INSTRUMENT TR ANSFORMERS

CLE
Indoor or outdoor current transformer

The CLE is primarily used for high


current metering on low voltage
systems and is available in single or
dual ratios. It can be used with
uninsulated bus bar or cable up to
600 volts, or with insulated primary
conductors at higher voltages.

Product features no wires are connected. This safety feature avoids dan-
• 600 volt, indoor or outdoor gerous voltages across the secondary terminals if the
• 10 kV BIL, 25 - 400 Hertz primary is energized. The center post also serves as a
• 8.25" (210 mm) window opening third terminal on dual ratio transformers.
• Window plates and bar-types available
Primary
Application The large 8.25" (210 mm) window allows for multiple
The CLE is primarily used for high current metering on primary conductors. Optional Micarta® window plates
low voltage systems and is available in single or dual are available to change the window opening to a cruci-
ratios. It can be used with uninsulated bus bar or ca- form configuration for direct bus bar sleeve mounting.
ble up to 600 volts, or with insulated primary conduc-
tors at higher voltages. Mounting
Optional two-piece mounting feet are constructed of
Construction and insulation corrosion-resistant aluminum. The CLE may also be se-
The ring-type core and fully distributed winding are cured to a wall panel or bracket by using mounting
assembled to a glass filled polypropylene window holes in the transformer body.
liner and injection molded in thermoplastic rubber.
The thermoplastic rubber insulating material is per- Test reports
manently molded to the core and coil assembly, re- Test reports are stored electronically and can be
sulting in a compact unit with excellent mechanical, e-mailed in various formats at the time of shipment.
thermal, and dielectric characteristics.
Standards
Secondary terminals and cover This unit meets or exceeds all requirements of IEEE
The CLE is supplied with large compression-type ter- C57.13-2016 and can be tested to other standards as
minals with slotted head screws, a short circuit de- requested.
vice, and a clear, rectangular snap-on cover suitable
for locking with a meter seal. This clear plastic cover UL Recognized Component
allows a visual check of connections and is keyed to The CLE is a UL Recognized Component (file number
ensure the shorting clip is across the terminals when E96461).
Dimensions (inches [mm])

1.31
[33]
2.63
[67]
X1 X2

1.31
[33]
INSTRUCTION
PLATE

SECONDARY
PRIMARY POLARITY MARKER COMPRESSION TYPE
POLARITY MARKER SECONDARY TERMINALS
3.00
FOR #14 TO #3 WIRE
[76]
HOLES FOR
.38 MOUNTING BOLTS
4-TOTAL
12.88
[327]

4.125
11.38
[105] [289]
I A
5D RATING
8.2 ] DECAL
10
[2 BOTH
4.125 SIDES
[105] 5.69
[144]

4.13 4.13
[105] [105]

4.88 4.88
[124] [124]

11.38
[289]
.31 [8] DIA HOLE
4-TOTAL

D C B A

A
A B C D THK
B
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm)
C
D 3.374 86 5.374 137 8.25 210 9.50 241 0.125 3

Window plate

4.81 [122]

1.31
1.88
[33]
[48]

2.12
.44 [11] WIDE SLOT [54]
3.18 [81] .13
[3]
4.13 [105] 4.13 [105]

.44 HOLE .63


4-TOTAL [16]
2.19
[56]

9.63 [244] .06 RATIO


APPROX.

One-piece base
Selection guide: CLE with metering accuracy
Style number
Primary Rating factor IEEE metering without with two-piece with
ampere rating 30°C 55°C accuracy @ 60 Hz hardware mounting feet window plates
2000 2.0 1.5 0.3B-0.9 7524A63G01 7524A64G01 7524A66G01
3000 2.0 1.5 0.3B-1.8 7524A63G02 7524A64G02 7524A66G02
4000 1.5 1.2 0.3B-1.8 7524A63G03 7524A64G03 7524A66G03
5000 1.33 1.0 0.3B-1.8 7524A63G04 7524A64G04 7524A66G04
6000 1.0 0.75 0.3B-1.8 7524A63G05 7524A64G05 7524A66G05
1000/2000 3.0/2.0 2.2/1.5 0.3B-0.5/0.3B-0.9 7524A63G06 7524A64G06 7524A66G06
1500/3000 3.0/2.0 2.2/1.5 0.3B-0.5/0.3B-1.8 7524A63G07 7524A64G07 7524A66G07
2000/4000 2.0/1.5 1.5/1.2 0.3B-0.9/0.3B-1.8 7524A63G08 7524A64G08 7524A66G08
2500/5000 2.0/1.33 1.5/1.0 0.3B-1.8/0.3B-1.8 7524A63G09 7524A64G09 7524A66G09
3000/6000 1.33/1.0 1.0/0.75 0.3B-1.8/0.3B-1.8 7524A63G10 7524A64G10 7524A66G10

*Also available with NEMA 4-hole primary bar, baseplate, and other accessories. Contact your ABB sales representative or call +1-252-827-3212 for more information.

Dual rated CTs with metering and relaying accuracy are available upon request.

Selection guide: CLE with relaying accuracy

Primary Rating factor IEEE relaying Style number


ampere rating 30°C 55°C accuracy @ 60 Hz (no hardware)
2000 2.0 1.5 C50 923A696G01
3000 2.0 1.5 C100 923A696G02
4000 1.5 1.2 C100 923A696G03
5000 1.33 1.0 C100 923A696G04
1000/2000 3.0/2.0 2.2/1.5 C30/C50 923A696G06
1500/3000 3.0/2.0 2.2/1.5 C50/C100 923A696G07
2000/4000 2.0/1.5 1.5/1.2 C50/C100 923A696G08
2500/5000 2.0/1.33 1.5/1.0 C100/C200 923A696G09
*Also available with NEMA 4-hole primary bar, baseplate, and other accessories. Contact your ABB sales
representative or call +1-252-827-3212 for more information.Contact your ABB sales representative or call
+1-252-827-3212 for more information.
Dual rated CTs with metering and relaying accuracy are available upon request.

Optional accessories
Accessory Style number
Mounting feet (set of two with mounting hardware) 9628A05G27
Window plates (set of two with mounting hardware) 9628A05G28

1VAP428261-DB Rev E August 2021

— —
ABB Inc. We reserve the right to make technical We reserve all rights in this document and in
3022 NC 43 North changes or modify the contents of this doc- the subject matter and illustrations con-
Pinetops, NC 27864 ument without prior notice. With regard to tained therein. Any reproduction, disclosure
Phone: +1 252 827 3212 purchase orders, the agreed particulars to third parties or utilization of its contents
shall prevail. ABB does not accept any – in whole or in parts – is forbidden without
­responsibility whatsoever for potential er- prior written consent of ABB Inc.
rors or possible lack of information in this ­Copyright© 2021 ABB
document. All rights reserved
abb.com/mediumvoltage

You might also like