The work of “Extension of 1no New 110KV EHT Service at Pelakuppam Village for a maximum
demand of 10500KVA to M/s Cheyyar SEZ Developers, Near Plot No:A1, Sipcot Industrial Park,
Pelakuppam Village, Tindivanam, Villupuram District” was administratively approved and technically
sanctioned vide reference (2) and (3).
Based on that M/s.Cheyyar SEZ Developers, have paid the amount of Rs.4,31,65,980/- on
21.08.2023 vide Doc.No.2350850561.
M/s.Cheyyar SEZ Developers, has submitted the switchyard layout, equipments and panels
drawings for scrutiny. The remarks for the C & R panel drawings was received from P&C wing and the
same is herewith forwarded.
1. The drawings are generally found in order.
2. Any modification as stated by field TANTRANSCO engineers during commissioning shall be
incorporated,
3. The equipments shall be fixed 20CMs above the gland plate,
4. Any wire to Trip circuit may be identified with Red color sleeve.
5. Mixing of DC -1 and DC – 2 circuits should be avoided and the system has to be designed
accordingly.
6. Lugs for CRP wiring should be of suitable size Ring Type.
7. 3 sets of A3 Size as manufacture drawings of CRP should be provided along with the panel.
8. All the CT/PT TB should be of disconnecting type.
9. Contactors and contact multiplication relays should be industrial grade suitable for substation
environment application and of reputed manufacturers only and type tested.
10. Most of the auxiliary relay, Trip relays are ABB Make which require special ABB Make Crimping
tool, ABB Make extractor for wire removal. Hence one number ABB Make Crimping tool, 1 No
extractor and sufficient lugs to be supplied along with Panel.
11. All the Manual related to Main relay, Backup relay, BCU, Aux relay, EM and Switches etc to be
supplied along with the panel- 3 Sets Hard copy+ 1 set Soft copy
12. For download/upload the setting, Disturbance Recorder, Event list, RS 232 to USB
Communication cable is required for P442 Line Distance relay. Hence 1 No MOXA make RS232
to USB Converter shall be supplied along with the panel.
13. 1 No of RXMVB-2 and 1 No RXPSU-14n ABB Make relay with sufficient NO/NC shall be
supplied as spare along with the panel.
14. Tri Vector meter to be configured for CT Ratio and VT Ratio.
15. Construction:
a. Paint thickness min 70 microns.
b. Door Hinges shall be minimum 3 Nos.
c. All cable entries should be through cable glands hermitically sealed and rodent proof.
d. TB wise wiring schedule should be included in drawing.
e.The colour of the panel shall be following choice for new station.
Exterior - stoved enamel grey
Interior - stoved enamel white
Bus frame - stoved enamel black
Finish - glossy surface treatment shall be done as per BIS.
f. Labels to be provided at front and rear of the panel for each device.
g. Name plate to be provided on the top of each panel on front, large and bold name plates
shall be provided for circuit / feeder designation
h. Name plate and labels shall be made of non rusting metal or 3 ply lamicoid.
i. Wire termination shall be made with solder less crimping type and tinned copper lugs,
which firmly grip the conductor. Insulated sleeves shall be provided at the wire
terminations.
sufficient height (150mm )to be maintained for terminal block from the
gland plate
Push button to be given for Trip reset and LED Reset in Main P442 and
P141 Back up relays
In CT, core 1 used for Metering purpose, core 2 used for Distance
6 protection and core 3 used for backup protection with adopted ratio of
600/1A to be mentioned.
P442 relay Input wired from Carrier Selector switch IN position only.
15 Carrier OUT position to be wired and Auto Reclosure selector switch
IN/OUT position also to be wired.
Function blocking signal wired from Distance relay to Backup relay and
20&27
Back relay to Distance relay.
31&32 Isolation link to be provided for Trip coil 1 and Trip coil 2.
96 Master trip relay for Busbar protection and 86 UF Master trip relay
for Under frequency protection to be provided and corresponding wiring
to be done.
195,295 TSR-B Type relay is not accepted for Trip circuit supervision,
31&32
RXTCS may be proposed for Trip Circuit Supervision.
Line earth switch open position to be added (89LE ) For line isolator
34
close operation (89L)
Separate Annunciation window allotted for SF6 low, SF6 Lockout ,96
42
operated and 86UF operated.