You are on page 1of 4

KD22

Engine type 3029DSG20


Alternator type KH00404T
Performance class G3

GENERAL CHARACTERISTICS
Frequency (Hz) 50
Voltage (V) 400/230
Standard control panel APM303
Optional Control Panel APM403
POWER
ESP PRP
Voltage Standby Amps
kWe kVA kWe kVA

415/240 17.6 22 16 20 31
400/230 17.6 22 16 20 32
380/220 17.6 22 16 20 33

DESCRIPTIVE
DIMENSIONS COMPACT VERSION
Kohler Co. Provides one-source responsibility for the Length (mm) 1700
generating system and accessories Width (mm) 896
The generator set and its components are prototype- Height (mm) 1181
tested, factory-built, and production-tested
Dry weight (kg) 649
A one-year limited warranty covers all systems and
components Tank capacity (L) 100
Mechanic governor
Mechanically welded chassis with antivibration
suspension DIMENSIONS SOUNDPROOFED VERSION
Main line circuit breaker Commercial reference of the enclosure M137
Radiator for core temperature of 48/50°C max with Length (mm) 2100
mechanical fan 938
Width (mm)
Protective grille for fan and rotating parts (CE option)
Height (mm) 1285
9 dB(A) silencer supplied separately
Dry weight (kg) 795
Charger DC starting battery with electrolyte
12 V charge alternator and starter Tank capacity (L) 100
Delivered with oil and coolant -30°C Acoustic pressure level @1m in dB(A) 75
Manual for use and installation Sound power level guaranteed (Lwa) 92
Acoustic pressure level @7m in dB(A) 63
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03001 (KD22) 05/19
KD22
ENGINE CHARACTERISTICS

GENERAL ENGINE DATA EXHAUST


Engine model JOHN DEERE Exhaust gas temperature @ ESP 50Hz (°C) 555
Engine type 3029DSG20 Exhaust gas flow @ ESP 50Hz (L/s) 78
Air inlet Athmo Max. exhaust back pressure (mm H2O) 625
Cylinders arrangement L
Number of cylinders 3
FUEL
Displacement (L) 2.91
Consumption @ 110% load (L/h) 8.5
Charge Air coolant -
Consumption @ 100% load (L/h) 7
Bore (mm) x Stroke (mm) 106 x 110
Consumption @ 75% load (L/h) 5
Compression ratio 17.2 : 1
Consumption @ 50% load (L/h) 3.6
Speed (RPM) 1500
Pistons speed (m/s) Maximum fuel pump flow (L/h) 111
5.5
Maximum stand-by power at rated
31
RPM (kW) OIL
Frequency regulation (%) +/- 2.5% Oil capacity (L) 6
BMEP (bar) 7.70 Min. oil pressure (bar) 1
Governor type Mechanical Max. oil pressure (bar) 5
Oil consumption 100% ESP 50Hz (L/h) 0.07
COOLING SYSTEM Oil sump capacity (L) 5.3
Radiator & Engine capacity (L) 16.10
Max water temperature (°C) - HEAT BALANCE
Outlet water temperature (°C) - Heat rejection to exhaust (kW) 31
Fan power (kW) 0.70 Radiated heat to ambient (kW) 6
Fan air flow w/o restriction (m3/s) 1.74 Heat rejection to coolant (kW) 18
Available restriction on air flow (mm
20
H2O)
Type of coolant Glycol-Ethylene AIR INTAKE
Thermostat modulating range HT (°C) - Max. intake restriction (mm H2O) 300
Intake air flow (L/s) 28

EMISSIONS
Emission PM (mg/Nm3) 5% O2 74
Emission CO (mg/Nm3) 5% O2 1165
Emission HC+NOx (g/kWh) 17.4
Emission HC (g/kW.h) 1

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03001 (KD22) 05/19
KD22
ALTERNATOR CHARACTERISTICS

GENERAL DATA OTHER DATA


Alternator type KH00404T Continuous Nominal Rating 40°C (kVA) 20
Number of Phase Three phase Standby Rating 27°C (kVA) 21.5
Power factor (Cos Phi) 0.8 Efficiencies 100% of load (%) 87.4
Altitude (m) 0 to 1000 Air flow (m3/s) 0.088
Overspeed (rpm) 2250 Short circuit ratio (Kcc) 0.64
Number of pole 4 Direct axis synchro reactance unsaturated (Xd) (%) 184.5
Capacity for maintaining short circuit at Quadrature-axis synchro reactance unsaturated (Xq)
Yes 80
3 ln for 10 s (%)
Insulation class H Open circuit time constant (T'do) (ms) 850
T° class (H/125°), continuous 40°C H / 125°K Direct axis transient reactance saturated (X'd) (%) 14.6
T° class, standby 27°C H / 163°K Short circuit transient time constant (T'd) (ms) 44
AVR Regulation Yes Direct axis subtransient reactance saturated (X''d) (%) 8.4
Total Harmonic Distortion in no-load Subtransient time constant (T"d) (ms) 14
3.6
DHT (%) Quadrature-axis subtransient reactance saturated
Total Harmonic Distortion, on load DHT 19.2
2 (X"q) (%)
(%)
Subtransient time constant (T"q) (ms) 10
Wave form : NEMA=TIF <45
Zero sequence reactance unsaturated (Xo) (%) 3.38
Wave form : CEI=FHT <2
Negative sequence reactance saturated (X2) (%) 12.5
Number of bearing Single Bearing Armature time constant (Ta) (ms) 12
Coupling Direct No load excitation current (io) (A) 0.5
Voltage regulation at established rating 1 Full load excitation current (ic) (A) 1.5
(+/- %)
Full load excitation voltage (uc) (V) 15.9
Recovery time (Delta U = 20% 200
transient) (ms) Engine start (Delta U = 20% perm. or 50% trans.)
Protection class IP 23 (kVA) 50.2

Technology Brushless Transient dip (4/4 load) - PF : 0,8 AR (%) 14.1


No load losses (W) 550
Heat rejection (W) 2307
Unbalanced load acceptance ratio (%) 100

DIMENSIONS
Dimensions soundproofed version Dimensions DW compact version
Type soundproofing M137 Type soundproofing -
Length (mm) 2100 Length (mm) 2074
Width (mm) 938 Width (mm) 932
Height (mm) 1285 Height (mm) 1382
Dry weight (kg) 837 Dry weight (kg) 858
Tank capacity (L) 100 Tank capacity (L) 240
Acoustic pressure level @1m in dB(A) 75 Acoustic pressure level @1m in dB(A) -
Sound power level guaranteed (Lwa) 92 Sound power level guaranteed (Lwa) -
Acoustic pressure level @7m in dB(A) 63 Acoustic pressure level @7m in dB(A) -
Dimensions DW soundproofed version Dimensions DW 48h soundproofed version
Type soundproofing M137-DW Type soundproofing M137-DW48
Length (mm) 2100 Length (mm) 2100
Width (mm) 932 Width (mm) 932
Height (mm) 1486 Height (mm) 1539
Dry weight (kg) 1046 %PdnetE_5% 1053
Tank capacity (L) 240 Tank capacity (L) 470
Acoustic pressure level @1m in dB(A) 75 Acoustic pressure level @1m in dB(A) 75
Sound power level guaranteed (Lwa) 92 Sound power level guaranteed (Lwa) 92
Acoustic pressure level @7m in dB(A) 62 Acoustic pressure level @7m in dB(A) 62

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03001 (KD22) 05/19
KD22
CONTROL PANEL

APM303, comprehensive and simple APM403, basic generating set and power plant control

The APM303 is a versatile unit which can be operated in


manual or automatic mode. Equipped with an LCD screen,
the user-friendly APM303 offers high-quality basic functions The APM403 is a versatile control unit which allows
to guarantee simple, reliable operation and supervision of operation in manual or automatic mode
your generating set. It offers the following features: Measurements : voltage and current
Measurements: kW/kWh/kVA power meters
phase-to-neutral and phase-to-phase voltages, active power Standard specifications: Voltmeter, Frequency meter.
currents, effective power, power factors, Kw/h energy meter Optional : Battery ammeter.
Fuel, oil pressure and coolant temperature levels J1939 CAN ECU engine control
Supervision: Alarms and faults: Oil pressure, Coolant temperature,
Modbus RTU communication on RS485 Overspeed, Start-up failure, alternator min/max, Emergency
Reports: stop button.
2 configurable reports Engine parameters: Fuel level, hour counter, battery
Safety features: voltage.
Overspeed, oil pressure, coolant temperatures, minimum Optional (standard at 24V): Oil pressure, water temperature.
and maximum voltage, minimum and maximum frequency, Event log/ Management of the last 300 genset events.
maximum current, maximum active power Mains and genset protection
Phase sequence Clock management
Traceability: USB connections, USB Host and PC,
Stack of 12 stored events Communications : RS485 INTERFACE
For further information, please refer to the data sheet for the ModBUS protocol /SNMP
APM303. Optional : Ethernet, GPRS, remote control, 3G, 4G,
Websupervisor, SMS, E-mails

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03001 (KD22) 05/19