You are on page 1of 12

UNM IT/Telecommunications

Guide Specification
Labeling 11/07/08
27 0553
 
Labeling
27 0553
1 PART 1: GENERAL
1.01 SCOPE OF WORK
A. Work covered by this Section shall consist of furnishing labor, equipment, supplies,
materials, and testing unless otherwise specified, and in performing the following
operations recognized as necessary for the labeling of the telecommunications
infrastructure as described on the Drawings and/or required by these specifications.
B. It is the intent of the University to create a Class 3 system of administration as per
current ANSI/TIA/EIA 606 Standards. As such, all elements must be labeled with
unique identifiers as described in the following sections. UNM’s labeling layout
uses a “from/to” format in labeling.
C. This section includes minimum requirements for the following:
1. Labeling Communications Cabling
2. Labeling Closet Hardware
3. Labeling Work Stations

2 RELATED SECTIONS
A. Division 27, Section 270528 Pathways for Communication Systems.
B. Division 27, Section 270553 Identification for Communication Systems.
C. Division 27, Section 271116 Communications Cabinets, Racks, Frames, and
Enclosures.
D. Division 27, Section 271119 Communications Termination Blocks and Patch
Panels.
E. Division 27, Section 271123 Communications Cable Management and
Ladder Rack.
F. Division 27, Section 271313 Communications Copper Backbone Cabling.
G. Division 27, Section 271323 Communications Optical Fiber Backbone
Cabling.
H. Division 27, Section 271333 Communications Coaxial Backbone Cabling.
I. Division 27, Section 271513 Communications Copper Horizontal Cabling.
J. Division 27, Section 271523 Communications Optical Fiber Horizontal
Cabling.
K. Division 27, Section 271533 Communications Coaxial Horizontal Cabling.
L. Division 27, Section 271543 Communications Faceplates and Connectors.

3 PART 2 - PRODUCTS
3.01 LABELS
 

A. Follow current Telecommunication Design Methods Manuel (TMDD) Connecting


Hardware Identification Color Coding standard.

 
Page  1  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 
B. The size, color and contrast of all labels should be selected to ensure that the
identifiers are easily read.
C. All labels are to be mechanically printed, no hand printed labels allowed for any
component.
D. Labels should be visible during the installation of and normal maintenance of the
infrastructure. Labels should be resistant to the environmental conditions at the
point of installation (such as moisture, heat or ultraviolet light) and should have a
design life equal to or greater than that of the labeled component.
E. Provide vinyl substrate with a white printing area and black print. If cable jacket is
white, provide cable label with printing area that is any other color than white,
preferably orange or yellow – so that the labels are easily distinguishable.
F. Labels shall be flexible vinyl or other substrates to apply easy and flex as cables
are bent.
G. Labels shall use aggressive adhesives that stay attached even to the most
difficult to adhere to jacketing.

4 PART 4: EXECUTION
4.01 LABELING INSTALLATION
A. Horizontal Copper Cable Labeling:
1. All horizontal cables shall be labeled with self-laminating marking tape, Brady
ID-Pro labeler, Panduit LS7 labeler, or equivalent labeling system. Identification
shall be as follows:
2. At the TR end, the cables shall be labeled with the location of where the other end
of the cable is terminated including room number, TO number, and jack position.
Place label on a visible part of cable within 12” of termination point for ease of
identification after termination.
a. Example: Two cables going to room 114, first TO, first jack position
would be labeled as: 114-1A1. The second cable in the second TO, third
jack position would be 114-2A3.

         Cable  1          114-­‐1A1                
   
         Cable  2          114-­‐2A3                
   
               
               
3. At the TO end, the cables shall be labeled 4” from termination with the following:
Data .TR. Rack. Patch Panel. Port. This shall be visible by removing outlet cover
plate.
a. Example: Data, TR Room 114, rack 1, patch panel 1, port 03 would be:
D.114. 1.1.03

         Cable  1            
D.114.1.1.03          
   
 
Page  2  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

               

b. For voice cabling in older building with separate voice closets and no
patch panels, include the TR and as much information as practical such as
column, row, block number, and port number or pairs.
i. Example: TR room 105, on a 110 block in the first column, third
row down, port 4 would be: V.105.1.3.04

C1   C2   C3   C4   C5  
           
                     

R1                      
         
                     

R2                      
         
                     

R3                      
         

ii. Example: TR room 105, no discernable pattern of columns or rows


or ports, and/or mixed environment of 110 and 66 blocks, the label
could be: V.105.E wall.24/25.

                        110  
             
  66     66                  
                                         
                        66    
       
110                            
                   
                             
 
Page  3  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

4. For CATV coaxial drop cables, at the splitter or tap, the cables shall be labeled
with the location where the other end of the cable is terminated including room
number, TO number, and jack position. If not collocated with a TO, indicate room
number at a minimum. Place label on a visible part of cable within 12” of
termination point for ease of identification after termination
a. Example: A cable going to room 114, first TO, sixth jack position would

    CATV       C.114.1A6      

be labeled as: C.114.1A6.

b. Generally speaking, coaxial cables will be in the sixth position when


collocated with a standard TO.

5. For coaxial cables at the TO, they shall be labeled 4” from termination with the
words “From Room” and the room number where the splitter or tap is. This shall
be visible by removing outlet cover plate.
a. Example: Room 115 would simply be: From Rm 115.

    CATV       From  Rm  115      

B. Telecommunications Outlet (TO) Labeling Scheme:


1. TO’s are labeled alphanumerically in a clockwise rotation around the room.
Typically, the first TO located to the left of the main entrance of the room is
labeled 1A, followed by 2A, 3A, etc. Where two entrances are present, designate
one as the main entrance and label accordingly.
a. The intent is to have unique identification for each TO. The starting
point and nomenclature of the TO’s are irrelevant to the location inside
the room.
2. Floor box TO’s are to be prefaced with “FB” to read FB1A, FB2A, etc. Wireless
Access Point TO’s in ceilings are to be prefaced with “WAP” to read WAP1,
WAP2, etc. Overhead projectors in ceilings will have the designation of “AVP”.
Elevators to be prefaced with “Elev” to read Elev1.

3. On subsequent TO installations, the TO will be labeled alphanumerically


depending on the new TO is. If the new TO is between 1A and 2A, the new TO
would be labeled as 1B. If another one is later added between 1B and 2A, it
would be labeled 1C. If it is after the last TO in the room, 3A, it would be labeled
4A.
 
Page  4  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

                       
          ▲ ▲ ▲ ▲      
        1B   1C   2A    2B    
           
    ◄ 1A            
                   
           
               

4. Seek clarification from UNM Telecommunications for any labeling issues that
arise.

C. Faceplate Labels:
1. Faceplates will be labeled using the plastic insert to cover a printed identification
tag. Each of the 2 labels in a faceplate are meant to have 2 lines for a total of 4
individual lines per faceplate.
2. The TO label will vary slightly depending on whether a unified cabling platform
is used where all cables go to one TR, or separate voice and data closets are used.
3. See addendum 1 for an example of the new UNM Telecommunications labeling
on a faceplate with unified cabling.
4. See addendum 2 for an example of the old UNM Telecommunications labeling on
a faceplate.
5. See addendum 3 (1) for an example spreadsheet in MS Excel with dimensions for
the labels.
a. Line 1 contains the preface “D” for Data, the specific TR, rack, patch
panel, and the range of ports used for termination. In case of separate
voice and data closets, only the data information is conveyed here.
i. Example: For cables going to TR Room 114, rack 1, patch panel 1,
ports 3-5, line 1 would read: D.114.1.1.03/05.
b. Line 2 also contains information regarding where cables are terminated in
the closet, but is used for subsequent cable installations to that specific
TO.
i. Example: Another 3 cables were added to the same TO at a later
date. For cables that go to TR Room 114, rack 3, patch panel 3,
ports 22, 23 and 24, line 2 would read: D.114.3.3.22/24
c. Line 3 is only used if separate voice and data closets are being used. Line
3 contains the preface “V” for Voice, the TR, and the TO number and jack
position.

 
Page  5  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 
d. Line 4 is the unique identifier for the TO. It contains the UNM Building
number, the room that the TO is located in, and the alphanumeric
designation of the TO as per section 4.01.B.
i. Example: A TO in room building 255, room 114, designated as 2A
would be: 255-114-2A.

D. Horizontal 110 and 66 Block Labeling for voice:


1. For 110 blocks, if the cables are for room terminations label the appropriate
corresponding space for the port with the room number, TO, and jack position.
a. Example: A cable going to room 114, first TO, first jack position would be
labeled as: 114-1A1. A cable in the second TO, third jack position would be
114-2A3.
2. For 66 type blocks, if the cables are for room terminations tag the cable with the
room number, TO, and jack position with a loose paper tag with string that is
easily accessible and readable.
a. Example: A cable in room 114, first TO, first jack position would be labeled
as: 114-1A1. A cable in the second TO, third jack position would be 114-2A3.
3. If the 110 block is for the tie cable between the voice patch panel in the rack and
the wallboard, label the space corresponding to the port with the rack, patch panel
and port information as per section 4.01.E.2. For tie cables between the rack and
wallboard a 110 block should always be used.
a. Example: Rack 1, patch panel 1, would be: Rack1 Voice PP1.
b. See addendum 3 (2) for an example label.

E. Patch Panel Labeling:


1. For station cabling going to a TO, label each port on the patch panel with the
room number, TO, and jack position.
a. Example: A cable in room 114, first TO, first jack position would be labeled
as: 114-1A1. A cable in the second TO, third jack position would be 114-2A3.
b. Example: A cable going to a floor box TO labeled FB1A in room 114 in the
second jack position would be labeled as: 114-FB1A2
2. For voice patch panels connected to a 110 block within the TR, label each port on
the voice patch panel with the corresponding 110 block source information as per
section 4.01.D.3.
a. Example: A 110 block in the first column, third row down, port 4 would be:
1.3.04
3. Due to amount of space allocated for TO designation on patch panels, place room
number on top and TO on bottom.
a. See addendum 3 (3) for an example label.
 
Page  6  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

F. Equipment Room:
1. Equipment Racks shall be labeled with an (1”) one inch self-laminating marking
tape, Brady ID-Pro labeler, Brother P-touch labeler, or equivalent labeling system
at the base of the rack. Starting in front of the equipment rack, left to right,
identification shall be as follows: Rack 1, Rack 2, and Rack 3.
2. Patch panels shall be labeled with a self-laminating marking tape, Brady ID-Pro
labeler, Brother P-touch labeler, or equivalent labeling system. Starting from top
to bottom in sequence. Place label on the left side of the patch panel vertically,
identification shall be as follows: PP 1, PP 2, PP3, and so on.

G. Vertical/Riser/Intrabuilding Copper Cable Labeling:

1. All riser cables shall be labeled with self-laminating marking tape, Brady ID-Pro
labeler, Panduit LS7 labeler, or equivalent labeling system.
2. At the TR, the copper riser cables shall be labeled with from/to, cable count, and
pair information on both ends. Place label on a visible part of cable close to
wiring block for ease of identification after termination.
a. Example: From ER B065 to TR 114, first of 2, 100 pair cables would be:
ER B065 to TR114 1-100. The second 100 pair cable between the rooms
would be ER B065 to TR114 101-200.
3. Label cabling every 50’ along the length of the cable in open trays, and on each
side of wall penetrations

H. Vertical/Riser/Intrabuilding Fiber Cable Labeling:


1. All riser cables shall be labeled with self-laminating marking tape, Brady ID-Pro
labeler, Panduit LS7 labeler, or equivalent labeling system. Identification shall be
as follows:
2. At the TR, the fiber riser cables shall be labeled with from/to, fiber type, and fiber
count on both ends. Place label on a visible part of cable/innerduct close to fiber
distribution unit (FDU) for ease of identification after termination.
a. Example: From ER B065 to TR 114, first cable, would be: ER B065
to TR114 24sm/24mm.
b. If a second fiber bundle between the rooms is installed with the same fiber
count, place a (F2) and the end of the label.
i. Example: From ER B065 to TR 114, second cable, would be: ER
B065 to TR114 24SM/24MM. (F2)
3. Label cabling every 50’ along the length of the cable in open trays, and on each
side of wall penetrations.

 
Page  7  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

I. Vertical/Riser/Intrabuilding 110-Block Labeling


1. At the ER and TR, voice riser cables are terminated on their respective 110
blocks. Label each pair on each row of 110 blocks with the matching pair
count information.
2. Place the entire cable label of “from/to” in the center of the 110 block label as
per section 4.01.G.
3. See addendum 3 (4) for an example label.

J. Coax trunk Labeling (CATV)


1. CATV coaxial trunk cables shall be labeled at each termination point with the
information indicating the location of the next termination point of the cable,
such as an amplifier, DCT, splitter, or tap.

K. Vertical/Riser/Intrabuilding and Campus Fiber FDU labels

1. Labels shall indicate type of fiber (single mode or multi-mode 50µm or 62.5
µm), from/to information, pair count, loss for each strand, and length of cable.
2. See addendum 3 (5) for an example label.

L. Interbuilding/Campus/Backbone Copper and Fiber Cable Labeling:


1. All interbuilding cables shall be labeled permanently with from/to
information, cable type and size, installation date, and installing contractor at
each end.
a. Example: From Bldg 256 to Bldg 203, a 200 pair copper cable,
installed by Lobo Enterprises on September 22, 2008 would be:
From Bldg 256 to Bldg 203 (200 Pair)
Lobo Enterprises 9/08.
b. An as-built is to be provided to UNM Facilities of which manhole, and
pull-boxes the cable passes through.

 
Page  8  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 
Addendum 1:

 
Page  9  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 
Addendum 2

 
Page  10  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 
Addendum 3 (1): MS Excel with dimensions for the labels.

Dimensions: Row = 16, Column = 21, Font Arial 10


Alignment: Rows 1 and 3 vertical bottom, horizontal center
Alignment: Rows 2 and 4 vertical top, horizontal center

1 D.101.1.1.12/13 D.101.1.1.14/15 D.101.1.1.16/17 D.101.1.1.18/19


2 D.101.1.2.03 D.101.1.2.04

3 V.101.1A3 V.101.2A3 V.101.3A3 V.101.4A3


4 255-114-1A 255-114-2A 255-114-3A 255-114-4A
Row

Addendum 3 (2): 110 block labeling for voice patch panels.

Addemdum 3 (3): Patch panel labeling.

Addemdum 3 (4): Copper riser labeling.

 
Page  11  of  12  
 
UNM IT/Telecommunications
Guide Specification
Labeling 11/07/08
27 0553
 

Addemdum 3 (5): High pair count labeling

   

 
Page  12  of  12  
 

You might also like