Panel Board OT HVAC panel board


Type of panel board Outdoor panel
Cable Entry Cable entry Bottom

AHU Panel Board : 3 Nos AHU 5000CFM/3.7KW Induction Motor 3Ph DOL Start and 1No AHU
Motor 3Ph DOL Start , Speed control Via VFD in Steps using Push Botton UP/DOWN, required
control on terrace and remote control from second floor OT.
Panel Board Description
Panel Board VRV/DX Outdoor of OT : Outdoor unit VRV ( 18HP 3Nos and 20HP 1Nos ) and Out
and 5.5TR 4Nos ) and Povisoin should be provided for 4Nos Heaters of Rating 10KW

VFD Make LS/ABB/Schinder/Allen Bradley


Breaker, MCB, MCCB ABB/Schiender/LT

Logic Operation of panel Board


Panel-1 Local Control from terrace floor Panel-2 Remote Control from Second floor OT
Push Botton ON/OFF VFD Speed UP/Down Reset of VFD Push Botton ON/OFF
Indication RYB, ON/OFF, Trip for all 4 AHU's Indication RYB, ON/OFF, Trip for all 4 AH
Protection MPR-D2 Relay, OU/UV, OC, phase sequence relay Protection Same as Local Panel
Meter Digital Energy Consumption
VFD View Glass front View for all 4AHU's

Logic Operation of VRV/DX panel Board


VRV 18HP 3Nos VRV Outddor Unit + 20HP 1Nos VRV Outdoor Unit
DX 11 TR DX 4nos and 5.5 TR DX 4Nos
Heater 10KW 3Phase Heater for Each OT AHU

SPOC M Devadas
Contact 9640430438
Date 28th July 2023
Timeline Urgent
or 3Ph DOL Start and 1No AHU 550CFM/5KW Induction
h Botton UP/DOWN, required two panel board for local

3Nos and 20HP 1Nos ) and Outdoor unit DX ( 11TR 4Nos


ters of Rating 10KW

trol from Second floor OT


VFD Speed UP/Down Reset of VFD
RYB, ON/OFF, Trip for all 4 AHU's, Manul/Auto
Same as Local Panel