NOTES:-

(SCALE 1:30)

SPACING OF STIRRUPS NOT MORE THAN 100mm


OVER LAPPING LAP LENGTH = 60 X BAR DIAMETER.

Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Y9 Y10 Y11 Y12

Ld+10d
TOP CONTINUOUS BAR
2215 2875 3085 3590 3100 4460 2895 3430 1960 800 EXTRA REINF. TOP
NOTE:-
690 SHEAR REINF.AS/SCHEDULE

Ld+10d
RAMP TO RAMP FROM Ld = 49d
GR. LVL GR. LVL EXTRA REINF. BOTTOM

X1 BOTTOM CONTINUOUS BAR


UP
IS PROHIBITED IN THIS REGIONS SECTION X-X
TYPICAL BEAM LAPPING DETAIL
150mm SUNK
4865

150mm SUNK 2 2
TOC LVL.
-2650
DN X
3 3
d+c d c f e e+c d+c d c

Ld+10d
X2
TOC LVL.
2345

-2800

Ld+10d
a a
b X b b
X3 a+b a+b
1070

TYPICAL BEAM ELEVATION DRAWN


X4 REV BY & DATE STATUS

X
3165

d+c d c f e e+c e+c

Ld+10d
X5 ST-1

Ld+10d
a
b X b
a+b a
5180

1 1

TYPICAL CANTILEVER BEAM ELEVATION

X6
5220

X7
5175

LECTURE THEATRE AT WEST KIDWAI


NAGAR, VMMC COLLEGE & SAFDARJUNG
HOSPITAL, NEW DELHI
+2800
T.O.C +2650
T.O.C
X8

150
450
ST-1
3100

B5 230
SECTION 3-3
(SCALE 1:30)
X9 ARCHITECTS
1115

X10 TYPICAL CUTOUT DETAIL


2530

ARINEM
TOC LVL.
-2800 1st Floor Akash II,
31, Gokhle Marg, B - 1/3,Hauz Khas,
Lucknow-226001 U.P. (INDIA)
X11 Ph.: +91 522-4107252
New Delhi-110016(INDIA)
Ph.: 011-41525299,
Fax: +91 522-2209800
2200

1 1 RETAINING WALL RETAINING WALL E-mail : delhi@arinem.com


E-mail : admin@arinem.com

+2800 SLAB +2800 SLAB


X12 T.O.C +2650 T.O.C
T.O.C

150
UP Engineering Design & Research Pvt. Ltd.
Corporate Office:
E

900
900
D-152 (First Floor)
4595

TOC LVL. RETAINING WALL RETAINING WALL Galaxy North Avenue-2; Gaur City-2

-1950
-2800
B8
SECTION 1-1
B8
SECTION 2-2
DR Sector-16C Greater Noida (UP)
Cell: +91-9971122470
DN Email: santosh.singh@edr-group.com
(SCALE 1:30) (SCALE 1:30) CONSULTING
DN 400 400 ENGINEERS Web: www.edr-group.com
X13
1220

X14
BEAM SCHEDULE FOR UPPER BASEMENT FLOOR

SPACING AT SUPPORT (L/4) SPACING AT CENTER


UPPER BASEMENT FLOOR BEAM LEVEL SIZE BOTTOM MAIN BOTTOM TOP MAIN TOP REINF TOP REINF SIDE FACE ( LEG & DIA OF STRRUPS ( LEG & DIA OF STRRUPS DESIGN BY : BKJ DATE: 11-07-2023
(SCALE 1:100) (WxD) BAR REINF EXTRA BAR LEFT RIGHT BAR
MARK
(a) (b) (c) (d) (e) (f)
DRAWN BY : MDI CHKD : SKS
B1 AS/PLAN 300X900 4-25 2-20 4-20 4-25 4-25 2-16 4L-T10@100c/c 4L-T10@150c/c
SLAB REINF. SCHEDULE B2 AS/PLAN 230X750 3-25 3-20 3-20 3-25 3-25 2-16 2L-T10@100c/c 2L-T10@150c/c DRAWING TITLE :-
B3 AS/PLAN 450X900 4-25 4-20 4-25+ 4-20 4-32 4-25+ 4-20 2-16 4L-T10@100c/c 4L-T10@150c/c
SLAB SLAB BOTTOM REINFORCEMENT TOP REINFORCEMENT B4 AS/PLAN 230X600 3-25 3-16 3-20 3-25 3-25 - 2L-T10@100c/c 2L-T10@150c/c
MARK THK -
FRAMING PLAN & SLAB REINF. DETAIL AT
SHORT SPAN LONG SPAN SHORT SPAN LONG SPAN B5 AS/PLAN 230X450 3-20 2-20 3-16 3-20 3-20 2L-T10@100c/c 2L-T10@150c/c
B6 AS/PLAN 200X450 3-20 - 3-16 2-20 2-20 - 2L-T10@100c/c 2L-T10@150c/c
UPPER BASEMENT FLOOR LEVEL
S1 150 T12@150 c/c T10@200 c/c T12@150 c/c T10@200 c/c
B7 AS/PLAN 230X450 3-20 2-16 3-16 3-20 3-20 - 2L-T10@100c/c 2L-T10@150c/c
S2 175 T12@150 c/c T12@200 c/c T12@150 c/c T12@200 c/c B8 AS/PLAN 400X900 4-25 4-16 4-20 4-25 4-25 2-16 4L-T10@100c/c 4L-T10@150c/c
DRAWING NO:- MISC. REV. NO. - R0