YVAG12~18 YVAG020~040
YMAA/YVAE YCAE-X/H YCAE130G-0B YVAG
Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Contents
1) Introduction and welcome
2) Safety
3) Basic electrical fundamentals
4) YVAG
5) YMAA
6) YCAE-X
2 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Introduction and welcome
3 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
What can you know and learn from this training ?
1. Electrical Safety & Basic electrical fundamentals
2. Panel Position on the Chiller & Panel Layout
3. Communication Architecture
4. Inverter Driver
5. Control Board
6. SC-EQ Kit
7. Electronic Motor Protector
8. Overload Relay
9. Electrical data and Power Connection
10. Wiring Diagram
11. Fixed pump option for YMAA
12. Temperature sensor R-T Table
13. Field Wiring and check before starting up
4 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Basic Electrical Safety
Insulation test(500VDC)
--Test between live part and ground or device enclosure. Test voltage 500VDC, resistance not less than 5MΩ
--Carry out the test in factory or field after change compressor or fan
Withstand voltage test
--Test between live part and ground or device enclosure. Test voltage 1800VAC at 1S.
--Carry out the test in factory
Ground continuity test
--Test between all ground points and main ground point in panel. Resistance not more than 0.1Ω.
Anti-electric shock
--IP54 enclosure and waterproof cable connector
--Alarm label (Disconnect the power before open the panel door)
--Alarm label (Don’t open the cover until 5 minutes after disconnecting all power for driver)
--Use circuit breaker for Short circuit protection
5 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Basic electrical fundamentals
How to read the wiring diagram ? Line type
1. Basic character and graphic symbol
2. Line type
3. Wire Number
4. Terminal block function
Control Board
5. Notes and comments
6. Main circuit and control circuit Plug
By panel vendor
Wire Number Terminal block
By customer By factory
Character Symbol
Graphic Symbol
Main Circuit
Control Circuit
6 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Basic electrical fundamentals
Main circuit and control circuit
Main Circuit
Control Circuit
Notes
Character
symbol
instruction
7 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Basic electrical fundamentals
Electrical device Character Symbol: -BDP12+EXT
- Format symbol, Represent for component symbol
B Basic letter symbol, Represent for category: sensor or transducer
DP Auxiliary letter symbol, Represent for function: Discharge pressure
1 Serial number: system 1
2 Serial number: 1# device in system 1
+ Link symbol
EXT External device
8 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Basic electrical fundamentals
Electrical device Graphic Symbol
Graphic Character Graphic Character Graphic
Device Device Device
Symbol Symbol Symbol Symbol Symbol
Main circuit Transform
-QMCB -T Plug
breaker er
Coil of Contactor -KM Common Terminal
-SF
or relay -KWP Switch (XTB)
Contactor Main Emergency
-KM -SEM
contact stop switch
-KM
Auxiliary contact Fuse -F
-KWP
Thermal element Solenoid
-FR -YMSV
of Overload Relay valve
Contact of
-FR Motor MC
Overload Relay
9 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG012/014/016/018-0BE
YVAG020/022/025/028/033/040-0AE
YVAG012/014/016/018-0AM
10 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG012~018(0B,CE)
Driver Pump
Filter
Relay
BLDC Fan
Reactor
Pump
Comp
Control TB
Board
YVAG012~018(0B) YVAG012(0B) YVAG014/16/18(0B)
11 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG020~033,040
Fan Comp Driver
BLDC Fan
E-Panel
Control
Board
Filter
Comp
Comp
YVAG020~33
Power TB
Pump Contactor
Comp Driver Power Protector
Reactor
YVAG040
Fan Driver
Reactor
Filter
Fan Power
BD Pump Power
Control TB Contactor
YVAG040
Protector
Board
YVAG020~33
12 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG Main Elec Components
YVAG YVAG020-033- YVAG014/016/018-
Component YVAG040-0AE YVAG012-0AM
012~018-0BE 0AE 0AM
220/230V 1N~ 380/400V 3N~ 380/400V 3N~
Power 220/230V 1N~ 50Hz 220/230V 1N~ 50Hz
50Hz 50Hz 50Hz
13 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG012~018-0BE
DRV-060B-A
14 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG020-033-0AE
N PCB
Function PIN definition
0. symbol
Power
1 R,S,T R,S,T
supply
NF164J
Compresso U0,V0,
DRV-180D-A 2
r output W0
DCL1,
U,V,W
Reactor terminal 1,
3 Reactor
DCL2 2
Pin1 PE
Pin2 /
Control
4 CN331 Pin3 N
power
Pin4 /
Pin5 L
Pin1
Communic
Pin2 GND
5 ation 1 CN38
Pin3 A
(RS485)
Pin4 B
Pin1
Communic
Pin2 GND
6 ation 2 CN2
Pin3 A
(RS485)
Pin4 B
7 63H PCN2 /
5437413 Control
Pin1 15V
(YORK-IO-002+IPU3) 8
power output
CN4 Pin2 5V
Pin3 GND
Pin1 P(DC+)
DC Power Pin2 NA
9 CN28
output Pin3 NA
Pin4 N(DC-)
15 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG040-0AE
NF165J
Control Board
Rectifier Diode
16 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YVAG012-0AM YVAG014/016/018-0AM
17 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Electrical Data of YVAG
YVAG020/0 YVAG028/0
MODEL TYPE YVAG012 YVAG014 YVAG016 YVAG018 YVAG025 YVAG040
22 33
Maximum Operating
24A 33A 33A 36A 17A 19A 21A 29A
Current
Recommended Minimum
4mm2 6mm2 6mm2 6mm2 4mm2 4mm2 4mm2 6mm2
Conductor Size
Recommended Breaker
C type C type C type C type C type C type C type C type
(EARTH LEAKAGE
32A 2P 40A 2P 40A 2P 50A 2P 25A 4P 25A 4P 32A 4P 40A 4P
PROTECTOR)
18 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YMAA/YVAE
YCAE-X
YCAE-XH
YCAE130G-0B
19 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YMAA45/65 & YCAE65X
Micro Power Relay Control
Panel is behind
Breaker Protector Board
EC MF1
of the cover
EC
Emergency
Fan
Button
Control
Filter
Panel
HMI
YCAE65X
SmartviewⅡ
Protector
12VDC
Contactor
Main
Control
Contactor Power Control TB
Board
Driver
& Overload Breaker
Relay
Fan
YMAA45/65
Control
Power TB
TB
Compressor
Contactor YCAE65X
20 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YMAA80/100/130 & Smartview Ⅱ Box
EC MF2
EC MF1
Contactor
Control
Board
Fan
Smartview Ⅱ Box
Control
Panel Item Indoor Outdoor
Control
Driver
Power TB
TB
Installation Wall mounted Bottom
IP Class IP20 IP54
Contactor
YCAE130X & Overload Relay
21 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YMAA160-260
MF3
MF2
MF1
CONTROL
PANEL
SmartviewⅡ HMI
Emergency
Button
Driver
160/200CE
MF3
HMI
Driver
CONTROL
PANEL
22 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
230/260CE
YCAE130G-0B(Tier2) & YCAE130XH
Fan contactor
ic motor Board
Control
Protecto Board
r Contr
ol TB Control TB
Compressor Micro
Breaker Compressor
Contractor Power TB Contractor
YCAE130G-0B
23 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
YCAE100/130X & YCAE130XH
DRV-180C-A BOX
Filter
Driver BD
Plastic Cover
WARNING
Cooling Fan DC Reactor RISK OF ELECTRICAL SHOCK
AND/OR ELECTRICAL ENERGY -
Driver communicates with main control board HIGH CURRENT LEVELS.
by RS485 CAPACITORS STORE HAZARDOUS
Cooling Fan runs based on the IGBT ENERGY. DO NOT OPEN COVER
UNTIL 5 MINUTES AFTER
temperature DISCONNECTING ALL SOURCES
Circuit breaker is installed in the main control OF SUPPLY.
panel
24 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Communication Architecture
6 channels of RS-485 are supported
A1/B1 for HMI 1
A2/B2 for BAS with Modbus RTU slave
A3/B3 for network thermostat T8600 or
HMI 2
A4/B4 for communication among the
modular chillers
A5/B5 for fan motor
A6/B6 to communicate with INV
compressor driver
Low cost Indoor display(Wire Controller)-
support 16 modules
7” display(Smart View Ⅱ)-Support 32
modules
25 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
SC-EQ Kit
Figure 1 SC-EQ
Figure 2 SC-EQ
Installed in YMAA
Installed in YCAE
371W06163-001
371W06163-002
SC-EQ(031-03610-000)
26 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Electronic Motor Protector
Code Function Code Function Setting value
C01 Overcurrent 27A
E01 Overcurrent
C02 LRA 27X6=162A
E02 Locked rotor C03 Start-up delay 6s
E03 Loss phase C04 Overcurrent 10s
delay
C05 Frequency 50Hz
C06 Fault reset OFF
C07 Fault record Record the last fault
C08 Access OFF
C09 Reset to 显示C09时按住UP+DN持
续8s直到显示“nn”即恢复出
Default 厂值
SET—按住持续3s进入参数设置,更改后按一下SET以示确认;
UP—”+”,持续按住3s数值自动累加;
DN—”-”,持续按住3s数值自动减;
RESET—故障手动复位;退出参数设置;
警告:运行状态禁止按SET键
27 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Overload Relay
CB CB CB CB CB CB CB CB CB
T1N160TMD T1N160TMD T1N160TMD T1N160TMD T1N160TMD T1N160TMD T3N250TMD T3N250TMD T3N250TMD
Circuit breaker Type ABB
R80FFC 3P R80FFC 3P R100FFC 3P R100FFC 3P R160FFC 3P R160FFC 3P R250FFCL 3P R250FFCL 3P R250FFCL 3P
ABB ABB ABB ABB ABB ABB ABB ABB ABB
Hard:2.5-70 Hard:2.5-70 Hard:2.5-70 Hard:2.5-70 Hard:2.5-70 Hard:2.5-70 M8 wire screw M8 wire screw M8 wire screw
Power Cable Connection
Flexible:2.5-50 Flexible:2.5-50 Flexible:2.5-50 Flexible:2.5-50 Flexible:2.5-50 Flexible:2.5-50 on the CB on the CB on the CB
Power Cable Connection Screw M6x20 M6x20 M6x20 M6 M8x20 M8x20 M8x20 M8x20 M8x20
29 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Electrical Data and Power Connection
Model YCAE65X YCAE100X YCAE130X YCAE65XH YCAE130XH
30 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Fixed Pump Option For YMAA45~130
Pump Starter
31 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Resistance-Temperature Table (1)
电阻-温度表RESISTANCE-TEMPERATURE TABLE,R25= 10KΩ±2%,B25/50=3977K±2%
Except Compressor Discharge temp sensor
Temp R(t) Temp R(t) Temp R(t) Temp R(t) Temp R(t) Temp R(t)
(℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ)
-40 334.2 -12 62.6 16 15.1 44 4.5 72 1.6 100 0.7
-39 313.0 -11 59.3 17 14.4 45 4.3 73 1.6 101 0.6
-38 293.4 -10 56.1 18 13.8 46 4.2 74 1.5 102 0.6
-37 275.0 -9 53.2 19 13.1 47 4.0 75 1.5 103 0.6
-36 258.0 -8 50.4 20 12.5 48 3.8 76 1.4 104 0.6
-35 242.1 -7 47.8 21 12.0 49 3.7 77 1.4 105 0.6
-34 227.3 -6 45.3 22 11.4 50 3.6 78 1.3
-33 213.4 -5 43.0 23 10.9 51 3.4 79 1.3
-32 200.5 -4 40.8 24 10.5 52 3.3 80 1.2
-31 188.5 -3 38.7 25 10.0 53 3.2 81 1.2
-30 177.3 -2 36.7 26 9.6 54 3.1 82 1.2
-29 166.8 -1 34.9 27 9.2 55 3.0 83 1.1
-28 156.9 0 33.1 28 8.8 56 2.8 84 1.1
-27 147.8 1 31.5 29 8.4 57 2.7 85 1.0
-26 139.2 2 29.9 30 8.0 58 2.6 86 1.0
-25 131.1 3 28.4 31 7.7 59 2.5 87 1.0
-24 123.6 4 27.1 32 7.4 60 2.5 88 0.9
-23 116.6 5 25.7 33 7.1 61 2.4 89 0.9
-22 110.0 6 24.5 34 6.8 62 2.3 90 0.9
-21 103.8 7 23.3 35 6.5 63 2.2 91 0.9
-20 98.0 8 22.2 36 6.2 64 2.1 92 0.8
-19 92.5 9 21.1 37 6.0 65 2.1 93 0.8
-18 87.4 10 20.1 38 5.7 66 2.0 94 0.8
-17 82.6 11 19.2 39 5.5 67 1.9 95 0.8
-16 78.1 12 18.3 40 5.3 68 1.8 96 0.7
-15 73.9 13 17.4 41 5.1 69 1.8 97 0.7
-14 69.9 14 16.6 42 4.9 70 1.7 98 0.7
-13 66.1 15 15.8 43 4.7 71 1.7 99 0.7
32 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Resistance-Temperature Table (2)
电阻-温度表RESISTANCE-TEMPERATURE TABLE,R25= 50KΩ±2%,B25/50=4000K±2%
Only for Compressor Discharge temp sensor
Temp R(t) Temp R(t) Temp R(t) Temp R(t) Temp R(t) Temp R(t)
(℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ) (℃) (KΩ)
-40 1732.5 -12 315.4 16 75.5 44 22.4 72 7.9 100 3.2
-39 1621.8 -11 298.4 17 72.0 45 21.5 73 7.7 101 3.1
-38 1518.7 -10 282.4 18 68.7 46 20.7 74 7.4 102 3.0
-37 1422.7 -9 267.4 19 65.6 47 19.9 75 7.2 103 2.9
-36 1333.3 -8 253.3 20 62.7 48 19.1 76 6.9 104 2.9
-35 1249.9 -7 240.0 21 59.9 49 18.4 77 6.7 105 2.8
-34 1172.2 -6 227.4 22 57.2 50 17.7 78 6.5 106 2.7
-33 1099.8 -5 215.6 23 54.7 51 17.0 79 6.3 107 2.6
-32 1032.2 -4 204.5 24 52.3 52 16.4 80 6.0 108 2.5
-31 969.2 -3 194.0 25 50.0 53 15.8 81 5.9 109 2.5
-30 910.4 -2 184.1 26 47.8 54 15.2 82 5.7 110 2.4
-29 855.5 -1 174.7 27 45.8 55 14.6 83 5.5 111 2.3
-28 804.2 0 165.9 28 43.8 56 14.1 84 5.3 112 2.3
-27 756.4 1 157.6 29 41.9 57 13.6 85 5.1 113 2.2
-26 711.6 2 149.8 30 40.1 58 13.1 86 5.0 114 2.2
-25 669.7 3 142.3 31 38.4 59 12.6 87 4.8 115 2.1
-24 630.6 4 135.3 32 36.8 60 12.2 88 4.7 116 2.0
-23 594.0 5 128.7 33 35.3 61 11.7 89 4.5 117 2.0
-22 559.7 6 122.4 34 33.8 62 11.3 90 4.4 118 1.9
-21 527.6 7 116.5 35 32.4 63 10.9 91 4.2 119 1.9
-20 497.6 8 110.9 36 31.1 64 10.5 92 4.1 120 1.8
-19 469.4 9 105.6 37 29.8 65 10.1 93 4.0 121 1.8
-18 443.0 10 100.5 38 28.6 66 9.8 94 3.9 122 1.7
-17 418.2 11 95.8 39 27.5 67 9.4 95 3.7 123 1.7
-16 395.0 12 91.3 40 26.4 68 9.1 96 3.6 124 1.7
-15 373.2 13 87.0 41 25.3 69 8.8 97 3.5 125 1.6
-14 352.7 14 83.0 42 24.3 70 8.5 98 3.4
-13 333.5 15 79.1 43 23.3 71 8.2 99 3.3
33 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’
Field Wiring and check before starting up
1. Connect power cable, and power cable size should match the maximum current of the chiller. Every
module should be provided a circuit breaker upstream. Confirm reliable connections.
2. Connect system flow switch on the module 1#. Module flow switch has been installed on every module in
factory.
3. Connect external interlock switch or short-circuit the terminals in panel.
4. Connect remote ON/OFF switch (if necessary).
5. Connect remote cooling/heating mode switch (if necessary).
6. Connect system leaving/return water and ambient temp sensor to module 1#.
7. Connect wire controller or indoor smartview Ⅱ touch screen to module 1#.
8. Connect communication cable for all modules by the way hand in hand.
9. Connect BAS device(if necessary).
10. Set the modus ID for every module.
34 Johnson Controls — Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’