Product description 1

Safety relays
Functional information 2
3TK2845 multifunction device Technical data 3
Mounting, wiring, 4
commissioning

Manual Applications 5

3TK2890-0B
Edition 07/2015
NEB926208722000/RS-AC/005
Last update: 09 July 2015
Safety Notices
This manual contains information that you should observe to ensure your own personal safety and prevent
material damage. The instructions for your personal safety are marked by a safety alert symbol. Instructions
relating solely to material damage are not marked by a safety alert symbol. Depending on the degree of hazard,
the warning information is shown as follows in decreasing sequence:

Danger
indicates that death or serious injury will result if proper precautions are not taken.

Warning
indicates that death or severe personal injury may result if proper precautions are not taken.

Caution
with a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken.

Caution
indicates that property damage may result if proper precautions are not taken.

Notice
indicates that an undesirable event or state may arise if the relevant notes are not observed.

In the event of a number of levels of danger occurring simultaneously, the warning corresponding to the high-
est level of danger is always used. A warning on a safety alert symbol indicating possible personal injury may
also include a warning relating to material damage.

Qualified personnel
The product/system to which this documentation relates may only be used/operated by personnel qualified
for the respective tasks, taking account of the appropriate documentation for those tasks,
in particular, the safety and warning notices contained in the documentation. Qualified personnel are defined
as
persons who are able, thanks to their training and experience in handling these products/systems, to recognize
risks and avoid potential hazards.

Intended use
Note the following:

Warning
Siemens products may only be used for the applications described in the catalog and the associated technical
documentation. If third-party products or components are to be used, they must be recommended or
approved by Siemens. To ensure trouble-free and safe operation of the products, they must be appropriately
transported, stored, assembled, installed, commissioned, operated and maintained. The permissible environ-
mental conditions must be maintained. The notes in the associated documentation must be complied with.

Copyright Siemens AG 2007 All rights reserved Disclaimer of liability


The reproduction, transmission, or use of this document or its con- We have reviewed the contents of this publication to ensure consis-
tents is not permitted without express written authority. Offenders tency with the hardware and software described. Since variance can-
will be liable for damages. All rights, including rights created by pat- not be precluded entirely, we cannot guarantee full consistency. The
ent grant or registration of a utility model or design are reserved. information in this publication is reviewed regularly and any neces-
sary corrections are included in subsequent editions. We welcome
any suggestions for improvement.

Technical Assistance: Phone: +49 (911) 895-5900 (8°° - 17°° CET) Fax: +49 (911) 895-5907
e-mail: technical-assistance@siemens.com
Internet: www.siemens.com/sirius/technical-assistance
SIEMENS AG
Industry Sector  Siemens AG 2007
P.O. Box 4848 Technical data subject to change.
D-90026 Nuremberg, Germany
Table of Contents

1 Product description 1-1


1.1 3TK2845 multifunction device . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Function, properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.1 Several safety functions combined in one enclosure . . . . . . . . . . . . 1-4
1.2.2 Examples of using 3TK2845 modules . . . . . . . . . . . . . . . . . . . 1-6
1.3 3TK2845 order numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7

2 Functional information 2-1


2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.1.1 Function description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.1.2 Symbol description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.2 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.2.1 3TK2845-.HB.. "Monitored and automatic start" . . . . . . . . . . . . . . 2-7
2.2.2 3TK2845-.DB.. "Monitored start" . . . . . . . . . . . . . . . . . . . . . . 2-12
2.2.3 3TK2845-.EB.. "Enabling button" . . . . . . . . . . . . . . . . . . . . . . 2-16
2.2.4 3TK2845-.FB.. "Spring force interlocked tumbler" . . . . . . . . . . . . . . 2-21
2.2.5 3TK2845-.GB.. "Magnetic force interlocked tumbler" . . . . . . . . . . . . 2-24

3 Technical data 3-1


3.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.3 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.4 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6

4 Mounting, wiring, commissioning 4-1


4.1 Mounting and coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3 Meaning of the LED indicators . . . . . . . . . . . . . . . . . . . . . . . 4-6

5 Applications 5-1
5.1 3TK2845-.HB40 "Monitored start and automatic start",
instantaneous outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2 3TK2845-.HB41 "Monitored start and automatic start",
time-delayed outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.3 3TK2845-.DB40 "Monitored startup", instantaneous outputs . . . . . . . . 5-6
5.4 3TK2845-.DB41 "Monitored start", time-delayed outputs . . . . . . . . . . 5-8
5.5 3TK2845-.EB40 "Enabling button" . . . . . . . . . . . . . . . . . . . . . . 5-10
5.6 3TK2845-.FB41/2/4 "Spring force interlocked tumbler" . . . . . . . . . . . 5-12
5.7 3TK2845-.GB41/2/4 "Magnetic force interlocked tumbler" . . . . . . . . . 5-14

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 i
3TK2845 Multifunction Device Manual
ii NEB926208722000/RS-AC/005
Important notes

Important notes

Purpose of the manual


The information provided in this manual is intended to assist with the configura-
tion of safety-oriented functions as part of an overall installation or machine.

Target group
This manual is aimed at people with the required qualifications to commission
and operate the 3TK2845 multifunction device.

Scope of validity
This manual applies to multifunction devices with the following order numbers:
3TK2845-.HB40 *)
3TK2845-.HB41 *)
3TK2845-.HB42 *)
3TK2845-.HB44 *)

3TK2845-.DB40 *)
*)
3TK2845-.DB41
*)
3TK2845-.DB42
3TK2845-.DB44 *)

*)
3TK2845-.EB40
3TK2845-.EB41 *)
*)
3TK2845-.EB42
*)
3TK2845-.EB44
*)
3TK2845-.FB41
*)
3TK2845-.FB42
3TK2845-.FB44 *)

*)
3TK2845-.GB41
3TK2845-.GB42 *)

3TK2845-.GB44 *)

*) 8th position in order no.: 1 = screw terminal, 2 = spring-loaded terminal

Shutdown response to power failure / device failure:


On all 3TK28 devices, safety integrity level SIL CL 3 refers to the outputs with
stop category 0. The time-delayed outputs are redundantly configured but can-
not guarantee the set time in case of a failure (e.g. loss of power supply, device
failure). These devices enter the safe state in the event of a failure, which
always means that the outputs go to "zero" in this case.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 iii
Important notes

Standards and approvals


You can use the 3TK2845 safety relays in EMERGENCY-STOP facilities comply-
ing with ISO 13850 (09.2008) and in safety circuits complying with EN 60204-1
(06.2007), e.g. for moving covers and protective doors or contactless protective
equipment conforming to IEC 61496-1 (03.2009).
Depending on the external wiring, PLe in accordance with DIN EN ISO 13849-1
(12.2008) or SIL CL 3 in accordance with IEC 62061:2005 (02.2011) must be
achieved.

Installation note
Measures to be taken to improve immunity to conducted radio-
frequency interference:
o Spatial separation of sensitive circuits from interference sources
o Use of twisted-conductor cables
o Sufficient distance between conductors emitting interference and the con-
ductors of sensitive circuits
o Right-angled crossing of cables and conductors where possible
o Routing of the conductors as close as possible to the ground plane
o Use of electrostatic / electromagnetic shields

Disclaimer of liability
The products described here have been developed to carry out safety-oriented
functions as part of a complete plant or machine. A complete safety-oriented
system generally features sensors, evaluation units, signaling units, and reliable
shutdown concepts. It is the responsibility of the manufacturer to ensure that a
system or machine is functioning properly as a whole. Siemens AG, its regional
offices, and associated companies (hereinafter referred to as "Siemens") cannot
guarantee all the properties of an entire plant, system or machine that has not
been designed by Siemens.
Nor can Siemens assume liability for recommendations that appear or are
implied in the following description. No new guarantee, warranty, or liability
claims above those standard to Siemens can be derived from the following
description.

Up-to-the-minute information
You can obtain further assistance by calling the following numbers:

Technical Assistance: Phone: +49 (911) 895-5900 (8°° - 17°° CET)


Fax: +49 (911) 895-5907
or on the Internet at:
e-mail: technical-assistance@siemens.com
Internet: www.siemens.com/sirius/technical-assistance

SIEMENS AG, Technical Assistance


Breslauer Str. 5
D-90766 Fuerth, Germany

Correction sheet
A correction sheet is included at the end of this manual. Please use it to enter
your suggestions for improvements, additions and corrections, and send it back
to us. This will help us to improve the next edition of the manual.

3TK2845 Multifunction Device Manual


iv NEB926208722000/RS-AC/005
Product description 1
Chapter Subject Page

1.1 3TK2845 multifunction device 1-2

1.2 Function, properties 1-3

1.3 3TK2845 order numbers 1-7

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 1-1
Product description

1.1 3TK2845 multifunction device

Fig. 1-1: Illustration of the device version with screw connection, instantaneous enabling circuit

Fig. 1-2: Illustration of the device version with spring-loaded terminals, delayed enabling circuits

3TK2845 Multifunction Device Manual


1-2 NEB926208722000/RS-AC/005
Product description

1.2 Function, properties


The 3TK2845 multifunction device is used to implement safety-related functions
such as EMERGENCY-STOP monitoring, protective door monitoring and moni-
toring functions using contactless protective equipment (ESPE) such as light
curtains and safety shutdown mats in machines with movable components.

The device is especially suited for:

– Use on machines that operate without an interface to a bus system (stand-alone


operation)

– Use on machines requiring several protection functions


(e.g. EMERGENCY-STOP and a protective door, enabling button and protective door
and locked protective door tumblers)

– Use on machines having components which must be switched off during operation
(e.g. for servicing)

The advantage of using this device is the fact that several safety-related func-
tions can be implemented using only one 3TK2845 multifunction device rather
than using several safety relays. In addition, the device is also suited for opera-
tional switching, cascading and adding safety relays either using contacts or
switching electronically.

Note:
Under the link https://support.industry.siemens.com/cs/ww/en/ps/16391/dl 
"Simulation safety switching device 3TK2845", you will find a simulation of the
devices that will illustrate the functionality for you.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 1-3
Product description

1.2.1 Several safety functions combined in one enclosure

Conventional design
Until now, common combinations of safety applications such as EMERGENCY-
STOP and protective door monitoring could only be implemented by using sev-
eral individual safety relays (as in the example shown; Fig. 1-3).

Fig. 1-3: Versions: 3TK2841 One safety relay required per safety function

3TK2845 Multifunction Device Manual


1-4 NEB926208722000/RS-AC/005
Product description

Configuration with 3TK2845


Multifunction devices of the 3TK2845 series combine several functions in one
device.
These devices are suitable for monitoring up to two safe 2-channel sensors and
1 safe 1-channel sensor (cascading input) and they also offer you the option of
connecting a mode switch.
Two solid-state enabling circuits and two relay enabling circuits ensure safe
shutdown here.

Fig. 1-4: Versions: 3TK2845 EMERGENCY-STOP and protective door monitoring + key-operated switch
for bridging the protective door in maintenance mode

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 1-5
Product description

1.2.2 Examples of using 3TK2845 modules

Monitoring of EMERGENCY-STOP and positioning switches with possible main-


tenance for intervening in a secured area.

Monitoring of position switches and possible operation using an enabling button


in "unsafe" mode (maintenance).

3TK2845 Multifunction Device Manual


1-6 NEB926208722000/RS-AC/005
Product description

1.3 3TK2845 order numbers


Monitored and automatic start
Screw terminal Spring-loeaded terminal Time delay
3TK2845-1HB40 3TK2845-2HB40 instantaneous
3TK2845-1HB41 3TK2845-2HB41 time-delayed 0.05 … 3 s
3TK2845-1HB42 3TK2845-2HB42 time-delayed 0.5 … 30 s
3TK2845-1HB44 3TK2845-2HB44 time-delayed 5 … 300 s

Monitored start
Screw terminal Spring-loaded terminal Time delay
3TK2845-1DB40 3TK2845-2DB40 instantaneous
3TK2845-1DB41 3TK2845-2DB41 time-delayed 0.05 … 3 s
3TK2845-1DB42 3TK2845-2DB42 time-delayed 0.5 … 30 s
3TK2845-1DB44 3TK2845-2DB44 time-delayed 5 … 300 s

Enabling button
Screw terminal Spring-loaded terminal Time delay
3TK2845-1EB40 3TK2845-2EB40 instantaneous
3TK2845-1EB41 3TK2845-2EB41 time-delayed 0.05 … 3 s
3TK2845-1EB42 3TK2845-2EB42 time-delayed 0.5 … 30 s
3TK2845-1EB44 3TK2845-2EB44 time-delayed 5 … 300 s

Spring force interlocked tumblers


Screw terminal Spring-loaded terminal Time delay
3TK2845-1FB41 3TK2845-2FB41 time-delayed 0.05 … 3 s
3TK2845-1FB42 3TK2845-2FB42 time-delayed 0.5 … 30 s
3TK2845-1FB44 3TK2845-2FB44 time-delayed 5 … 300 s

Magnetic force interlocked tumblers


Screw terminal Spring-loaded terminal Time delay
3TK2845-1GB41 3TK2845-2GB41 time-delayed 0.05 … 3 s
3TK2845-1GB42 3TK2845-2GB42 time-delayed 0.5 … 30 s
3TK2845-1GB44 3TK2845-2GB44 time-delayed 5 … 300 s

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 1-7
Product description

3TK2845 Multifunction Device Manual


1-8 NEB926208722000/RS-AC/005
Functional information 2
Chapter Subject Page

2.1 General 2-2

2.1.1 Function description 2-5

2.1.2 Symbol description 2-6

2.2 Versions 2-7

2.2.1 3TK2845-.HB.. "Monitored and automatic start" 2-7

2.2.2 3TK2845-.DB.. "Monitored start" 2-12

2.2.3 3TK2845-.EB.. "Enabling button" 2-16

2.2.4 3TK2845-.FB.. "Spring force interlocked tumbler" 2-21

2.2.5 3TK2845-.GB.. "Magnetic force interlocked tumbler" 2-24

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-1
Functional information

2.1 General
SIRIUS safety relays and the safety chain
A safety chain generally consists of the functions detection, evaluation and
switching-off.
Detection:
– This means the sensing of a safety requirement, e.g. when an EMERGENCY-STOP
facility is actuated or a hazardous area protected by sensors such as light arrays or
laser scanners is entered.
Evaluation:
– This means the detection of a safety requirement and the safe initiation of the
reaction (e.g. switching-off of the enabling circuits).
– This means the monitoring of the correct functioning of the actuator and the
sensor.
Switching-off:
– This means the switching-off of the hazard (e.g. of a power supply via the
downstream contactors).
SIRIUS safety relays play a role in the evaluation and reaction part of this
safety chain.
The safety functions are shown in a uniform schematic diagram (refer
to Chapter 2.2) for a quick overview of the special functions of the individual
device types.
The sensor interface inputs, the actuator interface outputs and enabling circuits,
as well as the special safety logic can all be seen at a glance.

Cascading input
1. Safe linking of safety relays
In this application a higher-level safety relay switches off the 3TK2845 via a safe
output and the cascading input.
Example:
A -- higher-level -- EMERGENCY-STOP circuit must switch off the whole system.
Several lower-level functional groups (e.g. protective doors) with local switch-off
can be operated.

Notice
When faults are ruled out (protected laying of the control lead), the application's
safety category corresponds to that of the higher-level safety relay.

2. Additional safety sensor circuit


The cascading input is AND-connected with the sensor inputs Y12, Y22. PLc
according to EN ISO 13849-1, or SIL CL 2 according to IEC 62061 can be
achieved when the cascading input is wired to single-channel safety sensors
(positive opening) and the routing of the connecting cable is protected.
The start function is set to automatic start. Cascading input 1 can be switched
with floating or solid-state switching elements. Both types of switching
elements must be fed by the same power supply as the device.

3TK2845 Multifunction Device Manual


2-2 NEB926208722000/RS-AC/005
Functional information

3. Operational switching
The cascading input can be used for operational (non-safe) switching. Switching
is possible with floating or solid-state switching elements. Floating switching
elements must be fed by the same power supply as the device.

4. Initial device start


4.1 Cross-circuit detection:
o If a voltage of + 24 V DC is applied at Y35, cross-circuit evaluation between
Y11/Y12 and Y21/Y22 is deactivated (necessary for non-floating sensors,
e.g. light barriers).
o If a voltage of + 24 V DC is applied at Y65, cross-circuit evaluation between
Y41/Y42 and Y51/Y52 is deactivated (necessary for non-floating sensors,
e.g. light barriers).
o If no voltage is applied at Y35 or Y65, cross-circuit detection is active
(necessary for pressure sensitive mats according to the cross-circuit
principle, and non-floating sensors, e.g. EMERGENCY-STOP).

Note:
If 1-channel sensors are used, Y35 (in the case of 1-channel sensor on Y12 or
Y22 or Y65 (in the case of 1-channel sensor on Y42 or Y52)) must be supplied
with a voltage of +24 V DC.

Note:
If a pressure sensitive mat is used, it MUST be wired before switching on the
device. Otherwise, the device will not detect the pressure sensitive mat, and a
device fault will occur when the pressure sensitive mats are actuated.

5. Switch-on conditions
o Voltage present at A1/A2.
o Sensor circuit Y12/Y22 closed (exception in the case of variant
3TK2845-.EB4.).
o Sensor circuit Y42/Y52 closed (exceptions during maintenance).
o Cascading input supplied with 24 V DC.
o Feedback circuit closed (supplied with 24 V DC).
o An ON signal at Y34 is required for monitored start.

For the safe monitoring of device function, sensors and actuators, the state of
all input variables must remain unchanged for at least 400 ms after the 3TK2845
outputs drop out. If, for example, a sensor circuit is closed during this time, a
device fault occurs that can only be remedied by resetting the supply voltage.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-3
Functional information

6. Monitoring the ON button


o Both the positive and negative signal change are monitored on the ON button.
o If the ON button is pressed for longer than 5s, the ON command is rejected in
the device and the device does NOT start when the ON button is released!
o Monitored start requires status "1" at input Y34 as the start condition. When
this condition is fulfilled, the safe outputs become active, that is, they are set
to "1" (depending on the device version).
The start signal at input Y34 is only valid when the following applies:
- The time sequence of the START signal corresponds to the values
"0 - 1 - 0".
- The value "1" must be present for 0.2 to 5 s.

ಱಯ
,1 ಱಯ
67$57
287
ุV V

7. Use of a 1-channel sensor connection on Y11/12, Y21/22, or Y41/42, Y51/52


o If a single-channel sensor is to be connected to one of the two 2-channel
sensor inputs, cross-circuit detection must be deactivated for this sensor
circuit. The single-channel sensor must be supplied with an external + 24 V
DC signal in this case.
o If a single-channel sensor is desired at sensor input Y11/12, Y21/22, terminal
Y35 must also be supplied with + 24 V DC
o If a single-channel sensor is desired at sensor input Y41/42, Y51/52, terminal
Y65 must also be supplied with + 24 V DC.

8. Monitoring the feedback circuits


External actuators such as contactors or pneumatic valves are monitored with
the feedback circuit.
o The feedback circuit is tested for correct functioning when all enabling cir-
cuits are switched off (must be closed within 200 ms after switching off the
enabling circuits). If the feedback circuit remains open after opening the
enabling circuits, the device assumes a fault state (LED 24 & 44 flash). It
must not be possible to switch the device on in this state.
o An ON command is not accepted during a fault in the feedback circuit.
o If the fault in the feedback circuit is corrected, the device can be started again
as normal.
o If an actuator with feedback is not used, feedback input Y64 must be supplied
with 24 V DC.

3TK2845 Multifunction Device Manual


2-4 NEB926208722000/RS-AC/005
Functional information

2.1.1 Function description

Automatic sensor detection


Sensors such as EMERGENCY-STOP control devices or position switches and
safety shutdown mats have different modes of operation.
While EMERGENCY-STOP control devices, for example, interrupt the sensor
circuit when activated, safety shutdown mats establish a cross-circuit between
the two input channels of the evaluation system when stepped on. This means
that
1. in the case of a sensor which interrupts the sensor circuit, a cross-circuit
leads to a fault.
2. in the case of safety shutdown mats an interruption of the sensor circuit
leads to a fault.

All safety shutdown mats and switching strips operating in a 4-wire configura-
tion that work in accordance with the principle of cross-circuit tripping can be
connected to the 3TK2845 safety relay.
The tripping of the 3TK2845 is initiated by a cross-circuit in the sensor cables.
If the safety shutdown mat resistance is < 1000 Ω for the mat + the connecting
leads, safe evaluation is performed in accordance with DIN EN 1760-1 and
DIN EN 1760-2.

The 3TK2845 automatically detects the mode of operation of the connected


sensor.

If, during first activation of the sensor after a device restart,


1. opening of the sensor circuits is detected, the 3TK2845 only accepts
sensors which open the sensor circuits (floating NC contacts such as
EMERGENCY-STOP control devices or position switches). A cross-circuit
between the sensor circuits leads to a fault.
2. a cross-circuit is detected between the sensor circuits, the 3TK2845 only
accepts sensors causing a sensor circuit short-circuit (safety shutdown
mats). Opening of the sensor circuits leads to a fault.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-5
Functional information

2.1.2 Symbol description

Explanation of symbols

Symbol Meaning

START button

EMERGENCY-STOP

Protective door

Enabling button

Light curtain, light array, light barrier

Safety shutdown mat

Cross-circuit monitoring

Feedback circuit

Key-operated switch

Table 2-1: Explanation of symbols

3TK2845 Multifunction Device Manual


2-6 NEB926208722000/RS-AC/005
Functional information

2.2 Versions
2.2.1 3TK2845-.HB.. "Monitored and automatic start"

The 3TK2845-.HB.. has two sensor inputs (Y11/12; Y21/22) with monitored start,
(Y41/42; Y51/52 with automatic start), one cascading input (1, with automatic
start) as well as one switching input (key-operated switch). On the output side
there are two relay and two enabling circuits and two solid-state enabling cir-
cuits as well as one solid-state signaling output.
Standard operation
In standard operation (key-operated switch "OFF") all enabling circuits are acti-
vated. All input blocks are AND-connected to one another and affect all enabling
circuits at the same time. Some are time-delayed (in the versions:
3TK2845-.HB41; -.HB42; -.HB44).
Maintenance
During maintenance (key-operated switch "ON") only two of the four enabling
circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door)
has no function. The hazardous area can be entered since the dangerous motion
has been switched off via the two inactive enabling circuits. The sensor input
Y12/Y22 and the cascading input (1, with automatic start) still affect the active
enabling circuits.
Monitored start is required:
o At initial start after applying the control supply voltage.
o After opening and closing sensor circuits Y12/Y22 (even if this is followed by
deactivation and reactivation of cascading!)

Automatic start takes place:


o After closing sensor circuits Y42/Y52 (following "standard operation")
o After activation of the cascading input (not on first switching on the device
AND after opening and closing of the sensor on Y12/Y22).
o After exiting maintenance mode (not if the sensor on Y12/Y22 has been
actuated!)

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-7
Functional information

Outputs:
o Standard operation (Y72/Y82 at 0 V):
All enabling circuits (13/14, 24, 33/34, 44 or 13/14, 24, 37/38, 48 with the
time-delayed versions 3TK2845-.HB41; -.HB42; -.HB44), some time-delayed,
switch on with the Start command or on closing of sensor circuit Y42/Y52
(automatic start, if Y12/Y22 was not opened).
All enabling circuits are deactivated by actuating a sensor
Signaling circuit 52 always switches inversely to the enabling circuits
o Maintenance (Y72/Y82 at 24 V DC):
If sensor circuit Y12/Y22 or the cascading input (1, with automatic start) is
opened during maintenance, all enabling circuits switch off, and signaling
circuit 52 is active.

Starting maintenance mode from the idle condition:


Enabling circuits 13/14 and 24 (13/14 and 48 with the time-delayed versions)
switch on with the Start command (if all other switch-on conditions are met at
the same time).
Enabling circuits 13/14 and 24 switch on when the key-operated switch is
actuated (24 V DC at Y72/Y82) regardless of the status at input Y42/Y52
(if the sensor at Y42/Y52 was the only cause of switching off).
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

Starting maintenance from standard operation (all enabling circuits active).


Enabling circuits 33/34 and 44 switch off when maintenance mode is
selected, but enabling circuits 13/14 and 24 remain active.
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

3TK2845 Multifunction Device Manual


2-8 NEB926208722000/RS-AC/005
Functional information

Status diagrams

Standard
Normoperation
albetrieb Maintenance
Servicebetrieb Standard
Normoperation
albetrieb

Y34

1
Eingänge

Y12/22
Inputs

Y42/52

Changeover fromNorm
Um schaltung standard
al- / operation to maintenance
Servicebetrieb
-
Y72/82

13/14

24
Ausgänge
Outputs

33/34

48

52

Fig. 2-1: Status diagram: 3TK2845-.HB40

Standard operation
Norm albetrieb Maintenance
Servicebetrieb

Y 34

1
Eingänge

Y12/22
Inputs

Y42/52

Changeover fromNorm
Um schaltung standard
al- / operation to maintenance
Servicebetrieb
Y72/82

13/14

24
Ausgänge
Outputs

37/38

48

52

tv tv tv tv tv tv

Fig. 2-2: Status diagram: 3TK2845-.HB41

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-9
Functional information

Connections: Monitored and automatic start instantaneous


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
instantaneous 14

or

Y11
Y12
or Sensor connection Safe solid-state output
Y21 240
instantaneous
Y22

or

Y34 START button

Safe relay output


- with cross-circuit detec- 33
Y35 instantaneous
tion (not connected) 34
refers to
- without cross-circuit
Y11/Y12,
detection (with 24V DC =
Y21/Y22
terminal A1 connected)

or Y41
Y42 Safe solid-state output
Sensor connection instantaneous 44
Y51
or Y52

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
(must not be used for 52
Y72
Key-operated switch safety-related applica-
Y82
tions)

External device monitor-


Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


2-10 NEB926208722000/RS-AC/005
Functional information

Connections: Monitored and automatic start, time-delayed


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
instantaneous 14

or

Y11
Y12
or Sensor connection Safe solid-state output
Y21 24
instantaneous
Y22

or

Y34 START button

Safe relay output


- with cross-circuit detec- 37
Y35 time-delayed
tion (not connected) 38
refers to
- without cross-circuit
Y11/Y12,
detection (with 24V DC =
Y21/Y22
terminal A1 connected)

or Y41
Y42 Safe solid-state output
Sensor connection time-delayed 48
Y51
or Y52

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
(must not be used for 52
Y72
Key-operated switch safety-related applica-
Y82
tions)

External device monitor-


Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-11
Functional information

2.2.2 3TK2845-.DB.. "Monitored start"

The 3TK2845-.DB.. has two sensor inputs (Y42/Y52, Y12/Y22 with monitored
start), one cascading input (1, with automatic start) as well as one switching
input (key-operated switch). On the output side there are two relay and two
enabling circuits and two solid-state enabling circuits as well as one solid-state
signaling output.
Standard operation
In standard operation (key-operated switch "OFF") all enabling circuits are acti-
vated. All input blocks are AND-connected to one another and affect all enabling
circuits at the same time. Some are time-delayed (in the versions:
3TK2845-.DB41; -.DB42; -.DB44).
Maintenance
During maintenance (key-operated switch "ON") only two of the four enabling
circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door)
has no function. The hazardous area can be entered since the dangerous motion
has been switched off via the two inactive enabling circuits. The sensor input
Y12/Y22 and the cascading input (1, with automatic start) still affect the active
enabling circuits.
A monitored start is required:
o At initial start of the device.
o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52).
o After exiting maintenance mode, if the protective door has been opened.
Automatic start takes place if:
o Cascading input 1 (if no Y12/Y22 or Y42/Y52 sensor has been actuated previ-
ously).
o Service switch Y72/Y82 (if the protective door has not been opened during
maintenance).
Outputs:
o Standard operation (Y72/Y82 at 0 V):
All enabling circuits (13/14, 24, 33/34, 44; or 13/14, 24, 37/38, 48 with the
time-delayed versions 3TK2845-.DB41; -.DB42; -.DB44), some time-delayed,
switch on with the Start command.
All enabling circuits are deactivated by actuating a sensor.
Signaling circuit 52 always switches inversely to the enabling circuits.
o Maintenance (Y72/Y82 at 24 V DC):
If sensor circuit Y12/Y22 or the cascading input (1, with automatic start) is
opened during maintenance, all enabling circuits switch off, and signaling
circuit 52 is active.

Starting maintenance mode from the idle condition:


Enabling circuits 13/14 and 24 (13/ and 48 with the time-delayed versions)
switch on with the Start command regardless of the status at sensor input
Y42/Y52 (if all other switch-on conditions are met at the same time).
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

Starting maintenance from standard operation (all enabling circuits active)


Enabling circuits 33/44 and 44 switch off when maintenance mode Y72/Y82 is
selected, but enabling circuits 13/14 and 24 remain active.
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

3TK2845 Multifunction Device Manual


2-12 NEB926208722000/RS-AC/005
Functional information

Status diagrams

StandardNorm
operation
albetrieb Maintenance
Servicebetrieb Standard
Normoperation
albetrieb

Y 34

1
Eingänge

Y 12/22
Inputs

Y 42/52

Changeover fromNorm
Um schaltung standard operation to maintenance
al- / Servicebetrieb
-
Y 72/82

13/14

24
Ausgänge
Outputs

33/34

44

52

Fig. 2-3: Status diagram: 3TK2845-.DB40

Y34

1
Eingänge

Y12/22
Inputs

Y42/52

Y72/82

13/14

24
Ausgänge
Outputs

37/38

48

52

tv tv tv

Fig. 2-4: Status diagram: 3TK2845-.DB41

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-13
Functional information

Connections: Monitored start instantaneous


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
instantaneous 14

or

Y11
Y12
or Sensor connection Safe solid-state output
Y21 24
instantaneous
Y22

or

Y34 START button

Safe relay output


- with cross-circuit detec- 33
Y35 instantaneous
tion (not connected) 34
refers to
- without cross-circuit
Y11/Y12,
detection (with 24V DC =
Y21/Y22
terminal A1 connected)

or Y41
Y42 Safe solid-state output
Sensor connection instantaneous 44
Y51
or Y52

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
(must not be used for 52
Y72
Key-operated switch safety-related applica-
Y82
tions)

External device
Y64
monitoring circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


2-14 NEB926208722000/RS-AC/005
Functional information

Connections: Monitored start time-delayed


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
instantaneous 14

or

Y11
Y12
or Sensor connection Safe solid-state output
Y21 24
instantaneous
Y22

or

Y34 START button

Safe relay output


- with cross-circuit detec- 37
Y35 time-delayed
tion (not connected) 38
refers to
- without cross-circuit
Y11/Y12,
detection (with 24V DC =
Y21/Y22
terminal A1 connected)

or Y41
Y42 Safe solid-state output
Sensor connection time-delayed 48
Y51
or Y52

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
(must not be used for 52
Y72
Key-operated switch safety-related applica-
Y82
tions)

External device
Y64
monitoring circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-15
Functional information

2.2.3 3TK2845-.EB.. "Enabling button"

The 3TK2845-.EB.. has two sensor inputs (Y12/Y22 enabling button with
automatic start, Y42/Y52 protective door with monitored start/automatic start),
one cascading input (1, with automatic start) as well as one switching input
(key-operated switch). On the output side there are two relay and two enabling
circuits and two solid-state enabling circuits as well as one solid-state signaling
output.

Standard operation
In standard operation (key-operated switch "OFF") all enabling circuits are
activated. The cascading input (1, with automatic start) and the protective door
input Y42/Y52 are AND-connected with each other and affect all enabling cir-
cuits at the same time. Some are time-delayed. Input Y12/Y22 for the enabling
button has no function in this context. The opening of the protective door or a
missing signal at the cascading input CAS/OS deactivates all enabling circuits.

Maintenance
During maintenance (key-operated switch "ON") only two of the four enabling
circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door)
has no function. The hazardous area can be entered since the dangerous motion
has been switched off via the two inactive enabling circuits. The dangerous
motion can be started again via the enabling button at sensor input Y12/Y22
despite the protective door being open.
Parameterization for monitored/automatic start for sensor circuit Y42/Y52:
o If Y32 is at 24 V DC, the device powers up in automatic start.
o If there is no voltage at Y32, the device powers up in monitored start.
- If the protective door is not opened during maintenance, all enabling circuits
close automatically on exiting maintenance mode. This applies to both
monitored start and automatic start.
If "monitored start" is parameterized:
- A monitored start is required:
o At initial start after applying the control supply voltage.
o After opening and closing sensor circuits Y42/Y52 (even if this is followed by
deactivation and reactivation of cascading!)

- Automatic start takes place:


o After activation of the cascading input (not on first switching of the device
AND after opening and closing of the sensor on Y12/Y22 if maintenance
mode is not selected).
o After exiting maintenance mode (if Y42/Y52 has not been actuated).
If "automatic start" is parameterized:
o After the switch-on conditions have been met, all enabling circuits switch in
(not in maintenance mode!)

3TK2845 Multifunction Device Manual


2-16 NEB926208722000/RS-AC/005
Functional information

Outputs:
- Standard operation (Y72/Y82 at 0 V):
o All enabling circuits (13/14, 24, 33/34, 44; or. 13/14, 24, 37/38, 48 with the
time-delayed versions 3TK2845-.EB41; -.EB42; -.EB44) switch on with the
Start command
All enabling circuits are deactivated by actuating the sensor circuit Y42/Y52.
o Signaling circuit 52 always switches inversely to the enabling circuits.

- Maintenance (Y72/Y82 at 24 V DC):


General:
If cascading input 1 is opened during maintenance, all enabling circuits switch
off, and signaling circuit 52 is active.
o When exiting maintenance mode, all enabling circuits switch on only after a
renewed Start command (if Y42/Y52 has been actuated).

Starting maintenance mode from the idle condition:


o Enabling circuits 13/14 and 24 switch on with the Start command regardless
of the status at sensor input Y12/Y22 (if all other switch-on conditions are met
at the same time).
o Outputs 33/34 and 44 (37/38 and 24 with the time-delayed versions) can be
activated in maintenance mode with the enabling button (even if door
Y12/Y22 is opened).
o Signaling circuit 52 pulses with a frequency of 1.2 Hz.

Starting maintenance from standard operation (all enabling circuits active).


o Enabling circuits 33/44 and 44 (24, 37/38 with the time-delayed versions)
switch off when maintenance mode Y72/Y82 is selected, but enabling circuits
13/14 and 24 remain active.
o Outputs 33/34 and 44 (37/38 and 24 with the time-delayed versions) can be
activated in maintenance mode with the enabling button (even if door
Y12/Y22 is opened).
o Signaling circuit 52 pulses with a frequency of 1.2 Hz.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-17
Functional information

Status diagrams

Standard
Normoperation
albetrieb Maintenance
Servicebetrieb Standard operation
Norm albetrieb

Y34

1
Eingänge

Y12/22
Inputs

Y42/52

Changeover fromNorm
Um schaltung standard
al- /operation to maintenance
Servicebetrieb
Y72/82

13/14

24
Ausgänge
Outputs

33/34

44

52

Fig. 2-5: Status diagram: 3TK2845-.EB40

Standard operation
Norm albetrieb Maintenance
Servicebetrieb Standard operation
Norm albetrieb

Y34

1
Eingänge

Y12/22
Inputs

Y42/52

Changeover fromNorm
Um schaltung standard
al- operation to maintenance
- / Servicebetrieb
-/Servicebetrieb
Y72/82

13/14

24
Ausgänge
Outputs

37/38

48

52

tv tv tv tv tv tv

Fig. 2-6: Status diagram: 3TK2845-.EB40

3TK2845 Multifunction Device Manual


2-18 NEB926208722000/RS-AC/005
Functional information

Connections: Enabling button instantaneous


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
Y11 instantaneous 14
Y12 Safe solid-state output
Sensor connection instantaneous
Y21
Y22
24

or Y41
Y42
Sensor connection
Y41
or Y42 Safe relay output
33
instantaneous
34

Y34 START button

Safe solid-state output


- Monitored start
instantaneous
(not connected)
44
Y32 - Automatic start
(with 24 V DC = terminal
A1 connected)
- with cross-circuit detec-
Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
Y72 (must not be used for
Key-operated switch 52
Y82 safety-related applica-
tions)

External device monitor-


Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-19
Functional information

Connections: Enabling button time-delayed


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
Y11 instantaneous 14
Y12 Safe solid-state output
Sensor connection instantaneous
Y21
Y22
24

or Y41
Y42
Sensor connection
Y51
or Y52 Safe relay output
37
instantaneous
38

Y34 START button

Safe solid-state output


- Monitored start
instantaneous
(not connected)
48
Y32 - Automatic start
(with 24 V DC = terminal
A1 connected)
- with cross-circuit detec-
Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
Y72 (must not be used for
Key-operated switch 52
Y82 safety-related applica-
tions)

External device monitor-


Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


2-20 NEB926208722000/RS-AC/005
Functional information

2.2.4 3TK2845-.FB.. "Spring force interlocked tumbler"

The 3TK2845-.FB.. has two sensor inputs (Y12/Y22 EMERGENCY-STOP with


monitored start, Y42/Y52 protective door with tumbler and monitored start), one
cascading input (1, with automatic start) as well as one door enable input. On
the output side there are one relay enabling circuit and two solid-state enabling
circuits as well as a solenoid control output and a solid-state signaling output.
Not enabled
If the protective door is not enabled, it cannot be opened. Cessation of the
signal at the inputs Y12/Y22 or at the cascading input (1, with automatic start)
deactivates the enabling circuits.
Enabled
The solenoid control output and the second solid-state enabling circuit are acti-
vated via a signal to the door enable input after the delay time has passed. This
enables the protective door.
A monitored start is required:
o At initial start of the device.
o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52).
o After cessation of the door enable (Y82), if the protective door has been
opened.
Automatic start takes place only:
o In the case of a cascading input (if no sensor has been actuated previously).
o After cessation of the door enable, if the protective door has not been
opened.
Outputs:
o Standard operation (Y82 at 24 V):
Enabling circuits 13/14 and 24 switch on with the Start command.
Enabling circuits 13/14 and 24 are deactivated by actuating a sensor.
Signaling circuit 52 always switches inversely to the enabling circuits.
o Door enabling mode (Y82 at 0 V DC):
In the mode for door enabling, outputs 13/14 and 24 are always inactive.

Starting the mode for door enabling from the idle condition:
Enabling circuits 37/38 and 48 are inactive, and the spring force interlocked
tumbler remains enabled (protective door can be opened).
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

Starting the mode for door enabling from standard operation (all enabling cir-
cuits active)
Enabling circuits 13/14 and 24 switch off when maintenance Y82 is selected,
and enabling circuits 37/38 and 48 switch off after the set time and enable the
door tumbler.
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-21
Functional information

Status diagram

Door Standard
Standard operation
Norm albetrieb enabling
Türfreigabe Norm al

Y34 Start
Start

1 Cascading
Kaskadier
Eingänge

Y12/22 EMERGENCY Stop monitored


NO T HALT Überwacht
Inputs

Y42/52 Protective
Schutztürdoor monitored
Überwacht

Y72 Magnet monitoring


M agnetüberwachung

Y82 Door enabling


Türfreigabe

13/14 OUT1
O UT1
Ausgänge

24 OUT2
O UT2
Outputs

37/38 OUT3
O UT3door interlock
Türverriegelung

48 OUT4
O UT4door interlock
Türverriegelung

52 Signaling output
M eldeausgang
tv

Fig. 2-7: Status diagram: 3TK2845-.FB4.

3TK2845 Multifunction Device Manual


2-22 NEB926208722000/RS-AC/005
Functional information

Connections: Spring force interlocked tumbler


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output
13
Y11 instantaneous
14
Y12
Sensor connection
Y21
Y22
Safe solid-state output 24
Y34 START button instantaneous

- with cross-circuit detec-


tion (not connected)
Y35 - without cross-circuit
Safe relay output
detection (with 24V DC =
switch-on delay 37
terminal A1 connected)
e.g. for door interlock 38

or Y41
Y42
Sensor connection
Safe solid-state output
Y51
switch-on delay
or Y52 48
e.g. door interlock

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
Y72 Magnet monitoring (must not be used for 52
Y82 Door enable safety-related applica-
tions)
External device monitor-
Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-23
Functional information

2.2.5 3TK2845-.GB.. "Magnetic force interlocked tumbler"

The 3TK2845-.GB.. has two sensor inputs (Y12/Y22 EMERGENCY-STOP with


monitored start, Y42/Y52 protective door with tumbler and monitored start), one
cascading input (1, with automatic start) as well as one door enable input. On
the output side there are one relay enabling circuit and two solid-state enabling
circuits as well as a relay solenoid control output and a solid-state signaling
output.

Not enabled
If the protective door is not enabled, it cannot be opened. Cessation of the
signal at the inputs Y12/Y22 or at the cascading input (1, with automatic start)
deactivates the enabling circuits (13, 14; 24).

Enabled
The solenoid control output and the second solid-state enabling circuit are
deactivated via a signal to the door enable input after the delay time has passed.
This enables the protective door.

A monitored start is required:


o At initial start of the device.
o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52).
o After closing the door enable, if the protective door has been opened.

Automatic start only:


o In the case of a cascading input (if no sensor has been actuated previously).
o After closing the door enable, if the protective door has not been opened.

Outputs:
o Standard operation (Y82 at 24 V DC):
Enabling circuits 13/14 and 24 switch on with the Start command.
Enabling circuits 13/14 and 24 are deactivated by actuating a sensor.
Signaling circuit 52 always switches inversely to the enabling circuits.
o Door enabling mode (Y82 at 0 V DC)
In the mode for door enabling, outputs 13/14 and 24 are always inactive.

Starting the mode for door enabling from the idle condition:
Enabling circuits 37/38 and 48 are inactive, and the magnetic force interlocked
tumbler remains enabled (protective door can be opened).
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

Starting the mode for door enabling from standard operation (all enabling cir-
cuits active):
Enabling circuits 13/14 and 24 switch off when door enabling is selected (Y82 at
0 V DC), and the magnetic force interlocked tumbler becomes inactive after the
set time (protective door can be opened).
Signaling circuit 52 pulses with a frequency of 1.2 Hz.

3TK2845 Multifunction Device Manual


2-24 NEB926208722000/RS-AC/005
Functional information

Status diagram

Standard operation
Norm albetrieb Door
Türfreigabe Standard
Norm al
enabling
Y34 Start
Start

1 Cascading
Kaskadier
Eingänge

Y12/22 EMERGENCY Stop monitored


NO T HALT Überwacht
Inputs

Y42/52 Protective
Schutztür door monitored
Überwacht

Y72 Magnet monitoring


M agnetüberwachung

Y82 Door enabling


Türfreigabe

13/14 OUT1
O UT1
Ausgänge

24 OUT2
O UT2
Outputs

37/38 OUT3
O UT3 door interlock
Türverriegelung

48 OUT4
O UT4 door interlock
Türverriegelung

52 Signaling output
M eldeausgang
tv

Fig. 2-8: Status diagram: 3TK2845-.GB4.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 2-25
Functional information

Connections: magnetic force interlocked tumbler


Inputs (sensors) Outputs (enabling circuit)
Sensor Terminals Description Description Terminals
1 Cascading Safe relay output 13
Y11 instantaneous 14
Y12
Sensor connection
Y21
Y22
Safe solid-state output 24
Y34 START button instantaneous

- with cross-circuit detec-


Y35
tion (not connected)
refers to
- without cross-circuit
Y11/142,
detection (with 24V DC = Safe relay output
Y21/Y22 37
terminal A1 connected) off-delay
38
e.g. door interlock

or Y41
Y42
Sensor connection
Y51 Safe solid-state output
or Y52 off-delay 48
e.g. door interlock

- with cross-circuit detec-


Y65
tion (not connected)
refers to
- without cross-circuit
Y41/Y42,
detection (with 24V DC =
Y51/Y52 Solid-state signaling
terminal A1 connected)
output1)
Y72 Magnet monitoring (must not be used for 52
Y82 Door enable safety-related applica-
tions)
External device monitor-
Y64
ing circuit

1) Solid-state signaling output


Enabling circuits active: Signaling output OFF
Enabling circuits inactive: Signaling output ON
Key-operated switch operation: Signaling output clocked (approx. 1.2 Hz)

3TK2845 Multifunction Device Manual


2-26 NEB926208722000/RS-AC/005
Technical data 3
Chapter Subject Page

3.1 Technical data 3-2

3.2 Terminals 3-4

3.3 Terminal assignment 3-5

3.4 Dimensional drawings 3-6

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 3-1
Technical data

3.1 Technical data


Type 3TK2845-.....
Standards EN 60204-1, EN ISO13489-1, IEC 62061
EMC EN 60947-5-1
Category in accordance with DIN EN13841-1 PLe /CAT 4
Safety Integrity Level Claim Limit (SIL CL) 3
Test verification documents TÜV
Overvoltage category II
Rated insulation voltage Ui 300 V
Rated impulse withstand voltage Uimp 2,5 kV
Rated control supply voltage Vs 24 V DC
Operating range 0,85 to 1,15 U s
Rated power 5W
Short-circuit protection Semiconductor outputs: Short-circuit-proof
Use 4 A gL/gG or quick-response fuse-links for
the floating safe outputs, e.g. LV HRC type 3NA,
DIAZED type 5SB, NEOZED type 5SE
Switching frequency z during rated operation 2000 1/h
Response time Max. 60 ms
Release time, (stop category 0) in the case of 45 ms
EMERGENCY-STOP
Release time, (Stop category 1) at the safe Max. 300 seconds (adjustable)
outputs during EMERGENCY-STOP
Supply power buffering 25 ms
Recovery time during EMERGENCY-STOP/ At least 200 ms/at least 8 seconds
power failure
Minimum EMERGENCY-STOP command time 30 ms
START button command time 0.2 to 5 seconds
Permissible ambient temperature Ta during –25 to +60 °C/–40 to +80 °C
operation and storage
Total resistance of sensor circuit RSG Max. 250Ω
Total capacity of sensor circuit C SG max. 500 nF
Degree of protection according to EN 60529, IP20
enclosure/terminals
Touch protection, DIN VDE 0106, Part 100 Finger-safe
Weight 0.4 kg
Permissible mounting position Any
Shock resistance Sine wave 8/10 and 15/5 g/ms
PFHD 6.86 x 10 -9
PFD 6.1 x 10 -4
Table 3-1: Technical data

3TK2845 Multifunction Device Manual


3-2 NEB926208722000/RS-AC/005
Technical data

Type 3TK2845-.....
HFT 1
Lifetime 20 years
SFF [%] > 90 %
T1 20 years
Table 3-1: Technical data (Contd.)

Data sheet
You can find all the technical data of the product in the
Siemens Industry Online Support.

1. Enter the full article number of the desired device in the "Product" field, and
confirm with the Enter key.
2. Click the "Technical data link.

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 3-3
Technical data

Rated operating currents Ie in accordance with IEC 60 947-5-1

Notice
A gL/gG 4 A or quick-response fuse (DIN EN60947-5-1) must be connected
upstream of the device as short-circuit protection (For information, refer to
chapter 3.2).

Utiliza-
Rated operational Rated opera-
Terminal(s) tion cate-
voltage Ue tional current Ie
gory

13, 14; 33, 34; 37, 38 DC-13 24 V 1.0 A

13, 14; 33, 34; 37, 38 AC-15 230 V 3.0 A

24; 44; 48 DC-13 24 V 1,0 A

52 DC-13 24 V 0.5 A
Table 3-2: Rated operational currents Ie

3.2 Terminals

The 3TK2845 multifunction device has a total of 24 terminals available either as


screw terminals or spring-loaded terminals, which are suitable for the following
connection cross sections:

3TK2845-1... 3TK2845-2...

0,8 ... 1.2 Nm



∅ 5 ... 6 mm / PZ2 7 ... 10.3 lb-in
10 1 x 0.5 ... 4.0 mm²
2 x 0.25 ... 1.5 mm²
2 x 0.5 ... 2.5 mm²
10 2 x 0.5 ... 1.5 mm²
2 x 0,25 ... 1.5 mm²
1 x 0.5 ... 2.5 mm²
10
— 2 x 0,25 ... 1.5 mm²

AWG 2 x 20 to 14 2 x 24 to 16

The rated supply voltage Us (24 V DC) is applied at terminals A1(L+) and A2(M).

The terminals have degree of protection IP20 according to EN 60 529.

Protection against direct contact is given as shock-hazard protection according


to DIN EN 50274 (VDE 0660, Part 514).

3TK2845 Multifunction Device Manual


3-4 NEB926208722000/RS-AC/005
Technical data

3.3 Terminal assignment

3TK2845-1DB40 3TK2845-1EB40 3TK2845-1DB41/42/44 3TK2845-1EB41/42/44


3TK2845-1HB40 3TK2845-1HB41/42/44
3TK2845-1FB40 3TK2845-1FB41/42/44
3TK2845-1GB40 3TK2845-1GB41/42/44

1 Y11 Y12 Y35 Y21 Y22 1 Y11 Y12 Y32 Y21 Y22 1 Y11 Y12 Y35 Y21 Y22 1 Y11 Y12 Y35 Y21 Y22

A1+ 24V
DC
Y41 Y42 Y65 Y51 Y52 A1+ 24V
DC
Y41 Y42 Y65 Y51 Y52 A1+ 24V
DC
Y41 Y42 Y65 Y51 Y52 A1+ 24V
DC
Y41 Y42 Y65 Y51 Y52

3TK28 3TK28 3TK28 3TK28


SIRIUS SIRIUS SIRIUS SIRIUS
DEVICE DEVICE DEVICE DEVICE
1,5 1,5
1 2 1 2
14 13 14 13 14 13 14 13
0,5 2,5 0,5 2,5
24 A1 24 A1 24 A1 24 A1
0,05 3s 0,05 3s
34 33 Y12/22 34 33 Y12/22 38 37 Y12/22 38 37 Y12/22
44 Y42/52 44 Y42/52 48 Y42/52 48 Y42/52
1 Y72/82 1 Y72/82 1 Y72/82 1 Y72/82

*E01* 3TK2845-1.... *E01* 3TK2845-1EB40 *E01* 3TK2845-1.... *E01* 3TK2845-1....

13 14 24 Y72 Y82 A2- 13 14 24 Y72 Y82 A2- 13 14 24 Y72 Y82 A2- 13 14 24 Y72 Y82 A2-

33 34 44 Y34 Y64 52 33 34 44 Y34 Y64 52 37 38 48 Y34 Y64 52 37 38 48 Y34 Y64 52

Fig. 3-1: Terminal assignment

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 3-5
Technical data

3.4 Dimensional drawings

45
115
a
7,2 7,2 2,9 b
118,5 x 37
138,5 x 37

5
91,5
68,2

75,1
98,4
102

d
c
28,8

6
Fig. 3-2: Dimensional drawing

3TK2845-1... 3TK2845-2...

a 94 -

b 65 -

c 82,6 84,8

d 105,9 107,7

3TK2845 Multifunction Device Manual


3-6 NEB926208722000/RS-AC/005
Mounting, wiring, commissioning 4
Chapter Subject Page

4.1 Mounting and coding 4-3

4.2 Wiring 4-4

4.3 Meaning of the LED indicators 4-6

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 4-1
Mounting, wiring, commissioning

Warning
Hazardous voltage! Can lead to electric shock and burns. Turn off and lock out all
power supplying this device before working on this device.

Notice
Taking the ambient conditions into account, you must install the devices in con-
trol cabinets with the IP32, IP43 or IP54 degree of protection.

Notice
The actuators/sensors must be actuated at least once a year. (Fault detection
according to IEC 62061)

3TK2845 Multifunction Device Manual


4-2 NEB926208722000/RS-AC/005
Mounting, wiring, commissioning

4.1 Mounting and coding


The 3TK2845 multifunction device is designed for snap-on mounting on a 35mm
standard mounting rail complying with DIN EN 60 715. The devices can also be
screw mounted with two push-in lugs, order number 3RP1903.
35 mm standardmounting rail
3RP1903

Fig. 4-1: 3TK2845 multifunction device for snap-on or screw mounting

Removable terminals simplify exchanging the device according to need. The ter-
minals are coded to prevent confusion.

Warning
Before replacing the terminals, you must disconnect the system and device
from the power supply.

The terminal blocks can be disconnected in the order a, b and can be connected
in the order c, d.

b D
C

c
B
a A

A, B, C, D:
Coding
d

Fig. 4-2: Mounting and coding of the removable terminals

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 4-3
Mounting, wiring, commissioning

4.2 Wiring
The 3TK2845 multifunction device is available either with screw terminals or
spring-loaded terminals.
Please refer to the following table for details of the required connection cross-
sections and maximum permissible torques.
1
3RP1903
DIN ISO 2380 -1A 0,5 x 3

7
~10°
7
2 8
~10°

3TK2845-1... 3TK2845-2...
5 3

0.8 ... 1.2 Nm



4 ∅ 5 ... 6 mm / PZ2 7 ... 10.3 lb-in
10 1 x 0.5 ... 4.0 mm²
2 x 0.25 ... 1.5 mm²
4 2 x 0.5 ... 2.5 mm²
10 2 x 0.5 ... 1.5 mm²
2 x 0.25 ... 1.5 mm²
1 x 0.5 ... 2.5 mm²
10
— 2 x 0.25 ... 1.5 mm²
5
3 AWG 2 x 20 to 14 2 x 24 to 16

Fig. 4-3: Overview of the connection cross sections/maximum permissible torques

Warning
Use a power supply unit with protective extra-low voltage (SELV, PELV). This
means that these modules must only be subjected to a voltage of Um in the
event of a fault. The following applies to this switching device: Um < 60.0 V.
You can find more detailed information about protective extra-low voltage in the
data sheets of the power supplies to be used.

Caution
For the non-floating outputs (24, 44, 48, 52) it must be ensured that the actuators
or loads to be switched have the same ground potential as the 3TK2845.

Notice
External loads must be equipped with a protective circuit which is suitable for the
respective load (e.g. RC elements, varistors, suppressors) to reduce
electromagnetic interference and to enhance the service life of the OSSD.

3TK2845 Multifunction Device Manual


4-4 NEB926208722000/RS-AC/005
Mounting, wiring, commissioning

The 3TK2845 multifunction device is ready for operation after the power supply
is connected at terminals A1 and A2. The device runs a self-test during which
the proper functionality of the internal electronics is checked. The internal circuit
elements are cyclically monitored for faults during operation.

If any sensor responds, the multifunction device will be safely switched off.

Devices equipped with a time delay (3TK2845-B41/B42/B44) have a sealable


cover cap to protect the set delay time against unauthorized changes.

It can be ordered as an accessory with the order number 3RP1902.

4
4
3
1
5

2
3RP1902
Fig. 4-4: Sealable cover cap

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 4-5
Mounting, wiring, commissioning

4.3 Meaning of the LED indicators


Nine LEDs indicate the operating status and the function of the device.
Display during self-test:
2 s lamp test: all LEDs light up, i.e. the two-color "DEVICE" LED lights up yellow
and then the device LED flashes green for approximately 4 seconds.

LED Meaning
Device OFF No supply voltage / supply voltage too low or internal fuse tripped.
Green Supply voltage in the permissible operating range
Green flashing Self-test after restart
Red Device defective → replace device
Red flashing Sensor fault (cross-circuit, configuration changed during operation)
→ remedy fault and restart device
14 -- 13 OFF Output passive
Green Output active
24 OFF Output passive
Green Output active
Green flashing Feedback circuit open
34 -- 33 OFF Output passive
(38 -- 37)
Green Output active
44 (48) OFF Output passive
Green Output active
Green flashing Feedback circuit open
Y 12/22 OFF Input passive (switch-on condition not fulfilled)
Green Input active
(If device flashes red: the configuration has been changed during
operation)
Green flashing Cross-circuit at the input (if device flashes red),
Sensor simultaneity not fulfilled
Y 42/52 OFF Input passive (switch-on condition not fulfilled)
Green Input active
(If device flashes red: the configuration has been changed during
operation)
Green flashing Cross-circuit at the input (if device flashes red),
Sensor simultaneity not fulfilled
Y 72/82 OFF Input passive
Green Input active
Table 4-1: Meaning of the LED indicators

3TK2845 Multifunction Device Manual


4-6 NEB926208722000/RS-AC/005
Applications 5
The following chapter lists common applications. The 3TK2845 multifunction
device can be used for all of these applications. The advantage of using this
device is the fact that several safety-related functions, e.g. protective door mon-
itoring, monitoring functions using contactless protective equipment (ESPE),
such as light curtains, safety shutdown mats and EMERGENCY-STOP control
devices, can be implemented using only one 3TK2845 multifunction device
rather than using several safety relays. In addition, the device is also suited for
operational switching, cascading and adding safety relays (either using contacts
or switching electronically).

This chapter contains only a few examples of possible applications. Depending


on the application, the wiring can differ from the examples shown here.

Chapter Subject Page

5.1 3TK2845-.HB40 "Monitored start and automatic start", 5-2


instantaneous outputs

5.2 3TK2845-.HB41 "Monitored start and automatic start", time- 5-4


delayed outputs

5.3 3TK2845-.DB40 "Monitored startup", instantaneous outputs 5-6

5.4 3TK2845-.DB41 "Monitored start", time-delayed outputs 5-8

5.5 3TK2845-.EB40 "Enabling button" 5-10

5.6 3TK2845-.FB41/2/4 "Spring force interlocked tumbler" 5-12

5.7 3TK2845-.GB41/2/4 "Magnetic force interlocked tumbler" 5-14

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-1
Applications

5.1 3TK2845-.HB40 "Monitored start and automatic start",


instantaneous outputs
Brief description:
Monitoring an EMERGENCY-STOP control device with monitored start and a protec-
tive door with automatic start and maintenance.

Properties:
Stop category 0 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.HB40 on page 2-9

Note:
Connecting several position switches in series for protective door monitoring is
not permissible for PLe according to DIN EN ISO 13849-1 (fault detection).

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-2 NEB926208722000/RS-AC/005
Applications

L+(24V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22

3TK2845-.HB40
13 14 24 Y72 Y82 A2 33 34 44 Y34 Y64 52

Q1-Q4

START
Q1 Q3
Q2 Q4

M1 M2 Q1 Q2 Q3 Q4
M
Fig. 5-1: Monitored start and automatic start, instantaneous outputs;
max. achievable PL = e; SIL CL= 3

L+(24 V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22
7.+%

13 14 24 Y72 Y82 A2 33 34 44 Y34 Y64 52


START

Q1 Q2
Q1 Q2

M1 M2
Q1 Q2
M

Fig. 5-2: Monitored start and automatic start, instantaneous outputs;


max. achievable PL = c; SIL CL = 1

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-3
Applications

5.2 3TK2845-.HB41 "Monitored start and automatic start",


time-delayed outputs
Brief description:
Monitoring an EMERGENCY-STOP control device with monitored start and a protec-
tive door with automatic start and maintenance.

Properties:
Stop category 0/1 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.HB41 on page 2-9

Note:
Connecting several position switches in series for protective door monitoring is
not permissible for PLe according to DIN EN ISO 13849-1 (fault detection).

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-4 NEB926208722000/RS-AC/005
Applications

L+(24V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22

3TK2845-.HB41
13 14 24 Y72 Y82 A2 37 38 48 Y34 Y64 52

Q1-Q4

START
Q1 Q3
Q2 Q4

Q1 Q2
Q1 Q2 Q3
Q3 Q4 Q4
M1 M2
M

Fig. 5-3: Monitored start and automatic start, time-delayed outputs;


max. achievable PL = e; SIL CL = 3

L+(24 V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22
7.+%

13 14 24 Y72 Y82 A2 37 38 48 Y34 Y64 52


START

Q1 Q2
Q1 Q2

M1 M2 Q1 Q2
M

Fig. 5-4: Monitored start and automatic start, time-delayed outputs;


max. achievable PL = c; SIL CL = 1

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-5
Applications

5.3 3TK2845-.DB40 "Monitored startup", instantaneous


outputs
Brief description:
Monitoring an EMERGENCY-STOP control device and a protective door with moni-
tored start and maintenance.

Properties:
Stop category 0 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.DB40 on page 2-13

Note:
Connecting several position switches in series for protective door monitoring is
not permissible for PLe according to DIN EN ISO 13849-1 (fault detection).

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-6 NEB926208722000/RS-AC/005
Applications

L+(24V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22

3TK2845-.DB40
13 14 24 Y72 Y82 A2 33 34 44 Y34 Y64 52

Q1-Q4

START
Q1 Q3
Q2 Q4

M1 M2 Q1 Q2 Q3 Q4
M

Fig. 5-5: Monitored start, instantaneous outputs; max. achievable PL = e; SIL CL = 3

L+(24 V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22
7.'%

13 14 24 Y72 Y82 A2 33 34 44 Y34 Y64 52


START

Q1 Q2
Q1 Q2

M1 M2
Q1 Q2
M

Fig. 5-6: Monitored start, instantaneous outputs; max. achievable PL = c; SIL CL = 1

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-7
Applications

5.4 3TK2845-.DB41 "Monitored start", time-delayed out-


puts
Brief description:
Monitoring an EMERGENCY-STOP control device with monitored start and a protec-
tive door with automatic start and maintenance.

Properties:
Stop category 0/1 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.DB41 on page 2-13

Note:
Connecting several position switches in series for protective door monitoring is
not permissible for PLe according to DIN EN ISO 13849-1 (fault detection).

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-8 NEB926208722000/RS-AC/005
Applications

L+(24V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22

3TK2845-.DB41
13 14 24 Y72 Y82 A2 37 38 48 Y34 Y64 52

Q1-Q4

START
Q1 Q3
Q2 Q4

Q1 Q2
Q1 Q2 Q3
Q3 Q4 Q4
M1 M2
M

Fig. 5-7: Monitored start, time-delayed outputs; max. achievable PL = e; SIL CL = 3

L+(24 V DC)

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y35 Y21 Y22
7.'%

13 14 24 Y72 Y82 A2 37 38 48 Y34 Y64 52


START

Q1 Q2
Q1 Q2

M1 M2
Q1 Q2
M

Fig. 5-8: Monitored start, time-delayed outputs; max. achievable PL = c; SIL CL = 1

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-9
Applications

5.5 3TK2845-.EB40 "Enabling button"


Brief description:
Monitoring an EMERGENCY-STOP control device and a protective door with moni-
tored start and maintenance with enabling button.

Properties:
Stop category 0 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.EB40 on page 2-18

Note:
Terminal Y32 can be used to choose between autostart (24 V) and monitored start
(0 V) for the protective door input (Y41/Y42 and Y51/Y52).

Note:
Connecting several position switches in series for protective door monitoring is
not permissible for PLe according to DIN EN ISO 13849-1 (fault detection).

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

Notice
When faults are ruled out (protected laying of the control lead to cascading
input 1), the application's safety category corresponds to that of the higher-level
safety relay.

3TK2845 Multifunction Device Manual


5-10 NEB926208722000/RS-AC/005
Applications

L+(24V DC)

START

A1 1 Y32 Y11 Y12 Y34

3TK2841-1BB40
Y35 Y21 A2 Y22 14 24

L+(24V DC) M Enabling button


Zustimmschalter
I II III

A1 Y41 Y42 Y65 Y51 Y52 1 Y11 Y12 Y32 Y21 Y22

13 14 24 Y72 Y82 A2 33 34 44 Y34 Y64 52


3TK2845-.EB40

Q1-Q4

Q1 Q3
Q2 Q4
Q1 Q2 Q3 Q4
M1 M2 M

Fig. 5-9: Enabling button; max. achievable PL = e; SIL CL = 3

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-11
Applications

5.6 3TK2845-.FB41/2/4 "Spring force interlocked tumbler"


Brief description:
Monitoring an EMERGENCY-STOP control device and a protective door with tum-
bler (spring force, interlocked when de-energized).

Properties:
Stop category 0 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.FB4. on page 2-22

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-12 NEB926208722000/RS-AC/005
Applications

closed open

actuator
11 21
E1(+)

E 2 (-) 12 22
magnet
protective door
51 52
21 22
41 42

3SE5322-0SD21

13 14
3SE5112-0CH01

L+(24 V DC )

3TK2845-.FB41/2/4
A1 Y41 Y42 Y65 Y51 Y52 1 Y 11 Y12 Y 35 Y21 Y22

13 14 24 Y72 Y82 A2 37 38 48 Y 34 Y64 52


START

Q1
protective
enable
door

Q2 Q1
Q2

M1
1 Q2
Q1
M

Fig. 5-10: Spring force interlocked tumbler; closed and locked;


max. achievable PL = e; SIL CL = 3

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-13
Applications

5.7 3TK2845-.GB41/2/4 "Magnetic force interlocked tumbler"


Brief description:
Monitoring an EMERGENCY-STOP control device and a protective door with tum-
bler (magnetic force, interlocked when switched on).

Properties:
Stop category 0/1 according to EN 60204-1;
Two solid-state enabling circuits;
Two floating enabling circuits;
One solid-state signaling output;
Us 24 V DC

Function:
See Status diagram: 3TK2845-.GB4. on page 2-25

Notice
The only sensors that can be used are safety sensors with positive-opening con-
tacts.

3TK2845 Multifunction Device Manual


5-14 NEB926208722000/RS-AC/005
Applications

closed open

actuator
11 21
E1(+)

E 2 (-) 12 22
magnet
protective door
51 52
21 22
41 42

3SE5322-0SB21

13 14
3SE5112-0CH01

L+(24 V DC )

A1 Y41 Y42 Y65 Y51 Y52 1 Y 11 Y12 Y 35 Y21 Y22 3TK2845-.GB41/2/4

13 14 24 Y72 Y82 A2 37 38 48 Y 34 Y64 52


START

Q1
protective
enable
door

Q2 Q1
Q2

M1
Q1 Q2
M

Fig. 5-11: Magnetic force interlocked tumbler; closed and locked;


max. achievable PL = e; SIL CL = 3

3TK2845 Multifunction Device Manual


NEB926208722000/RS-AC/005 5-15
Applications

3TK2845 Multifunction Device Manual


5-16 NEB926208722000/RS-AC/005
FROM (please complete):

Name

TO: Company/Department
SIEMENS AG
DF CP PRM IM 2
Werner von Siemens Str. 48 Address

92220 Amberg/Germany
Phone

Fax: 09621 / 80-3337


Fax

Manual for Safety Relays 3TK2845 Multifunction Device

Did you come across any mistakes while reading this manual? If so, please
use this form to tell us about them.
We appreciate any comments and suggestions for improvement.