You are on page 1of 10

Filed with the Iowa Utilities Board on August 18, 2020, E-22439

Spec No.: ZTT 17-79999

TECHNICAL SPECIFICATION
Optical Ground Wire

October 24,
A Linda Miller Felix
2017

Version Date Prepared Reviewed Approved

Address: No.5, Zhongtian road, Nantong economic and technological development zone, Jiangsu Province, China
Tel: +86-513-89191138 Fax: +86-513-8359 9670 Zip code: 226010 Website: www.zttcable.com
Filed with the Iowa Utilities Board on August 18, 2020, E-22439

1.GENERAL
1.1 SCOPE

This specification covers Optical Ground Wire Cables (OPGW) for the installation on high
voltage overhead power lines. The cable contains optical fibers for data transmission and
telecom purposes and is installed instead of a ground wire.

The specification describes the basic design of an OPGW-cable with its main components: the
fibers, the optical fiber unit and the cable armoring. Furthermore this specification contains
information concerning the quality assurance during manufacturing, the final acceptance tests,
the type tests and the packaging. Any technical data mentioned in this product specification
serve for describing the product only and should not be understood as an assurance of
properties.

1.2 Cable Description

Cable which has the dual performance functions of a conventional ground wire with
telecommunication capabilities.

1.3 Quality

ZTT ensures a continuing level of quality in our cable products through several quality control
programs including ISO 9001.

1.4 Reliability

ZTT ensures product reliability through rigorous qualification testing of each product family. Both
initial and periodic qualification testing are performed to assure the cable's performance and
durability in the field environments.

1.5 Reference

The cable which ZTT offered are designed, manufactured and tested according to international
standards as follows:

IEC 60793-1 Optical fiber Part 1: Generic specifications


IEC 60793-2 Optical fiber Part 2: Product specifications
ITU-T G.652 Characteristics of a single-mode optical fiber cable
Characteristics of a non-zero dispersion-shifted single-mode optical fiber and
ITU-T G.655
cable
EIA/TIA 598 B Color code of fiber optic cables
Aerial optical cables along electrical
IEC 60794-4-10
power lines – Family specification for OPGW
Optical fiber cables-Part 1-2: Generic specification-Basic optical cable test
IEC 60794-1-2
procedures
IEEE Standard for testing and performance for optical ground wire (OPGW) for
IEEE1138-2009
use on electric utility power lines
IEC 61232 Aluminum – clad steel wire for electrical purposes
IEC 60104 Aluminum magnesium-silicon alloy wire for overhead line conductors
IEC 61089 Round wire concentric lay overhead electrical stranded conductors

www.zttcable.com All Rights Reserved Copyright © 2017 Page 2 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

2. OPTICAL FIBER
The optical fiber is made of high pure silica and germanium doped silica. UV curable acrylate
material is applied over fiber cladding as optical fiber primary protective coating. The detail data of
optical fiber performance are shown in the following table.

Optical fiber uses special spun device successfully controlled the value of PMD, and makes sure
that it can keep stable in cabling.

G.652D Fiber
Specifications
Category Description
After cabling

Attenuation @1310 nm ≤ 0.35 dB/km

Attenuation @1383 nm ≤ 0.35 dB/km

Attenuation @1490 nm ≤ 0.24 dB/km

Attenuation @1550 nm ≤ 0.20 dB/km

Attenuation @1625 nm ≤ 0.23dB/km


Attenuation vs Wavelength
1285-1330nm vs 1310nm ≤0.03 dB/km
1525-1575nm vs 1550nm ≤0.02 dB/km
Point Discontinuity
≤ 0.05 dB
1310nm
≤ 0.05 dB
1550nm
Zero Dispersion Wavelength 1304~1324 nm
Optical
Specifications Zero Dispersion Slope ≤ 0.092 ps/nm2∙km
Dispersion Value
≤ 3.2 ps/nm∙km
@1310nm
≤ 18 ps/nm∙km
@1550nm
≤ 22 ps/nm∙km
@1625nm
PMD Link value ≤0.06 ps/√km

Cable Cutoff Wavelength (λcc) ≤ 1260 nm


Macro bending Loss
(1 turns; Ф32 mm) @1550 nm ≤ 0.03 dB
(100 turns; Ф50 mm) @1310 nm ≤ 0.03 dB
(100 turns; Ф50 mm) @1550 nm ≤ 0.03 dB
(100 turns; Ф60 mm) @1625 nm ≤ 0.03 dB
Mode Field Diameter @1310 nm 9.2±0.4μm
@1550nm 10.4±0.5μm

Dimensional Cladding Diameter 125 ±0.5μm


Specifications Core/clad concentricity error ≤0.5μm

www.zttcable.com All Rights Reserved Copyright © 2017 Page 3 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

Cladding Non-Circularity ≤0.7%

Coating Diameter 245 ±5μm

Coating-Cladding Concentricity <12μm


Mechanical
Proof stress ≥0.69Gpa
Specifications
Temperature Dependence -60℃~85℃
≤ 0.05 dB/km
@1310nm,1550nm, 1625 nm
Temperature Humidity Cycling
-10℃~85℃ up to 98%H ≤ 0.05 dB/km
@1310nm,1550nm, 1625 nm
Environmental
Water Immersion 23±2℃
Specifications ≤ 0.05 dB/km
@1310nm,1550nm, 1625 nm
Heat Aging 85±2℃
≤ 0.05 dB/km
@1310nm,1550nm, 1625 nm
Damp Heat
≤ 0.05 dB/km
85℃ at 85%RH

www.zttcable.com All Rights Reserved Copyright © 2017 Page 4 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

3. CABLE STRUCTURAL DRAWING

Serial No: ZTT2017-79999

OPGW Cable Specifications Bid No: OPGW


ZhongTian

Cable Type: OPGW - 36G652-ALT-119 [102.5;106.5]

Cross Section: AS wire


Optical fibers and Gel
loose tube
FRP

Thermal barrier
AL-covered layer

Material No Material No. Material Dia.


Fiber G.652 36
OPGW AL tube 1 Inner-Dia. 6.20 Outer-Dia. 9.60 mm
Structure Layer1 20.3%AS wire 14 Diameter 2.65 mm

according to IEC60794-4-1, IEEE-1138 standards


Stranding direction of outer layer is left hand(S-Stranding)
Cable Diameter 14.90 mm
Cable Weight 652 kg/km
Supporting Cross Section 119.4 mm2
Section of AS Wire 77.22 mm2
Section of AL Tube 42.19 mm2

Rated Tensile Strength (RTS) 102.5 kN


Technical Data Modulus of Elasticity (E-Modulus) 124.5 kN/mm2
Thermal Elongation Coefficient 14.6 ×10-6/℃
Permissible Maximum Working Stress 686.8 N/mm2
Everyday Stress(EDS) 137.4 ~214.6 N/mm2
DC Resistance 0.418 Ω/km
Short Time Current ( 1s ) 10.3 kA
2
Short Time Current Capacity I(Ambient=40℃)
t 106.5 kA2S
Minimum Bending Radius: Installation: 298 mm
Operating: 223 mm
Temperature Installation -10℃ ~ +50 ℃
Range: Transportation and Operation -40℃ ~ +80 ℃
Remarks: All Sizes and Values are Nominal Values
Diameter Tolerance: ±1%; Weight Tolerance: ±2%;
Rev. ZECT-TD Designer linda.cai Authorized Miller Zhang 2017/10/23

www.zttcable.com All Rights Reserved Copyright © 2017 Page 5 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

4. COLOR IDENTIFICATION OF FIBER IN OPGW


4.1 Color code of fiber in OPGW shall be identified referring to the following table:

Typical number of fiber: 36

Fiber units Fiber No. & Color


1 2 3 4 5 6
Blue Orange Green Brown Gray White
Blue tube
7 8 9 10 11 12
Red Black Yellow Violet Pink Aqua
13 14 15 16 17 18
Blue Orange Green Brown Gray White
Orange tube
19 20 21 22 23 24
Red Black Yellow Violet Pink Aqua
25 26 27 28 29 30
Blue Orange Green Brown Gray White
Green tube
31 32 33 34 35 36
Red Black Yellow Violet Pink Aqua

www.zttcable.com All Rights Reserved Copyright © 2017 Page 6 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

5. TEST REQUIREMENTS FOR OPGW


5.1 General

There are different test series to assure the quality of OPGW:

 Routine test (in–process testing according to internal quality plan)

 Factory acceptance test (FAT, witnessed by customer)

 Type test (only in case of a basic new design, repetition in exceptional cases)

OPGW tests shall be in accordance with applicable standards or agreements between purchaser
and manufacturer.

As a general rule the tests will be performed according IEC 60794-4-10.However, if necessary
tests can be done according to IEEE Std1138.

Type test

Type test may be waived by submitting maker’s certificate of the similar product performed in an
internationally acknowledged independent test organization or laboratory. If type test should be
performed, it will be carried out according to an extra type test procedure reached to an
agreement between purchaser and manufacturer.

Routine test

The optical attenuation coefficient on all production cable lengths is measured according to IEC
60793-1-CIC (Back-scattering technique, OTDR). Standard single-mode fibers are measured at
1310nm and at 1550nm. Non-zero dispersion shifted single–mode (NZDS) fibers are measured
at 1550nm.

Factory test

Factory acceptance test is carried out on one sample per order in the presence of the customer
or his representative. The requirements for quality characteristics are determined by relevant
standards and agreed quality plans.

5.2 Test items

The following table shows that the test items will be carried out according to corresponding
references.

www.zttcable.com All Rights Reserved Copyright © 2017 Page 7 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

Routine FAT Type Test Test Procedure

Test on fibers

Mode field diameter IEC 60793-1-45


Geometric parameter IEC 60793-1-20
Attenuation (OTDR) ● ● IEC 60793-1-40
Chromatic dispersion IEC 60793-1-42
Cut-off wavelength (cable cut off) IEC 60793-1-44

Test on wires before stranding

Diameter ● ● IEC61232/ IEC60104


Tensile strength ● ● IEC61232/ IEC60104
Stress at 1% extension(Only ACS wire) ● ● IEC61232
Elongation at break ● ● IEC61232/ IEC60104
Wrapping test(Only AA wire) ● ● IEC60104
Conductivity ● ● IEC61232/ IEC60104
Thickness of Al-cladding (Only ACS wire) ● ● IEC61232
Torsion test (Only ACS wire) ● ● IEC61232

Tests on OPGW

Quality of surface ● ● IEC 60794-4-10


Direction of lay outer ● ● IEC 60794-4-10
Lay length ● ● IEC 60794-4-10
Diameter of cable ● ● IEC 60794-4-10
Weight of Cable ● ● IEC 60794-4-10
DC-resistance ● IEC 60794-4-10
Breaking strength test ● ● IEC 60794-4-10
Stress Strain Test ● IEC 60794-4-10
Tensile performance test ● IEC 60794-4-10
Sheave test ● IEC 60794-4-10
Aeolian vibration simulation ● IEC 60794-4-10
Galloping test ● IEC 60794-4-10
Creep test ● IEC 60794-4-10
Temperature cycle test ● IEC 60794-4-10
Water penetration ● IEC 60794-4-10
Short circuit current test ● IEC 60794-4-10
Lightning test ● IEC 60794-4-10

Notes: The mark “●” means different test items which belongs to different test series.

www.zttcable.com All Rights Reserved Copyright © 2017 Page 8 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

6. PACKING AND DRUM


OPGW shall be wound round a non-returnable wooden drum or iron-wooden drum. Both ends of
OPGW shall be securely fastened to drum and sealed with a shrinkable cap. The required
marking shall be printed with a weatherproof material on the outsides of drum according to
customer’s requirement.

Outside diameter

Inside diameter

Wooden
Wooden strip seal
Iron

Inner tub
Iron

Drum diameter

Arbor hole
Iron

Flange diameter
D
d

b
B A

www.zttcable.com All Rights Reserved Copyright © 2017 Page 9 of 10


Filed with the Iowa Utilities Board on August 18, 2020, E-22439

Drum Dimensions & Weights


Cable Diameter Drum Length
D b B d A weight
(mm) (m)
cm cm cm cm cm kg

2000 130 90 110 80 10.5±0.5 210

3000 140 90 110 80 10.5±0.5 220


14.5-15.0
4000 150 90 110 80 10.5±0.5 230

5000 160 90 110 80 10.5±0.5 250

www.zttcable.com ALL Rights Reserved Copyright © 2017 page 10 of 10

You might also like