You are on page 1of 1

This example is with Threshold #9 set to 90%

APM802 Load Shed

Power
threshold
reaches or
exceeds 90%

5 second
delay

Load 90% Gen runs


5 second
shed 1 Yes threshold No
delay normally
active active?

90%
60 second Load 1
threshold No
delay active
active?

Yes 15 second
delay

5 second
delay No

90%
Load 5 second
Yes threshold
shed 2 delay
active?

90%
45 second Load 2
threshold No
delay active
active?

Yes 15 second
delay

5 second
delay
No

90%
Load 5 second
Yes threshold
shed 3 delay
active?

90%
30 second Load 3
threshold No
delay active
active?

Yes 15 second
delay

5 second
delay No

90%
Load 5 second
Yes threshold
shed 4 delay
active?

90%
15 second Load 4
threshold No
delay active
active?

Yes

Gen will stay


running
assuming the
load stays at
or below
100% of rated

You might also like