Professional Documents
Culture Documents
OPERATION
&
MAINTENANCE
MANUAL
NUMBER OF REFRIGERATION CIRCUIT Dual Dual Dual Dual Dual Dual Dual Dual Dual
Oil per system (liters) 4.1 4.1 4.1 4.7 4.68 4.68 4.94 4.94 4.94
Refrigerant R-134a
Charge per system (oz)** 235 330 400 504 570 650 750 850 945
Qty. – Diameter (mm) 2 – 560 2 – 630 2 – 700 2 – 700 3 – 700 3 – 700 4 – 700 4 – 700 4 – 700
Nominal CFM 8400 10000 15000 15000 22500 22500 30000 30000 30000
Motor kW – RPM 0.66–1010 0.86–1020 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000
Tube Dia–Rows–Fins per inch 3/8–3–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–3–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–5–14
HIGH PRESSURE SWITCH Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10
Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10
Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5
REFRIGERANT LINES+ Suction line size (OD), inch 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8
Liquid line size (OD), inch 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ 69/65/60 69/65/60 69.3/65.8/60.5 69.7/66.1/60.9 69.8/66.3/61 72.9/69.3/64.1 72.8/69.3/64 72.9/69.3/64.1 73.3/69.8/64.5
OPERATING WEIGHT, Kg. 800 925 980 1060 1325 1400 1525 1600 1675
NOTE:
* Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures.
** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping.
+ Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.
++ Based on free field area at ARI conditions. Tolerance: ±2dBA.
NUMBER OF REFRIGERATION CIRCUIT Dual Dual Dual Dual Quadruple Quadruple Quadruple Quadruple Quadruple
Oil per system (liters) 4.94 4.94 5.2 5.2 4.94 4.94 5.2 5.2 22
Refrigerant R-134a
Charge per system (oz)** 1125 1145 1350 1660 945 1090 1250 1390 2520
Qty. – Diameter (mm) 6 – 700 6 – 700 6 – 800 6 – 800 6 – 800 8 – 800 8 – 800 10 – 800 16 – 800
Nominal CFM 45000 45000 73266 73266 69000 93256 87032 108790 192048
Motor kW – RPM 1.45–1000 1.45–1000 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970
Tube Dia–Rows–Fins per inch 3/8–4–14 3/8–5–14 3/8–3–14 3/8–3–14 3/8–4–14 3/8–3–14 3/8–3–14 3/8–4–14 3/8–3–14
Total face area (Sq. ft.) 70 70 120 120 120 140 140 175 304
HIGH PRESSURE SWITCH Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10
Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10
Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5
REFRIGERANT LINES+ Suction line size Dual 2-1/8 2-1/8 2-5/8 2-5/8 N.A. N.A. N.A. N.A. N.A.
(OD), inch
Quadruple N.A. N.A. N.A. N.A. 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8
Liquid line size Dual 1-1/8 1-1/8 1-3/8 1-3/8 N.A. N.A. N.A. N.A. N.A.
(OD), inch
Quadruple N.A. N.A. N.A. N.A. 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ 73.3/69.8/64.5 73.3/69.8/64.5 74.7/1.2/66 75.7/72.7/66.9 76.2/72.7/67.4 77.1/73.6/68.3 77.7/74.2/69 78.1/74.6/69.3 81.4/77.9/72.6
OPERATING WEIGHT, Kg. 2100 2600 3500 3700 4250 4700 5600 5095 8500
NOTE:
* Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures.
** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping.
+ Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.
++ Based on free field area at ARI conditions. Tolerance: ±2dBA.
CNX 150 460-3-60 414 506 25.7 35 2 11.4 125 0.66 1.0 2.4 2
CNX 220 460-3-60 414 506 39.0 50 2 15.9 158 0.86 1.6 4.1 2
CNX 240 460-3-60 414 506 45.7 60 2 18.1 187 1.45 2.5 10.0 2
CNX 300 460-3-60 414 506 56.1 75 2 22.7 225 1.45 2.5 10.0 2
CNX 360 460-3-60 414 506 60.6 80 2 23.6 193 1.45 2.5 10.0 3
CNX 420 460-3-60 414 506 70.5 90 2 28.0 220 1.45 2.5 10.0 3
CNX 480 460-3-60 414 506 77.5 100 2 30.0 262 1.45 2.5 10.0 4
CNX 540 460-3-60 414 506 91.0 125 2 36.0 262 1.45 2.5 10.0 4
CNX 600 460-3-60 414 506 108.8 150 2 43.9 323 1.45 2.5 10.0 4
CNX 720 460-3-60 414 506 147.1 200 2 58.7 404 1.45 2.5 10.0 6
CNX 840 460-3-60 414 506 147.1 200 2 58.7 404 1.45 2.5 10.0 6
CNX M00 460-3-60 414 506 183.5 250 2 72.5 513 2.15 3.4 10.0 6
CNX M10 460-3-60 414 506 207.6 275 2 83.2 590 2.15 3.4 10.0 6
CNX M20 460-3-60 414 506 207.0 250 4 43.9 323 2.15 3.4 10.0 6
CNX M40 460-3-60 414 506 276.7 325 4 58.7 404 2.15 3.4 10.0 8
CNX M60 460-3-60 414 506 335.3 400 4 72.5 513 2.15 3.4 10.0 8
CNX 2M00 460-3-60 414 506 342.1 400 4 72.5 513 2.15 3.4 10.0 10
CNX 2M40 460-3-60 414 506 548.6 650 4 117.4 801 2.15 3.1 10.0 16
LEGEND:
MCA - Minimum Circuit Ampacity
MOCP - Maximum Over Current Protection
RLA - Rated Load Amps
LRA - Locked Rotor Amps
kW - Kilowatt
FLA - Full Load Amps
3
4
5
1
2
3
4
5
7
1550 [61.0]
203 [8.0]
357.5 [14.07]
255.0 [10.00]
TYP
TYP
1550 [61.0]
203 [8.0]
2121
375.6 [14.80]
335.4 [13.20]
[83.50]
2197
[86.50]
TOP VIEW
"B" "C"
73 [2.875] 965 968 968
(37.99") (38.11") (38.11")
275 [10.826]
13
2185 [86.023]
285.0 [11.220]
SYSTEM PROTECTION
The unit is equipped with protective devices against motor overloads and proper system settings are factory set to ensure
safe and reliable operation of the unit. Some of these devices and settings are as follows:
- Compressor Motor External Overload Relay
- Compressor Motor Winding Over Temperature Protection
- Low suction Pressure
- High Discharge Pressure
- Low Oil Pressure
- Compressor Anti-Recycling Timer
14
On/Off
SET Menu
CLASSIC
AIR CONDITIONERS
TOUT = 10°C TIN = 15°C
COOLING 75% Esc
Machine Starting:
- If OFF, the machine is started by pushing the ON/OFF button.
- The ON LED (green) will lit.
- On the main screen is showed the status “STARTING”.
- After 15 seconds of delay the system will be running.
Machine Shut-Down:
- The machine is halted pushing again the ON/OFF key.
- The ON LED (green) is switched off.
- On the main screen is showed the status “STOPPING”.
- All the compressors are stopped.
- Blower motor will be switched off after pre-set delay timing when all compressors are switched off.
- On the main screen is showed the status “SYSTEM OFF”.
Set Point Change:
- Press “SET”, the LCD will ask the password input.
- Using the “UP” and “DOWN” keys input the correct password.
- Press “SET”, the “MODIFY” word appears to allow the parameter to be changed. The LCD will show the actual
value.
- Using the “UP” and “DOWN” keys modify the set point value.
- Press “SET” to store it or “ESC” to exit without memorizing.
COMPRESSOR CONTROL
Control setting to switch on / off the compressors is through digital output signals from an external controller fed to the
micro-processor board. When the system is started up, the software starts to check all the necessary inputs to start the
unit. It scans the digital/analogue inputs. If any unwarranted interruption occurred the alarm signal is generated and the
compressor will be shut-off.
15
CB1 CB2
LUG/ETB
L1A
L2A
L3A
L1B
L2B
L3B
CC1 CC2
T1A
T2A
T3A
T1B
T2B
T3B
OLR1 OLR2
T1A
T2A
T3A
T1B
T2B
T3B
COMP COMP
1 2
COMP COMP
1 2
COMPRESSOR POWER & CONTROL CONNECTION IN PART WINDING STARTING (PWS) (AS APPLICABLE) COMPRESSOR IN PWS CONNECTION WITH CB (OPTIONAL)
HVTB HVTB
L1 L1
L2 L2
L3 L3
CB1 CB2
L1A
L2A
L3A
L1B
L2B
L3B
L1C
L2C
L3C
L1D
L2D
L3D
CC1 CC3 CC2 CC4 CC1 CC3 CC2 CC4
T1D
T2D
T3D
T1C
T2C
T3C
T1D
T2D
T3D
T1A
T2A
T3A
T1B
T2B
T3B
T1A
T2A
T3A
T1B
T2B
T3B
COMP COMP COMP COMP
2 2
1 2 1 2
MB MB
1O CC1 4O CC2
3A 3B
CC3 CC4
CC1A-2A 61A CC2A-2A 61B
CB1A-1A CB2A-1A
1 23A 1 23B
CONDENSER FAN MOTOR POWER AND CONTROL CONNECTIONS COMP. SSPS CONNECTION(AS APPLICABLE)
CNX 360~420 COMP. 1: SSPS1
CNX 220~300 CNX 480~600
HVTB HVTB HVTB 3-FAN MOTOR LAYOUT HVTB HVTB 1 8A
L1 L2 L3 2-FAN MOTOR LAYOUT L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 4-FAN MOTOR LAYOUT M1/11 M2/14
C1 1
C1 C2 3 3 C1 1 2
1 2
CONTROL
PANEL C2 2
CONTROL
PANEL L1/MP/L L2/R/N
CONTROL 4 C2 2
PANEL
(REMOVE JP3A)
CB6 CB6 CB7 CB6 CB7 COMP. 2:
SSPS2
1 8B
M1/11 M2/14
2
104C
104C
104D
104A
104B
104A
103C
105C
104B
104A
103C
105C
104B
103D
105D
103A
105A
103B
105B
103A
105A
103B
105B
103A
105A
103B
105B
L1/MP/L L2/R/N
FMC1 FMC2 FMC1 FMC3 FMC2 FMC1 FMC3 FMC2 FMC4 (REMOVE JP4B)
(SEE NOTE 3)
35C
36C
37C
35C
36C
37C
35D
36D
37D
35B
36B
37B
35B
36B
37B
35B
36B
37B
35A
36A
37A
35A
36A
37A
35A
36A
37A
2 2 2
1 C.HTR2 2
FM1 FM1 FM1 COMP. 2: CC2A-1B 101A
TO MB T.K. TO MB T.K. TO MB T.K.
FMC1 12A FMC1 FMC1
12A 12A 13A 12A 13A
9 NO 9 NO 9 NO
104E
104A
105C
103E
105E
104F
105A
103C
104D
105F
103A
104B
105D
103F
105B
103D
HGS -- --
103B
(REMOVE JP5B)
FMC1 FMC3 FMC2 FMC4 FMC5 FMC6
JUMPER SETTINGS - MB BOARD AHU CONTROL INTER-CONNECTIONS
35C
36C
37C
35D
36D
37D
35A
36A
37A
35B
36B
37B
35E
36E
37E
35F
36F
37F
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
16
A12
UVM UNDER VOLTAGE MONITOR
A13 (EMERGENCY) YR COOLING RELAY
YR1-1A
YR2-1A
71A
71B
A14 (COOLING STAGE 1) ___ FIELD WIRING
A15 (COOLING STAGE 2)
A18
SPLICE-CLOSED END
A19 (AUX. ALARM COMP1)
TERMINAL BLOCK OR TERMINATION POINT
A20 (AUX. ALARM COMP2)
AC (DIGITAL COM) JUNCTION OF WIRES
CROSSING OF WIRES, NO CONNECTION
R1(DIG OUT) CC1
1C 1O
PDS1
3A COMP1 CONTACTOR EARTHING/GROUND
2C R2(DIG OUT) 2O 15A COMP1 PUMP DOWN SOLENOID
(OPTIONAL)
UL1
R3(DIG OUT) 14A COMP1 CAPACITY UNLOADER SOLENOID
3C 3O
(OPTIONAL) NOTES
R4(DIG OUT) CC2
4C 4O
3B COMP2 CONTACTOR 1. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C
PDS2
5C R5(DIG OUT) 5O 15B COMP2 PUMP DOWN SOLENOID OR ITS EQUIVALENT.
(OPTIONAL)
UL2
R6(DIG OUT) 14B COMP2 CAPACITY UNLOADER SOLENOID
6C 6O
(OPTIONAL) 2. USE COPPER CONDUCTOR WIRES ONLY.
HGS
7C R7(DIG OUT) 7O HOT GAS BY-PASS SOLENOID
R8(DIG OUT)
(OPTIONAL)
3. COMPRESSORS ARE PROVIDED WITH INTERNAL
8C 8NO
COMMON FAULT INDICATION
LINE BREAK OR SSPS FOR THERMAL PROTECTION.
8NC (VOLT-FREE CONTACT)
30B DPT2
D2 - - COMP2
USER INTERFACE BOARD (A9-DP2) 31B
+ + DISCHARGE PRESSURE TRANSDUCER
SH
SH
On/Off * S1 32B OPT2
ON DIP O2 - - COMP2
SERIAL CABLE (A10-OP2) 33B OIL PRESSURE TRANSDUCER
SET MENU * + + (FOR RECIP. COMP ONLY)
TOUT=15°C TIN=28°C 1 2 3 4 SH
COOLING 75%
COM1
ESC * GND
17
POWER SUPPLY L2
(NOTE 4) L3
T1C
T2C
T3C
T1D
T2D
T3D
T1A
T2A
T3A
T1B
T2B
T3B
COMP COMP COMP COMP
1 2
3 4
2 2 2 2
MB MB AB AB
FAN LAYOUT
COMP1 COMP2
COMP3 COMP4
104D
105C
105D
104A
104E
104B
103C
103D
105A
105E
105B
104F
103A
103E
103B
105F
103F
35D
36D
37D
35B
36B
37B
35A
36A
37A
35E
36E
37E
35F
36F
37F
2 2
FM3
T.K. FMC3 FM4
TO MB TO AB T.K.
12C 13C FMC4
12D 13D
9 NO 9 NO
FM1 FM2
T.K. FMC1 T.K.
12A 13A FMC2
12B 13B
10 NO 10 NO
13 NO 13 NO
FM6
T.K. FMC5 T.K. FMC6
12E 13E 12F 12F 13F
14 NO 14 NO
CONDENSING UNIT AIR HANDLING UNIT LOW PRESSURE 10 ± 5 30 ± 5 JU2 - CLOSED TD1 - OPEN
CONTROL PANEL CONTROL PANEL
HIGH PRESSURE 300 -- TL1 - OPEN
LVTB
G
HPS1 ~4 350 ± 10 300 ± 15 DIP SWITCH SETTINGS - MB1 BOARD
BMR (24Vac) FAN MOTOR # OFF (PSIG) ON (PSIG) 1 2 3 4
ATB S1
17 125 175 ON OFF OFF OFF
FM1,2,5,6
ATB BMR-1A FM3,4 175 225 JUMPER SETTINGS - MB BOARD
1
JU1 - OPEN TU1 - OPEN
(REMOVE JP6) (AHU MOTOR CONTROL)
ATB TD1 - OPEN
JU2 - OPEN
67
TL1 - OPEN
ATB
20 DIP SWITCH SETTINGS - AB BOARD
R2 (230Vac) 1 2 3 4
ATB S1
2 OFF ON OFF OFF
R2-1
MOTOR STARTER CONTROL JUMPER SETTINGS (COMMON)
AHU MOTOR ON/OFF JU3 - CLOSED (1,2) JU11 - CLOSED (1,2)
SWITCHING CONTACT
JU4 - CLOSED (1,2) JU12 - CLOSED (1,2)
ATB AHU MOTOR FAULT JU5 - CLOSED (1,2) JU13 - CLOSED (1,2)
(N.C CONTACT)
1
JU6 - CLOSED (1,2) JU15 - CLOSED (1,2)
(REMOVE JP7)
ATB
JU7 - CLOSED (1,2) JU19 - CLOSED (1,2)
52
JU8 - CLOSED (1,2) TU2 - CLOSED
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
18
F3 TRANS2 F4
3 4
460V
230V
ATB
S1 F1 F2
5 6
1A 1B 2
C.HTR1
CC1A-1B 100A
UVM CONNECTION (OPTIONAL)
C.HTR2
L1 L2 L3 CC2A-1B 100B
C.HTR3
CC5A-1B 100C
Ø Ø Ø CC6A-1B 100D
C.HTR4
L1 L2 L3 UVM
1 UVM-1 8
Ø Ø SSPS1
1A
(REMOVE JP1) SSPS2
1
SSPS3
TO ATB TO ATB
15 17
SSPS1 24V AC PE
8A A1 (SSPS-1)
(CB1A-1)
JP4A 23A A2 (CB-1)
A13 (EMERGENCY)
YR1-1A 71A
A14 (COOLING STAGE 1)
YR2-1A 71B
A15 (COOLING STAGE 2)
A16
A18
7C R7(DIG OUT) 7O
28A SPT1
S1
- - COMP1
ST1 29A SUCTION PRESSURE TRANSDUCER
(A5-SP1) + +
SH
SH SH
30A DPT1
T.OUT
D1 - -
(A6-DP1)
COMP1
31A DISCHARGE PRESSURE TRANSDUCER
+ +
SH
SH
32A OPT1
O1 - -
ST2
(A7-OP1)
COMP1
(A1-ST1) 33A OIL PRESSURE TRANSDUCER
+ +
SH SH
SH
28B SPT2
S2 - - COMP2
TIN (A8-SP2) 29B SUCTION PRESSURE TRANSDUCER
+ +
SH
30B DPT2
D2 - - COMP2
USER INTERFACE BOARD (A9-DP2) 31B
+ + DISCHARGE PRESSURE TRANSDUCER
SH
SH
On/Off * S1 32B OPT2
ON DIP O2 - - COMP2
SERIAL CABLE (A10-OP2) 33B OIL PRESSURE TRANSDUCER
SET MENU * + +
TOUT=15°C TIN=28°C 1 2 3 4 SH
COOLING 75%
COM1
ESC * GND
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
19
A13
YR COOLING RELAY
YR3-1A 71C
A14 (COOLING STAGE 3)
___ FIELD WIRING
YR4-1A 71D
A15 (COOLING STAGE 4)
A16
+ DISCONNECT TAB - 1/4"
A17 SPLICE-CLOSED END
A18
32C OPT3
O1 - -
ST2
(A7-OP1)
COMP3
(A1-ST1) 33C
+ OIL PRESSURE TRANSDUCER
+
SH SH
SH
28D SPT4
S2 - - COMP4
TIN
(A8-SP2) 29D SUCTION PRESSURE TRANSDUCER
+ +
SH
30D DPT4
D2 - - COMP4
(A9-DP2) 31D
+ + DISCHARGE PRESSURE TRANSDUCER
SH
SH
S1 32D OPT4
TO MASTER BOARD MB ON DIP O2 - - COMP4
SERIAL CABLE (A10-OP2) 33D
+ OIL PRESSURE TRANSDUCER
X53 1 2 3 4 +
SH
X52
GND
20
POWER SUPPLY L2
(NOTE 4) L3
T1G
T2G
T3G
T1C
T2C
T3C
T1D
T2D
T3D
T1H
T2H
T3H
T1A
T2A
T3A
T1B
T2B
T3B
T1E
T2E
T3E
T1F
T2F
T3F
COMP COMP COMP COMP
2 2 2 2
1 2 3 4
MB MB AB AB
OLR1-1A 11A OLR3-1A OLR2-1A 11B OLR4-1A OLR5-1A 11C OLR7-1A OLR6-1A 11D OLR8-1A
10A 9A 10B 9B 10C 9C 10D 9D
FAN LAYOUT
COMP1 COMP3
CONTROL PANEL FAN1 FAN3 FAN5 FAN7 FAN9 FAN11 FAN13 FAN15
FAN2 FAN4 FAN6 FAN8 FAN10 FAN12 FAN14 FAN16
COMP2 COMP4
104N
105N
104P
103N
105P
104M
103P
104L
105M
104G
104O
105L
104J
103M
105G
105O
104C
103L
105J
103G
103O
105C
104A
104E
103J
103C
104D
104H
105A
105E
103D
105D
103H
105H
103A
103E
104B
104K
103B
105B
103K
105K
104F
105F
103F
104I
105I
103I
FMC1 FMC5 FMC3 FMC7 FMC2 FMC6 FMC4 FMC8 FMC9 FMC13 FMC11 FMC15 FMC10 FMC14 FMC12 FMC16
35M
36M
37M
35G
36G
37G
35O
36O
37O
35C
36C
37C
35D
36D
37D
35H
36H
37H
35N
36N
37N
35A
36A
37A
35E
36E
37E
35B
36B
37B
35K
36K
37K
35P
36P
37P
35F
36F
37F
35L
36L
37L
35J
36J
37J
35I
36I
37I
FM1 FM5 FM3 FM7 FM2 FM6 FM4 FM8 FM9 FM13 FM11 FM15 FM10 FM14 FM12 FM16
2 2 2 2
FM1 FM2 FM9 FM10
TO MB T.K. TO MB T.K. TO AB T.K. AB T.K.
FMC1 FMC2 FMC9 FMC10
12A 12A 13A 12B 12B 13B 12I 12I 13I 12J 12J 13J
9 NO 13 NO 9 NO 13 NO
FM5 FM6 FM13 FM14
T.K. FMC5 T.K. FMC6 T.K. FMC13 T.K. FMC14
12E 13E 12F 13F 12M 13M 12N 13N
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
21
F3 TRANS2 F4
3 4
460V
230V
S1 F1 F2 ATB
5 6
1A 1B 2
C.HTR1
CC1A-1B 100A
UVM CONNECTION (OPTIONAL)
C.HTR2
L1 L2 L3 CC2A-1B 100B
CC5A-1B
C.HTR3
100C
Ø
L1
Ø
L2
Ø
L3 CC6A-1B 100D
C.HTR4
UVM
1 UVM-1 8
Ø Ø SSPS1
1A
(REMOVE JP1) SSPS2
1
SSPS3
TO ATB TO ATB
15 17
SSPS1 24V AC PE
8A A1 (SSPS-1)
(CB1A-1)
JP4A 23A A2 (CB-1)
A13 (EMERGENCY)
YR1-1A 71A A14 (COOLING STAGE 1)
YR2-1A 71B A15 (COOLING STAGE 2)
A16
A18
15B CC2-1A
8C R8(DIG OUT) 8NO UL2-4
16B
COMMON FAULT INDICATION
8NC (VOLT-FREE CONTACT)
28A SPT1
S1
- - COMP1
ST1 29A SUCTION PRESSURE TRANSDUCER
(A5-SP1) +
+
SH
SH SH
(OPTIONAL) 24 30A DPT1
D1 - -
LEAVING AIR TEMP. SENSOR T.OUT COMP1
25 (A6-DP1) 31A
(PTC : -10 ~ +50 C) + DISCHARGE PRESSURE TRANSDUCER
+
SH SH
SH
ST2
O1 -
(A7-OP1)
(A1-ST1) +
SH
(OPTIONAL) SH
26 28B SPT2
RETURNING AIR TEMP. SENSOR S2 - - COMP2
27 TIN
(PTC : -10 ~ +50 C) (A8-SP2) 29B SUCTION PRESSURE TRANSDUCER
SH
+ +
SH
30B DPT2
D2 - - COMP2
(A9-DP2)
USER INTERFACE BOARD +
31B
+ DISCHARGE PRESSURE TRANSDUCER
SH
SH
On/Off * S1
ON DIP O2 -
SERIAL CABLE (A10-OP2)
SET MENU * +
TOUT=15°C TIN=28°C 1 2 3 4
COOLING 75%
COM1
ESC * GND
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
22
P
10C 9C A4 (HPS-3)
OLR OVER LOAD RELAY
A5
SSPS4
8D
(CB4A-1)
A6 (SSPS-4)
AO3
SSPS SOLID STATE PROTECTIVE SYSTEM
JP4D 23D A7 (CB-4)
AO2 TRANS TRANSFORMER
JP5D 64D A8 (OL-4)
HPS4
10D
OLR6-1A OLR8-1A
9D A9 (HPS-4) TK/TOP FAN MOTOR (PROTECTION) THERMAL CONTACT
P AO1
A10
A11
UL COMPRESSOR UNLOADER SOLENOID
A12 UVM UNDER VOLTAGE MONITOR
A13
YR3-1A 71C
YR COOLING RELAY
YR4-1A 71D
A14 (COOLING STAGE 3)
A17
+ DISCONNECT TAB - 1/4"
A18 SPLICE-CLOSED END
A19 (AUX. ALARM COMP3)
O1 -
ST2
(A7-OP1)
(A1-ST1) +
SH
SH
28D SPT4
S2 - - COMP4
TIN
(A8-SP2) 29D SUCTION PRESSURE TRANSDUCER
+ +
SH
30D DPT4
D2 - - COMP4
(A9-DP2) 31D
+ + DISCHARGE PRESSURE TRANSDUCER
SH
SH
S1
ON DIP O2 -
TO MASTER BOARD MB
SERIAL CABLE (A10-OP2)
X53 +
1 2 3 4
X52
GND
23
17
1
(REMOVE JP6)
67
20
1
(REMOVE JP7) (REMOVE JP7)
52
24
MODELS: CNX2M40
25
R1 R2 R1 R3 R5 R1 R3 R5 R7 R1 R3 R5 R7 R9
R3 R4 R2 R4 R6 R2 R4 R6 R8 R2 R4 R6 R8 R10
26
LOCATION OF UNIT
When selecting the location for the unit, the following points should be kept in mind:
1. Provisions for a concrete slab which will allow for minimum clearance from building or structures
2. That the terrain allows for drainage away from the unit.
3. If the unit is to be roof mounted, inspect the roof for load bearing capacity. The roof should have sufficient structural
strength to carry the weight of the unit.
4. Availability of electric power.
5. Position the unit to provide for unrestricted air circulation and to prevent any possibility of air recirculation.
6. Check minimum clearances required for your unit, with regard to walls, or other obstructions.
7. Air cooled equipment should not be installed under low structural overhangs which can cause condenser air recircu-
lation or restriction.
8. Care should be taken to prevent air from other sources from entering condenser, if this air is at a high temperature.
Sweat connection:
Units are provided with service valves and are ready for brazing. After wrapping the service valve with a wet cloth, the
piping set can be brazed to service valve using either silver rod or silfos rod brazing materials.
Refrigerant Charging:
(To be used for system having a holding charge and to compensate for length of liquid line).
1. When system wired, piped and evacuated, the unit is ready for refrigerant charging. All charging lines and manifolds
must be purged with refrigerant vapor prior to admitting refrigerant into the system to prevent contamination system
with non-condensable.
27
WIRING
All wiring must comply with the "National Electric Code" and local electrical standards. The power supply, voltage,
frequency and phase must coincide with the unit nameplate.
Power wiring to the equipment must be adequately sized for maximum ampacity as shown on unit name plate. The unit
wiring diagram, completely illustrates the internal wiring and field connection needed for power supply and control wiring.
The power supply should be run through the sized shielded cable or rigid conduit and through a separate fused disconnect
switch/circuit breaker. For control wiring, use approved thermostat wire (minimum 18 gauge). Never use telephone wire for this
purpose. A sized circuit breaker/fused disconnect switch should be located adjacent to the unit for safety & servicing purposes.
Wiring connection to the unit must have insulation suitable for temperatures of a minimum of 600C.
Minimum circuit ampacity for each model is shown on the name plate and product catalog. Equipment wiring diagram
should be examined and thoroughly understood before field wiring connections are made.
Power supply should be checked to be certain that supply voltage agrees with equipment nameplate. Serious damage to
compressors and motors can occur, if improper voltage is applied.
1. Connect the manifold gauge to suction & discharge line service valves. Prepare recommended instruments for check-
ing Voltage, Amps, RPM, CFM, static pressure, etc.
2. Start the blower fan and condenser fan. Check the amperage against the nameplate ampere.
3. Start the compressor and observe the following points (on multiple compressor units, it is highly recommended to start
the compressors one by one to achieve careful observation for each compressor).
(a) Check compressor discharge and suction pressures. If not within system design limits, determine why and take
corrective action.
(b) Check liquid line sight glass and expansion valve operation. If there are indications that more refrigerant is required,
leak test all connections and system components and repair any leaks before adding refrigerant.
(c) Observe oil level in compressor crankcase sight glass (if available) and add oil as necessary to bring to recom-
mended oil level.
All compressors are charged with somewhat greater than the normal oil level required for adequate lubrication, in order
to provide some allowance for oil which will be circulating in the system during operation. Depending on the system
design, the amount of oil in the system at the time of compressor installation, oil lost due to leakage, etc., it may be
necessary either to add or remove oil from a system any time it is first placed in operation with a different compressor.
An abnormally low oil level may result in a loss of lubrication; while an excessively high oil level may result in oil
slugging and possible damage to the compressor valves or excessive oil circulation. The oil level may vary consider-
ably on initial start-up if liquid refrigerant is present in the crankcase, and the oil level should be checked with the
compressor running after having reached a stabilized condition.
(d) Thermostatic expansion valves must be checked for proper superheat settings. Recommended superheat is 150F
to 200F.
(e) Using suitable instruments, carefully check line voltage and amperage at the compressor terminals. Voltage must
be within ±10% of that indicated on the compressor nameplate. If high or low voltage is indicated, notify the power
company. The current normally should not exceed 110% of the nameplate rating. If amperage draw is excessive,
immediately determine the cause and take corrective action. On three phase compressor motors, check to see
that a balanced load is drawn by each phase.
(f) Carry out any necessary tests, recording airflow rates, entering/leaving temperatures, sound levels, outdoor tem-
peratures, supply airflow rates in occupied spaces and any other specified parameters.
29
Before making an installation, check the electric power supply. The power supply must be of the same characteristics as
that on the nameplate.
Normally the wire size used establishes the circuits maximum permissible load. For example a number 12 wire circuit is
considered to be a 20 ampere circuit and is protected by a 20 ampere fuse. The unit amperage nameplate rating should
not exceed 80% of the circuit rating, 16 amperes.
When identifying electrical trouble in any unit, check the power supply at the main disconnect switch and the unit. A high
or low voltage condition may prevent the unit from starting, or if the unit is running, compressor can cut-off automatically
on the motor overload. On some installations, the voltage may be entirely adequate when tested, but may drop or surge
some time later due to increase or decrease of load on the power line. This condition may be repeated daily at the same
hour. When this condition is suspected, make arrangements with the local power supplier to place a recording voltmeter
on the line to check and correct the erratic voltage conditions.
The voltage drop should not be more or less than 10% of the units rated voltage. If the voltage at the meter is correct, but
the voltage at the unit fluctuates 10% or more, the branch circuit is not adequate.
UNBALANCED VOLTAGE
Unbalanced voltage on a three phase circuit may be the source of electrical trouble. If balanced supply voltages are not
always maintained, so with the three line currents will not be equal. Unbalanced voltage on a three phase compressor
motor may overheat and trip the motor on external or internal current sensing motor protector, whichever one is provided.
To determine that an unbalanced voltage condition exists, the supply voltage at the main disconnect switch and at the
unit disconnect switch should be measured. Voltage unbalance is calculated as follows.
The percentage of voltage unbalance equals one hundred times the ratio of the Maximum Voltage Deviation from the
Average Voltage, and the Average Voltage.
Because of the unbalanced voltage condition in a three phase circuit, it is possible that one phase winding in the com-
pressor motor may be over-heated while the other have a temperature within normal limits. Where unbalanced voltage on
a three phase circuit exists, the power company should be notified of such unbalance to determine, if the situation can be
corrected.
A common source of unbalanced voltage on a three phase circuit is a single phase load between two of the three phases.
A large lighting or heating circuit connection to one phase of a three phase circuit can easily cause sufficient variations in
motor currents to endanger the motor. Interchange the single phase loads to equally divide the entire loads among the
three phases. Balance the supply voltage as evenly as possible.
Unless the unbalanced voltage condition can be corrected, the only way to insure motor safety is to be sure that the
protectors are in the high current phase when using two leg protection, or to use protectors in all three legs.
30
FAN MOTOR
The condenser fan motor is a single speed electrical motor with ball bearings, protected with an automatic reset internal overload.
CRANKCASE HEATERS
The function of the crankcase heater is to hold the compressor oil reservoir at a temperature higher than the coldest part
of the system. The low wattage heaters are energize continuously and it is not necessary to have them de-energize when
the compressor is operating.
Power must be supplied to crankcase heater for minimum of 12 hours prior to system start up. If power is off 6 hours or
more, crankcase heater must be on for 12 hours before operating the system. Failure to follow these instructions may
result in compressor damage.
Crankcase heaters are effective to retard migration of liquid refrigerant to the crankcase during off cycle. But they are not
a remedy for slugging or flood back due to liquid refrigerant accumulating in a trapped suction line, improper piping
practice, over feeding to the evaporator, leaking solenoid valve, etc.
In some cases where migration of refrigerant to the crankcase occurred due to long storage time, shutdown period,
defective components, etc. The crankcase heater may be ineffective. Such cases may be easily observed by high oil
level and cold crankcase. In these cases, it is highly recommended to front seat or close both suction and discharge
service valves of the compressor and release all liquid refrigerant from the compressor.
The liquid refrigerant dilutes the oil in the crankcase and the refrigerant rich oil will be pumped to the rods and the
bearings through the crankshaft. As the refrigerant boils off, there will not be enough oil for sufficient lubrication at the
bearings furthest from the oil pump. The center and rear bearings may seize or may wear enough to allow the rotor to
drop and drag on the stator causing it to short. Also the liquid refrigerant washes the oil off the pistons and cylinders
during the suction stroke causing them to wear during the compression stroke.
When the crankcase is filled with liquid refrigerant and the compressor starts severe agitation, oil foaming etc. will cause
major damage to the compressor.
Periodic checking for proper operation of crankcase heater is highly recommended.
VOLTAGE MONITOR
This device protects the motors in the unit from faults such as; under or over voltage, unbalance & phase reversal of the
power supply. When the device sensed such faults, it will cut-off the supply in the control circuit thereby cutting off power
to the motors. The voltage monitor will re-set automatically when power is brought back to it’s normal conditions.
TRIP & RE-SET VOLTAGE (% OF SET POINT)
LINE VOLTAGE
UNDER VOLTAGE OVER VOLTAGE PHASE IMBALANCE
RANGE
TRIP RE-SET TRIP RE-SET TRIP RE-SET
190 - 480 VAC 90% 93% 110% 107% 6% 4.5%
31
Semi-hermetic Compressor:
These Semi hermetic reciprocating compressors are accessible –hermetic type. Compressor and motor are enclosed in
a hermetically sealed housing, with out shaft seal. The compressors are equipped with an oil sight glass through which
the oil quantity and its conditions in the crankcase can be observed. These compressors can be disassembled in the field
for service.
Refrigerant-cooled motor –compressors have an oil pressure lubrication system. This system is supplied by a positive
displacement oil pump, working in either direction. It is protected by a screen and is made accessible for quick oil
pressure checking by a Schrader check valve. The use of oil pressure control safeguards the lubrication system. These
compressors can be provided with capacity control (optional). The use of unloading provides optimal part load capacities.
Scroll Compressors:
Scroll Compressors are used in some of these units. The major benefits being:
1. Low Sound Level: Quieter operation because of no dynamic suction and discharge valves action.
2. Low vibration and discharge pulses.
3. High Energy Efficiency: Because of high volumetric efficiency it minimize pressure and heat transfer losses.
4. High Capacity: Due to its high mass flow and high compression ratios.
5. High Durability: With its robust design, few moving parts, low motor strains, large internal volume for liquid handling
makes this compressor highly reliable.
6. High Charge Limit: Therefore, lower applied costs as no suction accumulator required, no need for pump down
system and check valve in discharge line.
Low capacity can be caused by inefficient compressor, that is, the compressor does not pump sufficient quantity of
refrigerant, even though a full charge is available in the system.
Electrical and mechanical tests should be performed to determine if the compressor is defective. If the compressor is found
to be all right but the electrical components are defective, remove and replace the defective electrical components only.
Below are some tests that should be performed on the compressor to determine, if the compressor is defective.
1. Test compressor motor winding for ground.
2. Test compressor motor windings for continuity.
3. Test that compressor motor will run both without a load and under a load.
4. Test the current or ampere drawn.
5. Observe sound level of compressor.
To establish that the compressor suction and discharge valves are operating and holding properly, attach gauges to the
liquid and suction service valves. "Front seat" the liquid service valve.
32
If the first acidity test shows that the acid content is below the safe level, as indicated in the test kit instructions, and the
oil is clean, the clean-out system can be removed. If an in-line suction filter drier was used, it can remain in the system
provided the pressure drop through the filter does not exceed the manufacturers listed pressure drop. For a badly
contaminated system that indicates acid in the oil after 8 to 12 hours of operation, change the suction and liquid line filter-
driers and check the system after 24 hours of operation.
There are instances where contaminants are discovered in a refrigeration system with the compressor still operational.
The same procedure applies, when cleaning these systems, as on a compressor burn-out.
SOURCE OF CONTAMINATION
There are many ways in which a refrigerant system can become contaminated. The most common of these are as
follows:
1. Improper or inadequate dehydration.
2. Wet refrigerant.
3. Wet oil (caution: It is best to purchase oil in small containers and use as needed. Open containers will absorb mois-
ture).
4. Refrigerant leaks (allowing system to operate in a vacuum).
5. Failure to remove oil and moisture after having opened the system for repair.
6. Higher than normal operating temperatures and pressures will cause a breakdown of the oil and refrigerant.
7. Improper use of soldering or brazing flux.
33
The control is preset to open when the suction pressure is 10 ± 5 psig. The contacts of the control will close when the
suction pressure rises to 30 ± 5 psig. To test the control for the correct pressure setting, install a compound gauge to the
gauge port on the suction service valve. "Front seat" the liquid valve and start the unit. Note the gauge pressure, when
the compressor stops.
To determine the cut-in pressure, allow the suction pressure to build slowly and observe the gauge pressure at the time
when contact closes. A good functional low pressure switch must have both cut-out and cut-in pressure within ± 2 psig.
Pump down operation takes place as soon as the signal for cooling is switched off. The system’s control closes the liquid
line solenoid valve while the compressor is continuously running to pump out a substantial portion of refrigerant in the
evaporator. The compressor will shut off when either the suction pressure goes down at a pre-set pressure of 25 psi or
at a pre-set timing of 10 seconds whichever is satisfied first. On call for the next cooling cycle, the solenoid valve will get
energized ahead of the compressor at a pre-set timing. This is to allow refrigerant to flow in the evaporator and thereby
increasing the suction pressure above the low pressure trip setting before the compressor starts.
A pump down control may be necessary on an installation where additional protection for the compressor is required to
prevent slugging of oil or liquid refrigerant.
Below are some conditions which may exist in an installation where additional protection is required:
1. Migration of refrigerant to the compressor during the off cycle.
2. Flooding, at start-up, due to improperly trapped lines or coil.
3. Suction line in slab or beneath ground forming a large trap.
4. Suction line in cool area causing refrigerant to condense during off cycle.
5. Where condensing unit is installed using existing coils and copper lines, or on a new installation where the above said
conditions exist that cannot be avoided, which could result in compressor damage.
34
Compressor starts and runs, 1. Additional current passing through 1.Check wiring diagram. Check for
but short cycles on overload overload protector. added fan motors, pumps, etc. con-
protector. nected to wrong side of protector.
2. Low voltage to unit (or unbalanced if
three phase). 2. Determine the reason and correct.
3. Check current, replace protector.
3. Overload protector defective.
4. Check airflow across the condenser
4. Excessive discharge pressure. coil, restrictions in refrigeration sys-
tem.
5. Suction pressure too high.
5. Check for possibility of misapplica-
6. Compressor too hot - return gas hot. tion. Use stronger unit.
Suction line frosted or 1. Expansion valve passing excess re- 1.Re-adjust valve or replace with
sweating. frigerant or is oversized. smaller valve.
2. Expansion valve stuck open. 2. Clean valve of foreign particles, re-
3. Evaporator fan not running. place if necessary.
4. Overcharge of refrigerant. 3. Determine reason and correct.
4. Correct charge.
35
Head pressure too high. 1. Refrigerant overcharge. 1. Correct the refrigerant charge.
2. Air in system. 2. Recharge the system after a thorough
3. Dirty condenser. triple evacuation.
4. Malfunction of condenser fan (air- 3. Clean.
cooled). 4. Check and correct or replace.
5. Excessive air temperature entering 5. Check for short circuiting of con-
condenser. denser discharge air, correct it.
6. Restriction in discharge line. 6. Correct it.
Head pressure too low. 1.Low ambient temperatures (air- 1. Install fan cycling switch, if not pro-
cooled). vided. Check the setting and opera-
2. Refrigerant shortage. tion, if provided.
3. Damaged valves in compressor. 2. Correct the refrigerant charge after
leak testing.
3. Repair/replace the compressor.
High suction pressure. 1. High load on evaporator. Load in ex- 1. Check the design.
cess of design conditions. 2. Follow manufacturer's guide line and
2. Unbalanced system. Oversized air correct it.
handling unit matched with under 3. Repair/replace compressor.
sized condensing unit.
4. Check and adjust the superheat ac-
3. Compressor discharge valve leaking. cordingly.
4. Expansion valve widely open. 5. Check the expansion valve bulb is
5. Improper bulb location or installation. properly tighten at correct location.
36
Loss of oil pressure. 1. Loss of oil from compressor due to: 1. (a) Correct the system piping.
(a) Oil trapping in system. (b) Trace out the wiring/defective controls/
(b) Compressor short cycling. components, etc. and correct it.
(c) Insufficient oil in system. (c) Add oil.
(d) Operation at excessively low (d) Check the superheat of expansion
suction pressure. valve and other possible causes
like clogged filter, low CFM, iced
2. Excessive liquid refrigerant returning
evaporator etc. and correct it.
to compressor.
2. Check the system for correct super
3. Malfunctioning oil pump.
heat and other possible causes like
4. Restriction in oil pump inlet screen. clogged filter, low CFM, iced evapo-
rator, etc. and correct it.
3. Repair or replace it.
4.Clean/replace it (oil change recommended).
Space temperature too high. 1. Control setting too high. 1. Reset control.
2. Expansion valve too small. 2. Use larger valve.
3. Cooling coils too small. 3. Add surface or replace.
4. Inadequate air circulation. 4. Improve air movement.
Unit noisy. 1. Loose parts or mountings. 1. Find and tighten.
2. Tubing rattle. 2. Tighten the pipe support.
3. Bent fan blade causing vibration. 3. Replace blade.
4. Fan motor bearings worn. 4. Replace motor.
37
COMPRESSOR 80061402 80061408 80061411 80061414 80069717 80069720 80069723 80069726 80069729
COMPRESSOR CONTACTOR 80009857 80009861 80009861 80009863 80009863 80009865 80009865 80009865 80009867
CAPACITY UNLOADER KITS NIL NIL NIL NIL 80057700 80057700 80057700 80057700 80057700
COND. FAN MOTOR 80022715 80023704 80023703 80023703 80023703 80023703 80023703 80023703 80023703
COND. FAN MOTOR CONTACTOR 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851
FILTER DRYER 80053141 80053142 80053142 80053142 80053142 80053142 80053117 80053117 80053117
FILTER DRYER CORE 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765
SIGHT GLASS 80020000 80020001 80020001 80020001 80020001 80020001 80020004 80020004 80020004
MECHANICAL SHUT OFF VALVE 80070540 80070541 80070541 80070541 80070541 80070541 80070542 80070542 80070542
PUMP DOWN SOLENOID VALVE 80070520 80070521 80070521 80070521 80070521 80070521 80070660 80070660 80070660
PRESSURE GAUGE - SUCTION 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030
PRESSURE GAUGE - DISCHARGE 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031
PRESSURE GAUGE - OIL NIL NIL NIL NIL 80060030 80060030 80060030 80060030 80060030
ADJ. HIGH PRESSURE SWITCH 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730
MICROSMART CONTROLLER 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645
USER INTERFACE CARD 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650
PTC TEMP. SENSOR 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655
RELATIVE PRES. TRANSDUCER -DP 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656
RELATIVE PRES. TRANSDUCER -OIL NIL NIL NIL NIL 80064657 80064657 80064657 80064657 80064657
RELATIVE PRES. TRANSDUCER -SUCTION 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658
MODEL NUMBER CNX720F CNX840F CNXM00F CNXM10F CNXM20F CNXM40F CNXM60F CNX2M00F CNX2M40F
COMPRESSOR 80069732 80069732 80069735 80069738 80069729 80069732 80069735 80069735 80068318
COMPRESSOR CONTACTOR 80009868 80009868 80009865 80009865 80009867 80009868 80009865 80009865 80009851
CAPACITY UNLOADER KITS 80057700 80057700 80057700 80057700 80057700 80057700 80057700 80057700 NIL
COND. FAN MOTOR 80023703 80023703 80023700 80023700 80023700 80023700 80023700 80023700 80023700
COND. FAN MOTOR CONTACTOR 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851
FILTER DRYER 80053117 80053117 80053113 80053113 80053117 80053117 80053117 80053117 80053113
FILTER DRYER CORE 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765
SIGHT GLASS 80020004 80020004 80020005 80020005 80020004 80020004 80020004 80020004 80020005
MECHANICAL SHUT OFF VALVE 80070542 80070542 80070543 80070543 80070542 80070542 80070542 80070542 80070543
PUMP DOWN SOLENOID VALVE 80070660 80070660 80070509 80070509 80070660 80070660 80070660 80070660 80070509
PRESSURE GAUGE - SUCTION 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030
PRESSURE GAUGE - DISCHARGE 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031
PRESSURE GAUGE - OIL 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 NIL
ADJ. HIGH PRESSURE SWITCH 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730
MICROSMART CONTROLLER 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645
USER INTERFACE CARD 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650
PTC TEMP. SENSOR 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655
RELATIVE PRES. TRANSDUCER -DP 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656
RELATIVE PRES. TRANSDUCER -OIL 80064657 80064657 80064657 80064657 80064657 80064657 80064657 80064657 NIL
RELATIVE PRES. TRANSDUCER -SUCTION 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658
38
Compressor 2% 1% 3% 2%
HPS/Sensor/Transducer 2 1 3 2
Expansion valve 1 0.5 2 1
Filter drier 2 1 3 2
Heater-crankcase 3 1 4 2
NOTE : When ordering spare parts, please quote the complete model number on the unit nameplate.
39
Run test all motors and check the amperage, abnormality etc. X
Run test compressors and check the amperage, noise, oil level, pressure
etc. and correct them accordingly. X
Check the thermostat/control devices for correct operation, calibrate/
re-adjust as required. X
SPECIAL : Manifold gauge set, R-134a charging cylinder, belt tension checker, leak detector, vacuum pump with
electronic gauges, thermometer & hook type ammeter/voltmeter/ohmmeter.
40
41
42
43