You are on page 1of 6

REQUIRED QUANTITY: 2

CABINET TYPE TRANSFORMER SPECIFICATIONS

Electric specifications

Rating in 500 KVA


____________ No. of Phases: 3 PHASE
_____________ Cycles: 60 HZ
_____________
KVA:

temperature rise Impedance: ± 7.5%,


________ %

Winding: X
______ 65°C ______55°C _

Primary Voltage: X
________ 13,200
Delta ________line – line ________ Grd Y/ _________ line – earth

Primary BIL: _____ 60kV _____ 75kV X


_____ 95kV _____ 125kV _____ 150kV Other: __________

2.5% +2 -2
Primary TAPS: ______ +/-2 – 2 ½% ______ -4 –2 ½% ______ No other: ____________________

Voltage _____ 240 Delta (3 wires) ______ 480 Delta (3 wires) _____ 208 Y/120 (4 wires)
Secondary:
X
_____ 480 Y/277 (4 wires)

Secondary BIL: X
______ 30KV Other: ________
Primary and Secondary Connections

______ LoopFeed______ double Loop Feed ______ Radial


Feed Configuration X

Other: ____________________

Construction: ______ live front X


______ dead front

Primary Terminals: _____ well only _____


X well and inserted terminal

_____ Integral load break terminal _____ Porcelain Terminal with Eye Bolt

Terminal BIL x
____ 60KV ____ 75KV ____ 95KV ____ 125KV ____ 150KV
Primary:
Other: ____________

Capacity of the
Radial FeedPrimary:
x
_______ 200 Amp. ___ 400 Amp. _______ 600 Amp. Other:___________
Primary and Secondary Connections (continued)

Primary Switch
Manual oil:
x ON/OFF Radial
______ ______ Ring (2 Int. – on/off) Other: _____________

Switch location in Switch Handle


Primary Compartment: Operated by Insulating Rod:
x
x
_____ YES _____ NO ____ YES ____ NO

x
Primary Fuse Type: _____ Bayonet (oil immersed) _____ Bayonet in series with current limiting fuse
(range
partial)

_____ Removable internal fusible _____ current limiting fuse


element in dry well

Other: ___________________________

Mechanical interlock
between fuses
Number of Primary Fuses: 3
__________ switches:

x
______ YES ______ NO

Number of Fuses Included Removable Fuses with


Replacement: Insulating Rod:
__________ ______ YES ______ NO

x
Secondary Terminal: _____ NEMA spade type _____ Copper Threaded Stud Other:______________

Construction and Finish


Core Arrangement/

Winding: ______ of 5 segments Other: ______________________

HV winding: x
_____ Copper ____Aluminum LV winding: x
______ Copper ______ Aluminum

Insulating Oil: x
____ Mineral Oil ____Silicone ____ Flame retardant fluid Other: ______________

YES x YES ______ NO


Self Cooled: x
______ PCB free: ______
______ NO

Vacuum Filled: x
______ YES 7-15
______psig
Tank specified for:
______ NO

Applicable Standards: X
_______ IEEE C57.12.28 X
_______ IEEE C57.12.29 Other: ______________________

Composition of the _______ Mild steel ______ 304 stainless steel Other: ANSI C57.12.29.
__________________
Cabinet:

_______ Carbon Steel ______ 409 stainless steel


Finish: ______ ANSI Color 61 X
_____ Munsell 7GY 3.29/1.5 Other: __________________

(Light grey) (Green)

Accessories

X
______ Drain and sampling valve X
______ vacuum pressure gauge X
______ Information Plate
stainless steel

X
______ Labeled “No PCBs” X
______ 1” filler cap
X
______ Thermometer

X
______ Ground connection X
______ pressure relief valve
______ security labels
NEMA

X
______ Hoisting hooks X
______ spare fuses
X
______ Oil gauge
Test Result

Oil Tests** Transformer Tests Test Report

_____________________________ASTM D 877 ______ IEEE C57.12.00 ____ oil test report

_____________________________ASTM D 974 ______ IEEE C57.12.90


____ Transformer test report

_____________________________ASTM D 1500 ______ Others

____ Factory test report

_____________________________ASTM D 1524

____ Short Circuit Current Calculations


_____________________________ASTM D 924

**Fill with the values of the results


____ Others