Professional Documents
Culture Documents
YVAM Air-Cooled Centrifugal Liquid Chiller: Field Installation Procedure For YVAM Units With 20 Fans, HFC-134A, 60 HZ
YVAM Air-Cooled Centrifugal Liquid Chiller: Field Installation Procedure For YVAM Units With 20 Fans, HFC-134A, 60 HZ
Chiller
Field Installation Procedure for YVAM Units with 20 Fans,
HFC-134A, 60 Hz
035-28539-000
Safety symbols
The following symbols are used in this document to alert the reader to specific situations:
DANGER
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not
taken.
WARNING
Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment
if proper care is not taken.
CAUTION
Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or
environmental pollution if proper care is not taken or instructions and are not followed.
Note: Highlights additional information useful to the technician in completing the work being
performed properly.
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not to
be connected inside the OptiViewTM cabinet.
Devices such as relays, switches, transducers and controls and any external wiring must not be installed
inside the cabinet. All wiring must be in accordance with Johnson Controls’ published specifications
and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for
damage/problems resulting from improper connections to the controls or application of improper
control signals. Failure to follow this warning will void the manufacturer’s warranty and could cause
serious damage to property or personal injury.
Revision notes
Revisions made to this document are indicated in the following table. These revisions are to
technical information, and any other changes in spelling, grammar, or formatting are not included.
Table 1: Revision notes
Affected pages Description
6 Removed reference to 50.20-NM5 from Associated literature section
6 Updated title of Screw and Scroll Chiller to Air-Cooled Chiller in Associated
literature section
Associated literature
Table 2: Associated literature
Manual description Form number
Equipment Pre-Startup and Startup Checklist 160.88-CL1
Unit Startup Checklist 160.88-CL2
Installation, Operation, and Maintenance 160.88-OM1
Unit Power Wiring 160.88-PW1
Field Control Wiring 160.88-PW2
Liquid Chiller Log Sheet 160.88-MR1
Air-Cooled Chiller Long Term Storage 50.20-NM7
Nomenclature
Figure 1: System nomenclature
Chiller components
See Figure 5, Figure 6, and Figure 7 for the major components of the YVAM chiller.
CAUTION
The Johnson Controls warranty may be voided if the following restrictions are not adhered to.
• Do not open valves or connections under any circumstances because such action will result in
loss of the factory refrigerant (Form 1) or nitrogen charge (Form 2).
• Do not dismantle or open the chiller for any reason except under the supervision of a
Johnson Controls representative.
WARNING
Rigging and lifting should only be done by a professional rigger in accordance with a written rigging
and lifting plan. The most appropriate rigging and lifting method depends on job specific factors, such
as the rigging equipment available and site needs. A professional rigger must determine the rigging
and lifting method to be used. It is beyond the scope of this manual to specify rigging and lifting
details.
Scope
This procedure covers the rigging, locating, and final assembly of the YVAM units with total fan
quantity of 20 fans. It is intended for use by the qualified field service teams.
WARNING
The unit must only be lifted by the base frame at the points provided. Never move the unit on rollers,
or lift the unit using a forklift truck. Care must be taken to avoid damaging the condenser cooling fins
when moving the unit.
• The accessory lifting lugs must be inserted into the respective holes in the base frame, noting
the right hand and left orientation of these lugs, and secured using the locking pin.
• The following steps are a guide to help the rigger understand some of the risks that chiller rig
may pose and are not intended to provide the final instructions for the lifting event.
Foundation requirements
Mount units on a flat and level foundation, ground or roof, that can support the entire operating
weight of the equipment. Contact your nearest Johnson Controls Sales Office for shipping and
operating weights.
Ground locations
For ground level locations, the unit must be installed on a suitable flat and level concrete base that
extends to fully support the two side channels of the unit base frame. A one-piece concrete slab
with footings that extend below the frost line is recommended.
The slab must not be tied to the main building foundation because operational noise can telegraph.
Mounting holes are 5/8 in. (15.88 mm) are provided in the base rails for bolting the unit to its
foundation. See Figure 13 for locations.
For ground installations, precautions must be taken to protect the unit from tampering by or injury
to unauthorized persons. Fasteners on access panels can prevent casual tampering. However,
further safety precautions such as unit enclosure options, a fenced-in enclosure, or locking devices
on the panels may be advisable. Check with local authorities for safety regulations.
Roof locations
Sufficient structure must be provided to safely support the entire operating weight of the unit,
service personnel, and service tooling. Do not damage the roof during installation. If the roof
is of bonded construction, consult a building contractor or architect for special installation
requirements. Use spring isolators to minimize vibration transmission into building structure.
The building must have adequate structural support at the spring isolator locations. This is the
region directly under the side and end base rails of the chiller. Johnson Controls do not supply the
structural support.
Seismic applications
Avoid installing chillers on springs or roofs where earthquakes are a risk. Springs and roofs amplify
earthquake forces. Rigidly mounting chillers to ground level concrete pads is the best option for
Other considerations
Any ductwork or attenuators fitted to the unit must not have a total static pressure resistance at full
air flow that exceeds the capability of the fans installed on the unit.
When it is required to surround the units in addition to whatever optional louver package is
selected, make sure that the screening can pass the required chiller cfm without exceeding 0.1 in.
wg (24.9084 Pa) external static pressure.
CAUTION
Clearance dimensions provided in Figure 12 are necessary to maintain good airflow and ensure
correct unit operation. It is also necessary to consider access requirements for safe operation and
maintenance of the unit and power and control panels. Local health and safety regulations, or practical
considerations for service replacement of large components, may require larger clearances than those
recommended.
Clearance requirements
Adequate clearances around the units are required for the unrestricted airflow for the air-
cooled condenser coils and to prevent recirculation of warm discharge air back onto the coils.
If these clearances are not maintained, airflow restriction or re-circulation causes a loss of
unit performance, an increase in power consumption, and can cause the unit to malfunction.
Consideration must also be given to the possibility of down drafts, caused by adjacent buildings,
which may cause recirculation or uneven unit airflow.
The results of the restricted airflow or hot air recirculation can diminish performance as outlined
in Form 150.12-AD2, Air-Cooled Chiller Derating Due to Airflow Restrictions. Johnson Controls’ unit
controls optimize the operation without nuisance high pressure safety cutouts. However, the
system designer must consider the potential for performance degradation.
For locations where significant cross winds are expected, such as exposed rooftops, use an
enclosure of solid or louver type to prevent wind turbulence interfering with the unit airflow.
When units are installed in an enclosure, the enclosure height must not exceed the height of the
unit on more than one side. If the enclosure is of louvered construction, the same requirement of
static pressure loss applies as for ducts and attenuators. See Other considerations.
Note: The isolator Y dimension is hole center base rail to base rail.
Figure 15: One in. deflection spring isolators dimensions, in. (mm)
The following table shows the rated capacity for units with any load point above 1,518 lb (689 kg).
Table 6: Type B model detail
Type B model P/N Color code Rated capacity, lb Rated capacity, kg YORK P/N
029-25334-008 (433997) Dark purple Up to 1,148 Up to 521 029-25334-008
029-25334-009 (433998) Dark green 1,149–1,530 522–694 029-25334-009
029-25334-010 (433999) Gray 1,531–2,040 695–925 029-25334-010
029-25334-012 (434000) White 2,041–2,312 926–1,049 029-25334-012
029-25334-013 (434001) Gray/red 2,313–3,570 1,050–1,619 029-25334-013
Note:
• All dimensions are in in. (mm) in accordance with ANSI Y14.
• Standard finish for housing is powder coated, for spring is powder coated, and for
hardware is zinc electroplate. For color, see the previous tables.
• Installation requires a bolting or anchoring mount to support the structure with a
minimum two 5/8 in. (15.88 mm) diameter bolt or two 1/2 in. (12.7 mm) diameter
concrete anchors.
• All springs are designed for 50% over-travel.
• See Installation of optional spring isolators for installation instructions.
• Isolators with 1 in. (25.4 mm) deflection must be of the same class for the entire unit.
That is, C2Ps must be used at all locations on a selected unit, or all CPs.
• Pin 63 is for isolators, X = no isolators only active selection, 1 = 1 in. (25.4 mm) deflection
not active, N = neoprene not active.
Note:
• All dimensions are in in. (mm) in accordance with ANSI Y14.
• See Installation of optional elastomeric isolators for installation instructions.
• Isolators are mount molded in weather-resistant Durulene™ compound as standard.
Isolators are also available in other materials such as natural rubber, extreme high
temperature silicone, high-damped silicone, nitrile, and EDPM.
• AL = mounting hole center to center spacing.
• HF = free height of mount, before loading. The operating height is calculated by the free
height less the static deflection under load. All dimensions are for reference only.
• Hardware uses zinc electroplate coating.
CAUTION
Power must remain on the chiller whenever the ambient temperature drops below 32°F (0°C) with
water in the evaporator to avoid evaporator damage. To avoid damage, ensure that the correct heater
option for 0°F (-17.8°C) minimum ambient or -20°F (-28.9°C) minimum ambient temperature is installed,
based on the lowest expected ambient temperature at the chiller location.
If glycol is installed in the evaporator, the glycol concentration must ensure that the freeze point is
below the lowest expected ambient temperature at the chiller location to avoid evaporator damage.
CAUTION
Any debris left in the water piping between the strainer and evaporator could cause serious damage
to the tubes in the evaporator and must be avoided. Be sure the piping is clean before connecting it to
the evaporator. Keep evaporator nozzles and chilled liquid piping capped before installation to ensure
construction debris is not allowed to enter.
CAUTION
The installer or user must also ensure that the quality of the water in circulation is adequate, without
any dissolved gases, which can cause oxidation of steel or copper parts within the evaporator.
Permanent strainers
Permanent strainers are required in the evaporator water circuit to protect the chiller and the
pumps, the chilled water air handler coils and controls, and similar components. Johnson Controls
do not provide the permanent strainers. The strainer must be installed in the entering water circuit
upstream and near to the chiller.
Water piping must be arranged to prevent water voids from entering the chiller, and be controlled
as required to avoid rapid flow transients.
If the pumping arrangement is set up to discharge into the chiller, the strainer can be located
upstream of the pumps to protect both the chiller and the pumps. For this type of arrangement, the
piping between the pump and chiller must be thoroughly cleaned before chiller start up.
Stop valves
Stop valves can be provided in the evaporator water piping adjacent to the chiller to facilitate chiller
maintenance. Johnson Controls do not provide the stop valves. To monitor chiller operation, install
site thermometer wells and pressure taps in the piping as close to the chiller as possible.
Flow switches
Thermal dispersion flow switches are factory mounted in the chilled water nozzle and are factory
wired to the chiller OptiView control panel. This solid state flow sensor has no internal moving parts
and consists of a small internal heating element that uses the cooling effect from flowing fluids to
detect that flow has been established.
Wiring connections
Unit power wiring
The factory mounted VSD does not require wiring to the compressor motor. The motor power
wiring is factory connected to the VSD. Refer to the YVAM Unit Wiring and Field Control Modifications
Manual (Form 160.88-PW2). All wiring to the control panel is completed by the factory. A control
power transformer is factory furnished with the VSD.
Power wiring to the chiller is made through the single point power connection enclosure. Refer to
Field connections diagram for Model YVAM Single Point Power Connection Manual (Form 160.88-PW1) for
details.
CAUTION
Do not cut wires to final length or make final connections to the chiller power input terminals without
supervision from a qualified Johnson Controls representative.
Apply insulation
All evaporator parts are factory insulated on the shell surfaces, end sheets, liquid feed line to flow
chamber, compressor suction connection, and evaporator liquid heads and water connection
nozzles.
All facility chilled water piping surfaces must be insulated to prevent condensation from causing
any type of operational heat loss or component damage on all piping upstream and downstream of
the chilled water evaporator waterbox nozzles. Johnson Controls do not insulate the facility chilled
water piping surfaces.
WARNING
All appropriate electrical safety measures must be followed when testing these heaters since these
circuits will be energized.
CAUTION
The evaporator water loop must be filled before conducting the following tests to prevent damage to
the heaters for the evaporator related components.
5. Screw the fitting into the port until the back-up washer contacts the face of the port. Light
wrenching may be necessary.
6. To align the tube end of fitting to accept incoming tube or hose assembly, unscrew by
required amount, but not more than one full turn. More than one turn makes the locknut
push the O-ring into the machine threads beyond the fitting land area during Step 7.
7. Use two wrenches to hold the fitting in the required position. Tighten the locknut to the
appropriate torque value shown in Table 9or Table 10.
8. Inspect to ensure that O-ring is not pinched and that the back-up washer seats flat on face of
port.
Table 12: Two-pass and three-pass compact 150 psi nozzle arrangements
Two-pass nozzle arrangements Three-pass nozzle arrangements
In Out In Out
Lower rear side Upper rear side Lower rear side Upper front side
Rear = opposite VSD end Front = VSD end
Table 13: Two-pass and three-pass compact 150 psi nozzle sizes
Evaporator code Condenser Nozzle size, in. (mm)
Two-pass Three-pass
EB2514 25 mm 4G microchannel 6 (152) 4 (102)
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius (°C), subtract 32° and multiply by 5/9 or
0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (for example, a range of 10°F) from Fahrenheit to Celsius, multiply
by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6°C range