha l l be made with a m i crom eter h a v i n g b a l l noses of rad i i about 3 m m . The
accuracy of the m i crometer s h a l l be ±0 , 0 1 m m .
1 0.7.4 Metal ta p e f o r C D d e s i g n
The m i n i m u m measu red th ickness of the metal tape s h a l l not be less t han 90 % of the n o m i n a l
thickness:
The measure m e nts sha l l be made with a m i cro m eter having b a l l noses of rad i i about 3 m m . T h e
accu racy o f the m i crometer shal l be ±0 , 0 1 m m .
If the p u rchaser req u i res that the d i a meter of the core a n d/or the ove ral l d ia m eter of the ca b l e
s ha l l be measured , t h e measure m e nts s h a l l be carried out i n accord a nce with I E C 60 8 1 1 -2 0 3 .
1 0.9.1 P roce d u re
The test p i eces s h a l l be take n fro m that part of the i ns u lation where the deg ree of cross- l i n k i n g
is considered t o be t h e lowest for t h e c uring process e m ployed .
The test res u lts s h a l l comply with the req u i re m ents g iven i n Table 8 .
The capacita n ce s h a l l be measure d betwee n co n d u ctor a n d meta l scree n/s heath at a m bi ent
te mperature, a n d the a m b i e n t temperature s h a l l be recorded with the test d ata .
1 0. 1 1 . 1 P roce d u re
1 0 . 1 1 . 2 Req u i re m ents
The res u lts of the test s h a l l com p l y with the req u i re m e nts g iven in Table 8 .
The ass em bly s h a l l be heated by co n d u ctor curre nt o n ly , unt il the cable con d u ctor reaches the
req u i red te m pe ratu re .
If, for p ractical reaso n s , t h e test tem pe rature cannot b e reach e d , addi t i onal thermal i n s u lation
can be a p p l ied . The cond uctor tempe ratu re s h a l l be m a i ntained with i n the stated te m pe ratu re
l i m its for at le ast 2 h .
The cable s h a l l withsta n d , without fa i l u re , 1 0 pos itive a n d 1 0 negative voltage i m p u lses of the
a p p ro pri ate va l u e g iven in Ta b l e 4, co l u m n 8.
If a p p l i ca b l e , sam ples sha l l be taken fro m the ca b l e , the test s h a l l be a p p l ied and the
req u i re m e nts s h a l l be met as descri bed in 1 2 . 5 . 1 5 .
For cables with a longitu d i n a l ly a p p l ied metal tape or foi l bon ded to the overs heath , a 1 m
s a m pl e s h a l l be taken fro m the cable a n d s u bj ected to the tests a n d req u i re m e nts i n 1 2 . 5 . 1 6 .
11 Sa m p l e tests o n accessories
The c h a racte ristics of each component s h a l l be verified i n accord ance with the specificati ons
of the a ccessory m a n ufacturer, either thro u g h test reports from the m a n ufacturer of a gi ve n
com ponent o r t h ro u g h i ntern a l tests .
NOTE As components d iffe r from one man ufacturer to another, it is not possible to d efi ne common sample tests on
components i n this document.
For a ccessories w h ere the m a i n i n su lation can not b e routine tested (see 9 . 1 ) , the fo l l ow i n g
e l ectrical tests s h a l l be carried o u t b y t h e m a n ufacturer o n a fu l l y asse m bled accessory:
T h e seq ue nce i n w h i c h these tests a re carried out i s a t the d i scretion o f the m a n ufacturer.
NOTE Examples of main insu lations that are not routine tested a re insu lations taped a nd/o r moulded o n s ite.
These tests s h a l l be performed on one accessory of each type per contract if the n u mber of that
type i n the co ntract is a bove 50.
If the sa m p l e fa i l s either of the a bove two tests , two fu rther sam p l es of the same accessory type
shall be taken from the contract and s u bj ected to the same tests . If both additio n a l sam p l es
pass the tests , the other accessories of the same type from the contract s h a l l be rega rded as
having com p l ied with the req u i re m e nts of this docu m e n t . If either fa i l s , this type of accessory
of the contract s h a l l be reg a rded as h a v i n g fa i l ed to comply.
1 2 T y p e tests o n c a b l e syste m s
1 2. 1 G e n e ra l
The tests spec ified i n C l ause 1 2 a re i ntended to d e m o n strate the sati sfactory performance of
cable system s .
Once s u ccessfu l l y com p l eted , type tests need n o t be re peate d , u n less cha nges a re m a d e i n the
cable o r a ccessory with res pect to mate r i a l s , m a n ufacturing process, des i g n or d e s i g n e lectrical
stress leve l s , w h i c h m i g h t adversely change the performa nce characte ristics.
The clause or s u bcla use refe rences to be considered d u ri n g a type test on a cable system a re
g iven i n An nex C .
Type tests o n g a s i m mersed cable term i n ations s h a l l be carried o u t accord i n g t o I EC 622 7 1 -209
in add ition to the tests specified i n this docu ment.
Add itional e l ectri cal type tests a re req u i red i n I E C 6227 1 -2 0 9 , for the case where the gas
i m mersed term i nation i n s u l ator is to be s u p p l ied to the switchgear m a n ufactu rer, to demo nstrate
that the te r m i nation can meet the switch gear routi ne a n d on-site tests .
NOTE Tests on term i nations under e nviron mental conditions such as preci p itatio n and/or po l l ution are n ot s pecified
i n this document.
When type tests have been s u ccessfu l l y performed o n o n e or more cable system ( s ) of specific
cross-section ( s ) , a n d of the same rated voltage and construction , the type a p p roval s h a l l be
co ns i dered as val i d for cable systems with i n the scope of this document with oth er cross
sectio n s , rated voltages a n d constructions provided that a l l the fol l owi n g cond itions of a) to h )
a re met.
Type tests which have been s u ccessfu l l y performed accord i n g to p revi ous ed itions of t h i s
sta n da rd a re v a l id if the following co nd itions a re met:
a ) The voltage g ro u p i s not h i g h e r than that of the tested cable syste m ( s ) . Cable systems of
the same voltage g ro u p a re those of rated voltages having a com mon va l u e of Um , h i g h est
voltage for e q u i pment, a n d the same test voltage levels (see Ta b l e 4, col u m ns 1 a n d 2 ) .
b ) T h e nom i n a l conductor cross-sectio n a l area i s n ot l a rge r t h a n that o f the tested cable .
c) The cable a n d the accessories have the same or s i m i l a r constructions as that of the tested
cable system ( s ) .
C ables and accessories o f s i m i l a r constructi on a r e those o f the s a m e type a n d
m a n ufactu r i n g process of i n s ul ati on and s e m i -cond u ct i n g scree ns. Repetition o f t h e
e l ectrical type tests is not necessary on accou nt o f t h e d ifferences i n t h e co n d u ctor o r
con nector type or m ate rial or o f t h e p rotective laye rs a p p l ied over t h e screened cores o r
over the m a i n i n s u l ation part of the accessory, u n less these are l i kely t o have a s i g n ifica nt
effect on the res u lts of the test. In some i nsta n ce s, it can be ap propriate to repeat one or
more of the type tests ( e . g . bend i n g test, h eati ng cycle test and/or compati b i l ity test) .
d ) The ca l c u l ated n o m i n a l e lectri cal stress a n d the i m p u lse voltage stres s , calculated u s i n g
nom i n a l d i m e n s i o n s , at the cable co n d u ctor scree n , do n o t exceed the resp ective calcu lated
stresses of the tested cable syste m( s) by more th a n 1 0 % .
e ) The calcu lated n o m i n a l e l ectrical stress a n d the i m p u lse voltage stres s , calcu lated u s i n g
n o m i n a l d i m e n s i o n s , at t h e c a b l e i n s u lation scre e n , do n o t exceed the res pective ca l c u l ated
stresses of the tested ca b l e syste m ( s ) .
f) T h e calculated n o m i n a l e l ectrical stresses a n d the i m p u l se voltage stresses, cal c u l ated
u s i n g n o m i n a l d i m e n s i o n s , w i t h i n the m a i n i n s u lation parts of the accessory and at the cable
a n d accessory i nte rface s , do not exceed the res pective calcu lated stresses of the tested
cable syste m ( s ) .
g ) T h e s a m e type of g a s or g a s m ixtu re a n d press u re is used i n the cable co n nection e n c losu re
of a gas i m m e rsed term i nation .
NOTE Cla use H . 6 g ives req u i reme nts for approval of a gas immersed termi nation with a n alternative type of
gas.
h) A gas i m mersed term i n ation h as the same separat i n g i n s u lating barrier, stress cone
asse m b ly and ca b l e as a re used i n the type test, taking i nto acco u n t the re levant a l l owances
a n d req u i re m e nts of a) to g ) above .
The type tests o n ca b l e com ponents (see 1 2 . 5 ) need not be carried out o n s a m p les fro m cables
of di fferent vo ltage rati ngs a nd/or n o m i n a l cond uctor cross-sectional areas u n less d iffe rent
materials a n d/or d i ffe re nt m a n u facturing p rocesses are used to prod uce the m . H owever,
re petition of the a g e i n g tests on p i e ces of com pl eted ca b l e to check compati b i l ity of m ateri a l s
( s e e 1 2 . 5 . 5 ) can be m u tua l l y ag reed with the p u rchaser i f the com b i nation o f materials a p p l ied
over the screened core i s d i fferent fro m that of the ca b l e o n which type tests have been carried
out previo u sl y .
A type test certificate si g ned by the re prese ntative of a com petent witnessing body, or a re port
by the m a n ufacturer g i v i ng the test res u l ts a n d s i g ne d by the a p p ropriate q u a l ified offi cer, or a
type test certifi cate issued by an i nd e pe n d e n t test laboratory , s h a l l be accepta b l e as evidence
of type testi n g .
The type tests s h a l l com prise the e l ectrical tests on the complete cable system as s pecified i n
1 2 .4 a n d the a p p ropriate non-electrical tests o n cable components a n d com p l eted cable
s pecified in 1 2 . 5 .
The non-e lectri cal tests on cable compone nts a n d cable are l i sted i n Table 5 to Table 1 0 ,
i n d i cati ng w h i c h tests are a p p l ica b l e to each i n s u lation a n d oversheath com p o u n d . The tests
u n der fire cond i t i o n s, as l i sted in Table 1 0 , are o n l y req u i red if the m a n ufact ure r wi s hes to cla i m
co m p l i ance with these tests a s a special feature of t h e desig n of the c a b l e .
Cab les a n d accessories sha l l be ass e m b led in the m a n n e r specified by the manufact urer's
i n structions , with the g rade a n d q u a ntity of m ate rials s u p p l i e d , i n c l u d i n g l u bri ca nts if a ny .
Measu rement of res istivity of se m i-cond ucti ng scree ns descri bed i n 1 2 . 4 . 9 sha l l b e made o n a
separate s a m p l e .
1 2 .4 . 1 Test voltage v a l u e s
Prior to th e e l ectrical type tests , the i n s u lation t h i ckn ess of the cable s h a l l be measured by the
method s pecified in I E C 6 0 8 1 1 - 2 0 1 on a re presentative s a m p l e take n fro m the length to be
used for the tests , to check t h at the average thi ckness is not excessive com pared with the
n o m i n a l va l u e .
If the averag e th ic k n ess of the i n s u l ation exceeds t h e nominal value by m o re than 5 % but by
not more than 1 5 %, the test voltage shall be adj usted to g ive a n electri cal stress at the
co n d uctor screen equal to that a p p l y i n g when the average th ickness of the i n s u lation is e q u a l
to the n o m i n a l v al u e and the test voltages a re the n o r m a l va l u es specified fo r the rated voltage
of the cab l e .
T h e c a b l e l e n gth u s e d for t h e e l ectrical type tests sha l l not have a n average i n s u l ation th ickness
exceed i n g the n o m i n a l va l u e by more than 1 5 % .
The tests in ite ms a) to i) s h a l l be made in the fol l owing sequ ence (see a lso 1 2 . 3 ) :
j) res istivity of the cable se m i-cond ucting screens (see 1 2 .4 . 9 ) that s h a l l b e measured o n a
separate s a m p l e . No b e n d i n g test is req u i red o n the test s a m p l e .
The cable s a m p l e s h a l l be bent aro u n d a test cyl i nd e r (fo r exa m p l e , the h u b of a cable d r u m )
a t a m b ient tem peratu re for a t l e ast o n e com p l ete turn a n d unwo u n d , w i t h o u t ax i a l rotatio n . T h e
s a m p l e s h a l l then be rotated throu g h 1 8 0 ° a n d t h e p rocess repeate d .
In the case of cables with a l a m i n ated meta l tape o r foi l , a visual exa m i nation accord ing to
C l a use G . 1 sha l l be carried out, after completion of the three b e n d i n g cycl es.
The test voltage s h a l l be ra ised g ra d u a l l y to and held at 1 , 75 u0 for 1 0 s and then slowly
red uced to 1 , 5 u0 (se e Table 4 , col u m n 5 ) .
If, for p ractical reasons, the test tem pe rature cannot be reach e d , ad d it i o n a l thermal i ns u lation
can be a p p l i e d .
There s h a l l be no detecta b l e d ischarge, exceeding the declared sensitivity , from the test obj ect
at 1 , 5 u0 .
The sample shall be heated by co n d u ctor cu rrent only and the temperature of the con d u ctor
determi ned e ither by measu ring its res i sta nce o r by temperature sensors on the surface of the
scree n/s h eath , o r by te mperature se nsors o n the conductor of another s a m p l e of the same
cable heated by the same means.
If, for practical reason s , t h e test tem perature cannot b e reached , addi t i onal thermal i n su lation
can be a p pl i e d .
The conductor te m pe rature s h a l l be m a i nta i ned with i n t h e stated te m p e rature l i m its for at
least 2 h .
The cable s h a l l have a U-bend with a d i a meter not g reater than the test cyl i n d e r d i a meter fo r
the b e n d i n g test of 1 2 .4 . 3 . The d i a mete r and a l lowed tolera n ces s h a l l be as specified i n 1 2 .4 . 3 .
I f , for p ractical reasons , t h e test temperature can not be reached , additional thermal i n s u lation
can be a p p l i e d .
The conductor te mperature s h a l l be m a i ntained with i n the stated te mperature l i m its for at least
2 h of each heating period . This s h a l l be fol l owed by at least 1 6 h of natural coo l i n g to a
co n d uctor temperature less than or equal to 30 ° C or with i n 1 5 K of a m bient tem pe rature,
Whichever is the h i g he r , but with a max i m u m of 45 ° C . The conductor current during the last 2 h
of each heati n g period s h a l l be record ed .
If the cable ex h i b its excessive d i el ectric loss at th e test voltage, t h i s can affect coo l i n g . I n
extre me cases this cou l d p reve nt cool i n g of the co n d u ctor to with i n the specified te mperature
ra n g e . This behaviour s h a l l be considered a test fa i l u re .
Heating cycles with a cond uctor te m perature h i g h e r t han 1 0 K a bove the m ax i m u m cond uctor
te m perature in normal operation are considered v a l i d .
I n terru pti o n of the test is al lowed , p rov ided 20 com p l ete heati ng cycles i n total under voltage
are co m p l eted . G u ida nce co ncern i n g i nterruption of the test and the determi nation of v a l i d
heat i n g cycles is g iven i n An nex J .
A switc h i ng i m pul se voltage test s h a l l be carried out on the assembly for syste ms, cables a n d
accessories of voltage Um ;::: 3 0 0 kV .
The assembly s h a l l be h eated by conductor cu rre nt o n l y , u n t i l the cable cond uctor reaches a
steady te m peratu re 5 K to 1 0 K a bove the maxi m u m conductor te mperature i n normal ope rati o n .
If, for p ractical re asons , the test tem perature cannot b e reach e d , add itional thermal i ns u l ation
can be a p p l i ed .
The switc h i n g i m p u lse voltage s h a l l be a p p l ied accord i ng to the p roce d u re g iven i n I EC 60230
with sta ndard switc h i ng i m p u lse withsta nd voltage levels accord i n g to Table 4 , col u m n 1 0 .
The ass e m b l y s h a l l withsta n d , without fai l ure or flashover, 1 0 positive a n d 1 0 negative vo ltage
i m p u lses.
1 2 .4 . 7 . 2 Lig htn i n g i m pu lse voltage test fo l l owed by a p owe r frequ ency voltage test
The assem b ly s h a l l be heated by conductor cu rre nt o n l y , u n t i l the cable cond u ctor reaches a
steady tem pe rature 5 K to 1 0 K a bove the maxi m u m cond uctor te mperature i n normal ope rati o n .
T h e cond u ctor temperature s h a l l b e m a i nta i n ed with i n t h e stated temperature l i m its for a t least
2 h before the fi rst l i g ht n i n g i m pu lse voltage is a p p l i e d . The te m pe rature s h a l l be m a i nta i ned
with i n the above l i m its until the test i s co m p l eted .
If, for practical reasons, the test temperature can not b e reached , additional thermal insu lation
can be a p p l i e d .
The assembly sh al l withsta n d without fa i l u re or flas hover 1 0 positive and 1 0 negative voltage
i m p u lses of the a p p ro p ri ate v a l ue g iven in Table 4, col u m n 8 .
1 2 .4 . 8 Exa m i nation
1 2 .4 . 8 . 1 C a b l e a n d accessories
Exa m i nation of the cable by d issecti on of a s a m p l e a n d , whe never poss i b l e , of the accessories
by d is m a n tl i n g , with normal or co rrected vis i o n without m a g n ificat i o n , s h a l l reveal no s i g n s of
deterioration (e . g . e lectri cal d e g radation , leaka g e , corrosi o n or h armfu l s h ri n kage) w h i c h co u l d
affect the syste m i n serv i ce ope rat i o n .
A 1 m s a m p l e s h a l l be taken from the U-bend part of the cable l e ngth a n d s u bjected to the tests
in 1 2.5. 1 6.
1 2 .4 . 9 . 1 Gen eral
Measu rement of resistiv ity of the cable s e m i -con d u ct i n g screens s h a l l be made on sam ples
from the same m a n ufact u ri n g b atch as the cable u n d e r test.
The res istivity of extruded sem i-cond u cti ng screens a p p l ied ove r the co n d u ctor and ove r the
i n su lation s h a l l be dete r m i ned by measure me nts on test p i eces taken from the core of a s a m p l e
o f ca b l e as man ufact u red , a n d a s a m p l e o f c a b l e w h i c h has b e e n s u bjected t o the age i n g
treatment t o test t h e com pati b i l ity o f co m ponent materials specified i n 1 2 . 5 . 5 .
1 2 .4 . 9 . 2 P ro ce d u re
The measureme nts s h a l l b e made a t a te m perat ure wit h i n ± 2 K of the maxi m u m co n d u ctor
te mperature in normal operation .
1 2 .4 . 9 . 3 Req u i rements
The res istivity , b oth before a n d after a g e i n g , s h a l l not exceed the fol low i n g values :
1 2 .5.1 G e n e ra l
g ) tests for PVC a n d LS H F oversh eaths (ST 1 , ST 2 , a n d ST 1 2 ) at low tem peratu re (see 1 2 . 5 . 8 ) ;
h ) heat shock test fo r PVC oversh eaths ( S T 1 and S T2) (see 1 2 . 5 . 9) ;
i) ozo n e res i sta nce test for E P R i n s u l ation (see 1 2 . 5 . 1 O ) ;
j) h o t s e t test for E P R a n d X L P E i n s u lations (see 1 2 . 5 . 1 1 ) ;
k ) measurement o f d e n s ity for H O P E i n s u lation (see 1 2 . 5 . 1 2 ) ;
I) measurement of carbon b l ack content for b l ack P E ove rsheaths (ST 3 a n d S T7)
(see 1 2 . 5 . 1 3 ) ;
m ) test u nde r fi re conditions (ST1 , ST2 a n d S T 1 2 ) (see 1 2 . 5 . 1 4 ) ;
n ) water penetration test (see 1 2 . 5 . 1 5) ;
o ) tests for compone nts of cables with a l o n g itu d i n a l l y a p p l ied metal tape o r foi l , bonded to the
overs heath (see 1 2 . 5 . 1 6 ) .
The exa m i nation o f the cond u ctor a n d measure m e nts of i n s u lati o n , oversheath a n d metal
sheath thicknesses s h a l l be carried out i n accord a nce with , and s h a l l comply with the
req u i rem ents g iven i n 1 0 . 4 , 1 0 . 6 and 1 0 . 7 .
1 2.5.3.1 Sampling
The a g e i n g treatme n t sha l l be carried out i n accord ance wit h IE C 6 0 8 1 1 -40 1 u n d e r the
co nd itions s pecified in Table 6.
1 2.5.3.3 C o n d i ti o n i n g a n d m e c h a n i c a l tests
Cond itio n i ng a n d measurement of mechan ical p rope rties s h a l l be carried out in accord ance with
I E C 6 0 8 1 1 -50 1 : 2 0 1 2 and I E C 6 0 8 1 1 - 5 0 1 : 2 0 1 2/AM D 1 :20 1 8 , except that:
a) it is not com p u lsory to ca rry out tensile tests on the aged and u n aged test p i eces in
i m med iate s u ccess i o n , and
b ) any s u itable measuring i nstru ment can be used , for exa m p l e a m i cromete r.
The test res u lts fo r u n aged and aged test p i eces s h a l l comply with the req u i re ments g iven i n
Table 6 .
1 2.5.4.1 Sampling
1 2 . 5. 4 . 2 Age i n g treatm e n t
The a g e i n g treatme n t shal l be carried out i n accorda nce wit h I EC 6 0 8 1 1 -40 1 u n der the
co nd itions g iven i n Table 7.
C o nditi o n i n g a n d the measurement of mecha n i cal pro perties s h a l l be carried out i n accorda nce
with I E C 6 08 1 1 -5 0 1 : 2 0 1 2 and I E C 6 0 8 1 1 -501 : 2 0 1 2/A M D 1 :20 1 8 , except that:
a ) it is not compu lsory to ca rry out tens ile tests on the aged and un aged test p i eces i n
i m m e d i ate success i o n , and
b ) any s u itable meas u r i n g i n stru ment can be used, for exa m p l e a m i crometer.
The test res ults fo r u n aged and aged test p ieces s h a l l comply with the req u i re ments g iven i n
Ta ble 7 .
1 2.5.5 Ageing tests fo r p i eces o f cable t o check com pati b i l ity of m ate rials
1 2.5.5.1 G e n e ra l
T h e a g e i n g test on p ieces of com p l eted cable s h a l l b e carried o u t t o check that the i n s u l ati o n ,
t h e extruded se m i-co n d ucting scre e ns and t h e oversheath are n o t l i a b l e t o deteriorate
excessively in o pe rati o n d u e to contact with other compone nts in the c a b l e .
1 2.5.5.2 Sampling
The ageing treatment of the pieces of cable shall be carried out i n an air ove n , as described in
IEC 6 0 8 1 1 -40 1 , und e r the fo l l owi ng con d itions:
Test p i eces of i ns u l ation and overs heath from the aged p i eces of cable s h a l l be p re pared a n d
s u bj ected t o m e c h a n i c a l tests as described i n I EC 6 0 8 1 1 -40 1 .
The variations betwee n the med i a n va l ues of te n s i l e stre ngth a n d e longation at break afte r
ag e i ng a n d the correspond i n g val ues obta i n ed without a g e i n g (see 1 2 . 5 . 3 a n d 1 2 . 5 .4 ) s h a l l not
exceed the val ues a p p l y i n g to the test after a g e i n g i n an a i r oven g iven i n Ta b l e 6 for i n s u l ations
and in Ta b l e 7 for oversheaths.
1 2.5.6.1 P roced u re
The loss of mass test for ST 2 oversheaths s h a l l be carried out as described i n I E C 6081 1 -409
u n der the conditions g iven in Table 9 .
The res u lts s h a l l comply with the req u i re m e nts g iven in Tab l e 9 .
1 2.5.7.1 P roced u re
a ) either a n ove n with natu ra l air c i rcu l ation or one with fa n assisted circulation can be used .
I n the l atter case better temperature control is poss i b l e , however the test s a m p l e s h a l l n ot
be s u bjected to v i b rati o n , a n d
b ) if the oversh eath i s solidly bonded t o a metal s heath then the overs heath sha l l n ot be
removed fro m the metal s h eath but s h a l l be tested as if the metal s h eath were the m a n d re l .
T h e metal s h eath s h a l l b e s u p ported so that i t is n o t deformed d u ri n g t h e test.
The test cond itions g iven in the test method and Ta b l e 7 s h a l l be used .
The res u lts s h a l l comply with the req u i re me nts g iven i n Table 7 .
1 2.5.8.1 P roced u re
The test at low tem perature for ST 1 , ST 2 a n d ST 1 2 overs heaths s h a l l be carried out as described
in I E C 6 0 8 1 1 -505 and I E C 6 0 8 1 1 -506, e m ploying t h e test temperature g iven i n Table 9 .
The res u lts of the test s h a l l com p l y with the req u i re m e nts g iven in Table 9.
1 2.5.9.1 P roced u re
The heat shock test on ST 1 and ST 2 overs heaths s h a l l be carried out as described i n
I E C 6 0 8 1 1 -509, t h e test tem pe rature a n d d u ration b e i n g i n accord a n ce with Table 9 .
The res u lts of the test s h a l l com p l y with the req u i re m e nts g iven in Ta b l e 9 .
1 2 . 5. 1 0 . 1 P roced u re
1 2 . 5. 1 0 . 2 Req u i re m ents
The res u lts of the test s h a l l com ply with the req u i re m e nts g iven in Ta b l e 8 .
The d e n sity of HOPE i ns u l ation shall be measured in accorda nce with 1 0 . 1 1 a n d shall comply
with its req u i re m e n ts .
1 2 . 5. 1 3 . 1 P roced u re
If there is a n extru ded sem i-cond u ctive layer a p p l ied t o t h e overs heath , t h i s s h a l l n o t be
i n clu ded i n the test s a m p l e .
1 2 . 5. 1 4. 1 G e n e ra l
1 2.5.1 4.2.1 Determ i n ati o n o f acid ity (by pH meas u rement) and c o n d u ctiv ity o f gases
evolved d u ri n g c o m b u stion
The va l u e for the oversheath , Hi , of the i n d i v i d u a l h a logen content fo r each of the fou r ha logens
F, Cl, Br, and I, s h a l l be determi ned by carry i n g out the test accord ing to I E C 60754-3.
The values for each of the fou r i n d iv i d u a l halog e n s , Hi , and the s u m of the val ues for the
overs heath for the fou r ha logens, i . e . l_Hi , shall com p ly with the req u i re m e nts g iven in Table 1 0 .
The test under fi re conditions i n accord a nce with I EC 60332- 1 -2 s ha l l be carried out on a s a m p l e
o f completed ca b l e . D u ri n g the test, the dete r m i n ation o f fl a m i n g d ropl ets a n d parti cles s h a l l be
carried out i n accord ance with I E C 60332- 1 -3 .
The res u lts for I E C 60332- 1 -2 s h a l l com p l y with the req u i re m ents g iven i n Table 1 0 a n d the
fi lter paper ( I EC 60332- 1 -3 ) s h a l l not i g n ite d u ri n g the test d u rati o n .
If a fai l u re t o m eet the req u i re m e nts o f either sta n d a rd i s record e d , two more tests s h a l l be
carried out. I f both tests res u lt i n passes, the cable s h a l l be deemed to have passed the test.
1 2 .5.1 4.3.2 Test f o r vertical flame s p read o f vert i cal ly-mou nted cables
The test fo r vertica l flame spread of vertically-mou nted cables shall be carried out i n accorda nce
with I E C 60332-3-24 , on sa m p les of completed cab l e .
NOTE Hig her pe rfo rmance to meet the req u i rem ents of I E C 60332-3-22 [8] o r I E C 60332-3-23 [9] can be ag reed
between the purchaser and manufactu rer. The fire performance level ach ieved depends on cable design as wel l as
materi al performa nce.
The res u lts s h a l l com p l y with the req u i re m e nts g iven in Table 1 0.
The test for measure m e n t of s m oke d e ns ity of cables burn i ng u n d e r d efi n ed conditions shall be
carried o ut in accordance with I E C 6 1 034-2 on a sample of completed ca b l e .
1 2 . 5. 1 4. 3 . 4 Determ i nation o f acid ity (by pH measu rement) a n d c o n d u ctiv ity o f gases
evolved d u ri n g c o m b u stion of the n o n -m eta l l i c materials i n the cable
The test accord i ng to IEC 60754-2 s h a l l be carried out o n the non-meta l l i c components of the
cable. Non-meta l l i c com ponents with a mass less t h a n or e q u a l to 1 % of the total non- meta l l i c
mass n e e d n ot be tested .
The weig hted va l ues of p H a n d cond u ctivity of the n o n - meta l l i c components of the cable s h a l l
b e calcu lated accord i n g t o I E C 60754-2 a n d s h a l l comply with the req u i re m e nts g iven i n
Ta ble 1 0.
,
The we i g hted value fo r the cable, Hi , for each of the fo u r i nd iv i d u a l h a logens and the sum of
the weig hted val ues for the n o n -meta l l i c com ponents of the cable for the fo ur h a logens , i . e .
0
L, Hi s h a l l com ply with the req u i re ments g iven in Ta b l e 1 0 .
The test co n sists of two pa rts , one fo r the co m p lete c a b l e a n d all its des i g n e le me nts a n d o n e
for the water pen etrati o n i n the conductor. The a p pa ratu s , sa m p l i n g , test p roce d u re a n d
req u i reme nts sha l l b e i n accord a nce w i t h Annex E a n d A nnex F .
1 2 . 5. 1 6 Tests for compo nents o f cables with a l o n g it u d i n a l l y a p p l ied metal tape o r fo il,
bon ded to the oversheath
if cable systems with the same construction and accessories of the same fa m i ly have been
pre q u a l ified for a n equal or h ig h e r rated voltage , o r
i f t h e m a n ufacture r c a n demonstrate good service experience with c a b l e syste ms with eq u a l
or h i gh er ca l c u l ated e l ectrical stresses on the conductor a n d i nsu lation scree n s , i n the m a i n
i n s u l ation part(s) a n d i n boundaries o f t h e accessories a n d o f accessories o f t h e s a m e
fa m i ly , or
if the m a n ufacturer has fu lfi l l ed the req u i re me nts of a n e q u ivale nt lon g-term test, o n a cable
syste m at a n equal or h i g h e r voltage rati ng with t h e same construction a n d accessories of
the same fa m i ly , fol l owi n g a n ational or p u rchaser specificati o n .
When a p req u al ifi ed cable syste m is changed by u s i n g another cable a n d/or accessory that is
not part of a p req u a l ified cable system or i s a l ready preq u a l ified i n a n other cable syste m with
l ower calcu lated n o m i n a l e l ectri cal stresses at the i n s u lation screen of the s u bj ected system ,
the P Q test o n t h i s new com plete cable syste m s h a l l b e performed b y meet i n g a l l req u i re me nts
of 1 3. 2 .
The P Q test need o n l y b e carried out once u n less there i s a s u bsta n t i a l change i n the ca b l e
syste m w i t h res pect t o materi a l , m a n ufacturing process, des i g n or des i g n e lectrical stress
leve l s . A s u bstanti a l change is d efi ned as t hat which m i g h t adversely affect the performance of
the ca b l e system . The m a n u facturer sh oul d p rov ide a deta i led cas e , i n c l u d i n g test evidence, if
mod ifications a re i ntroduced w h i c h a re clai med not to constitute a s u bsta nt i al change .
P req u a l ification tests w h i ch h ave been successfu l l y perfo rmed accord i n g to the previous edition
of t h i s sta n d a rd are v a l i d .
For a more detailed u n d e rsta n d i n g of the need for a P Q or EQ tests , refe rence s h o u l d be made
to C I G R E T B 303 [6] .
The PQ test s h a l l com prise the e lectrica l tests on the com plete cable system with a p p rox i m ately
1 00 m of fu l l -s ized cable , i n c l u d i ng at least one of each type of accessory. The m i n i m u m length
of free cable between accessories s h a l l be 1 0 m. The seq ue nce of tests shall be as fol l ows :
The test can be conti n u ed for p req u a l ificati o n o f the c a b l e with t h e re pl aced accessory u nt i l a l l
req u i rem e nts o f 1 3 . 2 are met. I f t h e m a n ufact ure r decides t o i n c l ude t h e repa i red accessory i n
t h e cable syste m p re q u a l ification , t h e beg i n n ing o f t h e P Q test o f t h e com p l ete system i s
con s idered t o start after the re p ai r .
Prior to the PQ test of the cable syste m , the i n s u lation thickness of the cable sha l l be me asured
and the test voltage va l u es determ i n e d , as stated i n 8.4 and 1 2 .4 . 1 .
T h e test arran g e m ent s h a l l be re p resentative o f t h e i nsta l l ation desig n conditions, for exa m p le
ri g i d l y fixed , flex i b le a n d transi tion arra n g e m ents, u n d e rg ro u n d and i n a i r. I n partic u l ar, special
atte ntion shall be p ai d to thermo-mechan ical aspects of accessories .
A m b ient conditions can vary betwee n i n sta l lations a n d d u r i n g the test a n d a re not considered
to have a ny maj o r i nfl uence. Th e te mperature l i m its of 8 . 1 do not a pply.
If the cable system i nc l u des sections i nsta l l ed under d iffe rent cond itions ( e . g . d i rectly b u ried
a n d i n an a i r-fi l l e d c h a m ber) then the m a n ufacture r s h a l l sel ect one part of the cable syste m to
be used for determ i n ation of cable conductor te m pe ratu re . Temperatures sha l l be dete r m i ned
at this fixed positio n for the d u ration of the test. If a refe rence cable i s used for determ i n ation
of conductor tem peratu re (see An nex A) then the refe re nce cable shall be i n sta l l ed i n conditions
re p rese ntative of the cable syste m unde r test.
The h eati ng a rra ngeme nts s h a l l be se l ected so that the cable conductor atta i n s the te m pe rature
specified above , rem ote fro m the accessories . The s u rface te m peratu re of the cable s h a l l be
recorded for i nfo rm ati o n .
If, for p ractical reasons , t h e test tem perature cannot b e reach e d , ad d it i o n a l thermal i ns u lation
can be a p pl i e d .
I n terru pti o n o f t h e heati n g cycles or the test voltage i s a l l owed d u ring the test, however the
req u i red m i n i m u m n u m be r of cycles s h a l l be carried out i rrespective of i nterru ptions .
The test s h a l l be performed on the comp l ete assem b ly o r one or more cable sample s, with a
m i n i m u m total active length of 30 m , cut fro m the asse m b ly . The cable cond uctor te m pe rature
s h a l l be 0 K to 5 K a bove the max i m u m con d u ctor temperatu re i n normal operati o n a n d s h a l l
b e m a i ntained with i n t h e stated temperature l i m its for at least 2 h before t h e first l i g h t n i n g
i m p u lse voltage i s a p p l ied . Th e te m perature s h a l l be m a i ntained with i n the above l i m its wh ile
th e l i ghtn ing i m p u lse voltages are a p p l i e d .
The test asse m b l y o r cable s a m ples shall withsta nd without fai l u re 1 0 positive and 1 0 negative
voltage i m p u lses of the a p pro priate va l u e g iven i n 1 3 . 2 . 2 .
The exa m i nation of the cable system (cable a n d accessories) and the req u i re me nts s h a l l be as
stated in 1 2 . 4 . 8 .
The EQ tests s h a l l com p rise the e l ectri cal part of the tests on the com p l ete cable system as
spec ified i n 1 3 . 3 . 2 a n d the non-electrical tests on t h e cable as specified in 1 2 . 5 .
1 3.3.2 E l e ctrical part o f the exte n s i o n o f p req u a l ifi cation tests on c o m p l ete cable
system
1 3.3.2.1 G e n e ra l
If t h e p req u al ifi cati o n of a j o i n t is t o b e exte nded fo r u s e both i n flex i b le a n d i n rigid insta l lati o n s ,
one jo i n t s h a l l be i nsta l l ed i n a flex i b l e confi g u ration a n d the o t h e r o n e i n a rigid confi g u rati o n ,
s e e F i g u re 1 .
I
/EC
Key
1 term ination
2 cleat
3 joint
With the exception of the prov i s i o n s of 1 3 . 3 . 2 . 2 all the tests l i sted in 1 3 . 3 . 2 . 3 shall be a p p l ied
su ccess ively to the same sa m p l e .
T h e measu rement o f t h e res istivity of sem i-cond u cti ng scree ns, described i n 1 2 . 4 . 9 , s h a l l be
made o n a sepa rate sa m p l e from the same m a n ufact u r i n g batch of ca b l e .
Prior to the e l ectrical EQ tests, the i ns u l ation t h i ckness of the cable s h a l l be measured , a n d the
test voltage values determi ned as stated i n 8 . 4 a n d 1 2 . 4 . 1 .
The seq u e nce of the e l ectri cal p art of the E Q tests s h a l l be as fol l ows :
The assem b ly s h a l l be heated by cond uctor cu rre nt o n l y , u n t i l the cable cond uctor reaches a
te m perature 0 K to 5 K a bove the max i m u m con d u ctor te m pe rature i n normal operation .
If, for practical reason s , the test tem pe rature cannot be reach e d , addi t i onal thermal i ns u l ation
can be a p p l i e d .
Heat i n g cycles with a cond u ctor temperature h i g h e r than 5 K a bove the m ax i m u m co n d u ctor
tem perature in normal operation a re considered va l i d .
I nterru ption o f the test is a l l owed , provided 60 com p l ete heati ng cycles i n tota l a re completed .
G u ida nce concern i n g i nte rruption of the test and t h e dete r m i n ation of va l i d heati ng cycles is
g iven i n An nex J .
1 4 Type test o n ca b l es
1 6. 1 G e n e ra l
Tests on new i nsta l l ations (on-s ite tests ) a re carried out whe n the i n sta l lation of the ca b l e
syste m has b e e n com p l eted . The tests carried out s h a l l be i n accord ance with I E C 60060-3 .
For i nsta l l ations where only the overs heath test accord i n g to 1 6 . 2 is carried out, q u a l ity
ass u ra n ce proced u res d u ri n g i n stal l ation of accessories can , by agree ment between the
p u rch aser and m a n ufactu rer, re p l ace the i n s u l ation test accord i n g to 1 6 . 3 .
T h e u s e of very low freq u e ncy (VLF) a n d d a m ped A C ( DAC) waveforms for on-site tests a re not
recom m e n d e d , as fu rther stud ies of these test methods are req u i re d .
The el ectrica l test after i n sta l lation s h a l l be carri ed out o n the overs heath accord i n g to
I E C 60229 : 2 0 0 7 .
For the test to be effective, it is necessary t hat the g ro u n d m a kes good contact with a l l of the
outer s u rface of the oversheath . The test can n ot be carried out u n less the ove rsheath has an
outer e lectrode, for exam p le moist backfi l l or a cond u ctive layer.
The AC test voltage to be a p pl i e d s h a l l be s u bj ect to a g ree ment between the p u rchaser and the
man ufactu rer.
A voltage accord i n g to Table 1 2 , col u m n 4 s h a l l be a p p l ied for 1 h, except in cases where this
is not practica b l e , for exa m p l e , for very long circuit l e ngths . In such cases the al ternative lower
voltage accord i n g to Ta b l e 1 2 , col u m n 6 sha l l be a p p l ied fo r 1 h .
For i nsta l l ations which h ave been i n use , lower voltages t han g iven i n Table 1 2 a n d/or shorte r
d u rati o n s can be used . Val ues s h o u ld be negotiate d , ta k i n g i nto acco u n t the age, e nvi ro n me n t ,
h i story o f brea kdown s a n d the p u rpose o f carrying o u t the test.
A parti a l d ischarg e ( P D ) test u n der AC voltage i s reco m m e nded a n d can be carried out by
agree ment between the p u rchaser and the m a n u facture r. D i stri buted P D measure m e n ts can be
carried out a long the cable route . Typ ical pass criteria for such measure me nts are no detecta b l e
P D from t h e c a b l e system at 1 , 5 u0 , or a t the test voltage, i f lowe r. Whe n a p p l ica b l e , the test
proce d u re a n d pass criteria s h o u l d be a g reed . The PD test can be carried out d u ri ng the AC
voltage test of the i n s u lation (at the voltage used for that test) or as a separate test. PD tests
s h a l l not be consi d e red to re pl ace the AC voltage test of the i n s u l ati o n .
Normal Short-circuit
operation ( maximum duration 5 s)
oc
1c 2 3 4a 5a 5a 7a sa 9a 1 03
Rated Highest Value of Voltage Partial Tan o He ating Lightning Voltage Switching
volta g e volta g e U0 for test of 9.3 discharge measure- cycle impulse test after impulse
for equip- determin- test of 9.2 ment of voltage voltag e impulse voltage
ment ation of and 1 2 .4.5 test of test of voltage test of
test 1 2 .4.4 1 2 .4.6 1 0. 1 2 , test of 1 2.4.7. 1
volta g es 1 2.4.7.2 1 2.4.7.2
and
1 3. 2 . 5
u um Ua Volt- D u ra - 1 ,5 U0 Ua 2 U0 2 U0
age b tion b
kV kV kV kV min kV kV kV kV kV kV
220 to 230 245 1 27 318 30 1 90 1 27 254 1 050 254 -
pH value ( 1 2 .5. 1 4 . 2 . 1 ) - - - - - - - -
x
Cond uctivity test ( 1 2.5. 1 4 . 2 . 1 ) - - - - - - - -
x
Halogen content ( 1 2 . 5 . 1 4 . 2 . 2 ) - - - - - - - -
x
Key
b) maximum variationa % - -
±25 ±30
Elongation at break
a) minimum value after ageing % 300 350 - -
b) maximum variationa % - -
±25 ±30
a Variation: d ifference between the median value o btained after ageing and the median value obta i n ed without
agei ng, expressed as a percentage of the latter.
Without ageing
( I E C 6081 1 -50 1 : 2 0 1 2 and
I EC 608 1 1 -5 0 1 : 2 0 1 2/AM D 1 : 2 0 1 8 )
Minimum tensile strength N/mm 2 1 2,5 1 2,5 1 0, 0 1 2,5 1 2,5
Elongation at break:
a) minimum value after ageing % 1 50 1 50 300 300 300
b) maximum variationa % ±25 ±25 - - -
Tolerance K ±2 ±2 -
±2 ±2
Maximum indentation % 50 50 -
50 50
a
Variation: d ifference between the median value o btained after ageing and the median value obta ined without
agei ng, expressed as a percentage of the latter.
tolerance K - -
±3 ±3
Density
( I E C 6081 1 -606)
M i n i m u m dens ity g/cm 3 -
0 , 940 - -
tolerance K -
±2 -
d u ration h -
1 68 -
Req u i rement % � 20 � 20 � 20
Req u i rement -
no cracks no cracks no cracks
Heat shock test
( I E C 6081 1 -509)
Treatm ent: test temperature oc 1 50 1 50 -
tolerance K ±3 ±3 -
test d u ration h 1 1 -
a Due to cli matic conditions, nati onal sta ndards ca n req u i re the use of a lower or h i g he r test temperatu res .
Sum of values for the 4 i ndividual halogens (F, Cl, Br, I ) 'i,H; mglg - - ::; 5
Distance between t h e lower e d g e o f t h e t o p s u pport and the onset of > > >
charring mm 50 50 50
Lower extent of cha rri ng below the lower edge of the top s u p port mm ::; 540 ::; 540 ::; 540
um A
N
Term ination i nsta lled < 30° from the vertical
I II I II I II I II
> 1 70 to 245 625 2 000 800 2 000 1 250 2 500 2 000 2 500
� 300 1 250 2 000 1 250 2 000 1 575 2 500 2 500 2 500
Key
1 2 3 4 5 6 7
Test voltage for special
conditions
Value of U0 Preferred te st voltage (when use of the preferred test
Highest for
voltage of co lumn 4 is not
Rated poss ible, see 1 6. 3. 1 )
voltage for determination
voltage
equipment of test Voltage te st Voltage test
voltages after after
Multiplier Multiplier
installation of installation of
1 6.3 1 6.3
um Uo -
u - - -
kV kV kV kV x U0 kV x U0
Annex A
(i nfo rmative )
A.1 P u rpose
For some tests , it is necessary to raise the cable con d u ctor to a g iven te mperature, typ ically
5 K to 1 0 K a bove the maxi m u m tem perat ure i n normal operati o n , while the cable is e n e rg ized ,
e ither at power freq uency or u n d e r i m p u lse cond i t i o n s . I t is the refore not poss i b l e to have
access to the cond u ctor to e nab l e d i rect measure m e n t of te mperature.
Therefore, methods s h o u l d be used i n which the cond uctor te m pe rature can be mon itored a n d
contro l l e d thro u g h out the d u ration o f the test.
A. 2 . 1 G e n e ra l
The p u rpose o f the ca l i b ration is to dete r m i n e the cond u ctor tem pe rature by d i rect measurement
for a g iven c u rrent, with i n the temperature ra nge req u i red for the test.
The ca b l e used for c a l i b ration (he reafter cal led the refe re n ce cable) s h o u l d be take n from the
same l e n gth as the cable used fo r the m a i n test loo p .
T h e te mperature sensors s h o u l d b e attached t o the con d u ctor b y mechanical mea ns s i nce they
can move due to v i b rati o n s of the cable d u ring heati n g . Care s h o u l d be taken to m a i nta i n good
thermal contact d u ri n g the tests and to p revent leakage of heat to the a m bie nt . It is
recom mended t o mount the te m peratu re sensor( s ) , as shown i n F i g u re A .2, betwe e n two
stra n d s of a stranded cond u ctor or betwee n the (so l i d ) co n d u ctor a n d the co n d u ctor scree n . To
en abl e access to the conductor in the m i d d l e of the refe rence cable, a s m a l l hatch s h o u l d be
made by carefu l re moval of the layers above the cond uctor. After i nsta l l ing the temperature
sensor( s ) , the l ayers that have been re moved can be put back. Thi s can restore the thermal
behav i o u r of the refe rence ca b l e .
To p rove a n eg l i g i b l e heat transfe r towa rds the cable e nds, the d iffe re nce between the read i n g s
o f TC 1 c , T C 2 c and TC 3 c s h o u l d be l e s s than 2 K .
Dimensions in m i l l i metres
4
5
/EC
Key
It 1 ,5
'
0
'
Ii
2 3 4 /EC
Key
cond uctor 5 flexible thermal ins ulating compou nd
2 semi-conducting screens 6 temperature sensor
3 insu lation 7 cable oversheath
4 meta l s heath
F i g u re A.2 -
Exa m p l e of a n arra n g e m e n t of the temperatu re sensors
on the co n d u ctor of the refe re nce loop
A. 3 . 1 Method 1 -
Test u s i ng a refe re n ce cable
In t h i s method , a refe re n ce cable i d e ntical to the cable used for the main test loop is heated
with the same cu rre n t va l u e as the m a i n test loop.
- the reference cable carries the same cu rrent as the m a i n test loop at a n y t i m e ; s m a l l cu rrent
changes a re a l l owed in order to e q u a l ize the s u rface te m pe ratures on the test cable and the
refe rence ca b l e ;
- the reference cable is i n sta l l ed i n such a way that mut ual heating effects a re taken i nto
acco u nt throughout the test.
A te m p e rature sensor (TC8) s h o u l d be mou nted on or u n d e r the exte rnal s u rface of the m a i n
test loop a t t h e h ottest s pot, u s u a l ly i n t h e m i d d l e o f t h e l e n g t h , i n t h e s a m e way a s tem perature
sensor TC 1 8 is mou nted on the h ottest s pot of the refe rence cable to check that the oversheaths
of both loops are at a s i m i l ar te m perature.
The tem perature m easu red with temperature sensor T C 1 c on the conductor of the refe rence
loop can be considered to be re presentative for the co n d u ctor te m pe rature of the e n e rg ized test
l oo p .
The heating cu rre nt o f both loops s h o u l d be adj u sted such t hat t h e con d u ctor te mperature is
kept with i n the s pecified l i m i ts .
The reference cable can b e co n n ected i n series with the test cable i f the te m pe rature i s
measured via a n optical fi bre l i n k o r eq u i va l e n t .
The p u rpose of the c al i bration is to d eterm i ne the co n d u ctor tem pe rature by d i rect measurement
for a g iven c u rrent, wit h i n the te mperature range req u i red for the test.
The cable used fo r ca l i bration s h o u l d be taken fro m the same length as the cable used for the
main test loop and the way of heat i n g should be identica l .
D u r i n g ca l i b ration and d u ri ng the test of the m a i n l o o p , the cable cond u ctor te mperature of the
m a i n test loop s h o u ld be calculated in accordance with I E C 60853-2 [ 1 OJ, based on the
measured externa l te m peratu re of the oversheath (TC8 ) . The measure ment s h o u l d be carried
out with a tem pe rature sensor at the h ottest s pot, attached to or under the exte rnal s u rface, in
the same way as for the refe rence cable .
The heating c u rre nt s h o u l d be adj usted to obta i n the req u i red value of the calcul ated co n d u ctor
te mperature, based on the measured exte rnal tem pe rature of the oversheath.
Annex B
( n o rmative)
Rounding of numbers
EXAM P L E
Annex C
(i nfo rmative )
Ta b l e C . 2 g ives a s u m m a ry a n d referen ces for pre q u a l ification testi ng o f these cable syste m s .
T a b l e C . 3 g ives a s u m m a ry a n d refe rences for the exte nsion o f pre q u a l ification testing o f these
cable syste m s .
a Genera l 1 2. 1
h Partial d ischarge test at ambient and at high temperatures (after fi nal cycle i n 1 2 .4 . 4
item g above or after lightn ing impu lse voltage test i n item j below)
i Switching i m pulse voltage test 1 2 .4. 7. 1
j Lightning impulse voltage test fol lowed by power freq uency voltage test 1 2.4.7.2
k Partial d ischarge tests at ambi ent te mperatu re and at h i g h te m pe ratu re (if not 1 2 .4 . 4
carried out after item g above)
I Additional tests for accessories Annex H
m Examination 1 2.4.8
0 Non-el ectrical type tests for cable components and on completed cable 1 2. 5
h Examination 1 3.2.6
b Tests for the extension of the p req ual ification of a cable system 1 3. 3
c Electrical part of the extension of preq ual ification tests on complete ca ble 1 3. 3 . 2
system
d Test voltage values 1 3. 3 . 2 . 2
f Partial d ischarge test at ambient temperatu re after i nstallation of the accessories 1 2.4.4
that are part of the test
g Heating cycle test without voltage 1 3. 3 . 2 . 4
h Tan o measurement 1 2 .4 . 5
j Partial d ischarge test at am bient and h i g h temperatu res (after final cycle in item i 1 2 .4.4
above or after lightning impulse voltage test i n item I below)
k Switching impulse voltage test 1 2 .4.7 . 1
I Lightning impulse voltage test followed by power freque ncy voltage test 1 2.4.7.2
m Partial d ischarge test at high tem peratu re (if not carried out after item i above) 1 2 .4.4
Annex D
( n o rmative)
The p roced ure for d eterm i n i ng t h e vo l u me res i stivity o f the screens s h a l l b e a s fol l ows .
After the el ectrical measure m e nts , the d i a m eters ove r the conductor scree n a n d i nsulation
screen a n d the t h i cknesses of the conductor screen a n d i nsu lation screen shall be measured
at a m bient temperature, each b e i n g the average of si x measure m e nts made on the s a m p l e
shown i n F i g ure 0 . 2 .
Re x nx (De - Tc ) x Tc
Pc =
2 L
c
where:
Key
F i g u re D . 1 - D i m e n s i o n s fo r preparation of s a m p l es
for meas u rement of resistivity of c o n d u ctor screen
b ) i n su l ation scree n :
where:
A /EC
Key
F i g u re D . 2 - D i m e n s i o n s fo r preparation of s a m p l es
fo r measu re ment of res i stivity of i n s u lation screen
A n n ex E
( n o rmative)
A s a m p l e of cable at l east 8 m i n length which has not been s u bj ected to any of the tests
described in 1 2 .4 s h a l l be s u bjected to the be n d i n g test described in 1 2 . 4 . 3 .
A n ( 8 , 0 ± 0 , 050) m l e ngth of cable sha l l b e cut fro m t h e length which h a s been s u bjected t o the
be n d i n g test and placed horizonta l ly . A ring approximately 50 mm wide s h a l l be removed fro m
the centre of the length . T h i s r i ng s h a l l com prise a l l the l ayers exte rnal to the i n s u lation scree n .
Where the con d u ctor i s al so c l ai m e d to contai n a long itud i n a l water barrier, the ring s h a l l
comprise a l l l ayers externa l t o the conductor.
If the cable conta i n s i nterm itte nt ba rriers to l o n g itu d i n a l water penetrat i o n , then the sa m p l e s h a l l
conta i n a t least two o f these ba rri ers, t h e r i n g b e i n g removed fro m betwe e n t h e barriers. I n t h i s
case , the average d i sta n ce between the ba rrie rs i n s u ch cables s h o u l d be know n .
E.2 Test
The heati ng sha l l be a p p l ied for at least 8 h. The co n d u ctor tem pe rature sha l l be m a i nta i ned
wit h i n the stated te mperature l i m its fo r at least 2 h of each heati ng period . This shall be fol l owed
by at least 1 6 h of natural coo l i n g .
No voltage b e i n g a p p l ied throughout the test, it is reco m mended to co nnect a reference cable
in series with the cable to be tested , the te m pe ratu re being measured d i rectly on the conductor
of t h i s cable.
D u r i n g the period of testi ng , no wate r s h a l l e m erge from the ends of the test p i ece.
2 0
l{)
+I
0
0
0
- - - -
I. .I
s
p
/EC
Key
F i g u re E . 1 -
Schemat i c d i a g ra m of a p p a ratu s for wate r penetrat i o n test
A n n ex F
( n o rmative)
Arra nge a s u itable c h am ber to e n close one e nd of the test p i ece . The chamber shall be fitted
with an a i r vent a n d a separate vertical t u b e , both of at l e ast 1 0 mm i nte rnal d i a meter, with a
header ta n k to a l low the a p p l ication of a ( 1 , 0 ± 0 , 05 0 ) m head of water (see F i g u re F . 1 ) . The
chamber s h a l l be sealed to the s u rface of the i n s u l at i on scree n . The seal where the cable exits
the c h a m ber s h a l l not d eform the i n s u l ation d u ri n g the test.
F.2 Test
D u r i n g the period of testi ng , no wate r s h a l l e m erge from the end of the test p i ece .
d 0
L!)
+I
0
0
5 0
4
p
/EC
Key
water header ta n k
2 air vent
3 test piece
4 chamber
5 fu l l bore valve (optional)
d i nternal diameter <: 10 mm
p length = (4 000 ± 50) mm
Annex G
( n o rmative)
G.1 V i s u a l exa m i n at i o n
G.2.1 G e n e ra l
F/ w
where:
F is the force ( N ) ;
w is the width of the tape ( m m ) .
I n the case of a C D desig n (co m b i n e d design - C D meta l scre e n t hat com b i n es rad i a l
watertig htness a n d e l ectri cal properties ) , t h e concern i s that d e l a m i n ation cou ld d a m a g e t h e
meta l com ponent and al te r the e l ectri c fu nctional ity o f t h e scree n . Th erefore, t h e adhe si on
strength a n d peel strength o f the l a m i nated cove ring s h a l l be as h i g h as poss i b l e .
I n the case o f a n S D desig n (separate des i g n - S D design with rad i a l watertig htness a n d
e l ectrical properties, m a naged b y d ifferent metal components ) , there is n o concern that
d e l a m i nation will alter the e l ectri c fu ncti o n a l ity of the scre e n . The ca b l e can be operated with
short-c i rcuit ca p a b i l ity provided by the presence of the scre e n w i res. H oweve r, the adhesion
strength a n d peel strength s h a l l be h i g h e n o u g h to preserve the l a m i nate from fo l d i n g and
buckl i n g .
I n the case of a n SscD d es i g n (separate s e m i -con d u ctive des i g n - SscD desig n with separated
e l ectrical and rad i a l wate rtig htn ess p roperties with s e m i -cond uctive p l asti c-coated foi l ) , the test
ca n n ot be performed because the metal foi l i s so t h i n that it breaks d uring the adhesion or
pee l i n g stre ngth test.
The test speci mens s h a l l be taken fro m the cable cove ring whe re the metal tape or foi l a d h e res
to the oversheath.
There s h a l l be a total of five test specimens, three of them o n the ove rl ap of the metal fo i l or
the weld of the m eta l tape , a n d two of them on the o p pos ite side of the ca b l e .
/EC
Key
1 oversheath
2 metal tape or foi l
3 grips
After adj usting the conti n u o u s record i ng device, the m eta l tape or foi l s h a l l be stri pped from the
specimen at a n a n g l e of a p prox i mately 1 8 0° and the separation conti n u ed for a suffi cient
d istance to i n d i cate the adhesion strength va l u e . At l east o n e h a lf of the rem a i n i n g bonded area
s ha l l be peeled at a speed of a pprox i m ately 50 mm/m i n .
When the adhesion strength i s g reate r than the te n s i l e stre ngth of the metal tape o r foi l s o that
the latte r breaks before pee l i n g , the test s h a l l be term i nated and the b reak point sha l l be
record e d .
A s a m p l e speci m e n o f a p p rox i m ately 200 m m i n l e n gth shall be t ake n fro m the cable i n clud i n g
t h e overla pped portion of t h e metal foi l . T h e test s p e c i m e n s h a l l b e p re pared b y cutt i n g o n ly the
overlapped portion fro m this s a m p l e as shown in F i g u re G . 2 .
3 /EC
Key
s pecimen
2 oversheath
3 metal foi l or lami nated metal fo i l
/EC
Key
1 oversheath
2 metal foi l or lami nated metal fo i l
3 grips
F i g u re G .3 - Peel stre n gth of overlapped metal fo i l
The strength s h a l l be recorded against the s p a c i n g of the grips. Ty pical record ings are s h own
in F i g u re G.4 and F i g u re G . 5 .
Grip spacing
/EC
Grip spacing
/EC
Annex H
( n o rmative)
H.1 G e n e ra l
A n nex H s pecifies the proce d u re for additional tests , which a re e it he r type tests or exte nsion of
q u a l ifi cation tests for accessories for:
Accessories s pecified for i n sta l lation i n a i r only can b e tested without the water i m mersion test,
s u bj ect to a g ree ment between p u rchaser a n d m a n ufact urer. The risk of presence of water, for
exa m p l e i n terms of t u n n e l i n sta l l ation or any othe r risk of te mpora ry expos u re of joi nts or
accessories to water, should be considered i n this case.
Accessories tested with the water i m mers i o n test a re com p l i a n t when used fo r i n sta l l ation in a i r
a s well as i n other s ituatio n s . Accessories tested without t h e water i m mersion test a re not
com p l ia n t when used fo r b u ried i n sta l l ation or i n a n e nv i ronme nt with the risk of expos u re to
water.
The m a n ufact u re r of the accessory s h a l l provide a d rawing i n w h i ch all re levant features tested
u n d e r this a n nex a re clea rly d efi ned and i de ntified .
Table H . 1 l i sts the test proce d u res for d iffe rent types of accessories.
�
Copyright International Ele trotechnical Commission
I E C 62067 : 2 022 © I E C 2022 - 71 -
Ta b l e H . 1 - Test s e q u e nce
Clause H.3 Clause H.3 Clause H.4 Clause H.4.4 Clause H.6
Subjected to
20 thermal cycles x x xb - -
(20 therm al
cycles)
DC voltage
withstan d test x x x - -
screen to earth
DC voltage
withstan d test -
x - - -
screen to screen
Lightning impulse
voltage withstand
x x x - -
test screen to
earth
Lightning impulse
voltage withstan d -
x - - -
test screen to
screen
I nternal - - -
x -
pressure test
Cantilever - - -
x -
load test
Exa m i nation x x x - -
Electrical tests - - - -
x
a N ot appl icable to accessories for i nstal lation in air, tested without water immersion.
b N ot appl icable if the sheath sectionalizing insulation is external to the main body of the accessory, see H.4. 1 .
H.2 R a n g e of a p p roval
H.2.1 Range o f a p p roval for joi nts without screen o r metal sheath i nte rru pti o n
When the test seq u e n ce accord i n g t o t h i s a n nex has be e n su ccessfu lly performed fo r a j o i nt
des i g n without screen i nterru pti o n , the type a p p roval s h a l l be consi de red as v a l i d for a l l j o i nts
without scre e n i nterru ption for the s a m e cond u ctor s ize or s m a l ler, e m bodying the same bas i c
des i g n pri n c i p les a n d t h e s a m e materials tested at e q u a l or lower test voltages .
Where a pproval is req u i red for j o i nt outer p rotecti o n e m bodying e ntries for items such as
bond i n g leads , the outer protection tested s h a l l i n c l u d e these desig n feat ure s.
A s u ccessfu l test o n the j o i n t o ut e r p rotection with e m bodyi n g entries w i l l g ive a p p rova l to such
outer protection for a s i m i l a r j o i nt without e m bodyi n g entries, but not the convers e .
H.2.2 Range o f a p p rova l for j o i nts w i t h screen o r m etal s heath i nterru ption
When the test seq u e n ce accord i n g to t h i s a n nex has been su ccessfu lly performed fo r a j o i nt
des i g n with screen i nterru ption , the type a p p rova l s h a l l be considered as v a l i d for a l l j o i nts with
or without scre e n i nterru ption for the same cond u ctor s ize or s m a l ler, e m bodying the same
bas i c d e s i g n p r i n c i p les a n d the same materials tested at an eq ual o r lower voltage g ro u p .
Where approval is req u i red for j o i nt outer p rotection e m bodying e ntries for items s uch as
bond i n g leads , the outer protection tested s h a l l i n c l u d e these desig n feat ure s.
A s u ccessfu l test on the j o i n t o ut e r p rotection with e m bodyi n g entries w i l l g ive a p p roval to such
outer p rotection fo r a similar j o i nt without em body i n g entries, but not the convers e .
When the test seq uence accord i ng to this a n nex has been s u ccessfu lly perfo rmed on a cable
with screen or metal s h eath i nterruptio n , the type a pp roval s h a l l be considered as valid fo r a l l
cables with screen or meta l sh eath i n terruption offe red b y t h e s a m e m a n u facturer, e m bodying
the same basic design p r i n c i p les, at a n eq u a l or lowe r voltage g rou p .
When the test seq uence accord i n g to this a n nex has been s u ccessfu l ly performed for
term i n ations with an i n s u lated scree n , the type a p p rova l s h a l l be considered as v a l i d for a l l
term i n ations without a n i n s u l ated scree n , offe red by the same m a n ufacturer, e m body i n g the
same basic desig n pri n c i p l es , at an e q u a l o r lower voltage g ro u p .
H.3.1 C o n d i ti o n i n g o f s a m p l e fo r test
The test of j o i nts , cables with a m eta l sheath i n terruption a n d accessories for cable screen
i nterruption and/or earth co n n e ct i o n , s h a l l be a p p l i e d to a n accessory w h i c h has passed the
heati n g cycle voltage test (see 1 2 . 4 . 6 ) or to a separate accessory w h i c h has und ergone at least
20 thermal cycles accord i ng to 1 2 . 4 . 6 but without voltage a p p l i e d .
Add itional vo ltage tests accord i n g t o H . 3 . 3 can be carried out before com m e n c i n g the
heatin g/cool i n g cycles , at the d iscretion of the m a n ufact urer.
H.3.3.1 G e n e ra l
For accessories s u bj ected t o the water i m mers i o n test, voltage tests sha l l be carried out o n
com p letion o f t h e heat i n g cycles i n water, w i t h t h e test assem b ly sti l l i m me rsed. If it i s not
practi cable to carry out the e l ectrical tests whi lst the asse m b l y is sti l l i m m e rsed i n wate r, the
asse m b ly can be removed from the water a n d the voltage tests carried out with a m i n i m u m of
delay. In this case , earth i n g of the test object can be ach ieved by wra p p i n g with a wet fabric,
or by using a con d u ctive coat i n g a p p l ied over the entire exte rior s u rface of the test asse m b l y .
No b rea kdown of the test o bject shall occur d u ring any of the e lectrical withsta nd tests . F a i l u re
or flashover of a term i n ation of the cable s h a l l not be consi de red a fa i l u re of the test object.
A test voltage of 25 kV D C s h a l l be a p p l ied for 1 min betwee n both sides of the metal screen or
sheath i nterruption of the test o bject.
Table H.2 L i ghtn i n g i m p u ls e voltage with sta n d test betwee n screen a n d earth of j o i nts
-
with o r with o u t screen or m eta l sheath interru ption and accessories for cable s c reen
i n te rru pti o n a n d/o r eart h c o n n ecti o n
kV kV
1 050 47,5
1 1 75 to 1 425 62,5
1 550 72,5
a
See Table 4, col u m n 8.
Before the l i g h t n i n g i m p u lse test betwee n the metal screens/sh eath s , the ass e m b l y s h a l l be
removed from the wate r , if a p p l i ca b l e .
j o i nts with screen or m eta l s h eath i nterru pti o n a n d accessories for cable scree n
i n te rru pti o n a n d/o r eart h c o n n ecti o n
kV kV
1 050 95
1 1 75 to 1 425 1 25
1 550 1 45
a
See Table 4, col u m n 8.
The exa m i nation of the accessories s h a l l be done as stated i n 1 2 . 4 . 8 . 1 and in add ition fo r
accessories s u bj ected to the water i m mers i o n test:
the accessory s h a l l be e xa m i ned with res pect to the defi ned and clearly identified water
protection barri ers (see Cla use H . 1 ) ;
outer p rotection boxes fi l l ed with re movable com p o u n d s s h a l l b e reg a rded a s satisfactory i f
there is n o v i s i b l e evidence o f either i nternal voids or i ntern a l d i s p l ace ment of compound by
water i n g ress , or of com pound loss via the various sea l s or box wa l l s ;
for outer protections e m p loying a l ternative des i g n s a n d m ateria l s , there s h a l l b e n o evid e n ce
of water i n g ress or i nte rnal corrosi o n b e h i n d the d efi ned water-protection barriers.
H.4.1 C o n d i ti o n i n g o f s a m p l e fo r test
The test of term i n ations with an i n s u lated screen s h a l l be a p p l ied to an accessory which has
passed the heat i n g cycle voltage test (see 1 2 .4 . 6 ) or to a separate accessory which has
u n d ergon e at least 20 thermal cycles accord i n g to 1 2 . 4 . 6 but without voltage a p p l i e d . T h is
req u i rement can be o m i tted if the scree n i n s u lation is external to the m a i n body of the
accessory, for exa m p l e i n the case of s u p port i n s u lators .
A test voltage of 25 kV D C s h a l l be a p p l ied for 1 min between the screen and earth .
A test voltage i n accord a nce with Table H .4 sha l l be a p p l ied between the scree n and eart h .
kV kV
1 050 47,5
1 1 75 to 1 425 62,5
1 550 72 , 5
a
See Table 4, col u m n 8.
H.5. 1 . 1 Genera l
For in s u lators which wi l l be p ress urized in service , the type test p ress u re test s h a l l be carried
out a ccord i n g to I E C 6 2 1 55.
The canti lever load withsta n d test s h a l l be carried o ut accord i n g to I EC 6 0 1 37. The test load
for i n s u lato rs designed fo r Level I a n d Leve l II canti lever l oads s h a l l be i n accord a nce with
Table 1 1 . The test load for i n s u l ators d esig ned fo r other ca nti lever loads s h a l l be s u bj ect to
agree ment between the p u rchaser and the m a n ufacturer.
H.5.2.1 G e n e ra l
For i n s u lators w h i c h w i l l be pressu rized in serv i ce , the i nte r n a l p ress u re test accord i n g to
I E C 6 1 462 s h a l l be carried out. The req u i re me nts of I EC 6 1 462 s h a l l be met.
H.5.2.3 Be n d i n g test
H.6.1 G e n e ra l
I n add ition , t h e ty pe test for t h e p ress u re test on t h e i n su lator, accord ing t o I E C 6227 1 -20 9 ,
s h a l l be ca r r i e d out if the d e s i g n press u re of the i n s u lator req u i red for the a lternative gas is
h i g h er than the d es i g n p ress u re for w h i c h the i n s u lator has p reviously been type teste d .
T h e com pati b i l ity o f n e w gases or gas m ixture w i t h t h e components , espec i a l l y sea l s , o f the
cable term i n ation s h a l l be considered to avoid the poss i b i l ity of leaks deve l o p i n g in service.
Other tec h n ical aspects can req u i re eva l u ation d e p e n d i n g o n the n at ure of the a lternative g a s .
The leak rate type test on the i n s u lator of a cable te rmi nation accord i n g to I EC 62271 -209 s h a l l
b e carried out.
Annex I
(i nfo rmative )
It s h o u l d be noted that it is not poss i bl e to spec ify obj ective acceptance criteria for a l l pos s i b l e
types o f deterioration (such as d eformation or c h a n g es ) t h a t can be encou ntered d u ri n g a v i s u a l
i n spection .
When carry i n g out an exa m i n at i o n , care should be taken to avoid conta m i nation of s a m p l e s ,
kee p i n g i n m i n d t h a t t h e overa l l p u rpose i s t o c h e c k for s i g n s o f deteriorat i on which could affect
the operation of a cable syste m i n service.
In some cases, it can be h e l pfu l to have an u n treated sample of the cable or accessory
(or com pon ents of a n accessory) as a reference for t h e visual ins pectio n .
Sam p l es of cable, possi bly taken from d iffe rent posit i o n s i n t h e tested l e n g t h , a n d accessories,
for exa m p l e one of the joi nts and term i n ations , should be s u bj ected to the visual ins pect i o n , as
req u i red by t h i s docu ment.
Exa m i nation of the s a m p les with normal or co rrected vision without m a g n ification s h o u l d not
reve a l a n y deterioration of the types l isted below. The fol l ow i n g l ist i s not exha ustive , so a n y
u n expected or u n us u a l c h a n g es s h a l l a l so be considered a n d their pote n t i a l effe cts on operation
of a cable syste m i n service consi d e red by the exa m i n i n g persons when making a decision as
to their accept a b i l ity or otherwise.
da m age to the conductor which could have a detri me nta l effect on the cable performance;
ha rmfu l i nd e ntations in the cable core ( s ) , s h a rp i n dentations of the semi-con d u ctive screen
i nto the i ns u l ati o n ;
presence o f corrosion on meta l l i c parts , for exam p l e meta l l i c scre e n a n d connections;
i n d i cation of pos s i b l e mechan ical d e gradation i n the d i e l ectric parts ;
i n d i cation of poss i bl e electri cal degradation i n p r i m a ry i n s u lation of accessory and cable:
s h ri nkage , d efo rmation or other d i stortions that can affect com p l i a nce with the req u i re m e nts
of the re levant prod uct specificati o n , for exa m p l e creepage d i stances s h o u l d not fa l l be l ow
m i n i m u m acceptable val ues a n d there s h o u l d not be a ny change that wo u ld make a n y
hazardous pa rt accessi b l e ;
i n d i cation o f thermal degradatio n ( a l l components ) ;
crack i ng or d am ag e t o the i n su lati o n ;
da mage on t h e ca b l e sheath w h i c h could have a d etri me ntal effect on t h e c a b l e performance
fo r exa m pl e water i n g ress, poss i b l y lead i n g to co rros ion i n the long te r m ;
l e a k or e m ission o f i n su lati n g fl u i d : a n y leakage o f m ateria l i n vo lved i n the i n su lation o f a n
accessory sho u l d b e reporte d ;
s i g n ifi cant c h a n g e i n d i me n s i o n s w h i c h c o u l d h ave a detri me ntal effect o n t h e c a b l e or
accessory performance.
Annex J
(i nfo rmative )
D u r i n g the i nterru pti o n , no heating cycles a re a p p l ied to the cable system . As the i n te rru ptio n
o f t h e test is sche d u l e d , the interruption is m a d e after e n d i n g o f a com p l ete heat i n g cyc l e . After
the i nterruption period, the test is restarted by a p p l y i n g the test voltage tog ether with the start
of a new heati ng cycl e . O n ly com p l ete a p p l ied h eati ng cycles count towards the req u i red
n u m ber of heat i n g cycles . P l a n n i ng of i nterruptions to infl u ence the outcome of the test i s not
a l l owed .
T h e i nterrupted h eating cycle does n ot cou nt towa rds the req u i red n u m be r of heating cycles .
J.2 Va l i d h e at i n g cycles
Annex K
( n o rmative)
K. 1 C a l c u lati n g t h e we i g h te d va l u e fo r t h e c a b l e w h e n t h e h a l og e n co ntent of
i n d i v i d u a l n o n -meta l l i c m ateri a l is tested
The weig hted v a l u e for the h a logen content o f n o n - m eta l l i c materials in the c a b l e , Hi' for each
h a l ogen ( i . e . F, Cl, Br, I ) , is ca l c u l ated as fo l l ows:
L.( Hi Wi )
Hi = - x
�-�
L Wi
The s u m of the weig hted val ues of the h a l ogen conte nt of n o n -meta l l i c m ate rials i n the cable of
the fou r i n d i v i d u a l ha logens ( F , C l , Br, I ) , i .e . I. Hi' , s h a l l be ca l c u l ated .
K.2 Preparat i o n of t h e t e s t s a m p l e fo r m e a s u re m e n t of h a l o g e n c o n t e n t o n a
s a m p l e represe ntative of t h e n o n -meta l l i c m ateri a l s i n t h e ca b l e
B i b l iogra p h y
[2] I E C 60840, Power cables with extruded ins ulation a n d their accessories for ra ted
voltages a b o ve 30 kV (Um = 36 k V) up to 1 50 kV (Um = 1 70 k V) - Test methods a n d
requirements
[4] E l ectra N o . 1 5 1 , Recommenda tions for electrical tests, type, sample and routine, on
extruded cables and a ccessories at voltages > 1 50 ( 1 70) kV and $; 400 (420) k V,
Dece m b e r 1 9 9 3 , pp 20-28
[5] E l ectra No. 1 7 3 , A fter laying tests on high-voltage extruded insulation cable systems,
Aug ust 1 9 9 7 , pp 32-41
[7] I EC 601 83, G uidance for the selection of high-voltage A . G. cable systems
[8] I E C 60332-3-2 2 , Tests on electric a n d optical fibre cables under fire conditions -
Part 3 -22: Test for vertical flame spread of vertically-mounted b un ch e d wires or cables
- Category A
[9] I E C 60332-3-23 , Tests on electric a n d optical fibre cables under fire conditions -
Part 3 -23: Test for vertical flame spread of vertically-mounted b un ch e d wires or cables
- Category B
[1 2] I E C 608 1 1 - 1 00 , Electric and optical fibre cables - Test methods for non-metallic
ma terials - Part 1 00: General
[1 3] I EC 608 1 1 -405, Electric and optical fibre cables - Test meth ods for n on-metallic
ma terials - Part 405: Miscellan e o us tests - Thermal stability test for P VC insulations
and PVC sheaths
[ 1 5] I E C TS 6081 5-3, Selection a n d dim ensioning of high-voltage insula tors intended for use
in polluted con ditions - Part 3: Polymer insulators for a . c. systems
[1 9] E lectra N o . 205-3, Experiences with AC tests after installation on the main insulation of
polymeric (E) H V cable systems, Dece m b e r 2 0 0 2 , pp 26-36
[20] E lectra No. 227, Revision of qualification procedures for extruded high voltage A C
undergro und cable systems, Aug ust 2006, p p 3 1 -37
[22] C I G R E Tec h n i ca l B roch u re 84 1 , A fter laying tests on AC and D C cable systems with
n e w technologies, S e pte m b e r 2 0 2 1