You are on page 1of 4

INSTRUMENT TR ANSFORMERS

KOT-60, -75, -11, and -15


Outdoor current transformers

The KOT-60, -75, -11, and -15 outdoor


current transformers are designed
for high current metering and
relaying. All ratios are available with
a 3.25" diameter primary opening or
primary spade terminals.

Product features is positioned on a center post located midway


• KOT-60: 5 kV, 60 kV BIL; KOT-75: 8.7 kV, 75 kV BIL between the terminals. The center post also serves as
• KOT-11: 15 kV, 110 kV BIL; KOT-15: 25 kV, 150 kV BIL a third terminal on double ratio transformers.
• Outdoor, 60 Hertz
• Primary amperes: 600 - 4000 Junction box
A molded, glass-filled polypropylene junction box,
Application with provision for 1" conduit connections on three
The KOT outdoor current transformers are designed sides, encloses the secondary terminals.
for high current metering and relaying. They are avail-
able with a 3.25" diameter primary opening or primary Base
spade terminals. The baseplate is constructed of corrosion-resistant
aluminum and secured to the encapsulated base
Construction features support.
KOT units utilize a one-piece cast epoxy bushing to
provide insulation strength. The tube-type KOT bush- Mounting
ing has a 3.25" diameter brass-lined opening for the All KOT units can be mounted in upright, cantilever, or
primary conductor to pass through. The primary con- upside-down positions.
ductor and brass liner can be tied together electrically
through a terminal located on the end of the bushing. Test reports
Bar type bushings have multiple 0.25" thick, tin-plated Test reports are stored electronically and can be
copper terminal spades brazed to each end of a tubu- e-mailed in various formats at the time of shipment.
lar copper bus. The primary bushing is inserted
through the window of the molded core and coil as- Standards
sembly and secured in place with end plates. These units meet or exceed all requirements of IEEE
C57.13-2016 and can be tested to other standards as
Secondary terminals requested.
Large clamp-type terminals are equipped with slotted
hex-head tightening screws. A rotatable shorting bar
2

Dimensions (inches [mm]) 8.25


4.13
3.50 3.50
.250-20 TERMINAL STUD 2 OR 3 TOTAL.
HOLES FOR .50 BOLTS
UNIT IS SHIPPED WITH SHORT CIRCUITED
4-TOTAL
CONNECTION IN SHORTED POSITION

5.75
7.00

2.88

.63

10.50 SECONDARY
5.25 POLARITY
9.38 MARKER A/2
4.69 A

NAMEPLATE
PRIMARY
POLARITY
MARKER
POTENTIAL TAP
RATING DECAL
BOTH SIDES

17.25 Ø5.44
15.06

13.75
3.25 I.D. PRIMARY
OPENING
8.88

4.00
.25

Tube type

8.25
4.13
3.50
HOLES FOR .50 BOLTS
4-TOTAL .250-20 TERMINAL STUD 2 OR 3 TOTAL.
UNIT IS SHIPPED WITH SHORT CIRCUITED
.50 1.75 CONNECTION IN SHORTED POSITION.

2.50
1.75
5.75
7.00 HOLES FOR .50 BOLTS
6-TOTAL
1.75
2.50

.625
SECONDARY POLARITY
MARKER

B/2
B
A/2
A HOLES FOR .50 BOLT
4-TOTAL
10.50 .875
5.25 2.00
9.38
4.69
.50
2.00
.875
NAMEPLATE .50 1.75
PRIMARY 3.00
POLARITY .250
MARKER .250

.250

.250 RATING DECAL


BOTH SIDES
.250
.250
.250
17.38 Ø5.44

15.19

.250
13.88 .250
.250

9.00
15.19 REF

4.00
.250

With primary bar

7.00
[178]
5.75
[146]

7.00 3.25 2.00 4.25


[178] [83] [51] [108] 8.25
2.13
[210]
[54]

4.00
4.88 [102]
[124]
9.75
[248]

Base: all types and ratings


3

Dimensions and weights


With primary bar Tube-type
A B Unit Weight A Unit Weight
Style (in) (mm) (in) (mm) (lbs) (kg) (in) (mm) (lbs) (kg)
KOT-60 19.625 498 18.625 473 62-73 28-33 10.25 260 40 18
KOT-75 22.625 575 21.625 549 67-79 30-36 13.25 337 43 19
KOT-11 27.125 689 26.125 664 75-89 34-40 17.75 451 47 21
KOT-15 36.125 918 35.125 892 89-107 40-49 26.75 679 52 24

KOT tube-type
IEEE IEEE Style number
Primary Rating metering relaying Thermal
ampere rating factor accuracy accuracy rating* KOT-60 KOT-75 KOT-11 KOT-15
800 2.0 0.3B-0.9 C100 80 7524A32G01 7524A33G01 7524A34G01 7524A35G01
1200 2.0 0.3B-1.8 C200 80 7524A32G02 7524A33G02 7524A34G02 7524A35G02
1500 2.0 0.3B-1.8 C200 100 7524A32G03 7524A33G03 7524A34G03 7524A35G03
2000 2.0 0.3B-1.8 C200 100 7524A32G04 7524A33G04 7524A34G04 7524A35G04
3000 1.5 0.3B-1.8 C200 100 7524A32G05 7524A33G05 7524A34G05 7524A35G05
4000 1.5 0.3B-1.8 C200 100 7524A32G06 7524A33G06 7524A34G06 7524A35G06
0.3B-0.5
600/1200 3.0/2.0 0.3B-1.8 C100/C200 80 7524A32G07 7524A33G07 7524A34G07 7524A35G07
0.3B-0.9
1000/2000 3.0/2.0 0.3B-1.8 C100/C200 80 7524A32G08 7524A33G08 7524A34G08 7524A35G08
0.3B-1.8
2000/4000 2.0/1.5 0.3B-1.8 C100/C200 100 7524A32G09 7524A33G09 7524A34G09 7524A35G09

KOT - with primary bar


IEEE IEEE Style number
Primary Rating metering relaying Thermal No. of
ampere rating factor accuracy accuracy rating* bars+ KOT-60 KOT-75 KOT-11 KOT-15
800 2.0 0.3B-0.9 C100 80 B 923A271G01 923A273G01 923A275G01 923A270G01
1200 2.0 0.3B-1.8 C200 80 B 923A271G02 923A273G02 923A275G02 923A270G02
1500 2.0 0.3B-1.8 C200 100 C 923A271G03 923A273G03 923A275G03 923A270G03
2000 1.5 0.3B-1.8 C200 100 C 923A271G04 923A273G04 923A275G04 923A270G04
3000 1.33 0.3B-1.8 C200 100 D 923A271G05 923A273G05 923A275G05 923A270G05
4000 1.0 0.3B-1.8 C200 100 D 923A271G06 923A273G06 923A275G06 923A270G06
0.3B-0.5
600/1200 3.0/2.0 0.3B-1.8 C100/C200 80 B 923A271G07 923A273G07 923A275G07 923A270G07
0.3B-0.9
1000/2000 2.0/1.5 0.3B-1.8 C100/C200 100 C 923A271G08 923A273G08 923A275G08 923A270G08
0.3B-1.8
2000/4000 1.5/1.0 0.3B-1.8 C100/C200 100 D 923A271G09 923A273G09 923A275G09 923A270G09
* times normal, 1 second
Double current designs available upon request
Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.

+
Primary Bar Guide (in.) - (other bar dimensions available)
Maximum current (amps) = primary amps x RF @ 30°C

A: 1550 amps max B: 2400 amps max C: 3000 amps max D: 4000 amps max

.88
0.88 .88 2.00 2.5
3.00 1.75 3.0 1.75
0.88 .88
1.75
.50 2.00 2.5
0.50 1.75 .88
1.75 .50 1.75 .50 1.75
.25 .25
.25 .25

.25 .25 .25


0.25
.25

Max current available with rating factor.


Example: 1200 amps with rating factor of 2.0 = 2400 amps

Accessories:
4-hole spade spacer: 9625A38H01; 6-hole spade spacer: 9625A38H02
1VAP429301-DB Rev K January 2022

— —
ABB Inc. We reserve the right to make technical We reserve all rights in this document and in
3022 NC 43 North changes or modify the contents of this doc- the subject matter and illustrations con-
Pinetops, NC 27864 ument without prior notice. With regard to tained therein. Any reproduction, disclosure
Phone: +1 252 827 3212 purchase orders, the agreed particulars to third parties or utilization of its contents
shall prevail. ABB Inc. does not accept any – in whole or in parts – is forbidden without
­responsibility whatsoever for potential er- prior written consent of ABB Inc.
rors or possible lack of information in this ­Copyright© 2022 ABB
document. All rights reserved
abb.com/mediumvoltage

You might also like