You are on page 1of 126

AlgoRex® CS1140

Fire detection system

Planning
EP7F

Building Technologies
Fire Safety & Security Products
Technical specifications and availability subject to change without notice.

© Siemens Schweiz AG 2005-2011

We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights
and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our
prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
About this document

1 About this document ..............................................................................7

2 Safety regulations ...................................................................................9


2.1 Signal words and symbols ........................................................................9
2.1.1 Classification and meaning of signal words..............................................9
2.1.2 Symbols and their meaning ......................................................................9
2.1.3 Classification and meaning of additional symbols ..................................10
2.2 Safety-relevant working instructions .......................................................10

3 Main features of CS1140 ......................................................................12

4 Overview of technical data for CS1140...............................................13

5 Logical and physical structure ............................................................14

6 Bus systems ..........................................................................................15


6.1 Overview of buses...................................................................................16

7 C bus stations .......................................................................................17


7.1 Station .....................................................................................................17
7.2 Station type .............................................................................................17
7.3 Meaning of the endings 42, 43................................................................18
7.4 Hardware.................................................................................................18
7.5 Parallel operating unit .............................................................................18
7.5.1 General features/limitations ....................................................................18
7.5.2 'CA' parallel operating unit ......................................................................18
7.5.3 'CT11 visualizer for WINDOWS' remote control software.......................19
7.6 Logical AREAS........................................................................................20

8 Planning conforming to EN54-2 ..........................................................21


8.1 Binding functions.....................................................................................21
8.2 Options with requirements ......................................................................21
8.3 Outputs for triggering fire controls...........................................................21

9 Outline quantities of C bus participants.............................................22


9.1 Main CPU (CI/CC) limitation ...................................................................23
9.2 Operating unit limitation (CT/CI) .............................................................27
9.3 Gateway limitation (CK) ..........................................................................28

10 Establishing the hardware needed......................................................29

11 Selecting the appropriate control panel .............................................30

12 CI1142 in housing H38... (flat)..............................................................31

13 CI1142 in housing H38... (low) .............................................................33

14 CI1142 in housing H47..........................................................................35

15 CC1142/43 in housing H47... ................................................................37


15.1 Extra power supply in second H47 housing............................................39
15.2 Cable kits for additional power supply in H47 housing ...........................40

16 CC1142/43 in housing H67... ................................................................41


16.1 Possible forms of installation on component carrier H67... ....................43
16.2 Installation variants .................................................................................43
16.3 Possible combinations ............................................................................44
16.4 Additional power supply ..........................................................................45
16.5 Cable kits for additional power supply ....................................................46

17 AlgoPilot B3Q... operating terminal ....................................................47

3
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
About this document
17.1 Features ..................................................................................................48
17.1.1 Plexi glass doors for AlgoPilot B3Q6../566 .............................................48
17.1.2 Positioning of E3I020 RS232 plug-in module and PSA interface board
K3I090 .....................................................................................................49
17.1.3 Positioning E3I040 I bus/LON plug-in module ........................................49
17.1.4 Components and labeling kits for B3Q6../566 ........................................50
17.2 Installation options ..................................................................................51
17.3 Connection lines between control panel and external operating units ...53
17.4 Voltage supply (24 V)..............................................................................53

18 Housing range H23... / H26... / H28... ...................................................54


18.1 Recess-mounting of H23G230 and H28G200 ........................................55

19 Housing range H37... ............................................................................56

20 Housing range H38... ............................................................................57

21 Housing range H47... ............................................................................58

22 Housing range H67... ............................................................................59

23 Housing range H98... ............................................................................60

24 Overview of 19" options .......................................................................61

25 Principle of internal pre-wiring ............................................................62

26 Line plug-in modules ............................................................................63


26.1 Overview of recording periphery .............................................................64
26.2 "Interactive" detector line ........................................................................66
26.3 "Interactive" Ex detector line ...................................................................67
26.4 'CBA8000/TS9000' detector line .............................................................67
26.5 'AnalogPLUS' detector line......................................................................68
26.6 'MS9i addressing' detector line ...............................................................69
26.7 'Collective' detector line...........................................................................70
26.8 'FD20' detector line .................................................................................71

27 Control plug-in modules.......................................................................72


27.1 Using control plug-in modules.................................................................72
27.2 Overview of plug-in modules available with control outputs ...................72
27.3 Link options .............................................................................................72
27.4 Control outputs, station type CC11 .........................................................73
27.5 Control outputs, station type CI11...........................................................73
27.6 Control outputs, station type CT11 remote .............................................74
27.7 CPU-wide controls ..................................................................................75
27.8 Mimic display outputs, station types CT11 and CI11 ..............................76
27.9 Relay outputs, station types CT11 and CI11 ..........................................77

28 LON bus devices ...................................................................................78


28.1 Features ..................................................................................................78
28.2 LON bus as stub line...............................................................................78
28.3 LON bus as free topology .......................................................................79
28.4 Mimic display converter K3I050 ..............................................................79
28.5 LON I/O board K3I110 ............................................................................80
28.6 Display devices B3Q580 and B3Q590/595.............................................80

29 Gateway..................................................................................................82
29.1 Main features ..........................................................................................82
29.2 Application variants .................................................................................83

30 Remote transmission (not conforming to EN54-2) ............................84

4
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
About this document
31 Remote transmission (conforming to EN54-2) ..................................85
31.1 CPU-wide remote transmission ..............................................................86

32 Extinguishing ........................................................................................87
32.1 Main features of extinguishing SECTION ...............................................87
32.2 Degraded mode link E3G110 option.......................................................88
32.3 Key data ..................................................................................................88
32.4 Typical extinguishing system ..................................................................89
32.5 Functions needed....................................................................................89

33 Printer interface.....................................................................................90
33.1 Features ..................................................................................................90
33.2 CT11 application variant .........................................................................90
33.3 CC11 usage variant ................................................................................91
33.4 CI11 application variant ..........................................................................92
33.5 B2Q191/B1Q101 tape printer .................................................................93

34 PSA interface.........................................................................................94
34.1 Features ..................................................................................................94

35 Power supply.........................................................................................95
35.1 Power supply to control panel.................................................................95
35.2 Additional power supply ..........................................................................96
35.3 Operating unit with power supply as of control panel .............................97
35.4 Operating unit with autonomous power supply.......................................97
35.5 Power supply for remote transmission devices and options...................98

36 Emergency power supply ....................................................................99


36.1 Determining the battery capacity ............................................................99
36.2 Quiescent current table.........................................................................100
36.3 Capacity values for standard configurations.........................................101

37 Alarming concept................................................................................102
37.1 Cerberus alarm concept (CAC).............................................................102
37.2 Defining alarm organization ..................................................................103
37.3 Designing the system operating unit.....................................................103

38 Protective elements ............................................................................104

39 Commissioning ...................................................................................105

40 Flash programming, parameter setting ............................................106


40.1 Flash programming of new application software ..................................106
40.2 Download system data..........................................................................107
40.2.1 61.2.1 B3Q4../B3Q6../E3X10./E3H02...................................................107

41 CS1140 components in alphabetical order ......................................108

42 Spare parts for CS1140 components ................................................112

43 Configuration sheets ..........................................................................113

5
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
About this document
43.1 CI1142 in housing H38... (flat) ..............................................................114
43.2 CI1142 in housing H38... (deep) ...........................................................115
43.3 CI1142 in housing H47… ......................................................................116
43.4 CC1142/43 in housing H47… ...............................................................117
43.5 CC1142/43 in housing H47… (with extra power supply) ......................118
43.6 CC1142/43 in housing H67... (Standard)..............................................119
43.7 CC1142/43 in housing H67... (with 2 sets of batteries) ........................120
43.8 CC1142/43 in housing H67... (with extended connection panel)..........121
43.9 CS1140 in housing H98... or third-party housing ..................................122
43.10 AlgoPilot CT1142 operating unit ...........................................................123
43.11 Display and operating devices ..............................................................124
43.12 Externally positioned devices................................................................124
43.13 Printer B2Q191, B1Q101 ......................................................................125

6
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
About this document

1 About this document

Goal and purpose


This document describes how to plan the hardware components of the CS1140
control panel. Safe applications will result from consistently following these instruc-
tions.

Scope of validity
This document contains information about all CS1140 components for ≥EP7F, in-
cluding order numbers.

Target audience
This product documentation and the operating instructions are intended for the fol-
lowing people, who carry out a particular job and have been trained for it.

Group of persons Activity Qualification


Project Manager The Project Manager is responsible for the local He has had the technical training appropriate to
project management. He co-ordinates the sched- his function and the size of a project or the prod-
ules of all groups of people working on a project uct line used in the project and has attended the
as well as resources. He also continuously ob- training courses for project managers at the sup-
tains the technical information required for project plier's works.
realization.

Reference documents
Information in Document
825 Characteristics of collective detector lines
1204 Fire alarm signal in explosion-hazardous areas
001260 Description of hardware plug-in modules (CS1140 ’Modular’)
1274 Assembly instructions for housing series H47...
1275 Assembly instructions for housing series H67...
1393 Assembly instructions for housing series H26..../H28...
001508 Guidelines for connection factors, capacity, line resistance etc.
1669 PSA interface board, technical specification
1683 Lightning and surge protection for fire detection installations
1971 Assembly instructions for housing series H37...
004282 FlashTool operating instructions
006516 Designation strip templates for display and operating devices
A6V10062437 NK8000 Installation, Function & Configuration, Commissioning, etc.
TM
008478 Procedure for planning a Sinteso detector line (FD20)

Operational and safety regulations

Before groups of persons begin work on the system they must have read and understood the related
documents, in particular Chapter 2 "Safety regulations".

7
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
About this document
Disregard of the safety regulations
Products are designed for proper use, and before they are delivered they are
tested to ensure they function correctly. Siemens disclaims all liability for damage
or injuries caused by the incorrect application of the instructions or disregard of
warnings of danger contained in the documentation. This applies in particular to:
 Personal injuries or damage caused by improper use and incorrect use;
 Personal injuries or damage caused by disregarding safety instructions in the
documentation or on the product;
 Personal injuries or damage caused by poor maintenance or a lack of mainte-
nance.

Conventions
(...) Supplemental information
..) Comments
’.....’ Definition of descriptions
–> For details see page ...., or document .....
 Configuration sheets to be completed
E3X10. Stands for E3X102, E3X103
E3X10x Stands for E3X102, E3X103

Document identification
Location Meaning
Title page –System name
–Product type
–Document purpose
Last page bottom left –Document number
–Date of issue
Last page bottom right –Manual
–Register

Revision history
Version Date Brief description
008725_h_en_-- 06.2011 Chap. 8.2 Option with requirements added
Changes from E3M140 to E3M141, new diagrams of B3Q661 and
008725_g_en_-- 12.2010
battery changes
008725_f_en_-- 08.2009 Adjustment to EN54-2, EN54-4, minor changes
Chap. 41.8 positioning adjusted, Chap. 41.12 K3I110 added,
008725_e_en_-- 07.2008
Chap. 38 new graphics added, minor changes
Various corrections, order numbers changed from 6 to 10 digits,
'Asia/Pacific' component removed, E3H020 superseded by E3H021,
008725_d_en_-- 04.2008
graphics adapted
Z3S070 superseded by Z3S071, minor changes
K1H021 is replaced by K1H022 (Cerloop application)
008725_c_en_-- 10.2006
Corrections; Z3S080 is cleared
008725_b_en_-- 04.2005 OSS replaced by PSP, minor changes
008725_a_en_-- 02.2005 Edition EP7F-Z1, replaces Quicksilver document 4595

Training courses
Siemens offers the training required for all products. Information about courses is
available on the Siemens Intranet.

download
Current documentation is available on the Siemens Intranet.

Abbreviations
PSP Product Support Platform

8
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Safety regulations

2 Safety regulations
This chapter describes the danger levels and the relevant safety regulations appli-
cable for the use of our products. Please read the work instructions as well as the
chapter 1 'About this document' before beginning any work.

2.1 Signal words and symbols


2.1.1 Classification and meaning of signal words
The danger level - that is, the severity and probability of danger - is indicated by
the signal words listed below. Non-observance may lead to the consequences indi-
cated:

DANGER
Imminent danger!
 May cause danger to life or serious bodily injury!

WARNING
Dangerous situation!
 May cause serious bodily harm.

CAUTION
May cause dangerous situations!
 May cause minor injuries!

NOTE
Possibly harmful situation!
 May cause damage to the product or to objects in the immediate vicinity of the
product!

2.1.2 Symbols and their meaning


The symbols listed below indicate the nature and origin of the danger.

Fehler! Es ist nicht mög-


lich, durch die Bearbei-
Signal word General dangers
tung von Feldfunktionen
Objekte zu erstellen.

Fehler! Es ist nicht mög-


lich, durch die Bearbei-
Signal word Electrical voltage
tung von Feldfunktionen
Objekte zu erstellen.

Example of an indication of danger

Fehler! Es ist nicht mög-


lich, durch die Bearbei- DANGER
Disconnect the component from the power supply.
tung von Feldfunktionen External voltage
Objekte zu erstellen.

9
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Safety regulations

2.1.3 Classification and meaning of additional symbols

Tips and information.

Refers to extremely important or critical decisions to be taken into account before continuing the work.

2.2 Safety-relevant working instructions

Country-specific standards
The products are developed and produced in compliance with the relevant Euro-
pean safety standards. Should additional country-specific, local safety standards or
regulations concerning planning, assembly, installation, operation and disposal of
the product apply in the place of operation, then these standards or regulations
must also be taken into account in addition to the safety regulations mentioned in
the product documentation.

Electrical installations

Fehler! Es ist nicht mög-


DANGER Work on electrical installations may only be carried out by qualified electricians
lich, durch die Bearbei-
Work on electrical or by instructed persons working under the guidance and supervision of a quali-
tung von Feldfunktionen installations fied electrician, in accordance with the electrotechnical regulations.
Objekte zu erstellen.

 Control panels must be disconnected from the power supply during commission-
ing or maintenance work whenever possible.
 Connection terminals with an external voltage supply must be provided with a
sign reading 'DANGER – External voltage'.
 Mains leads to the control panel must be installed separately and provided with
a clearly marked fuse.
 Earthing must be carried out in compliance with local safety regulations.
 When work is carried out in explosion-hazardous areas, the appropriate safety
precautions must be taken.

Assembly, installation, commissioning and inspection work


 If any tools or accessories such as ladders are required, safe and suitable de-
vices must be used.
 Spurious activation of the remote transmission must be reliably prevented.
 Always inform the fire brigade before testing the remote transmission.
 The activation of fire controls for test purposes must not cause damage to the
system or parts thereof.
 Fire controls must only be activated after the test has been completed and the
system has been definitely handed over to the customer.
 Third party systems or devices must only be activated in the presence of the re-
sponsible person.
 When work on management stations and system terminals is performed, the
safety regulations of the connected sub-systems must be observed. This espe-
cially applies when switching off system components.
 In the case of extinguishing systems, always use the "General installation in-
structions" as a guideline. These guidelines are available on request.

10
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Safety regulations
Testing the product operability
 Evacuate and cordon off the extinguishing sector.
 Inform people about the possibility of fogging and noise.
 Inform people before testing alarm devices; take the possibility of panic reac-
tions into account.
 Inform the alarm and fault receiving stations connected to the system before car-
rying out the tests.

Changes to the system configuration and products


Modifications to a system or to individual products may cause faults or malfunction-
ing. Please request written approval from us and the relevant authorities concern-
ing intended system modifications and system extensions.

Components and spare parts


 Locally procured components and spare parts must comply with the technical
specifications laid down by the manufacturer. This compliance is always ensured
with original spare parts.
 Only use fuses with the specified fuse characteristics.
 Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the specified battery type or an equivalent battery type recommended
by the manufacturer.
 Batteries require environmentally safe disposal. They must be handed in at the
local collecting points.
 Please take into account that the extinguishing agent cylinders are pressurized
and must be replaced in compliance with the local safety regulations.

11
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Main features of CS1140

3 Main features of CS1140


 Fire detection system that can be configured in a modular manner
 2150 detectors possible per CC1143; 980 detectors possible per CC1142; 600
detectors possible per CI1142
 For processing collective and addressable detectors
 Logical and physical structure totally separate
 Control panel module as main CPU (for larger systems)
 Operating terminal as main CPU (for smaller to medium-sized systems)
 Interfaces for VdS peripheral devices, printer, PSA/pager, host systems, PLC
 Different input and output modules
 Extinguishing control module that functions autonomously
 Special mimic display activation module
 Multiple detector logic
 Parameterizable detector algorithms for interactive and SintesoTM detectors
 Central panel electronics can be installed in 4 different housing series
 Up to 16 freely selectable station types per C bus
 Convenient operation thanks to softkeys and large display
 Up to 64 independent logical AREAS (organizational levels)
 SINGLE AREA or MULTIPLE AREA operation
 Event memory with sub-menu / search functions
 Integrated real-time clock with backup battery
 Automatic summer/winter time changeover
 integrated degraded mode function
 Flexible detector parameterization via maintenance PC

Systems that can be connected CS1140 control panel pallet


Operation
Main CPU Operation
Main CPU B3Q…
AlgoRex® DS11 CI11 CC11 CT11
Collective

E3X10x
CPU

AnalogPLUS

WINDOWS-based
interactive + ex interactive + wireless (radio) CK11
configuration software

Gateway
TM
Sinteso FD20
addressed

AlgoWorks
Older detector systems
collective detectors
MS6 / MS7 / MS9
Addressable detectors
MS9i / MS9i-PLUS / MS716i
CBA8000/TS9000

12
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Overview of technical data for CS1140

4 Overview of technical data for CS1140


Operating voltage 115 / 230 VAC +10 % / –15 % 50...60 Hz
Power consumption 40...320 VA (per converter B2F020)
30...350 VA (per converter B2F040)
Battery operations should the mains fail Switchover without interruption
– Standard duration 12...24 h
– optional up to 72 h (see page 99)
Ambient conditions
Temperature during operation -5°C ... +40 °C
storage –20 °C... +60 °C
Air humidity max. 95%, no moisture condensation, according to 3K5 class as
defined in IEC 721-3-3
IP protection category (EN 60529 / IEC 529)
– Control panel IP50 H38 housing
IP30 H47/67 housing

– Remote AlgoPilot operating unit IP30 H37 housing


IP52 H26G220 housing
IP40 H28G200 housing
Dimensions
– Control panel in housing H38... W = 520 mm, H = 602 mm, D = 100 mm / 155 mm
H47... W = 434 mm, H = 735 mm, D = 300 mm
H67... W = 434 mm, H = 1130 mm, D = 300 mm
H98... W = 600 mm, H = 2110 mm, D = 300 mm
– Remote operating unit in housing H26G220 W = 366 mm, H = 219 mm, D = 76 mm
H28G200 W = 520 mm, H = 300 mm, D = 70 mm
H37G... W = 510 mm, H = 54 mm, D = 200 mm (214 mm)
Color
– Control panel housing H38... / H47... / H67... / H98... RAL 7035 light gray

– Front of AlgoPilot B3Q.. operating unit RAL 9006 silver, Pantone 427C, 431C gray

Pantone 421 gray


– Housing for operating consoles H26G220
RAL 7035 light gray
H28G200
1E110 dark gray
H28T...
RAL 7035 light gray
H37...

13
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Logical and physical structure

5 Logical and physical structure


The logical structure in the CS1140 fire detection system is totally separate from
the physical structure. This allows for maximum flexibility. Display and operation
are oriented towards geographical and organizational aspects and are not depend-
ent on the detector network's effective hardware installation.

Geographical conditions ( –> building structure)

1st
2nd floor
floor
Room 101
1st
Room 102
floor
Room 103
Room 104

Ground Room 104 (object)


Main building (area) floor
1st floor (section)

Logical structure Logical structure


The logical structure is a map of a system's
geographical circumstances. It can be flexibly
adapted to the building structure, room use, Main
etc. Area building

The logical structure within a control panel is


independent of the line arrangement of the
detector network. Ground 1st 2nd
Section
floor floor floor

Zone Ware- Room Room Room Canteen EDP


Reception
house 102 103 104 room

Element

Link
The lowest levels of the two structures are
linked to one another. The physical units (e.g.
Linking
detectors) at each logical or geographical
location are determined.
Level 3

DOW
Level 2

Level 1
DCW
Device D-Bus
Line 1 Line 2
Level 2 Line 3
Line 4

Level 1

Function unit I-Bus


Physical structure
The physical structure is a map of the hard-
ware. It is provided by the hardware installa-
tion. The number of levels used depends on C-Bus Control unit
the hardware used. CT11 CC/CI
Station Control terminal
Physical structure

14
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Bus systems

6 Bus systems
There are 6 levels of communication in the CS1140 fire detection system:

C bus
 Local data bus between control panel(s), operating console(s) and gateway(s)

I bus
 Internal data bus between the individual plug-in modules in the control panel (li-
ne modules, control modules, etc.)

D bus (interactive detector line / AnalogPLUS bus / collective detector line)


 Local detector bus; links the detector with the control panel

FDnet
TM
 Local device bus; links the Sinteso devices with the control panel

LON bus
 Local data bus for floor display/and operating terminal, mimic display converter
and I/O card

Data bus
 Local data bus for parallel displays, mimic displays or relays

Control terminal Gateway


CT11 CK11
I-Bus E3I040 LON-Bus DMS
E3H021 LMS modular
Data bus (Host system)

CERLOOP / CERBAN

C-Bus

Control unit CC11, CI11


CPU: I-Bus
E3X10. Line modules
or
AlgoPilot B3Q...
E3M... E3M... E3M... E3M... E3I040

LON-Bus
B3Q580/
B3Q590/
B3Q595

collective K3I110 In-/outputs


D-Bus AnalogPLUS-Bus
detection line FDnet
addressable K3I050
interactive AnalogPLUS collective SintesoTM
detectors detectors detectors devices
Data bus
B3R051
or
K3R072/
K3G060

15
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Bus systems

6.1 Overview of buses

Features C bus I bus LON bus Data bus


Field of application local system bus internal in control panel local data bus for floor local data bus for parallel
repeater display display, mimic displays or
relays
Transfer speed 57 kbaud 1000 kbaud 78 kbaud SPI bus 2 kHz
Length of line max. 1000 m max. 3 m max. 500 m as max. 1000 m
(G51 Ø0.8: 1400m) (inside housing only) free topology
max. 1000 m
as stub line
Number of participants ... 16 ... 16 ... 32 ... 24
and/or addresses C bus stations I bus plug-in modules LON bus devices max. 8 addresses
Number of wires 2 26 2 6
(+3 wires for degraded (+3 wires for supply)
mode)
Cable type twisted 1) flat cable twisted twisted
Loop line 4 – – –
T-branch 4 –
– –
see page 78
Short-circuit-proof yes – no yes
every participant with
isolator
Network structure master/master master/slave master/slave master/slave
Prompt event-controlled, in cycles, event-controlled in cycles
presence-monitored event-controlled presence monitoring typ. every 250 ms
(every 60 s)
Principle serial bus C bus network serial bus
– Cerberus protocol – Cerberus protocol – Echelon chip (LON – Cerberus protocol
– collision detection – SPI/Motorola protocol)
– Manchester coding – Cerberus specific
telegram
Special feature – – – –

Features D bus interactive AnalogPLUS bus Collective line FDnet


TM-
Field of application for interactive for AnalogPLUS for collective for Sinteso
detectors detectors MS6/7/9 detectors devices
Transfer speed 4.8 kbaud 2 messages/sec. (AC signal) 4 messages/sec.
Length of line see doc. 001508 see doc. 001508 see doc. 001508 see doc. 001508
(max. 120/300 nF) (max. 150/300 nF) (max.50/150/250/4 F) (max.210/330 nF) 2)
Number of participants ... 128 ... 128 1 address ... 126
and/or addresses D bus devices D bus devices (max. 25 detectors) FDnet devices
(interactive) (AnalogPLUS) (Sinteso)
Number of wires 2 2 2 2
Cable type twisted twisted twisted all cable types permitted
(untwisted permitted) (untwisted permitted) (twisted recommended)
Loop line 4 4 – 4
T-branch 4 – – 4
any Only one T-branch per-
mitted between 2 devices
Short-circuit-proof yes yes no yes
participants depending every participant every participant
on type with isolators with isolators
with/without isolators
Network structure master/slave master/slave master/slave master/slave
Prompt in cycles in cycles – in cycles
– typ. every 3 sec. – typ. every 64 sec. – typ. every 32 sec.
– interrupt in event of – interrupt in event of – interrupt in event of
alarm alarm alarm
Principle sensor/actor bus sensor/actor bus conventional sensor/actor bus
– Cerberus protocol – Cerberus protocol ’K31’ – current gain principle – Siemens protocol ’P2’
’K51’ – serial 8 bit – voltage thresholds – serial 32 bit
– serial 8 bit – starting up: daisy-chain – starting up: daisy-chain
Special feature detector parameters – – diff. parameter sets
download can be chosen
1) calibrated for cable impedance: 50  (MICC) / 110  (G51, Ø0.8 mm not shielded)
2) 500 nF for unshielded cables

16
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
C bus stations

7 C bus stations
Max. 16 stations (participants) can be operated in the C bus network.
 Any stations (CC, CI, CT, CK) in any arrangement are possible below the limits
stated below
 max. 64 AREAS

DMS/LMS
(management
system)
CERLOOP

Control terminal
CT11 Gateway CK11 1)
(max.15) (max. 2)

C-Bus

C-Bus network
- max. 16 stations
- 4 different types of stations
- loop line max. 1400 m with G51 ø 0.8 mm

Control terminal
I-Bus I-Bus
Main-CPU
Main-CPU Line Control Line Control
module module module module
CI11 CC11
(max.16) (max.15)
Detector Detector

1) If more than two, please contact hotline.

7.1 Station
 Participants on C bus network
 Several stations can be accommodated in the same housing or housings distrib-
uted geographically.

7.2 Station type


 Distinguished by function and illustrated by a particular component
 Certain components can be used for different station types

Station types available:


– CI11 Combination of main CPU and operating unit (AlgoPilot)
– CC11 Main CPU
– CT11 Operating unit (AlgoPilot)
– CA11 Parallel operating unit
– CK11 Gateway (e.g. conversion from C bus protocol –> CERLOOP protocol)

17
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
C bus stations

7.3 Meaning of the endings 42, 43


 Provides information about the outline quantities (see section 8) or the size of
the RAM available:
– Cx1142 2x512Kx8 bits
– Cx1143 4x512Kx8 bits

7.4 Hardware

Station type Component Function Function Function


'Main CPU' 'Operation' ’Gateway’
CI1142 AlgoPilot B3Q661/681/686 
CC1142 E3X102 
– –
CC1143 E3X103
CT1142
AlgoPilot B3Q661/681/686 
CA1142 –
CK1143 E3H021 – 

 Components for 'Asia/Pacific'


CI1143 AlgoPilot B3Q566 
CT1143  –
AlgoPilot B3Q566 –
CA1142

7.5 Parallel operating unit


One parallel ('CA') operating unit can be connected to each AlgoPilot ('CT'/'CI') op-
erating unit.

7.5.1 General features/limitations


– The connected parallel operating unit simulates (mirrors) the standard operating
unit (same mapping)
– The standard operating unit and parallel operating unit can be operated at the
same time
Permits > 16 operations per C bus network
– Serial communication (RS232), i.e. can only be activated via a stub line (no sa-
fety circuit)
– Monitored at both ends for communication breakdowns
– Recommended modem types: Zyxel xxx. Other modems: To be assessed locally
for the case in hand

7.5.2 'CA' parallel operating unit


– Same hardware as the standard operating unit B3Q661/681/686/566
– As of EP7F all AlgoRex terminal types and character sets are supported
– For software required see page 21

18
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
C bus stations

7.5.3 'CT11 visualizer for WINDOWS' remote control software


– For operating platform needed, see document 006824
– Terminal types supported: B3Q661/681/686/566
– For details, also see document A6V10225450

Standard control terminal Parallel control terminal


CT/CI CA
(RS232) V24 ....1000m
E3I020 E3I020
max. length of line
dependent on
type of modem
E3I020 Modem Modem E3I020
Dedicated
AlgoPilot line AlgoPilot

Hardware AlgoPilot with special software 24VDC


CA....xxx for B3Q6..
FBA FBA
B3Q321 B3Q321
BUS
C

max. length of line


dependent on
type of modem Visualizer
CT/CI E3I020 Modem Modem Remote Operation
Dedicated line
temporary public
telephone line
Tel. Tel.
E3I020 Modem Modem

(RS232) ....15m
AlgoPilot E3I020

Standard PC with keyboard, software


'CT11' visualizer for Windows'

CT/CI
B3D021

temporary public
telephone line
Tel. Tel.
E3I020 Modem Modem
(temporary)
AlgoPilot
e.g. Service Notebook, software
'CT11 visualizer for Windows',
AlgoWorks for Windows

19
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
C bus stations

7.6 Logical AREAS

CC CI CC CC
AREA

AREA
1 2 3 4 5 6 7 8 .. .. .. .. 61 62 63 64

CI CI

All AREAS control terminal

CK CK

 Max. 4 AREAS can be configured within one CPU ('CI' or 'CC').


 CPU-wide AREAS are not possible.
 CPU-wide controls are possible.
 Operating units ('CT'/'CI') can be assigned to any AREAS.
 Gateway assignments should only be made per station, not per AREA! In order
to avoid CERLOOP address problems, a C bus station must not be split over
two gateways!

20
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Planning conforming to EN54-2

8 Planning conforming to EN54-2

8.1 Binding functions


When planning the fire control panel, ensure that binding functions are planned
correctly in accordance with standard EN54-2 (e.g. detection, alarming, remote
transmission).
No more than one binding function may fail in the event a simple fault on fire con-
trol panels with more than 512 detectors. When using bus-based I/O modules in
particular, ensure that binding functions are not concentrated on one line but
spread over various lines. We would highly recommend using loop technology.

8.2 Options with requirements


The following options with requirements are available on fire detection system
Algorex CS1140. The chapter numbers belong to EN54-2.

Indications:
7.13 Alarm counter
8.3 Fault signals from points
8.4 Total loss of the power supply

Controls:
7.11 Delays to outputs
7.12.2 Dependencies on more than one alarm signal Type B
9.5 Disablement of addressable points
10 Test conditions

Outputs:
7.8 Output to fire alarm devices
7.9.1 Output to fire alarm routing equipment
7.10.1 Outputs to fire protection equipment Type A
7.10.2 Outputs to fire protection equipment Type B
7.10.3 Outputs to fire protection equipment Type C
8.9 Output to fault warning routing equipment

Inputs:
7.9.2 Alarm confirmation input from fire alarm routing equipment
7.10.4 Fault monitoring of fire protection equipment

8.3 Outputs for triggering fire controls


In accordance with EN54-2, the state of the fire protection equipment (fire controls)
of types B (without confirmation) and C (with confirmation) must be displayed using
separate light-emitting display elements. The freely programmable LED on the
B3Q661/B3Q681/B3Q686 can be used for this purpose. The active state must be
displayed separately for fire controls which are controlled and those with confirma-
tion, using one red LED in each case. If type B and C fire controls occur at the
same time or if freely programmable LEDs are used elsewhere, a parallel display
B3R051 should be provided.

21
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

9 Outline quantities of C bus participants


This section describes the limits of the various station types in terms of quantities.
Any performance limits which may be dependent on outline quantities are not cov-
ered.
 The details provided in the relevant Release Notes or the corresponding edition
of this document should be used for earlier EPs with the exception of the 'Maxi-
mum number of links in control objects 4 and 6 (RAM)' section of this docu-
ment which applies as of EP4.
The station type is selected depending on the prevailing requirements. The follo-
wing variants are available:

Station Components Flash ROM SRAM EPROM kit RAM set


type (2x1024Kx8 bits) soldered in
’Program file’
CI1142 AlgoPilot B3Q661/681/686 CIX00xxx 2x512Kx8 bits –
CC1142 E3X102 CCX00xxx 2x512Kx8 bits –
CC1143 E3X103 CCY00xxx 4x512Kx8 bits –
CT1142 AlgoPilot B3Q661/681/686 CTX00xxx 2x512Kx8 bits –
AlgoPilot B3Q6..
CA1142 CAX00xxx 2x512Kx8 bits –
(parallel operating unit)
CK1143 E3H021 CKY00xxx 8x512Kx8 bits –
 'Asia/Pacific' components
CIYT1xxx
CIYTExxx
CI1143 AlgoPilot B3Q566 4x512Kx8 bits –
CIYTLxxx
CIYT5xxx
CTYT1xxx
CTYTExxx
CT1143 AlgoPilot B3Q566 4x512Kx8 bits –
CTYTLxxx
CTYT5xxx
CAYT1xxx
AlgoPilot B3Q566 CAYTExxx
CA1143 4x512Kx8 bits –
(parallel operating unit) CAYTLxxx
CAYT5xxx
National variants of program files: 00 = international; T1 = China simple; TE = China traditional; TL = Korea standard; T5 = Thailand

22
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

9.1 Main CPU (CI/CC) limitation

The limits within the station types are given


by hard- and software.

Verify all given limits for each required station


by going through this flow chart.

Maximum number of devices per station (RAM)


select station with
higher RAM This limitation is for the CI1142, CC1142, CC1143 station types and depends on how the logical
capacity or an structure is formed.
additional station The limit values, depending on the estimated average number or ELEMENTS per OBJECT, can be
found in the following diagram.

Max. number of devices


number of
devices < X ?
no CC1143
yes

Example:
Average of 3 ELEMENTS per OBJECT
Result: Max. 3000 devices

! Do not go right up to limits!


Include reserve for:
- Changes to project
- System extensions
- Updates for future versions

CC1142

CI1142 (B3Q460/480/670)

Example:
Average of 5 ELEMENTS per OBJECT
Control panel assignment: 300 devices
CI1142 (B3Q661/681/686)
Free memory space: 600 devices (-200
reserve) (For use of this value, see page 26
'Max. number of texts')

ELEMENTS per OBJECT (average)

Important:
The curve is for the values entered for EP5.
The above limit value must however be corrected downwards for the following configuration.

Number of OBJECTS per SECTION (on average) < 3 CI1142: –15 %


CC1142: –
CC1143: –

Use of ELEMENT texts CI1142: –20 %


CC1142: –10 %
CC1143: –10 %

23
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

New definition of the number of devices to count:

Structure Number
of devi-
ces
 D bus participants with their own D bus address (e.g. DOT1151, DO1131, DM1154,
DCW1151, DOW1171...)
1
 FDnet participants with their own FDnet address (e.g. DOOT2x1, DO2x1, DM2x1,
DS221 ....)
 Every used input or output of a FDnet, interactive or AnalogPLUS line module
Example: DC1157 with 3 inputs –> 6 devices
DC1154 with 1 output and 1 input for confirmation message –> 4 devices 2
DCI222 with 4 inputs –> 8 devices
DCIO222 with 4 outputs and 4 inputs –> 16 devices
 Purely logical controls: Every 'Control ELEMENT' or 'Control OBJECT' that is not di-
2
rectly linked to a channel
 Collective lines (e.g. 1 line of the E3M080 plug-in module) 2
 Inputs of plug-in modules (e.g. E3X10x –> I4, E3L020 –> I2, K3I110 –> LONin, external
2
LON device –> LONin))
reduce number  Outputs of plug-in modules (e.g. E3X10x –> Q3, E3G050 –> Q1, K3I110 –> LONout,
of nodes or use 2
external LON device –> LONout)
an additional  Parallel displays/mimic displays (equipped with up to 384 LEDs / relays) 20
station
Limitation in the logical structure
number of
The limits of the logical structure depend on the node type, the highest possible CSX
no nodes < X ?
number and the maximum number of digits on the display. These limits are provided by
the system and are not dependent on the size of memory.
yes
'Limits of logical structure' table
Maximum number Maximum number Maximum number Maximum number
AREAS per SECTIONS per OBJECTS per ELEMENTS per
STATION AREA SECTION OBJECT
... 4 ... 255 ... 255 ... 99
select station with International
higher capacity or 5: ...255
use an additional
station
Maximum number of links in control objects 4 and 6 (RAM)
1 to 16 links can be programmed to activate control object 4 or 6.
number of Every link needs a particular volume of RAM.
no controls < X ? The maximum number of links is therefore limited as shown in the following diagrams.
Important:
yes – If controls are produced which span several CPUs (control object 6), all links must be
counted twice: Once in the control panel from which they originated and once in the
control panel to which they are linked.
Note:
– In order to optimize the performance of your system, you must keep the number of
controls spanning several CPUs as low as possible.
– Max. 40 controls spanning several CPUs (control object 6) are permitted per C bus.

24
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

Example:
CI1142 with 150 control objects with an average of 9 links.

The intersect between the number of control objects (150) and the number of links (9) must
fall within the permitted area.

'Limit values for controls' diagram for CI1142 and CC1142

Number of links
per control object

Exam-
4 links (on average) per control object =
max. 600 control objects

Permitted area No. of progr.


for control ob-
jects

'Limit values for controls' diagram for CC1143

Number of links
per control object
16 links per control object
= max. 600 control objects

4 links (on average) per control object =


max. 2400 control objects

Permitted area
for No. of progr.
control ob-

Maximum number of time channel OBJECTS


A maximum of 16 time channel OBJECTS are permitted per station.
select station
with higher
Maximum number of I bus components
capacity or use
'Maximum number of I bus components' table
an additional
station Station type CI1142 CC1142 CC1143
I bus components ...16 1) ...8 2) ...16 1) 3) ...16 1) 3)
1) Limitation due to software
number of 2) Approximate value (depending on housing size and/or 5V power consumption)
I-Bus-modules 3) Battery charging element (integrated in E3X10x) counts as one I bus plug-in module
no <X?

yes

25
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants
Limitation due to 5V power consumption
All I bus components are supplied with 24 V and 5 V. The power available for the 5 V supply is limited
select station with after the CPU:
higher capacity, 'Main CPU' Power available
use an additional
power supply or an E3X10x 1,100mA
additional station B3Q... / E3C011 250mA

'5 V power consumption of I bus components' table


I bus component Power consumption I bus component Power consumption
after ’CPU’ after ’CPU’
E3M060 34mA E3G060 10mA
E3M071 34mA E3G070 10mA
E3M080 55mA E3G080 35mA
consumption of E3M111 25mA E3C011 12mA
I-Bus-modules E3M171 45mA B3Q321 8mA
no <X? E3M120 65mA E3I020* 100mA
yes E3L020 10mA E3I040 70mA
E3L030 35mA K3I090* 1mA
E3G050 8mA E3M141 5mA
E3H021** –
* Is not an I bus component but is also supplied by the 'CPU'
** Is supplied via 24 V.

the capacity of the main


CPU is checked

 The limit values for the operating unit (CT/CI), gateway (CK) and additional
AlgoWorks programs must also be checked!

26
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

9.2 Operating unit limitation (CT/CI)


define the required number of control
terminals by going through
this flow chart

Maximum number of texts


There is a limit to the number of texts of external stations (or AREAS) which can be displayed on an
operating unit (CT/CI).
reduce number of The following calculation must be applied:
visible AREAS or use
an additional control 2x number of visible SECTIONS
terminal + number of visible OBJECTS
+ number of visible ELEMENTS with element text
= number of texts

'CT1142' limit value (B3Q661/681/686)


The maximum number of texts is fixed at 8500.

'CI1142' limit value (B3Q661/681/686)


The maximum number of texts depends on how many devices there already are in the control panel
configuration:

Number of texts per 100 non-configured devices

maximum number
of texts
no <X?
540
yes

Example:
Average number of ELEMENTS per OBJECT: 5 = 540 texts per 100 devices
Free memory space: 600 devices (according to example shown in diagram in
section 9.1)

the required number


of control terminals
is defined

ELEMENTS per OBJECT

 The limit values for the station (CI/CC), gateway (CK) and additional AlgoWorks
programs must also be checked!

27
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Outline quantities of C bus participants

9.3 Gateway limitation (CK)

check gateway configuration

Memory limitation (RAM)


use CK1143
type gateway

station type CC1143 – CK1143 (E3H021):


yes visible on CK ? – suitable for stations CI1142, CC1142, CC1143

no

Limitation of CERLOOP address range


use second
Max. 8 C bus stations (CI/CC) can be addressed by one gateway.
gateway of
correct type If there are more than 8 C bus stations (CC/CI), then these must be split over 2 gateways.

More than 2 gateways can also be configured for special applications.


number of
stations > 8 ? The visibility of C bus stations (CC/CI) on gateways may only be defined per station, and not per area!
yes

no

the configuration of
the gateway is checked

 The limit values for the station (CI/CC), the operating unit (CT/CI) and
additional AlgoWorks programs must also be checked!

28
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Establishing the hardware needed

10 Establishing the hardware needed


The key system data must be known in order to determine the hardware needed:

1. Define number and type of detector lines


 Depending on:
– Detector series
– Number of detectors, input and output modules
– Building structure

2. Define number and type of fire controls


 Depending on:
– The fire protection installations to be controlled
– Location of contacts (central or decentralized)
– Contact type of the individual contacts (250 V AC/10 A or 30 V DC/1 A)

3. Define number and type of operating units


 Depending on:
– Operating concept
– Language of operating front
– Parallel displays, fire brigade operating units

4. Options
 Depending on:
– Printer interface and printer
– PSA/pager interface
– Remote transmission device
– Gateway, etc.

5. Define capacity of emergency power battery


 Depending on:
– Total quiescent current
– Emergency power needed for operating period (country-specific)
– Type of remote transmission

6. Define housing type


 Depending on:
– Number and type of plug-in modules
– Optional devices needed
– Number and type of sets of batteries

7. Produce configuration sheet(s) (see page 113)


– Select sheets corresponding to configuration
– Complete everything

29
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Selecting the appropriate control panel

11 Selecting the appropriate control panel


With a suitable normal application, the control panel housing required can be de-
rived from the outline quantities of the main CPU.

Station type Housing Housing Housing Housing Housing


H38G220 H38G320 H47... H67... H98...
CI1142   
CC1142 /  
CC1143   
 suitable
 suitable to a limited extent (check)

H38G220 H38G320 H47... H67... H98...

434

600

735 434

520 520

300

602 CI1142 –> page 35 1130 2015


602

100 155

300

300

CI1142 –> page 31 CI1142 –> page 33 CC1142/43 –> page 37 CC1142/43 –> page 41 CC1142/43 –> page 60

Operating unit compulsory in housing


Operating unit not compulsory in housing front
front

30
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H38... (flat)

12 CI1142 in housing H38... (flat)


Component
H38G220: of Z3I470
H38G220 520 Set with B2F020
- cabinet
- door
- module chassis
- earth terminals B3Q...

B3Q...
602 Z3I380

FA2005-A1
H23B040

H23B010
88
100* Connection
Module
* incl. projecting door hinges for periphery
Z1K030

 Compact control panel in flat design


 Connected directly to the plug-in modules
 Only a very limited selection of options can be fitted
 Batteries: 2x 12 V/15 Ah
 Operating unit fitted in front (serves as main CPU at the same time)
 Additional display devices cannot be fitted
 Doors hinged on right, can be locked with 2 Allen screws

Module chassis Module chassis view


view 'Modules' Cabinet front view 'Fire control installations relay'

H38G220 absolutely essential


28 21 recommended
AC-DC converter

Note: space allocation


Z1K030

E3M060/071/171/120
E3I020

B2F020

and E3C011 are not Mains


acce-
possible at positions ssories
28+38
38
Z1K030

31
E3...

Mounting of
E3C011: 47 48 (Battery 12 V) B A 45.1 .. 45.3
Terminal block FA2005-A1
Z3B171
Z3B171
Z3B171
E3G070
Z1K030
Z1K030

and holder
containing in
E3...

cable set Z3I470 51 Important:


57 58 55.1 .. 55.3 Comply with max.
permissible number
EMC Precaution: (Battery 12 V)
Z3B171
Z3B171
Z3B171

of 'nodes' +
Z1K030
E3C011
Z3I470

Position 57 must FA2005-A1 I-Bus modules!


E3...

not be fit with either -> Details see chapter


E3I040 or E3G080 Outline quantities
modules
View A View B

 For details of H38… housing –> see section 20

31
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H38... (flat)

CT1142
(additional operating facilities)

Basic equipment
C-Bus mains RT = Remote transmission Option
Battery
B2F020 E3C011
24V FA2005-A1 CI1142
24V
24V
5V
I-Bus
AlgoPilot
B3Q... E3G...
E3G070 E3M... E3I040
E3L...
E3I020
or K3I090 1..2 1........7
RS232
24V Z3B171 LON-Bus
1 2 RT

250VAC 10A K3I050

internal or Fire control K3I110


Printer
external printer installations LON synoptic converter
LON I/O card
Floor indicator terminal B3Q580/
PSA/Pager B3Q59x

H38G220 components
Control and operating unit
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
H26T... Plexi glass doors for AlgoPilot B3Q... Option –> see page 48
Z5B... Labeling kit Depending on language –> see page 50
E3G070 5466610001 'Universal' control plug-in module For alarm devices and control outputs

Line plug-in modules  Depending on detector series For details of line plug-in modules –> see page 63

LON plug-in module For details of floor repeater display –> see page 78

Control plug-in modules  If more than 7 programmable control For details of control plug-in modules –> see page 72
outputs are needed

Interfaces  If there is space to fit


E3H021 A5Q00024660 'CERLOOP' gateway Double Euroboard (2 plug-in slots) –> see page 82
E3I020 4602390001 RS232 plug-in module For connecting B2Q191 printer or external printer
K3I090 5108200001 PSA interface board For connecting PSA/pager and internal/external printer

Power supply  For calculating the emergency power operation duration, see page 99
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
E3C011 5054790001 Plug-in battery charging module
FA2005-A1 A5Q00019677 12 V/15 Ah battery
Z3I460 4843120001 'CH' mains socket

Housing/options
H38G220 4849140001 'Doors with cut-out' housing kit For details of housing –> see page 57
H23B010 4762100001 Cover Compulsory or H23B040
H23B040 4845900001 Information module Brief operating instructions instead of H23B010
Z3I470 4843410001 Cable set for H38... Compulsory
Z3I380 4755670001 I bus flat cable + 'long' supply cable Needed for connection between levels
(e.g. items 28 <–> 38)
Z1K030 4842310001 Terminal block with board holder for Needed per plug-in module (E3H021 2 items)
CI11..
Z3B171 4843830001 1 x 250 V AC/10 A relay module Intermediate relay for fire controls (max.6)

32
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H38... (low)

13 CI1142 in housing H38... (low)


Component
H38G220: of Z3I470
520 Set with
- cabinet
- door B2F020
H38G320
- module chassis
- mains terminals
B3Q...

B3Q...

602
Z3I380

H23B010 FA...
H23B040
B3Q321 FA...

147 B3R051
155* Connection Module
for periphery
* incl. projecting door hinges Z1K030

 Compact control panel


 Connected directly to the plug-in modules
 Designed for a few plug-in modules, but large batteries and options being fitted
 Batteries: either 2x 12 V/15 Ah or 2x 12 V/24 Ah
 Operating unit fitted in front (serves as main CPU at the same time)
 Additional display devices can be fitted
 Doors hinged on right, can be locked with 2 Allen screws

Module chassis Module chassis view


view 'Modules' Cabinet front view 'Fire control installations relay'

H38G320 absolutely essential


27 28
21 23 Mains recommended
AC-DC converter

space allocation
Z1K030

terminals
Z1K030

Note:
E3I020

E3M...

E3M60/071/171/120
B2F020

Mains
and E3C011 are not acce-
possible at positions ssories
37 38
27+37
Z1K030
Z1K030
E3L020

E3M...

31
45.1 .. 45.8
(Battery 12 V) Z3B171
Z3B171
46 47 48 FA2006-A1 B A Z3B171
Mounting of Z3B171
or Z3B171
E3C011:
E3G070
Z1K030

Z1K030

Z3B171
FA2005-A1
E3H020 + 2x Z1K030

Terminal block Z3B171


E3....

Z3B171
and holder
containing in 51 55.1 .. 55.8 Important:
cable set 56 58 Comply with max.
(Battery 12 V) Z3B171
permissible number
Z3I470 Z3B171
FA2006-A1 Z3B171
of 'nodes' +
E3C011
Z1K030

Z3B171
Z3I470

or Z3B171 I-Bus modules!


E3....

FA2005-A1 Z3B171
Z3B171 -> Details see chapter
Z3B171
Outline quantities
View A View B
EMC Precaution:
Slot rows with E3C011 module must not be fit
with either E3I040 or E3G080 modules

 For details of H38… housing –> see section 20

33
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H38... (low)

CT1142
(additional operating facilities)

Basic equipment
C-Bus mains RT = Remote transmission Option
E3C011 Battery
24V 24V
B2F020
24V FA... CI1142
5V
I-Bus
AlgoPilot
B3Q... E3G070 E3M...
E3G...
E3L030 E3L... E3I040
or
E3I020 1..2 1........7
K3I090
RS232 24V Z3B171
B3R051 B3Q321 RT
LON-Bus
1 2
250VAC 10A
FBF FSK HM
Fire control K3I050
VdS peripheral
installations
Printer equipment K3I110
internal or LON synoptic converter
external printer LON I/O card
Floor indicator terminal B3Q580/
PSA/Pager B3Q59x

H38G320 components
Control and operating unit
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
H26T... Plexi glass doors for AlgoPilot B3Q... Option –> see page 48
Z5B... Labeling kit Depending on language –> see page 50
E3G070 5466610001 'Universal' control plug-in module For alarm devices and control outputs

Line plug-in modules  Depending on detector series For details of line plug-in modules –> see page 63

LON plug-in module For details of floor repeater display –> see page 78

Control plug-in modules  If more than 7 programmable control For details of control plug-in modules –> see page 72
outputs are needed

Interfaces  If there is space to fit


E3H021 A5Q00024660 'CERLOOP' gateway Double Euroboard (2 plug-in slots) –> see page 82
E3I020 4602390001 RS232 plug-in module For connecting B2Q191 printer or external printer
K3I090 5108200001 PSA interface board For connecting PSA/pager and internal/external printer

Power supply  For calculating the emergency power operation duration, see page 99
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
E3C011 5054790001 Plug-in battery charging module
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2005-A1 A5Q00019677 12 V/15 Ah battery
Z3I450 4842730001 'CH' mains socket

Housing/options
H38G320 4849430001 'Doors with cut-out' housing kit For details of housing –> see page 57
H23B010 4762100001 Cover Compulsory or H23B040
H23B040 4845900001 Information module Brief operating instructions instead of H23B010
B3Q321 5656840001 'CH' fire brigade operating unit CH only
B3R051 4905130001 '2x24 displays' parallel display Option
Z3I470 4843410001 Cable set for H38... Compulsory
Z3I380 4755670001 I bus flat cable + 'long' supply cable Needed for connection between levels
(e.g. items 28 <–> 38)
Z1K030 4842310001 Terminal block with board holder for Needed per plug-in module (E3H021 2 items)
CI11..
Z3B171 4843830001 1 x 250 V AC/10 A relay module Intermediate relay for fire controls (max.6)

Prefabricated control panel


CI1142-NL 5469880001 Control panel in H38 housing Prefabricated for 'NL' only

34
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H47...

14 CI1142 in housing H47...


H47G611:
Set with Component of
434 - door Z3I510
- frame
- module chassis
H47G611 - terminal blocks
- mains terminals
- battery supporting plate
- relay rail B3Q...

B2F020
B3Q...

735 Z1I060
E3C011 or
Z1I020
B3Q321 or
Z1I030
H23B010 or
Z1I100
H23B040 FA...

B3Q321 FA...

B3R051 Z3I380
300 can be plugged into
connection block Module

 Removable system control panel


 Separate connector panel (not recommended without connector panel)
 Space to fit options
 Batteries: either 2x 12 V/24 Ah or 2x 12 V/38 Ah
 Operating unit fitted in front (serves as main CPU at the same time)
 Additional display devices can be fitted
 Doors hinged on right with lock (DOM type)

Note: Supplied with cabinet set H47G611


H47G611

Cable duct
E3I020 if used, absolutely essential
mount at position 36! 22 23 24 25
(E3G070+E3...)

recommended space allocation


Fire control relay

Z3B171
21
AC-DC converter

Connection

Z3B171
- one or two connection cables Z1I060, Z1I020,
(Diverses)

panel

Z3B171
Z1I100 or Z1I030 are required for each module:
(Linien)

Z3B171
Z3I330

Z3I330
Z3I330
B2F020

Z3B171
Z3B171 Line modules
Z3B171
If Z3I041 or B3P020 Z3B171 LON module
is used, on Pos. 36 Control modules
Cable duct
E3M060/071/171/120 Extinguishing modules
and E3C011 not possible! 31 32 33 34 35 36 37Mains Interfaces
terminals
E3G070
E3L020

E3I020
Z1I030

Z1I030
E3M...

E3M...
Z1I030

One Z3I330 terminal block has space for:


E3M...

1)
Z1I...

Z1I...
Z1I...

either
Mounting of E3C011: - 2x Z1I030 or
Modules

Terminal block and - 8x Z1I060 or


41 42 43 44 45 46 47 48
holder containing in - 4x Z1I020, 4x Z1I100 or
cable set Z3I510 - 1x Z1I030 and 2x Z1I020
E3C011
Z3I510

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...
E3...

E3...

E3...

E3...

E3...

E3...

E3...

1) Protection elements

EMC Precaution: 51 52 55
Relative to each E3C011
module position, two
Batteries

positions to the right and (Battery 12 V) (Battery 12 V)


Z1I...

Important:
E3...

two positions to the left FA2006-A1 FA2006-A1


must not be fit with or or Comply with max. permissible number
either E3I040 or FA2007-A1 FA2007-A1 of 'nodes' + I-Bus modules!
E3G080 modules -> Details see chapter ‘Outline quantities’

 For details of H47… housing –> see section 21

35
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CI1142 in housing H47...

CT1142
(additional operating facilities)

Basic equipment
C-Bus mains RT = Remote transmission Option
E3C011 Battery
24V 24V
B2F020
24V FA... CI1142
5V
I-Bus
AlgoPilot
B3Q... E3G070 E3M...
E3G...
E3L030 E3L... E3I040
or
E3I020 1..2 1........7
K3I090
RS232 24V Z3B171
B3R051 B3Q321 RT
LON-Bus
1 2
250VAC 10A
FBF FSK HM
Fire control K3I050
VdS peripheral
installation equipment
Printer internal or K3I110
LON synoptic converter
external printer LON I/O card
Floor indicator terminal B3Q580/
PSA/Pager B3Q59x

H47G611 components
Control and operating unit
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
H26T... Plexi glass doors for AlgoPilot B3Q... Option –> see page 48
Z5B... Labeling kit Depending on language –> see page 50
E3G070 5466610001 'Universal' control plug-in module For alarm devices and control outputs

Line plug-in modules  Depending on detector series For details of line plug-in modules –> see page 63

LON plug-in module For details of floor repeater display –> see page 78

Control plug-in modules  If more than 7 programmable control For details of control plug-in modules –> see page 72
outputs are needed

Interfaces  If there is space to fit


E3H021 A5Q00024660 'CERLOOP' gateway Double Euroboard (2 plug-in slots) –> see page 82
E3I020 4602390001 RS232 plug-in module For connecting B2Q191 printer or external printer
K3I090 5108200001 PSA interface board For connecting PSA/pager and internal/external printer

Power supply  For calculating the emergency power operation duration, see page 99
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6
A
B1F120 4952330001 Converter 115/230 V AC ->24 V DC, 3 A Generally for supplying fire controls
B2F060 5112850001 Converter 115/230 V AC ->24 V DC, 4.5
A
E3C011 5054790001 Plug-in battery charging module
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2007-A1 A5Q00022897 12 V/38 Ah battery
Z3I450 4842730001 'CH' mains socket
Z3I1040 A5Q00004129 'CH' remote transmission kit
Z3I041 4962900001 Surge arrester kit Option

Housing/options
H47G611 4953850001 'Doors with cut-out' housing kit For details of housing –> see page 58
H23B010 4762100001 Cover Rather than H23B040 or B3Q321 or B3R051
H23B040 4845900001 Information module Brief operating instructions
B3Q321 5656840001 'CH' fire brigade operating unit CH only
B3R051 4905130001 '2x24 displays' parallel display Option
Z3I510 4848460001 Cable set for H47... / CI11... Compulsory
Z3I380 4755670001 I bus flat cable + 'long' supply cable Needed for connection between levels
Z1I020 4754990001 9-wire connection cable with board hol- For internal advance wiring
der, 0.5 m
Z1I030 4755090001 19-wire connection cable with board For internal advance wiring
holder, 0.5 m
Z1I060 5258020001 4-wire connection cable with board hol- For internal advance wiring
der, 0.5m
Z1I100 A5Q00007486 10-wire connection cable with board For internal advance wiring
holder, 0.5 m
Z3B171 4843830001 1 x 250 V AC/10 A relay module Intermediate relay for fire controls (max.8)
Z3I330 4751560001 Terminal block, 2x20 terminals 3 items are supplied with H47G611
Z3I420 4838180001 Back-up terminal block For extra back-up terminals
Z3G220 5258440001 Marine kit
Z3G240 5329500001 Kit for increased vibrations

36
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H47...

15 CC1142/43 in housing H47...


H47G601/611:
Set with
- door
H47G611 - frame
- module chassis
434 - terminal blocks
- mains terminals
- battery supporting plate
H47G601 - relay rail
B2F020

B3Q...
Z1I060
or
H23B010 E3X1.. Z1I020
735 or
H23B040
Z1I030
B3Q321 or
Z1I100
B3R051
FA...

FA...

300 Control terminal


installed separately
Z3I350 can be plugged into
Module
connection block

 Removable system control panel


 With separate main CPU (E3X10.)
 Separate connector panel (not recommended without connector panel)
 Space for options
 Batteries: either 2x 12 V/24 Ah or 2x 12 V/38 Ah
 Operating unit usually remote (can be fitted in doors)
 Doors hinged on right with lock (DOM type)

Supplied with cabinet set H47G601/611


Cable duct
H47G601 or H47G611

absolutely essential
22 23 24 25 recommended space allocation
Fire control relay

Z3B171
21
AC-DC converter

Connection

Z3B171
Z3B171 - one or two connection cables Z1I060, Z1I020,
panel
(Diverse)
(E3X10.)

Z3B171 Z1I100 or Z1I030 are required for each module:


(Lines)
Z3I330

Z3I330

Z3I330

Z3B171
B2F020

Note: Z3B171 Line modules


Z3B171
E3I020 if used, Z3B171
LON module
mount at position 32! Control modules
Cable duct Extinguishing modules
31 32 33 34 35 36 37Mains Interfaces
terminals
E3G050

One Z3I330 terminal block has space for:


E3L020
E3I020
Z1I030

Z1I030

Z1I030

E3H020 + 2x Z1I030

1) either
E3....
Z1I...

If Z3I041 or B3P020 - 2x Z1I030 or


Modules
E3X10. + 2 x Z1I030 + Z3I350

is used, on Pos. 36 - 8x Z1I060 or


42 43 44 45 47 48 - 4x Z1I020, 4x Z1I100 or
E3M060/071/171/120
and E3C011 not - 1x Z1I030 and 2x Z1I020
possible!
E3M...

E3M...

E3M...

E3M...

E3....

E3....
Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

1) Protection elements, Modem filter

52 55
Batteries

Mounting of E3X10.: (Battery 12 V) (Battery 12 V)


Terminal block for FA2006-A1 FA2006-A1 Important:
E3X10. containing in or or Comply with max. permissible number
cable set Z3I350+ FA2007-A1 FA2007-A1 of 'nodes' + I-Bus modules!
2 x Z1I030 -> Details see chapter ‘Outline quantities’

 For details of H47… housing –> see section 21


 For details of protective elements, modem filter –> see section 38, 29

37
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H47...
CT1142
(operation = separate C-Bus station)
Basic equipment
RT = Remote transmission Option
C-Bus mains
Battery
B2F020 CC1142/43
FA...
24V Battery 24V
charging module
CPU I-Bus
E3X10. or
Driver E3I020
K3I090 E3G...
1..........8 E3L030 E3M... E3I040
1..2 RS232 E3L...
24V 1 2
Z3B171
RT LON-Bus
K3I050
250VAC 10A
FBF FSK HM K3I110
Fire control internal or LON synoptic converter
installations Printer external printer LON I/O card B3Q580/
PSA/Pager VdS peripheral B3Q59x
equipment Floor indicator terminal

H47G601 and H47G611 components


Control and operating unit
E3X102 6290250001 Control panel module Flash ROM and 1MB RAM fitted
E3X103 6290380001 Control panel module Flash ROM and 2MB RAM fitted
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
H26T... Plexi glass doors for AlgoPilot B3Q... Option –> see page 48
Z5B... Labeling kit Depending on language –> see page 50
Flash program files
CCX00xxx (PSP) Flash program file For main CPU E3X102
CCY00xxx (PSP) Flash program file For main CPU E3X103
CKY00xxx (PSP) Flash program file For CPU E3H021
Line plug-in modules  Depending on detector series For details of line plug-in modules –> see page 63
LON plug-in module For details of floor repeater display –> see page 78
Control plug-in modules  If more than 7 programmable control outputs For details of control plug-in modules –> see page 72
are needed
Extinguishing module and operating unit For details of extinguishing unit –> see page 87
Interfaces  If there is space to fit
E3H021 A5Q00024660 'CERLOOP' gateway Double Euroboard (2 plug-in slots) –> see page 82
E3I020 4602390001 RS232 plug-in module For connecting B2Q191 printer or external printer
K3I090 5108200001 PSA interface board For connecting PSA/pager and int./ext. printer
Power supply  For calculating the emergency power operation duration, see page 99
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
B1F120 4952330001 Converter 115/230 V AC ->24 V DC, 3 A Generally for supplying fire controls
B2F060 5112850001 Converter 115/230 V AC ->24 V DC, 4.5 A Generally for supplying fire controls
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2007-A1 A5Q00022897 12 V/38 Ah battery
Z3I450 4842730001 'CH' mains socket
Z3I1040 A5Q00004129 'CH' remote transmission kit
Z3I041 4962900001 Surge arrester kit Option
Housing/options For details of housing –> see page 58
H47G601 4953720001 'Doors without cut-out' housing kit With remote operating unit
H47G611 4953850001 'Doors with cut-out' housing kit For fitting operating unit
H47E100 4748850001 Complete component carrier For fitting in third-party housing
H23B010 4762100001 Cover Rather than H23B040 or B3Q321 or B3R051
H23B040 4845900001 Information module Brief operating instructions
B3Q321 5656840001 'CH' fire brigade operating unit CH only
B3R051 4905130001 '2x24 displays' parallel display Option
Z3I350 4755380001 Cable set for H47/H67 Compulsory
Z3I380 4755670001 I bus flat cable + 'long' supply cable Needed for connection between levels
Z1I020 4754990001 9-wire connection cable with board holder, 0.5 m For internal advance wiring
Z1I030 4755090001 19-wire connection cable with board holder, 0.5 m For internal advance wiring
Z1I060 5258020001 4-wire connection cable with board holder, 0.5 m For internal advance wiring
Z1I100 A5Q00007486 10-wire connection cable with board holder, 0.5 m For internal advance wiring
Z3B171 4843830001 1 x 250 V AC/10 A relay module Intermediate relay for fire controls (max.8)
Z3I330 4751560001 Terminal block, 2x20 terminals 3 items are supplied with H47G611
Z3I420 4838180001 Back-up terminal block For extra back-up terminals
Z3G220 5258440001 Marine kit
Z3G240 5329500001 Kit for increased vibrations
Prefabricated control panel
CC1142-NL 5469910001 Control panel in H47 housing Prefabricated for 'NL' only

38
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H47...

15.1 Extra power supply in second H47 housing


Cable duct

H47G601 or H47G611
22 23 24 25

Fire control relay


21

AC-DC Wandler

max. 8
(Diverse)
(E3X10.)

(Lines)
Z3I330

Z3I330

Z3I330
B2F020
Cable duct
31 32 33 34 35 36 37 Mains
terminals

E3G050
E3L020
E3I020
Z1I030

Z1I030

Z1I030

E3H020 + 2x Z1I030
1)

E3....
Z1I...
Housing set H47G611
E3X10. + 2 x Z1I030 + Z3I350

or H47E100 and H47T111


42 43 44 45 47 48
E3M...

E3M...

E3M...

E3M...

E3....

E3....
Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...
52 55

(Battery 12 V) (Battery 12 V)
FA2006-A1 FA2006-A1
or or
FA2007-A1 FA2007-A1
H47E110

H47E110 and H47T101


21
22 25
(Battery 12 V) (Battery 12 V)
B2F020

FA2006-A1 FA2006-A1
or or
FA2007-A1 FA2007-A1

H15Z300 H15Z300

31
Application example:
Supplementary power 32 35
E3C011

Remarks:
Z3I870

supply on module chassis (Battery 12 V) (Battery 12 V)


H47E110 using three FA2006-A1 FA2006-A1 - Place housings next to or on top of each other (do not install at a
H15Z300 battery or or distance)
41 FA2007-A1 FA2007-A1 - the additional E3C011 are not used as I-Bus equipment
support plates
H15Z300 H15Z300 - use one Z3I870 cable set per supplementary power supply
E3C011
Z3I870

51 52 55
(Battery 12 V) (Battery 12 V)
E3C011

FA2006-A1 FA2006-A1
Z3I870

or or
FA2007-A1 FA2007-A1
H15Z300 H15Z300

 H47G611 or H47E100 and H47T111 housing kit –> for details, see section 21
 Details of principle wiring for power supply –> see chapter 35

Options needed
H47E110 4761840001 Component carrier empty
H47T101 4953560001 Housing frames + doors without cut-out
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
E3C011 5054790001 Plug-in battery charging module
H15Z300 4761970001 Retaining plate for batteries For the second and other sets of batteries
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2007-A1 A5Q00022897 12 V/38 Ah battery
Z3I870 4969440001 Cable kit For additional power supply

39
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H47...

15.2 Cable kits for additional power supply in H47 housing


The Z3I870 cable kit can always be used to wire the additional power supply. The
cable kit contains all the cables and wires needed for connections to the next ex-
tension.

CC1142/43 for H47E100 and H47E110

Z3I350

E3X10.

E3X10.
Z3I870

1. extension

E3C011

Z3I870
B2F020
2. extension

E3C011

E3C011

E3C011

Z3I870
E3C011

3. extension

E3C011

 Details of wiring –> see document 001260

40
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...

16 CC1142/43 in housing H67...


H67G601/611: Z1I070 or Z1I040 or
Set with Z1I050 or Z1I110 H67E101
- door
H67G611 - frame Module
- module chassis
434 - mains terminals
- battery supporting plate
H67G601 - relay rail
can be plugged
into connection block
B3Q...

H23B010
B2F020
H23B040
1130 B3Q321
B3R051 E3X10.

Z3I350

300
Control terminal installed separately
FA...

FA...

 Removable system control panel


 With separate main CPU (E3X10.)
 Separate connector panel
 Space for options
 Batteries: either 2x 12 V/24 Ah or 2x 12 V/38 Ah
 Operating unit usually remote (can be fitted in doors)
 Doors hinged on right with lock (DOM type)
Supplied with cabinet set H67G601/611
Cable duct
H67G601 or H67G611

absolutely essential
01 02 03 04 Mains 04 recommended space allocation
8x Z3B171

terminals
Z3I330

Z3I330

Z3I330

Z3I330

1)
Connection panel

- one or two connection cables Z1I070, Z1I040,


Z1I110 or Z1I050 are required for each module:
or

11 12 13 14 14
Fire control relay

8x Z3B171

Line modules
(E3X10.)

LON module
max. 8
Z3I330
Z3I330
Z3I330

Z3I330

Control modules
Comments: Extinguishing modules
or

- E3I020 if used mount Interfaces


Z3I570
at position 32! 21
One Z3I330 terminal block has space for:
B2F020

- B2F020 fits any Cable duct either


module space - 2x Z1I050 or
- 8x Z1I070 or
31 32 33 34 35 36 37 38 37Mains - 4x Z1I040 or 4x Z1I110
If Z3I041 or B3P020 is terminals - 1x Z1I050 and 2x Z1I040
used, on Pos. 36
E3L020

E3L020
E3X10. + 2 x Z1I050 + Z3I350

E3H020 + 2x Z1I050
E3I020
Z1I050

Z1I050

Z1I050

E3M060/071/171/120 1)
E3....

E3....
Z1I...

Z1I...
E3....
Z1I...

and E3C011 not 1) Protection elements, Modem filter


possible! 42 43 44 45 47 48
Modules

Mounting of E3X10.:
E3M...

E3M...

Terminal block for


Z1I...

Z1I...
E3....

E3....

E3....

E3....
Z1I...

Z1I...

Z1I...

Z1I...

Special feature:
E3X10. containing in
H67E100 has 3 different hole patterns for mounting.
cable set Z3I350 + 52 53 54 55 56 57 58 As a result, the relationship between connection block /
2 x Z1I030
modules / batteries can also be arranged differently
E3M...

E3M...

E3M...

E3M...

EMC Precaution:
Z1I...

Z1I...

Z1I...

Z1I...
E3....

E3....

E3....
Z1I...

Z1I...

Z1I...

Relative to each
E3X10. and E3C011 61
module position, two 62 65
positions to the right (Battery 12 V) (Battery 12 V)
Batteries

Important:
and two positions to
E3....
Z1I...

FA2006-A1 FA2006-A1 Comply with max. permissible number


the left must not be fit or or of 'nodes' + I-Bus modules!
with either E3I040 or FA2007-A1 FA2007-A1 -> Details see chapter ‘Outline quantities’
E3G080 modules

 For details of H67… housing –> see section 22


 For details of protective elements, modem filter –> see section 38, 29

41
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...
CT1142
(operation = separate C-Bus station)
Basic equipment
RT = Remote transmission Option
C-Bus mains
Battery
B2F020 CC1142/43
FA...
24V Battery 24V
charging module
CPU I-Bus
E3X10. or
Driver E3I020
K3I090 E3G...
1..........8 E3L030 E3M... E3I040
1..2 RS232 E3L...
24V 1 2
Z3B171
RT LON-Bus
K3I050
250VAC 10A
FBF FSK HM K3I110
Fire control internal or LON synoptic converter
installations Printer external printer LON I/O card B3Q580/
PSA/Pager VdS peripheral B3Q59x
equipment Floor indicator terminal

H67G601 and H67G611 components


Control and operating unit
E3X102 6290250001 Control panel module Flash ROM and 1MB RAM fitted
E3X103 6290380001 Control panel module Flash ROM and 2MB RAM fitted
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
H26T... Plexi glass doors for AlgoPilot B3Q... Option –> see page 48
Z5B... Labeling kit Depending on language –> see page 50
Flash program files
CCX00xxx (PSP) Flash program file For main CPU E3X102
CCY00xxx (PSP) Flash program file For main CPU E3X103
CKY00xxx (PSP) Flash program file For CPU E3H021
Line plug-in modules  Depending on detector series For details of line plug-in modules –> see page 63
LON plug-in module For details of floor repeater display –> see page 78
Control plug-in modules  If more than 7 programmable control outputs For details of control plug-in modules –> see page 72
are needed
Extinguishing module and operating unit For details of extinguishing unit –> see page 87
Interfaces  If there is space to fit
E3H021 A5Q00024660 'CERLOOP' gateway Double Euroboard (2 plug-in slots) –> see page 82
E3I020 4602390001 RS232 plug-in module For connecting B2Q191 printer or external printer
K3I090 5108200001 PSA interface board For connecting PSA/pager and int./ext. printer
Power supply  For calculating the emergency power operation duration, see page 99
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
B1F120 4952330001 Converter 115/230 V AC ->24 V DC, 3 A Generally for supplying fire controls
B2F060 5112850001 Converter 115/230 V AC ->24 V DC, 4.5 A Generally for supplying fire controls
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2007-A1 A5Q00022897 12 V/38 Ah battery
Z3I450 4842730001 'CH' mains socket
Z3I1040 A5Q00004129 'CH' remote transmission kit
Z3I041 4962900001 Surge arrester kit Option
Housing/options For details of housing –> see page 59
H67G601 4955500001 'Doors without cut-out' housing kit With remote operating unit
H67G611 4956600001 'Doors with cut-out' housing kit For fitting operating unit
H67G620 5778630001 Housing kit for marine
H67E101 5097050001 Complete component carrier For fitting in third-party housing
H23B010 4762100001 Cover Rather than H23B040 or B3Q321 or B3R051
H23B040 4845900001 Information module Brief operating instructions
B3Q321 5656840001 'CH' fire brigade operating unit CH only
B3R051 4905130001 "2x24 displays" parallel display Option
Z3I350 4755380001 Cable set for H47/H67 Compulsory
Z3I380 4755670001 I bus flat cable + "long" supply cable Needed for connection between levels
Z1I040 4755120001 9-wire connection cable with board holder, 0.8 m For internal advance wiring
Z1I050 4755250001 19-wire connection cable with board holder, 0.8 m For internal advance wiring
Z1I070 5258150001 4-wire connection cable with board holder, 0.8 m For internal advance wiring
Z1I110 A5Q00007487 10-wire connection cable with board holder, 0.8 m For internal advance wiring
Z3B171 4843830001 1 x 250 V AC/10 A relay module Intermediate relay for fire controls
Z3I330 4751560001 Terminal block, 2x20 terminals
Z3I420 4838180001 Back-up terminal block For extra back-up terminals
Z3I570 4956440001 133 mm 'TS35' mounting rail with bracket For max. 8 relays Z3B171
Z3G270 5661200001 Marine kit
Prefabricated control panel
CC1142-NL 5470000001 Control panel in H67 housing Prefabricated for 'NL' only

42
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...

16.1 Possible forms of installation on component carrier H67...

Special feature:
H67E101 is designed with 3 continuous perforated rasters. The connector panel /
plug-in module / battery split can thereby be arranged differently.

Rasters for plug-in modules Rasters for relays and terminal Rasters for cable ducts Rasters for accumulators
blocks

16.2 Installation variants


– 3 levels, plug-in module spaces – 2 levels, plug-in module spaces – 2 levels, plug-in module spaces
– 2 levels, connector panel – 3 levels, connector panel – 2 levels, connector panel
– 1 level, power supply – 1 level, power supply – 2 levels, power supply
Cable duct Cable duct Cable duct
H67G601 or H67G611

H67G601 or H67G611

H67G601 or H67G611

01 02 03 04 Mains 01 02 03 04Mains 01 02 03 04Mains


terminals terminals terminals
Z3I330

Z3I330

Z3I330

Z3I330

Z3I330

Z3I330
Z3I330

Z3I330

Z3I330

Connection panel

Connection panel
Connection panel

11 12 13 14 11 12 13
Fire control relay

14

Fire control relay


11 12 13 14
(E3X10.)
Z3I330

Z3I330

Z3I330
(E3X10.)

max. 8

Z3I330
Z3I330

Z3I330

max. 8
Z3I330
Z3I330
Z3I330

Fire control relay


max. 18

Z3I570 21 22 23 Z3I570
21 21
(E3X10.)
B2F020

B2F020
Z3I330
Z3I330
Z3I330

Cable duct Cable duct

31 32 33 34 35 36 37 38 31 Z3I580 31 32 33 34 35 36 37 38
B2F020

E3L020

E3L020

Cable duct
E3L020

E3L020

E3H020 + 2x Z1I050
E3I020
Z1I050

Z1I050

Z1I050
E3X10. + 2 x Z1I030 + Z3I350

E3H020 + 2x Z1I050
E3I020
Z1I050

Z1I050

Z1I050

E3X10. + 2 x Z1I030 + Z3I350

E3....
Z1I...
E3....

E3....
Z1I...

Z1I...
E3....

E3....
Z1I...

Z1I...
E3....
Z1I...

Modules

42 43 44 45 47 48 41 42 43 44 45 46 47 48 42 43 44 45 46 47
Modules

E3L020

E3L020

E3H020 + 2x Z1I050
E3X10. + 2 x Z1I030 + Z3I350
E3I020

E3M...

E3M...
Z1I050

Z1I050

Z1I050
E3M...

E3M...

E3....

E3....
Z1I...

Z1I...
E3....

E3....
Z1I...

Z1I...
Z1I...

Z1I...
E3....

E3....
Z1I...

Z1I...
E3....

E3....

E3....

E3....

Z1I...

Z1I...
Z1I...

Z1I...

Z1I...

Z1I...

E3....
Z1I...

Modules

52 53 54 55 56 57 58 52 53 54 55 57 58 52 55
(Battery 12 V) (Battery 12 V)
E3M...

E3M...

E3M...

E3M...

E3M...

E3M...

E3M...

E3M...

FA2006-A1 FA2006-A1
Z1I...

Z1I...

Z1I...

Z1I...
E3....

E3....

E3....
Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

Z1I...

E3....

E3....
Z1I...

Z1I...

H15Z300 H15Z300
Batteries

61 62 65 62 65 61 62 65
(Battery 12 V) (Battery 12 V) (Battery 12 V) (Battery 12 V)
+Z3I870
Batteries

(Battery 12 V) (Battery 12 V)
E3C011
Batteries

FA2006-A1 FA2006-A1 FA2006-A1 FA2006-A1


E3....
Z1I...

FA2006-A1 FA2006-A1
or or or or or or
FA2007-A1 FA2007-A1 FA2007-A1 FA2007-A1 FA2007-A1 FA2007-A1

43
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...

16.3 Possible combinations

Details for component


carrier:
Z3G170 = 4x
H67E101 –> see
page 59
H47 + H67 housing or H47E100 –> see
H98 housing page 58

Profile rail on rear of


H98G600

H67E101

32 plug-in module
H67E101 spaces

H67E101 or
H47E100/110

3 battery kits G1E010

5 universal carriers
Note:
The following mech.
components cannot
be fitted on G1E010: 5xG1E010
H47E100/110 – Z1I040....Z1I110
– Z1K020/030
– Z3I330

If the H67E101 component carrier is


installed in a third-party housing or in a
H98 housing, the H67Z020 shielding hood
must always be used to comply with CE
requirements.
H67E101
Note:
Slide the B2F020 converter up one raster

Attention:
H67Z020 is only suitable for H67E101
and H67E111 plug-in modules 38/48/58 4 slots for the H67Z020 shielding hood
cannot be used.
For the B2F020 –> E3X10 connection,
use the H67Z020 cable provided. H67Z020

44
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...

16.4 Additional power supply

Cable duct

H67G601 or H67G611
01 02 03 04 Mains
terminal

Z3I330

Z3I330

Z3I330
Cabinet set H67G611

Connection panel
or H67E101 + H67T111
11 12 13 14

Fire control relay


(E3X10.)

Z3I330
Z3I330

max. 8
Z3I330
21
B2F020

Cable duct

31 32 33 34 35 36 37 38
E3L020

E3L020

E3H020 + 2x Z1I050
E3I020
Z1I050

Z1I050

Z1I050
E3X10. + 2 x Z1I030 + Z3I350

E3....
Z1I...
E3....

E3....
Z1I...

Z1I...

Modules
42 43 44 45 46 47
E3M...

E3M...

E3....

E3....
Z1I...

Z1I...
E3....

E3....
Z1I...

Z1I...
Z1I...

Z1I...

52 55
(Battery 12 V) (Battery 12 V)
FA2006-A1 FA2006-A1
Batteries

H15Z300 H15Z300
61 62 65
(Battery 12 V) (Battery 12 V)
+Z3I870
E3C011

FA2006-A1 FA2006-A1
or or
FA2007-A1 FA2007-A1

H98G600
H47E110

21
22 25
H47E110 + H47T101
B2F020

(Battery 12 V) (Battery 12 V)
FA2006-A1 FA2006-A1
or or
FA2007-A1 FA2007-A1
H15Z300 H15Z300

Application example: 31 Remarks:


Auxiliary power supply 32 35 - Place housings one above the other (do not install at a distance)
+Z3I870
E3C011

on H47E110 module (Battery 12 V) (Battery 12 V) - the additional E3C011 are not used as I-Bus equipment
chassis using three FA2006-A1 FA2006-A1 - Use one Z3I870 cable set per auxiliary power supply
H15Z300 battery or or
support plates 41 FA2007-A1 FA2007-A1
+Z3I870

H15Z300 H15Z300
E3C011

51 52 55
(Battery 12 V) (Battery 12 V)
FA2006-A1 FA2006-A1
+Z3I870
E3C011

or or
FA2007-A1 FA2007-A1
H15Z300 H15Z300

 For details of H47…/H67…/ H98… housing –> see section 21, 22, 23
 Details of principle wiring for power supply –> see chapter 35
Options needed
H47E110 4761840001 Component carrier empty
H47T101 4953560001 Housing frames + doors without cut-out
B2F020 A5Q00025281 Converter 115/230 V AC >29.6 V DC, 6 A
E3C011 5054790001 Plug-in battery charging module
H15Z300 4761970001 Retaining plate for batteries For the second and other sets of batteries
FA2006-A1 A5Q00019356 12 V/24 Ah battery
FA2007-A1 A5Q00022897 12 V/38 Ah battery
Z3I870 4969440001 Cable kit For additional power supply

45
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CC1142/43 in housing H67...

16.5 Cable kits for additional power supply


The Z3I870 cable kit can always be used to wire the additional power supply. The
cable kit contains all the cables and wires needed for connections to the next ex-
tension.
CC1142/43 for H67E101 and H47E110

Z3I350

E3X10.

Z3I870

1. extension

E3C011

E3X10.

Z3I870
2. extension

E3C011
E3C011

Z3I870

3. extension B2F020

E3C011 E3C011

E3C011

Z3I870

4. extension E3C011

E3C011

 Details of wiring –> see document 001260

46
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17 AlgoPilot B3Q... operating terminal


There are 2 different forms of operating unit, the standard terminal and the comfort
terminal. Standard and comfort terminals can be mixed in the same system con-
figuration.

Application range Comfort terminals Standard terminals


International

B3Q661
Nordic

B3Q681
Switzerland

B3Q686
Asia/Pacific

B3Q566

47
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17.1 Features

Features Comfort termi- Standard termi-


nals nals
Large backlit display with plain text readout (LCD 240x128
points) for very user-friendly use
Context and system status-controlled convenient operation

using softkeys
Operating and display elements split functionally and ergo-
nomically
Detailed event information like type of event, location of event,
measure text, operating modes etc.
(same message principle on both terminals, even if using a
mixed installation!)
Integrated emergency operation function
Insertable designation strips in different languages

Access authorization via 4 different operating levels, depend-
ing on user profile
Can be configured as single AREA or multiple AREA operat-

ing unit
Access authorization via password or key switch
Options:
– Lockable Plexi glass doors H26T...
– RS232 plug-in module E3I020 or PSA interface board
K3I090
– I bus/LON bus converter E3I040 for LON devices (floor
repeater displays etc.)
– Parallel display B3R051

 See outline quantities section 9.2

17.1.1 Plexi glass doors for AlgoPilot B3Q6../566

AlgoPilot B3Q6…/566 Comfort terminal

Z3S200
For locking doors and/or
access authorization to oper-
ating unit

H26T030
Plexi glass doors

48
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17.1.2 Positioning of E3I020 RS232 plug-in module and PSA interface board K3I090

RS232 plug-in module E3I020 is secured to the rear of the operating terminal
using option Z1B020.
For installation details for E3I020, see docu-
ment 1393

The PSA interface board K3I090 is secured to the rear of the operating terminal
using option Z1B060.
–> For installation details for K3I090, see document 1669

Scope of supply for


Z1B020:
12-pole socket terminal
strip
Installation material
Shielding hood

Use flat cable F20A020

17.1.3 Positioning E3I040 I bus/LON plug-in module

LON plug-in module E3I040 connected on I bus of a


H28G200 remote AlgoPilot 'CT' can only be installed in housing
H28G200
–> For installation details for E3I040, see document
1393

Scope of supply for Z1B070:


H28T110 – Installation bracket with board holder and terminal
block numbered in red
– I bus flat cable and supply cable

AlgoPilot B3Q...

49
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17.1.4 Components and labeling kits for B3Q6../566

AlgoPilot operating terminal


B3Q661 A5Q00020708 'International' operating terminal Operating unit and main CPU at the same time
B3Q681 S54371-F12-A1 'Nordic' operating terminal ”
B3Q686 S54371-F11-A1 'CH' operating terminal ”
B3Q566 S54371-F13-A1 'China' operating terminal ”
Flash program file for operating unit (CT....)
CTX00xxx (PSP) 'International' Flash program file for B3Q661, B3Q68x
CTYT1xxx (PSP) 'China simple' Flash program file for B3Q566
CTYTExxx (PSP) 'China traditional' Flash program file ”
CTYTLxxx (PSP) 'Korea standard' Flash program file ”
CTYT5xxx (PSP) 'Thailand' Flash program file ”
Flash program file for parallel operating unit (CA....)
CAX00xxx (PSP) 'International' Flash program file for B3Q661, B3Q68x
CAYT1xxx (PSP) 'China simple' Flash program file for B3Q566
CAYTExxx (PSP) 'China traditional' Flash program file ”
CAYTLxxx (PSP) 'Korea standard' Flash program file ”
CAYT5xxx (PSP) 'Thailand' Flash program file ”
Flash program file for operating unit and CPU at the same time (CI....)
CIX00xxx (PSP) 'International' Flash program file for B3Q661, B3Q68x
CIYT1xxx (PSP) 'China simple' Flash program file for B3Q566
CIYTExxx (PSP) 'China traditional' Flash program file ”
CIYTLxxx (PSP) 'Korea standard' Flash program file ”
CIYT5xxx (PSP) 'Thailand' Flash program file ”
Available labeling kits (if no designation strips are available –> use templates from document 006516)
Z5B415 5706530001 'Portuguese' labeling kit
Z5B435 5706660001 'Dutch' labeling kit
Z5B505 5706790001 'Turkish' labeling kit
Z5B525 5706820001 'German CH' labeling kit
Z5B535 5706950001 'German D' labeling kit
Z5B545 A5Q00004396 'Italian CH' labeling kit
Z5B555 5707050001 'Italian I' labeling kit
Z5B565 5707180001 'French CH' labeling kit
Z5B585 5707210001 'French F' labeling kit
Z5B595 5707340001 'Danish' labeling kit
Z5B605 5707470001 'Finnish' labeling kit
Z5B615 5707500001 'Norwegian' labeling kit
Z5B625 5707630001 'Swedish' labeling kit
Z5B635 5707760001 'English' labeling kit
Z5B645 5707890001 'English GB' labeling kit
Z5B665 5707920001 'Spanish' labeling kit
Z5B685 5706400001 'Hebrew' labeling kit
Options
H26T030 5705300001 Plexi glass doors for AlgoPilot Including installation options
Z3S200 5703490001 Key switch module for AlgoPilot (KABA) For accessing operating unit
V2G050 5706110001 Cable for 9 V lithium battery To fault display should the mains and emergency power
battery fail
B3R051 4905130001 '2x24 displays' parallel display
Options for RS232 interface and PSA interface board to all AlgoPilots
E3I020 4602390001 RS232 plug-in module To connect a printer –> see page 90
Z1B020 4759070001 Installation options for E3I020 Compulsory for installation of E3I020 on rear of AlgoPilot
B3Q...
F20A020 4763170001 20-wire 0.165 m 'Micro' flat cable E3I020 –> B3Q.. connection if E3I020 is on rear of
B3Q...
K3I090 5108200001 PSA interface board For connecting PSA/pager and internal/external printer –
> see page 94
Z1B060 5259840001 Installation options for K3I090 Compulsory for installation of K3I090 on rear of AlgoPilot
B3Q...
Options for E3I040 to connect to I bus of AlgoPilot CT11 in housing H28G200
E3I040 4993100001 LON plug-in module Converter between I bus and LON bus
Z1B070 A5Q00001720 Installation options for E3I040 Compulsory for installation of E3I040 in housing
H28G200

50
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17.2 Installation options

Installed in H23/H26 housing Installed in H47/H67 housing


H23G230 Measurements: Measurements:
(H23) (H47)
W = 125 W = 434
H = 219 H = 735
D = 76 AlgoPilot D = 300
Measurements: B3Q... Measurements:
(H26) (H67)
B3R051 W = 366 W = 434
H26G220 H = 219 H = 1130
AlgoPilot D = 76 D = 300
B3Q...
Recessed mounting –> see page 55

B3Q321 H47T111 or
B3R051 H67T111
H23B010
H23B040

alternatively
Installed in H28 housing Installed in H37 housing
H28T110 Measurements: Measurements:
W = 520 H37G410 H37G410
H = 300 AlgoPilot W = 510
H28G200 D = 70 B3Q...
H = 540
D = 200

B3Q321
B3R051
H23B020
H23B040 AlgoPilot
H23B020 + E3I040 B3Q...
alternatively Measurements:
H37G420
W = 510
H = 540
H28T120 D = 214

H37G420

4 x B3R051

Recessed mounting –> see page 55

Installed in H38 housing Installed in 19" cabinet


(with autonomous power supply)
Measurements: 19" cabinet
H38G220 W = 515
H = 602
D = 88 (H38G220) G2A130
B3Q... D = 147 (H38G320)
B2F020

Alternatively B3Q...
Z3I470 H23B010
H23B040
B3Q321 G2A140 Alternatively
(H38G320 only) H23B020
B3R051 H23B040
(H38G320 only) B3Q321
E3C011
B3R051
FA2005-A1

51
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

Basic equipment
CC11, CI11, CK11 Option
mains
CT11 C-Bus separately connected
Battery LON-Bus parallel indicator
B2F020 E3C011 FA...
activation of Mimic Display
E3I040

I-Bus Parallel branching permissible

24V supply line


or
E3I020
K3I090
RS232
Data bus max.
1 2 F12A100
1000m
B3R051 B3R051 B3R051 B3R051
F12A100 F12A100/470
B3R051:
Printer internal or
- can be installed separately, however at max. 1000m
external printer
- max. 24 units, however max. 8 addresses
PSA/Pager - free allocation of the LEDs (programming according to application)
- line and equipment not monitored

B3Q321
CT11 LON-Bus CA11 B3Q321

24V E3I040 24V

I-Bus I-Bus

E3I020 C-Bus E3I020


RS232 RS232
1 2 1 2
not monitored

Components
AlgoPilot B3Q6../566 operating terminal
B3Q... AlgoPilot operating terminal All AlgoPilot variants –> see page 47
CT/CI/CA Flash program file For 'CT' / 'CI' / 'CA' –> see page 50
Z5B... Labeling kit Depending on language –> see page 50
Additional display and operating devices
B3Q321 5656840001 'CH' fire brigade operating unit CH only
B3R051 4905130001 '2x24 displays' parallel display
Housing H23/H26/H28/H37/H38/H47/H67/H98../19" For details of housing –> see page 54 – 61
Options
V2G050 5706110001 Cable for 9 V lithium battery For 3rd voltage source for B3Q6.../566
V2G040 4759230001 Cable for 9 V lithium battery For 3rd voltage source for B3Q4..
E3I020 4602390001 RS232 plug-in module For printer connection or 'CA11'
Z1B020 4759070001 Installation options for E3I020 / B3Q.... For installation of E3I020 on rear of AlgoPilot B3Q...
K3I090 5108200001 PSA interface board For connecting PSA/pager and internal/external printer
Z1B060 5259840001 Installation options for K3I090 Compulsory for installation of K3I090 on rear of AlgoPilot
B3Q...
Z3I530 4849720001 Adapter to K3R071/72, B3R051 Adaptation of flat cable on terminals
F12A100 4952750001 'Micro' 12-pole, 0.4 m flat cable For B3R051
F12A470 4952880001 'Micro' 12-pole, 1.5 m flat cable For B3R051
E3I040 4993100001 LON plug-in module Converter between I bus and LON bus
Z1B070 A5Q00001720 Installation options for E3I040 Compulsory for installation of E3I040 in housing H28G200
Autonomous power supply
B2F020 A5Q00025281 Converter 115/230 V DC ->29.6 V DC, 6 A
B2F040 5102990001 Converter 115/230 V DC ->29.6 V DC, 3.5
A
E3C011 5054790001 Plug-in battery charging module
FA2005-A1 A5Q00019677 12 V/15 Ah battery
Z3I470 4843410001 Cable set for H38... For AlgoPilot B3Q... connection with E3C011

52
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
AlgoPilot B3Q... operating terminal

17.3 Connection lines between control panel and external operating


units
Options:
Control B3Q321 (Fire department control terminal) Control
terminal B3R051 (Parallel indicators) terminal
AlgoPilot E3I040 (LON interface) AlgoPilot
B3Q... Printer, PSA/Pager B3Q...

Loop C-Bus
2..11 leads max. 1000m per Loop with ø 0,6mm G51 (incl. return line)
max. 1400m per Loop with ø 0,8mm G51 (incl. return line)

Control unit CC11/CI11

When planning a system, the following condition must be observed:


At least one operating unit must satisfy the EN54 standard, i.e. be equipped with
degraded mode and emergency supply.

EN54 requirements:
 Communication as loop line –> design C bus as loop line
 Operation even during degraded mode –> 3 extra wires for emergency
operation
 Second disconnected 24 V supply –> 3 extra wires or autonomous
supply
The number of wires in the connection cable depends on usage and the distances
between the stations:
 Is the operating unit supplied with 24 V by the control panel or autonomously?
 Is an emergency supply according to EN54 also managed?
 Is the degraded mode path (emergency operation) also managed?
Application C bus 24 V supply Emergency Degraded mode Number of wires
power supply path
24 V supply as of control panel EN54 ● ● ● ●
11
satisfied (2 wires) (3 wires) (3 wires) (3 wires)
24 V supply as of control panel without ● ●
5
degraded mode and emergency supply (2 wires) (3 wires)
Autonomous power supply EN54 satis- ● ●
5
fied (2 wires) (3 wires)
Autonomous power supply without de- ●
2
graded mode and emergency supply (2 wires)

Notes:
– Degraded mode path also needed between CPUs or to a remote gateway
– Degraded mode path and emergency supply are not designed as loop line
– Emergency supply via separate cable or C bus return

17.4 Voltage supply (24 V)


 The AlgoPilot B3Q... operating units are designed for the 20..30 V DC voltage
range
 The maximum current at 24 V is 400 mA
 Max. lengths of line (approximate values):
– With cable of ø 0.8 mm –> 180 m
2
– With cable cross-section of 1 mm –> 360 m
 The power requirement for the options (fire brigade operating unit, parallel dis-
play, printer, PSA/pager, LON plug-in unit) must also be taken into account

53
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H23... / H26... / H28...

18 Housing range H23... / H26... / H28...


H23G230
H28G200

H26G220

For operating unit B3Q... /


B3R051 / cover H23B020 with
lock (DOM)

H28T110

Front cannot be swiveled

H23G230:
Measurements 125 x 219 x 76 mm For parallel displays (4x H28T120
Material Plastic B3R051), with lock (DOM)
Color Pantone 421 gray
Protection category IP40

H26G220:
Measurements 366 x 219 x 76 mm
Material Plastic
Color Pantone 421 gray
Protection category IP40

H28...:
Measurements 520 x 300 x 70 mm
Material Steel sheet For printer B2Q191 with lock
Color Housing: RAL7035 light gray (DOM)
Doors 1E110 dark gray H28T020
Protection category IP30

For plan compartment (A4);


For installation B3R051 / cover
H28T130
H23B020 etc., with lock (KA-
BA)

With lock (KABA) H28T150

 All doors are hinged on the left!


 For details of housings H23../H26.../H28... –> see document 1393

54
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H23... / H26... / H28...

18.1 Recess-mounting of H23G230 and H28G200

H23U230
H23U230

H23G230
H23G230

UPR29

H23Z230 H28Z010

H23Z230

1 H28G200
UPR28

H28Z010

H28G200

H28Z020

H28G200

2 Opening in wall
 For details of housings H23../H26.../H28... –> see document 1393

Components
Housings and doors
H23G230 4750910001 Plastic housing For additional display and operating devices
H26G220 4628000001 Plastic housing For remote AlgoPilot B3Q... operating console
H28G200 4099440001 Housing (without doors) For various applications
H28T020 4105640001 Housing doors for printer B2Q191
H28T110 4749820001 Housing doors for AlgoPilot B3Q... / B3R...
H28T120 4749950001 Housing doors for 4 B3R051 parallel dis-
plays
H28T130 4759100001 Housing doors for plan compartment and
1x B3Q321 / B3R051 etc.
H28T150 4843670001 Housing doors without cut-out with KABA
lock
H23B020 4762780001 Cover for H28T110/130
Options for recessed mounting
H28Z010 4105930001 Recessed frame kit For recessed mounting of housing H28G200
H28Z020 4136000001 Recessed mounting intermediate piece With recessed mounting, also for 2 x H28G200
under one another
H23U230 5328790001 Recess-mounted box for B3Q5xx For recessed mounting of housing H23G230
H23Z230 5328820001 Recess-mounted frame for For recessed mounting of housing H23G230
B3Q5xx/B3R051
UPR28 4304340001 Recess-mounted box For 1 housing H28G200 (may be needed)
UPR29 4304470001 Recess-mounted box For 2 housings H28G200 one under the other (may be needed)

55
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H37...

19 Housing range H37...


H37G410
H37G420

1 1

H37G410: H37G420:
Measurements 540 x 510 x 200 mm Measurements 540 x 510 x 214 mm
Material Steel sheet Material Steel sheet
Color RAL7035 light gray Color RAL7035 light gray
Protection category IP30 Protection category IP30

H37G430

H37T120

4
2
3

H37Z010

H37T000
H37G430:
Measurements 540 x 510 x 200 mm
Material Steel sheet
Color RAL7035 light gray
Protection category IP30
1 For AlgoPilot B3Q...
2 Housing and inner doors for special applications
3 Spacer for installing 2 or more housings next to one another
4 Inner doors for housing H37G420, glass front printed in Swedish
 Details of housings H37... –> see document 1971

Components
Housing
H37G410 5339590001 Housing for AlgoPilot B3Q... (flat doors) Including plan compartment for A3 fire brigade orienta-
tion plans
H37G420 5341070001 Housing for AlgoPilot B3Q... (designer doors) Including plan compartment for A3 fire brigade orienta-
tion plans
H37G430 5339620001 Housing For special applications
H37T000 5334670001 Inner door For special applications
H37T120 5657230001 Inner doors for housing H37G420 Glass front printed in Swedish
H37Z010 5339750001 Spacer For between 2 or more housings

56
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H38...

20 Housing range H38...


H38G210 H38G310

Doors can be locked with 2 Allen screws

H38G210/220/230: H38G310/320:
Measurements 520 x 602 x 100 mm Measurements 520 x 602 x 155 mm
Material Steel sheet Material Steel sheet
Color RAL7035 light gray Color RAL7035 light gray
Protection category IP40 Protection category IP40
H38G220 H38G320

1
1
2 3

H38G230
Z1K030

1 For AlgoPilot B3Q...


2 For H23B010 or H23B040 –> see page 31
3 For B3Q321 / B3R051 / H23B010 or H23B040 –> see pages 33 and 51
 Details of housings H38... –> see document 1273

Components
Housing kits
H38G210 4849010001 'Doors without cut-out' (flat) housing kit Including component carrier
H38G220 4849140001 'Doors with cut-out' (flat) housing kit Including component carrier and 2 profile rails for 2 x 3 relays
H38G230 4849270001 'Plan compartment' housing kit Including retaining bracket
H38G310 4849300001 'Doors without cut-out' (deep) housing kit Including component carrier and 1 profile rail for 16 relays
H38G320 4849430001 'Doors with cut-out' (deep) housing kit Including component carrier and 1 profile rail for 16 relays

57
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H47...

21 Housing range H47...

H47G601 H47G611

1
2 H47E100

Including component carrier with: Doors can be locked with DOM lock
– Cable ducts
– 3 Z3I330 terminal blocks
– Relay rails (max. 8x Z3B171)
– Mains terminals (pre-wired)
– Retaining plate for batteries

430

H47T101 H47T111

1
2 690 (16HE) H47E110

H47G601/611:
Measurements 434 x 735 x 300 mm
Z1K020
Material Steel sheet
Color RAL7035 light gray
Protection category IP30
H15Z300 Z3S090

1 For AlgoPilot B3Q...


2 For B3Q321 / B3R051/H23B010 or H23B040 –> see pages 31, 37 and 51

 Details of housings H47... –> see document 1274

Components
Complete housing kits (with component carrier)
H47G601 4953720001 'Doors without cut-out' housing kit
H47G611 4953850001 'Doors with cut-out' housing kit
Housings, component carriers and options (individual parts)
H47T101 4953560001 Housing frames and doors without cut-out
H47T111 4953690001 Housing frames and doors with cut-out
H47E100 4748850001 Component carrier for H47... Including cable ducts, mains terminals and battery retaining
plate
H47E110 4761840001 Component carrier for H47... 'Empty' For non-standard applications
H15Z300 4761970001 Retaining plate for batteries For H47E110; max. 3 items per component carrier (= 3
pairs of batteries)
Z1K020 4754860001 Terminal block and board holder Without cables (for connecting directly to the plug-in mod-
ule)
Z3S090 4969570001 Key switch options (no locking cylinder) For subsequent retooling of DOM
–> KABA/KESO/SEA etc.

58
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H67...

22 Housing range H67...


H67G601/620 H67G611 H67T101 H67T111

1 1
2 2

Including component carrier with: Doors can be locked with DOM H67T101/H67T111:
– Cable ducts lock Measurements 434 x 110 x 300 mm
– Mains terminals (pre-wired) Material Steel sheet
– Retaining plate for batteries Color RAL7035 light gray
Protection category IP30

Z1K020

H67Z020

H15Z300 Z3S090

1 For AlgoPilot B3Q...


2 For B3Q321/B3R051/H23B010 or H23B040 –> see pages 31, 37 and 51

 Details of housings H67... –> see document 1275

Components
Complete housing kits (with component carrier)
H67G601 4955500001 'Doors without cut-out' housing kit
H67G611 4956600001 'Doors with cut-out' housing kit
H67G620 5778630001 'Doors without cut-out' housing kit for marine
Housings, component carriers and options (individual parts)
H67T101 4956150001 Housing frames and 'doors without cut-out'
H67T111 4956280001 Housing frames and 'doors with cut-out'
H67E101 5097050001 Component carrier for H67... Including cable ducts, mains terminals and battery retaining plate
H67Z020 4969020001 Shielding hood for H67E...
H15Z300 4761970001 Retaining plate for batteries For H67E110; max. 5 items per component carrier (= 5 pairs of bat-
teries)
Z1K020 4754860001 Terminal block and board holder Without cables (for connecting directly to the plug-in module)
Z3S090 4969570001 Key switch options (no locking cylin- For subsequent retooling of DOM –> KABA/KESO/SEA etc.
der)

59
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Housing range H98...

23 Housing range H98...


–> for details, see document 654 / ZH4.2 Installation of component carriers H47E.../H67E...
–> for details see page 44
600

H98G600 H98G600
H28V000

H28V010

19”
H98T000 Doors can be
locked with KABA
2015

H98T020 lock 1057-25 H98Z010


H15Z200

H67Z020

395
H15Z300
300
Note:
Doors hinged on right Doors hinged on left To conform to CE requirements, the H67Z020 cover cap
must be used
H98G600: H98T000/020:
Measurements 600 x 2110 x 300 mm Material Steel sheet
Material Steel sheet Color RAL7035 light gray
Color RAL7035 light gray Protection category IP40
Protection category IP40
 Upright cabinet made from steel sheet with doors and no windows
 For large control panels or special applications
 Several upright cabinets can be merged to form a group
 Doors hinged on right or left
 Installation level:
– Rear wall –> component carriers H67E101/111 and H47E100/110 or univer-
sal carrier G1E010 –> see page 44
– Cover strip H98Z010 per cabinet or group of cabinets

Mechanical components for H98 housing


Cabinet H98...
H98G600 4161280001 Housing 42HE with base
H98T000 4161310001 42HE doors, hinged on right, no windows
H98T020 4594150001 42HE doors, hinged on left, no windows
H98Z010 4176060001 Pair of cover strips for H98G600 Needed per cabinet or group of cabinets
H15Z200 4597160001 Folder pocket for H98T.. For holding documentation about the system
Component carrier
H67E101 5097050001 Component carrier for H67.. 'complete' With cable ducts and battery retaining plate
H67E111 5097180001 Component carrier for H67... 'Empty' For non-standard applications
H67Z020 4969020001 Shielding hood for H67E... If component carrier is fitted in third-party housing (conforms to
CE)
H47E100 4748850001 Component carrier for H47.. 'complete' With cable ducts and battery retaining plate
H47E110 4761840001 Component carrier for H47.. 'Empty' Without cable ducts and battery retaining plate
H15Z300 4761970001 Battery retaining plate for H47E110
H67Z020 4969020001 Shielding hood for H67E...
Options for front installation
H28V000 3795820001 Beams for 19" / 6HE adaptation
H28V010 3795660001 Hinge for 19" / 6HE adaptation for G2F031
Options for installation on rear wall
Z3G170 4762230001 Installation options for H47E.../H67E... For securing to rear wall (profile) –> see page 44
G1E010 3842760001 Universal carrier 3HE For securing options

60
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Overview of 19" options

24 Overview of 19" options

Use of third-party housings

19" housing 19" housing 19" housing

H67E101 Z2G030
H47E100 19”

G2A130

B3Q...

G2A140
Z3B180

19”

G2F031
19”

Components
19" options
Z3B180 4762070001 19" adapter kit for H47E.../H67E...
Z2G030 3781980001 19"/6HE hinge Consisting of hinge and spacer profile
G2A130 4750880001 19"/6HE adapter plate For AlgoPilot B3Q...
G2A140 4842280001 19"/6HE adapter plate For B3R051 / B3Q321 etc.
G2F031 4092900001 19"/6HE front frame For printer B2Q191

61
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Principle of internal pre-wiring

25 Principle of internal pre-wiring


Component carrier H47E... Component carrier H67E...

1 1
Connection cable Connection cable
Z1I030 –> short 0.5 m Z1I050 –> short 0.8 m
19-wire 19-wire
1
2 2
Connection cable Connection cable
Z1I020 –> short 0.5 m Z1I040 –> long 0.8 m
1
9-wire 2 9-wire
Z1I060 –> short 0.5 m Z1I070 –> long 0.8 m
4-wire 4-wire
Z1I100 –> short 0.5 m Z1I110 –> long 0.8 m
10-wire 10-wire
2

3 3
Terminal block Z1IK020 Terminal block
For directly connecting 3 Z1IK020
the periphery For directly connect-
ing the periphery

Components
Cables, terminals
Z1I020 4754990001 Connection cable, 9-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I030 4755090001 Connection cable, 19-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I040 4755120001 Connection cable, 9-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I050 4755250001 Connection cable, 19-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I060 5258020001 Connection cable, 4-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I070 5258150001 Connection cable, 4-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I100 A5Q00007486 Connection cable, 10-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I110 A5Q00007487 Connection cable, 10-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1K020 4754860001 Terminal block with board holder for H47/H67 Without cables, for direct connection

62
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26 Line plug-in modules


 There are different line plug-in modules for the various detector systems:
– E3M071 for interactive detectors
– E3M171 for interactive 'Ex' detectors
– E3M120 for CBA8000/TS9000 detectors
– E3M111 for AnalogPLUS detectors
– E3M060 for MS9i detectors
– E3M080 for collective detectors (limit value detectors)
TM
– E3M141 for Sinteso devices

I-Bus
E3X10.
ST10 ST10 ST10 ST10 ST10 MIMIC DISPLAY
E3M071 E3M171 E3M120 E3M111 E3M060 E3M080 E3M141
24V 1........4 1...... ..4 1 2......... 8 1........2
24V 24V

max. 500mA

max. 500mA
max. 500mA

ST10/MIMIC DISPLAY= plug for special application (E3G110) –> see page 88
TM
Detector AlgoRex AlgoRex CBA8000 AlgoRex MS9i AlgoRex Sinteso
system Interactive Interactive Ex TS9000 AnalogPLUS MS9i-PLUS Collective addressed
MS716i MS6/7/9
(MS6: Detectors without
light bulbs only
as AI)
Number of
1 1 4 4 1 8 2
lines
No. of
1 x 128 1 x 32 4 x 119 4 x 128 1 x 50 8 2 x 126
addresses
Loop line  –    – 
Stub line   –    
Short In every HFM and
circuit I/O module. In every In every In every
– – In every device
isolator Detectors both with device device device
and without
Special  Any number of  Any number of  Sep. 24 V  Evaluation of  Always just
features T-branches T-branches feed output line short 1
for circuit T-branch
 Sep. 24 V feed  Response I/O mod- can be selected between 2
output for indicator out- ules as devices
I/O modules put fault or
on detector alarm
can be pro-
 Response indi- grammed
cator output
on detector
can be pro-
grammed

Z1I020/040 Z1I030/050
Z1I100/110 Z1I060/070

E3M120
E3M111
E3M060 Z1I060/070
(only for CH)

E3M071 E3M141 E3M171 E3M080

63
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.1 Overview of recording periphery

FDOOT
FDO FDT
DOT FDL FDF FDM
DOW
DLO DF DM
DO DOTE DT
Interactive DOT115x DM115x
DO115x DCW1151 DT1152 DLO1191 DF119x
E3M071 DOTE1152 DMA1153
Interactive Ex Via SB3 Via SB3 Via SB3 Via SB3
– – –
E3M171 1) DOT1151A-Ex DT1151A-Ex DF1151-Ex DM115x-Ex
AnalogPLUS DM113x
DO113x – DOT1131 DT113x – DF119x
E3M111 DMA1133
Collective DM1101
DO110x – – DT110x DLO1191 DF119x
E3M080 DMA1103
MS9i
– – – – – – (AT50Mi)
E3M060
FD20 FDO221 FDOOT221 FDT221 FDF221-9 FDM221
– FDL241-9
E3M141 FDO241 FDOOT241-9 FDT241 FDF241-9 FDM223

OH320C
MS716i
Collective
MS6 MS9i
FDS Ex detector HI320C
MS712 MS24
Contact detec- Output modu-
OP320C tor le
Interactive Via DC1192
– – Via DC1192 CB320A DC1157-AA DC115x
E3M071 + SB3
Interactive Ex
– – – – – – –
E3M171 1)
AnalogPLUS Via DC1192
– – – CB320A DC113x DC113x
E3M111 + SB3
Collective Via DC1192
E3M080 + SB3
–   – – –
or
via SB2 2)
MS9i Via E90Mi
E90Mi
E3M060 – –  + DC1192 – E90Ci
etc.
+ SB3
FD20
FDS221 – – – – FDCI222 FDCIO222
E3M141
1) Before SB3, all E3M071 devices possible
2) Note page 70 for SB2 limitations

DO / FDO Optical smoke detector


DOT / FDOOT Neural and/or multi-sensor smoke detector
DOTE Multi-criteria smoke detector
DT / FDT Heat detector
DLO / FDL Linear smoke detector
DF / FDF Infrared flame detector
DOW Radio smoke detector
DCW Radio gateway
DM / FDM Manual call point
DC / FDC Input/output module
FDS Alarm sounder
DC1192 Detector line coupling
SB3/(SB2) Safety barrier 2)
CB320A Input module for collective detectors (SynoLINE300)
OH320C Multi-sensor smoke detector (SynoLINE300)
HI320C Heat detector (SynoLINE300)
OP320C Optical smoke detector (SynoLINE300)

64
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules
Components
Line plug-in modules
E3M071 4984050001 'Interactive' line plug-in module 1 loop line (max. 128 addresses)
E3M171 5286340001 'Interactive Ex' line plug-in module 1 stub line (max. 32 addresses)
E3M111 5115310001 'AnalogPLUS' line plug-in module 4 loop lines (4 x max. 128 addresses)
E3M141 S54405-A9-A1 'FD20' line plug-in module 2 loop lines (2x max. 126 addresses)
E3M080 4602680001 'Collective' line plug-in module 8 stub lines (8 x max. 25 detectors)
E3M120 5340130001 'CBA' line plug-in module 4 loop lines (4 x max. 119 addresses) for
CBA8000/TS9000
E3M060 4602260001 'MS9i' line plug-in module 1 loop line (1 x max. 50 addresses)
End-of-lines
With 20 V transzorb diode Contained in E3M080
E3M080
EOL22(Ex) 5162220001 End-of-line element For E3M080
Cables, terminals
Z1I020 4754990001 Connection cable, 9-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I030 4755090001 Connection cable, 19-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I040 4755120001 Connection cable, 9-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I050 4755250001 Connection cable, 19-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I060 5258020001 Connection cable, 4-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I070 5258150001 Connection cable, 4-wire, 0.8 m Prefabricated cables with board holder for H67...
Z1I100 A5Q00007486 Connection cable, 10-wire, 0.5 m Prefabricated cables with board holder for H47...
Z1I110 A5Q00007487 Connection cable, 10-wire, 0.8 m Prefabricated cables with board holder for H67...

65
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.2 "Interactive" detector line


 Number of addresses per line: Max. 128, –> limitations for certain device
types 1)
 T-branches possible anywhere

max. 30 detectors
Ventilation,
3 contacts air-conditioning,
1 Loop line elevator etc.
DOW1171

3 relay
DF1191/92 contacts

DCW1151 DC1157-AA DC1156


DO115x DOT115x DOTE1152 DT115x DM115x DBZ1197A
E3M071 DMA1153

D-Bus max. 128 addresses / 120 Ω 1)

DLO1191
DC1192 DC1192 DC1192 CB320A DO115x DC1154

24VDC
24VDC DOT115x
SB3 OH

T branch
DO115x
Feedback-
DO1101-Ex HI DJ1192
contact
MS716 collective DOT115x
collective

MS9 collective OP Stubline


DT1101-Ex DS11 collective max. 32 detectors
D2401 SynoLINE300C
max. 5 detectors BFST
Ex .
DLR11

2)
DF1101-Ex

Programmable control output for 1 external response indicator in each detector base

Means of linking for external


response indicators
allocated to another ZONE 1 Basic programming
3 allocated to the detector AI external is allocated to the
ZONE (Default) logic detector ZONE
Room 101 1 -> most frequent application variant (Default)
ZONE 7 2 synchronous with the detector AI internal
AI external is allocated to detector
Room 102 in the base
-> e.g. for detectors in hollow floors
or false ceilings
ZONE 5 3 allocated to another ZONE
ZONE 9 AI external is treated as a control output
-> can thus be allocated to any logic
False ZONE or several ZONES
ceiling Room 103
2 Room 104
allocated to the detector

1) For details, see document 001508


2) For details, see document 1204

66
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.3 "Interactive" Ex detector line


 Number of addresses: Max. 32, –> limitations for certain device types 1)
 T-branches possible

1 Stub line
the software can not proof wheter or not Non-Ex-
detectors are in the explosion hazard area
non-Explosion
hazard area Explosion hazard area
D-Bus max. 32 addresses / 70  1)

E3M171
SB3 DM115x-Ex DOT1151A-Ex DT1151A-Ex
Dxx115x DF1151-Ex
Dxx115x

DT1151A-Ex

Dxx115x
DOT1151A-Ex

1) For details, see documents 001508 and 1204

26.4 'CBA8000/TS9000' detector line


 Number of addresses per line: Max. 119

4 Loop lines

1
CBA8000/TS9000

2
CBA-Bus max. 119 addresses / 30 
E3M120
3
CBA8000/TS9000 CBA8000/TS9000 CBA8000/TS9000

67
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.5 'AnalogPLUS' detector line


 Number of addresses per line: Max. 128, for limitations, see 1)
 All detectors, HFM and input/output module with integrated short-circuit isolator

DJ1192
DJ1191
4 Loop lines
DF1191/92

1 DC1131
DBZ1197A DO113x
DM113x DOT1131 DT/DOT/DO113x
DMA1133

2
AnalogPlus-Bus max. 128 addresses / 150 Ω 1)

E3M111 DC1192 CB320A DC1192 DC1192 DC1134-AA


DO113x DC1136
3
24VDC 24VDC
SB3 OH
4
DO1101-Ex HI
24VDC DJ1192
collective

OP
DT1101-Ex collective detectors
SynoLINE300C BFST
Ex
2)
DF1101-Ex

Control output for 1 external response indicator in each AnalogPLUS detector base

fixed allocation (output active as


soon as the internal LED is flashing)

Room 101

ZONE 7
Room 102

ZONE 5
ZONE 9

False ceiling

Room 103
Room 104

1) For details, see document 001508


2) For details, see document 1204

68
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.6 'MS9i addressing' detector line


 The E3M060 allows existing system parts to be integrated with detectors of the
MS9i/MS7i series
 Number of elements (addresses) per line: Max. 50, but depends on element
type 1)

Z9..Si Parallel detectors (slaves)


MS716i
1 Loop line max. 4 detectors MS716 collective MS9
MS9 collective
DS11 collective
D2401
Z9..Mi
K5M010
F910 F930
R936 R930 AT50Mi 24VDC
R970
E3M060
Addressing bus MS9i max. 50 addresses / 50  1)

E90Mi E90Mi E90Mi E90Ci


F716i
ATAN50Mi R716i
DC1192 R970
MS716 collective
24VDC MS9 collective
SB3 DS11 collective
D2401
DJ1192
DO1101-Ex max. 20 detectors BFST
collective

DT1101-Ex

Ex
2)
DF1101-Ex

Control output for 1 external response indicator in each addressable detector base

fixed allocation (output active as


soon as the internal LED is flashing)

Room 101

ZONE 7
Room 102

ZONE 5
ZONE 9

False
ceiling
Room 103
Room 104

1) For details, see document 825


2) For details, see document 1204

69
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.7 'Collective' detector line


 All detectors within a line have the same collective address (OBJECT)
 Depending on application, end-of-line by means of transzorb diode or EOL22
(Ex)
 Number of detectors per line:
– DS11 detectors: Max. 25
– MS6/7/9/24: According to individual load factor 1)
 For detector types that can be activated, see compatibility overview (document
001260)

8 Stub lines DJ1192

DO110x DT110x
F716 F910 R970
mixed detector series
'new' detector series
(DS11, MS9, MS716)
2
line termination :Transzorb 20 V
line resistance :max.150 
DM1101 DM1101
DMA1103 AT50 ATAN50 DMA1103

'old' detector series


3 'old' detector series
(MS712, MS6)
line termination EOL22
line resistance :max.250 

DLO1191
4 DF1191/92

DBZ1197A DM1101 DT110x DO110x


DMA1103
E3M080

Restriction:
DLR11 only with E3X100 permissible
see document 1204 and UP 109

DO1101-Ex DT1101-Ex DF1101-Ex


5 no detectors permissible Line termination
EOL22 (Ex)
SB2
Ex

for details see document 1204

DC1192 DO1101-Ex DT1101-Ex DF1101-Ex


8 Line termination
EOL22 (Ex)
DO110x SB3
24VDC
Ex

1) For details, see document 825 for MS6/7/9, for DS11 collective 001508

70
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Line plug-in modules

26.8 'FD20' detector line


 Number of addresses per line: Max. 126, –> limitations for certain device types
1)
 Only 1 T-branch possible between 2 devices

Stub line Stub line


max. 32 devices max. 32 devices

FDOOT241-9 FDO221

2 Loop lines
FDS221 FDT221

FDF2x1-9

FDT241 FDCL221 FDS221


FDO221 FDO241 FDOOT221 FDM22x

E3M141 FDnet max. 126 addresses / 210 Ω


FDL241-9
FDO/FDOOT/FDT2x1 FDCI222 FDCIO222

FDT221 FDOOT241-9 1...........4 1..4 1..4


FDO221

Feedback-
T branch

DJ1191/92
FDT241 contact

FDS221

Stub line BFST


.
DLR11
max. 32 devices

Programmable control output for 1 external response indicator in each SintesoTM detector base

Means of linking for external


response indicators
allocated to another ZONE 1 Basic programming
3 allocated to the detector AI external is allocated to the
ZONE (Default) logic detector ZONE
Room 101 1 -> most frequent application variant (Default)
ZONE 7 2 synchronous with the detector AI internal
AI external is allocated to detector
Room 102 in the base
-> e.g. for detectors in hollow floors
or false ceilings
ZONE 5 3 allocated to another ZONE
ZONE 9 AI external is treated as a control output
-> can thus be allocated to any logic
False ZONE or several ZONES
ceiling Room 103
2 Room 104
allocated to the detector

1) For details, see document 001508

71
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27 Control plug-in modules


27.1 Using control plug-in modules
 To activate fire controls (shut down ventilation, close fire protection flaps etc.)
 To activate and monitor alarm devices
 To activate and monitor remote transmission devices
 To activate mimic displays=

27.2 Overview of plug-in modules available with control outputs

Plug-in modules Remote transmission


Contact outputs
Monitored control lines Driver outputs interface
(potential-free)
For alarm devices Programmable For remote transmission
Programmable
devices
E3X10. 2 8+1 
E3G070 2 7 1) 2) 
E3L020 16 1)
E3G050 8
E3G060 6 5)
K3R072 48 3)
K3G060 24 NO contact 4)
K3I110 16 NO contact 5) 6)
1) Can also be used as control inputs (e.g. 'Confirmation')
2) These inputs/outputs are sometimes also used to control the remote transmis-
sion device (if available)
3) For mimic display activation, connected to the AlgoPilot B3Q... or K3I050 oper-
ating unit (not I bus component) –> for details, see page 74
4) For use with K3R072 only –> for details, see page 77
5) Programmable
6) LON bus component –> for details, see page 79

27.3 Link options


 Any statuses of recording nodes can be linked with control OBJECTS
 Just one control ELEMENT (= control output) is usually assigned to one control
OBJECT
 A user text is assigned to every control OBJECT
Acquisition level Control level
AREA
interactive E3G050
AnalogPLUS SECTION K3I110
CBA8000/TS9000 ZONE
MS9i Statuses:
collective - Alarm
FD20 - Info E3L020
- switched off E3X10.
- on detector TEST E3G070
- Fault
- etc. Control
Digital input ‘active’ ZONE E3G060

Operating level
Acknowledgement circuit
Operatable functions: not
Visible statuses: - switch on/off monitored
- active - activate/de-activate
- switched off
- executed (Acknowledgement') monitored
- Fault

72
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27.4 Control outputs, station type CC11

Basic equipment Additional control modules according to application


I-Bus
CPU
E3X10. E3I040
E3L020 E3G050 E3G060
Driver Converter
Driver I-Bus/LON Driver
1..........8 1..........16 1.........8 1..........6
24V
Z3B171 Z3B171 LON-Bus
RT
30VDC 1A

250VAC 10A 250VAC 10A


K3I110 max. 24V/2A
(max. 4A/E3G060)
Fire control
installations
1......16

30VDC 1A

27.5 Control outputs, station type CI11

Basic equipment Additional control modules according to application


I-Bus
B3Q...
E3L020 E3G050 E3I040 E3G060
Converter
CPU Driver I-Bus/LON Driver
E3G070 1..........16 1..........8 1..........6
Driver
1..........7 Z3B171 LON-Bus
24V 30VDC 1A
Z3B171
RT 250VAC 10A
K3I110
max. 24V/2A
250VAC 10A (max. 4A/E3G060)
1......16
Fire control
installations
30VDC 1A

Z1I030/050

Z1I100/110

E3X10x

Z1I030/050
E3I040
E3L020 E3G070
1
E3G060

E3G050
K3I110

1 Board holders included in cable kit Z3I350

73
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27.6 Control outputs, station type CT11 remote

I-Bus
B3Q...
E3I040
Converter
I-Bus/LON

LON-Bus

K3I110

1......16

30VDC 1A

 For installation details for E3I040, see document 1393

E3I040

Z1B070
K3I110

Components
E3X102 6290250001 Control panel module For alarm devices and control outputs
E3X103 6290380001 Control panel module ”
B3Q... AlgoPilot operating console All AlgoPilot variants –> see page 47
E3G070 5466610001 "Universal" control plug-in module ”
E3L020 5466450001 "Driver" control plug-in module 16 control inputs or outputs
E3I040 4993100001 LON plug-in module Converter between I bus and LON bus
Z1B070 A5Q00001720 Installation options for E3I040 Compulsory for installation of E3I040 in housing H28G200
K3I110 5288120001 LON I/O board 16 control inputs/outputs each
E3G050 4602550001 "Contacts" control plug-in module 8 control output contacts
E3G060 5425390001 "Monitored" control plug-in module 6 monitored control lines for alarm devices
Z1I030 4755090001 Connection cable, 19-wire, 0.5 m 1 item per E3L020/E3G050/60/70 each (in housing H47...)
Z1I050 4755290001 Connection cable, 19-wire, 0.8 m 1 item per E3L020/E3G050/60/70 each (in housing H67...)
Z3B171 4843830001 1 x 250 V AC/10 A relay module For switching external voltage
Z1I100 A5Q00007486 Connection cable, 10-wire, 0.5 m 1 item per E3I040 (in housing H47...)
Z1I110 A5Q00007487 Connection cable, 10-wire, 0.8 m 1 item per E3I040 (in housing H67...)

74
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27.7 CPU-wide controls

Multi-area Single-area

CT CT Gateway CK

C-Bus

CC/CI CC/CI CC/CI CC/CI


CPU CPU CPU CPU
1 2 3 n

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B.. B.. B.. B..

B = AREA Control OBJECT/ELEMENT


Must be in the same CPU
● = activating data point Control device

 Limitation: See section 8

75
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27.8 Mimic display outputs, station types CT11 and CI11

24V LED flat cable F50F410


1

K3R072
cable lenght 1m, 24 red LEDs

F12A100 48
LED-Flachkabel F50F410
or
AlgoPilot B3Q... F12A470 Mimic display panel

Parallel branching permissible

LED flat cable F50F410


24V 1

K3R072
cable lenght 1m, 24 red LEDs

Data bus
48
max.1000m LED flat cable F50F410
Z3I530 (not monitored)
(Adapter) Mimic display panel
AlgoPilot B3Q...

 For details, see document 001260

K3R072:
 Short-circuit-proof outputs
 Output for local buzzer and 'Operation' LED
 Inputs for 'Buzzer off' and 'Lamp test' button
 Suitable for activating LEDs only
 Outputs can only be assigned to statuses of one logical node
 Max. 24 devices, but only max. 8 addresses

Mimic display
panel housing Short-circuit proof in-/outputs only
for inside housing application
AlgoPilot
max. permissible length
of the data bus 1000m
K3R072

K3R072

LED 1....24
wires 49+50 for ’LED operation’

LED 25....48
wires 49+50 unused

Key 'Switch-off buzzer' These in-/outputs can be in parallel with


Dimensions: Key 'Lamp test' other K3R072 if located in same cabinet
104 x 200 x 43mm Buzzer
Z3I520

Components
K3R072 5286050001 Mimic display activation
Z3I520 4849690001 Cable kit for K3R072 Includes 12 cables (2-wire with connectors, length =0.5 m)
F50F410 5291410001 LED flat cable for K3R072 50-wire, 24 red LEDs, cable length 1 m
Z3I530 4849720001 Adapter for K3R072/B3R051 Adaptation of flat cable on terminals
F12A100 4952750001 'Micro' 12-pole, 0.4 m flat cable From AlgoPilot B3Q... to K3R072/B3R051
F12A470 4952880001 'Micro' 12-pole, 1.5 m flat cable From AlgoPilot B3Q... to K3R072/B3R051

76
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Control plug-in modules

27.9 Relay outputs, station types CT11 and CI11


Flat cable supplied with K3G060
24V 1

K3G060 K3G060
1
24 outputs
max. 30V/1A
48 24
F12A100
or K3R072 1
AlgoPilot B3Q... F12A470 max. 24 24 outputs
devices, however max. 30V/1A
max. 8 addresses 24

Parallel branching permissible


Flat cable supplied with K3G060
+ / - 1)

24V 1

K3G060 K3G060
1
24 outputs
max. 30V/1A
Data bus 48 24
max.1000m
Z3I530 (not monitored) K3R072
(Adapter) 1
AlgoPilot B3Q... max. 24 24 outputs
devices, however max. 30V/1A
max. 8 addresses 24
+ / - 1)
1) External potential
(switchable via jumper X1......X24)

 For details, see document 001260

K3G060:
 2 K3G060 can be connected per K3R072
 24 potential-free relay closing contacts
 Contacts not monitored
 Contacts can be linked individually via jumpers to externally supplied V+ or V–

Housing provided by customer

24 relay outputs
K3R072
K3G060

K3G060

24 relay outputs

Components
K3R072 5286050001 Mimic display activation
K3G060 5287860001 Relay board Option for K3R072
Z3I530 4849720001 Adapter for K3R072/B3R051 Adaptation of flat cable on terminals
F12A100 4952750001 'Micro' 12-pole, 0.4 m flat cable From AlgoPilot B3Q... to K3R072/B3R051
F12A470 4952880001 'Micro' 12-pole, 1.5 m flat cable From AlgoPilot B3Q... to K3R072/B3R051

77
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
LON bus devices

28 LON bus devices


28.1 Features
 Activation via local 'LON' communication bus
 4 different device types
– B3Q580 = plain text display terminal
– B3Q590/595 = plain text operating terminal
– K3I050 = LON/mimic display converter
– K3I110 = LON I/O board
 Activation via LON plug-in module E3I040 (converter between I bus and LON
bus)
 The 'LON bus' function is available once per 'CI' / 'CT' and 'CC' station type
 Max. 32 devices per LON bus (device types can be mixed in any way)
 Monitored two-wire bus without loop line function
 All devices require a separate supply line as of E3I040
 LON bus line management
– As 'Stub line' up to 1000 m (without T-branches)
– As 'Free topology' up to 500 m (length of line to all devices added together)
(with 'MICC' : as 'Stub line' ....700 m / as
'Free topology' ...300 m)
– With special cable (Belden 85102 or 8471) and as 'Stub line' up to 2700 m
– Possible via twisted line only (twisted in pairs, 10 twists a meter)
 CPU-wide functions possible
 B3Q59x: 3 LEDs can be replaced. Permits application with different LED color.

28.2 LON bus as stub line


E3X10.
CC11
I-Bus
or CI11
B3Q... E3I040 CT11

max. length of LON-Bus 1000m


LON-Bus
24VDC
K3I110 B3Q590/
K3I050 B3Q580
595

(not monitored)
Data bus
24VDC

K3R072 K3R072
or or
B3R051 B3R051
For details see
Z1I100/110 K3R072 –> page 76 or
B3R051 –> page 51

E3I040
E3I040

Z1B070

78
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
LON bus devices

28.3 LON bus as free topology

E3X10. I-Bus CC11


or CI11
B3Q... E3I040
CT11
max. length of LON-Bus 500m
B3Q580

LON-Bus
24VDC

K3I110 B3Q590/
K3I050 B3Q580
595
(not monitored)
Data bus
24VDC

K3R072 K3R072
or or
B3R051 B3R051
For details see K3R072 –> page 76 or
B3R051 –> page 51

28.4 Mimic display converter K3I050


 Permits mimic display activation K3R072 or parallel display B3R051 to be con-
nected (max.24 devices, but just max. 8 addresses)
 Various local inputs/outputs

Measurements:
106 x 200 x 14 mm For K3R072/B3R051
H23G230
K3I050

Input for 'Buzzer off' Z3I530


button
The functions of these Input for 'Lamp test' Lon-Bus 24V
inputs/outputs relate Z3B230
button
to the K3R072 and/or
B3R051 50cm
'Buzzer' output
Z3I520
'Operation' LED output K3I050

79
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
LON bus devices

28.5 LON I/O board K3I110


 Input/output board
– 16 programmable monitored control inputs
– 16 programmable control outputs

Measurements:
122 x 220 x 14 mm
H23G230
K3I110

K3I110

28.6 Display devices B3Q580 and B3Q590/595


 Both devices with identical sizes
 For recessed mounting, see page 55

H23G230 H23G230

B3Q580 B3Q590
B3Q595
B3Q590 (Nordic lock)
B3Q595 (KABA lock)

Function B3Q580 plain text display terminal B3Q590/595 plain text operating terminal
LCD 2x40 characters, yellow backlit  
Alarm events display All OBJECTS from
All OBJECTS per station (cannot be selected)
1..16 selectable SECTIONS
Fault events display Can be selected (yes/no via AlgoWorks) Can be selected (yes/no via AlgoWorks)
Selectable display operating modes 14 (can be selected via AlgoWorks) 14 (can be selected via AlgoWorks)
Buzzer can be turned off  
3 programmable LEDs – 
'Continue' function key  
(also used for Buzzer off + lamp test) (also used for Buzzer off + lamp test)
'Acknowledge' / 'Reset' function keys – 
Key switch for operating access B3Q590 = Nordic

B3Q595 = KABA
Can be fitted in housing H23G230  
Insertable inscription strips  
Operating voltage 9...45 V DC 9...45 V DC
Current consumption at 24 V Standby: 20 mA / max: 180 mA Standby: 18 mA / max: 185 mA

80
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
LON bus devices

Components
E3I040 4993100001 LON plug-in module Converter between I bus and LON bus
K3I050 4967660001 LON/mimic display converter Converter between LON bus and data bus for K3R072 or
B3R051
K3I110 5288540001 LON I/O board 16 programmable control inputs/outputs
B3Q580 4961770001 plain text display terminal
B3Q590 4961800001 Plain text operating terminal with Nord. lock
B3Q595 5341100001 Plain text operating terminal with KABA lock
H23G230 4750910001 Plastic housing
Z3I520 4849690001 Cable kit for K3R072 Includes 12 cables (2-pole with connectors, length =0.5 m)
Z3I530 4849720001 Adapter for K3R072/B3R051 Adaptation of flat cable on terminals
Z3B230 5590010001 Mounting plate For K3I050 in H23G230
Z1B070 A5Q00001720 Installation options for LON plug-in module For use in H28G200
E3I040
Z1I100 A5Q00007486 Connection cable, 10-wire, 0.5 m For use in H47...
Z1I110 A5Q00007487 Connection cable, 10-wire, 0.8 m For use in H67...
Available labeling kits(if no designation strips are available –> use templates from document 006516)
Z5B710 5104480001 'Nordic' labeling kit For B3Q580 (S, N, FIN, DK)
Z5B720 5104510001 'Europe' labeling kit For B3Q580 (UK, GER, F, I)
Z5B730 5104640001 'Nordic' labeling kit For B3Q590/595 (S, N, FIN, DK)
Z5B740 5104770001 'Europe' labeling kit For B3Q590/595 (UK, GER, F, I)
Z5B750 5105740001 'CH' labeling kit For B3Q590/595/580

81
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Gateway

29 Gateway
29.1 Main features
 C bus network <–> DMS / LMS connection via V28 interface (RS232)
 Conversion C bus <–> CERLOOP/CERBAN/ISO1745
 For bridging distances of up to 1000 m (double V28 modem integrated)
 For distances > 1000 m, use FSK/PSK modem
 Several gateways are possible per C bus network, see section 8
 Is preferably accommodated in a housing of a fire control panel
 Can also be operated autonomously with separate supply (E3C011 + B2F020 +
batteries)
 Extra hardware is needed for the connection to the CERLOOP network
(K1H022, K1D081 or K1D121)
 Extra hardware is needed for the connection to the NK8000 network (NK823x.2,
NKA8011-A1, NZ8201)
 Check according to outline quantities section 9.3

CERLOOP (V28) CERBAN (V28)

CT11 CT11

E3H021 E3H021
C-BUS

CC11 I-BUS K1H022


CI11 CK1143
Line- Control- module CERBAN (FSK)

Detector
CERLOOP/
CERBAN/ K1D081
ISO1745
E3H021

DMS/LMS
DMS8000 M3P030
K1D140
Note: CERLOOP (FSK)
Select corresponding protocol depending on application.
Assign the DMS network address to CC/CI and CK (via program-
ming in AlgoWorks)

For valid DMS network address, see document 004075 NK8000 (Ethernet)
E3H021

K1H022
E3H021

NK823x.2
NKA8011-A1
K1D121 NZ8201
Installation of modem filter
under network terminals
–> see installation example on page
83

82
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Gateway

29.2 Application variants

C-Bus CERLOOP (V28)


M3P030
24VDC K1H022 K1D081 K1 OP IP
E3H021 DMS / LMS
TTL ST2 F14E320 A3/4 A1/2 F14A320 A1/2 K2 M3P030
OP IP
or

Installation example: CERLOOP (FSK)


H47 housing
K1D121 K1
DMS / LMS
A1/2 K2
Connection field

31 32 33 34 35 36 Mains 36 36 CERBAN (V28)


terminals E3H021
E3I020

24VDC
E3H021 + 2xZ1I030
E3H021 + 2xZ1I030

E3H021 + 2xZ1I030
E3G...
E3L...

M3P030 RS232 X2 DMS / LMS


E3X10. + 2xZ1I030 + Z3I350

M3P030
2x

42 43 44 45 47 48 47 47 48
NKA8011-A1 CERBAN (FSK)
+

NK823x.2
K1H022

K1D140
Z1K050

Z1K050

Z1K050
E3M...

E3M...

E3M...

E3H021 K1D140
NZ8201
K1D...

24VDC
TTL ST2 F14E320 A1/2 DMS / LMS

Batteries

essential ISO1745
E3H021
Options 24VDC
X2 DMS / LMS /
RS232
External system

Autonomous with its own power supply


mains NK8000 (Ethernet)
B2F020 E3C011 Batteries
B2F040 24V FA... E3H021
24VDC Ethernet
24V RS232 X2 NK823x.2 DMS8000
E3H021 I-Bus
ISO1745 or CERBAN protocol

 For details, see document 001260

Components to gateway
B2F020 A5Q00025281 Converter 115/230 V DC ->29.6 V DC, 6 A
B2F040 5102990001 Converter 115/230 V DC ->29.6 V DC, 3.5 A
Z1I... Connection cable with board holder For H47E... –> Z1I020/030; for H67E... –>
Z1I040/050
E3H021 A5Q00024660 Gateway plug-in module Needs 2 plug-in slots
CKY00xxx (PSP) Flash program file Software for C bus <–> CERLOOP/CERBAN
K1D081 4637730001 Dual modem board V28 For CERLOOP application
K1D121 4706010001 Dual modem board FSK/PSK For > 1000 m between E3H021 and DMS7000 (CER-
LOOP)
K1D140 4706140001 Modem board FSK/PSK For > 1000 m between E3H021 and DMS7000 (CER-
BAN)
K1H022 A5Q00014427 Communications board For use with CERLOOP
Z1K050 4952200001 Board holder For securing K1D... / K1H022
F14A320 3196520001 Flat cable, 14-wire, 0.5 m For connection K1H022 –> K1D... (CERLOOP)
F14E320 4514390001 Y-flat cable, 14-wire, 0.5 m For connection E3H021 –> K1H022 / E3H021 –>
K1D…
– 4634980001 Solid-state relay Compulsory for: K1D121 –> 2x / K1D081 –> 4x
M3P030 3787740001 Modem filter module Compulsory for CERLOOP application (V28)
NK823x.2 – Ethernet Port
NZ8201 – Installation kit for NK82xx For order no., see document A6V10238669
NKA8011-A1 – Mounting plate for NK823x

83
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Remote transmission (not conforming to EN54-2)

30 Remote transmission (not conforming to EN54-2)


Most fire detection installations are connected to a remote transmission. In alarm
status (alarm level 2) the fire detection system activates the remote transmission
device (RT device).

Remote transmission device


– Installed in control panel housing
– Space needed depends on RT device
– 24 VDC supply for control panel
– Single-channel (alarm + fault) or multi-channel (multi-criteria alarm)
– Block/release via AlgoPilot

Connections
– Via contact outputs and special inputs/outputs from central plug-in module
E3X10. or control panel module E3G070
– Via remote transmission interface E3G091 if 'Multiple criteria' are used
– Via control plug-in module 'VdS’ E3L030' 'Main detector' (ÜE) (Germany)
– Can be used spanning several CPUs (several CPUs linked to the same RT de-
vice)

Interfacing via E3X10. Interfacing via E3G070

I-Bus
AlgoPilot
B3Q... (CPU)
E3X10. I-Bus
CPU E3G070
Alarm Fault Alarm Fault
K2 24V K2 24V
E3....

RT-devices RT-devices
CC11 CI11

Interfacing via E3G091 Interfacing via E3L030

E3X10./E3G070 I-Bus
CPU

Q1.........Qx K2 24V

E3L030

E3G091

CC11 CC11
RT-devices CI11 CI11

RT

84
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Remote transmission (conforming to EN54-2)

31 Remote transmission (conforming to EN54-2)


Most fire detection installations are connected to a remote transmission. In alarm
status (alarm level 2) the fire detection system activates the remote transmission
device (RT device).

Remote transmission device


– Single-channel (alarm + fault) or multi-channel (multi-criteria alarm)
– Block/release via AlgoPilot

Connections
– Via outputs and special inputs/outputs from central plug-in module E3X10. or
control panel module E3G070
– Via remote transmission interface E3G091 if 'Multiple criteria' are used
– Via control plug-in module 'VdS’ E3L030' 'Main detector' (ÜE) (Germany)
If the E3L030 is present, the ÜE MUST be used.

– Can be used spanning several CPUs (several CPUs linked to the same RT de-
vice)

Interfacing via E3X10. Interfacing via E3G070

I-Bus
AlgoPilot
B3Q... (CPU)
E3X10. I-Bus
CPU E3G070
Alarm Fault Alarm Fault
K2 K2
E3....
FDCIO223

RT-devices RT-devices
CC11 CI11

Interfacing via E3G091 Interfacing via E3L030

E3X10./E3G070 I-Bus
CPU

K2 Fault
Q1.........Qx

E3L030

E3G091 FDCIO223
Alarm

CC11 CC11
RT-devices CI11 CI11

RT

85
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Remote transmission (conforming to EN54-2)

31.1 CPU-wide remote transmission

all-AREA single-AREA

CT CT Gateway CK

C-Bus

CC/CI CC/CI CC/CI


CPU CPU CPU

Area 1 Area 2 Area 3 Area 4

common RT-device
for all AREAS common RT-device for several CPUs
within CPU

● = activating data point 'RT' control element

RT device

 Even functions in degraded mode operation by means of degraded mode func-


tions

86
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Extinguishing

32 Extinguishing
32.1 Main features of extinguishing SECTION
 Extinguishing section consists of:
– Control plug-in module E3G080 (I bus component)
– 'Extinguishing' operating unit B3Q440
– Option Monitoring board K5L020 to monitor and control additional solenoid
extinguishing valves
 E3G080 is designed for one extinguishing SECTION

max. 600m 5 wires Ø 0.8 mm


H23G230

E3G080
Line and device monitored
Z1I030/050

B3Q440

E3G080

Z1K030

K5L020

 For details, see document 001260

CT11

C-Bus

CC11 CI11
I-Bus I-Bus
E3X10.
K5L020 AlgoPilot K5L020
E3G080 (option)
E3M... B3Q... E3G070 E3G080 E3M...
(option)
LON-Bus

Z3B171 Z3B171
LON-Bus

DM1103 DM1103
ST* ST*
24V 24V

B3Q440 *ST = B3Q440


- Ventilation switch off
- Door magnet
Extinguishing SECTION - etc.
Extinguishing SECTION

Manual activation
– Use collective yellow hand-operated button DM1103 with DMA1192-AC
Components for extinguishing section
E3G080 4759490001 'Extinguishing' control plug-in module Needed per extinguishing SECTION
E3G110 5049910001 Degraded mode link Option for 'Extinguishing' control plug-in module E3G080 (see section
32.2)
B3Q440 4759520001 'Extinguishing' operating unit Max. 4 possible (including labeling kit in 'English')
For other languages –> use templates of document 006516
H23G230 4750910001 Plastic housing 125x219x76 mm For B3Q440
Z1I030 4755090001 Connection cable, 19-wire, 0.5 m With board holder; for housing H47…
Z1I050 4755290001 Connection cable, 19-wire, 0.8 m With board holder; for housing H67…
Z1K030 4842310001 Terminal block + board holder For housing H38…
K5L020 4412320001 2-area extinguishing board For details, see document 001260
Z5B700 5104220001 'CH' labeling kit For B3Q440
87
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Extinguishing

32.2 Degraded mode link E3G110 option


 Allows extinguishing to be activated automatically even if the main CPU fails.
Depends on 2 detectors.
 The detectors in the extinguishing SECTION must be split over 2 independent
detector lines.

CC11, CI11
CPU Z1I030/050
I-Bus
E3X10.
or
E3G080 E3G110 E3M071 E3M071
B3Q...
K1 K1 K1 ST1 ST8 ST10 K1 ST10 K1
1......4

24/5V

Manual activation interactive


DM1103 detectors E3G110
B3Q440

Note:
'ST10' connector only provided for E3M060 (MS9i), E3M071 (interactive), E3M171 (interactive Ex),
E3M080 (collective) and E3M111 (AnalogPLUS)
'MIMIC DISPLAY' connector for E3M141

32.3 Key data

'Delayed' area valve – Activation delay of 0..240 s


– Limitation of activation period of 0..240 s or until reset
– Monitored line
– Line can be adjusted to area valve
'Non-delayed' main valve – Limitation of activation period of 0..240 s
(activation of pneumatic path) – Monitored line
– Line can be adjusted to main valve
Alarm horn – Can be turned off by extinguishing operating unit or control panel
– Monitored line
– Activation mode active continuously/can be programmed to pulse
Illuminated panel – Can be shut down separately or remains active until reset
– Monitored line
– Activation mode active continuously/can be programmed to pulse
Manual activation – Directly only E3G080
– Also functions when control panel is in 'degraded mode'
– Line monitored
Automatic activation – Via detector –> control panel, parameters can be set for alarm, either for:
– Detectors in same OBJECT
– Detectors in different OBJECTS
– Detectors in same or different OBJECTS
– All detector models can be used (interactive / AnalogPLUS / collective)
Stop/block button – Separate monitored line
'Loss of extinguishing agent' reporting contact – Separate monitored line
'Extinguishing blocked' reporting contact – Separate monitored line
'Extinguishing activated' reporting contact – Separate monitored line
Local operating unit – Using 'Extinguishing' operating unit B3Q440
– Usage recommended, but not compulsory
– Max. 4 operating units possible
– Via LON data bus with monitored line
– Length of line up to 600 m
Fire control – Via control panel control output
Special feature – Autonomously functioning I bus component
– Integrated degraded mode function
– Parameter settings via AlgoWorks
– User functions saved on E3G080
– Several extinguishing SECTIONS can be interlocked with one another
– Automatic adjustment function

88
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Extinguishing

32.4 Typical extinguishing system


 The requirements relating to monitoring depend greatly on the extinguishing
agent used and the properties of the mechanical hardware used
 The system must satisfy the local requirements

Pipe network
with nozzles

10

13

1
3

9 6 5

4 12
8
2 11

Extinguishing agent
Means of activation

32.5 Functions needed

Item Function Explanations FM200 CO2


1 Electrical activation 'Delayed' area valve  
2 Pneumatic activation 'Non-delayed' main valve 
3 Electronic alarm horn Possibly several devices depending on noise level  
4 Pneumatic alarm horn E.g. driven with control agent 
5 Illuminated panel In front of every door  
6 DM1103 manual activation Special button (yellow)  
7 Autom. activation 'Multi-detector dependent' Detector in 'Extinguishing' OBJECT type  
8 Local operating unit B3Q440 operating unit  
9 Stop or block button Special button or door lock contact  
10 'Activated' reporting contact Pressure control  
11 'Loss of extinguishing agent' reporting contact Bottle scales or pressure gauge  
12 'Mechanically blocked' reporting contact Mech. blocking on bottle battery  
13 Fire control Door magnet etc.  
 Compulsory
 Recommended or needed depending on mechanical hardware used or local requirements

89
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Printer interface

33 Printer interface
33.1 Features
 Available for station types CT11, CI11, CC11
 Designed for B2Q191, B1Q101 printers, commercially available ISO-LATIN1
printers and EPSON printers
 Depending on use, extra hardware needed to adapt levels
 Printer B2Q191 can be connected up directly (for installation inside housing)
 Printer can be switched on/off individually via the operating unit
 Is always assigned to all AREAS available in the station used
 Individual parameter settings per printer interface
 Event memory can only be printed out when the printer is connected to a CI11 or
CT11 station

33.2 CT11 application variant

AlgoPilot B3Q... CT11 E3I020


B3Q...
I-Bus ST2 to printer

ST2 F20A020 ST1


E3I020

ST2
RS232
C-Bus
max.1000m
or
Z1B020
K3
B2Q191 F20A020

24VDC K2 in cabinet H26/H28


(9...36VDC)

AlgoPilot B3Q...
CT11
I-Bus

(TTL) F20A410
ST2 F20A410 A3
B2Q191
max. 1m
24VDC B3Q...
K2
C-Bus

Condition:
– B2Q191 printer is in the same housing as the AlgoPilot B3Q… operat-
ing unit or in a neighboring housing

– With this application, the earth connection of the 'K3-5' terminal of


B2Q191
K3L080 must be routed to the housing, otherwise ground fault is pro-
duced (see document 001260)

in cabinet H26/H28

90
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Printer interface

33.3 CC11 usage variant

CC11 zum Drucker

I-Bus
E3X10.
ST2 F20A020 ST1
E3I020

X2
RS232 Z1I030/050
C-Bus max.1000m
E3I020
or

K3
B2Q191

24VDC K2
(9...36VDC) E3X10.

F20A020

CC11
I-Bus
E3X10.
(TTL)
ST2 F20A410 A3
max. 1m B2Q191

24VDC K2
C-Bus

Condition:
– B2Q191 printer is in the same housing as the main CPU (E3X10.) or
in a neighboring housing
F20A410
E3X10.
– With this application, the earth connection of the 'K3-5' terminal of
K3L080 must be routed to the housing, otherwise ground fault is pro-
duced (see document 001260)

zum Drucker
B2Q191

Components
B2Q191 4848880001 Tape printer 240 x 340 mm, 9 . . .36 V DC
E3I020 4602390001 RS232 plug-in module Level adjustment HCMOS –> RS232
Z1I030 4755090001 Connection cable, 19-wire with board hol- Also for internal cabling in housing H47…
der, 0.5 m
Z1I050 4755250001 Connection cable, 19-wire with board hol- Also for internal cabling in housing H67…
der, 0.8 m
Z1B020 4759070001 Installation options For securing E3I020 on the rear of AlgoPilot B3Q…
F20A020 4763170001 20-wire 0.165 m 'Micro' flat cable
F20A410 4953270001 20-wire 0.165 m 'Micro' flat cable

91
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Printer interface

33.4 CI11 application variant

AlgoPilot B3Q... CI11 E3I020 F20A140


I-Bus Z1K030

F20A140
E3I020 to printer
ST2 ST1
X2
RS232 B3Q...
C-Bus
max.1000m
or

K3
B2Q191

24VDC K2 in cabinet H38


(9...36VDC)

to printer
AlgoPilot B3Q... CI11 F20A140
I-Bus

ST2 F20A140 ST1


E3I020

X2
RS232 B3Q...
C-Bus
max.1000m
or
K3
B2Q191

24VDC K2 Z1I030 E3I020


(9...36VDC)
in cabinet H47

Components
B2Q191 4848880001 Tape printer 240 x 340 mm, 9 . . .36 V DC
E3I020 4602390001 RS232 plug-in module Level adjustment HCMOS –> RS232
Z1K030 4842310001 Terminal block + board holder For securing E3I020 to a plug-in space in H38…
Z1I030 4755090001 Connection cable, 19-wire with board holder, Also for internal cabling in housing H47…
0.5 m
Z1I050 4755250001 Connection cable, 19-wire with board holder, Also for internal cabling in housing H67…
0.8 m
F20A140 4968630001 20-wire 0.165 m 'Micro' flat cable

92
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Printer interface

33.5 B2Q191/B1Q101 tape printer


 Tape printer for event protocoling
 Integrated automatic paper winding device
 Thermomatrix printing unit
 Interface and printing unit monitored

 For more details, see document 001260

H28G200 housing 19" upright cabinet H housing

H28G200
H28T020

B1Q101

B2Q191
B2Q191
B2Q191
G2F031

G2F031 H28V000/010

B2Q191

B1F120

Z1K040

Printer with own power supply in housing H28, but no batteries

Components
B2Q191 4848880001 Tape printer 240 x 340 mm, 9 . . .36 V DC
B1F120 4952330001 Converter /230 V AC ->24 V DC, 3 A
H28G200 4099440001 520x300x70 mm housing bottom
H28T020 4105640001 Cover for H28G200
G2F031 4092900001 19"/6HE front frame For fitting printer B2Q191 in 19" cabinet
H28V000 3795820001 Beams for 19" / 6HE adaptation For G2F031
H28V010 3795660001 Hinges for 19" / 6HE adaptation For G2F031
Z1K040 4906650001 Holder For securing B1F120 to H28T020 (remove board holder)
B1Q101 5045800001 Tape printer 19" / 3HE, 9 . . .36 V DC Fit in 19" housing only (for more details, see document 1510)
Z3B040 3792490001 Winding fixture for B1Q101
– 3799770001 Replaced paper rollers (4 items)

93
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
PSA interface

34 PSA interface
34.1 Features
The PSA interface board K3I090 can be used universally and serves to analyze
the data transmitted by a control panel to its printer output and to transfer this to
a PSA or pager system in ESPA 4.4.4 format.
The optional printer is connected to the PSA interface board. If there is a printer
available, the data is forwarded straight to the printer. The interposed PSA inter-
face board is not visible to the control panel and printer.
The PSA interface board analyzes the print data for character strings at a particu-
lar position following defined rules. The rules are saved in the PSA interface
board. If a string of characters matches, the content of the printer message is
prepared for display on the pager or forwarded unchanged to the PSA.

 For details, see document 1669

94
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Power supply

35 Power supply

Concept
The power supply for the CS1140 fire detection system consists of:
 Converter (mains voltage –> system voltage 29.6 V)
 Battery charging unit (integrated in E3X10. or by means of E3C011)
 Batteries (capacityas required)

Special functions
– Automatic battery load test
– Battery charging characteristics can be programmed on the product

Application
– Individually define the battery capacity needed –> see page 99
– Protection for mains supply line in special cases only –> see page 104
– Max. 38 Ah per battery charging unit (> 38 Ah = additional power supply)
– Parallel operation of several battery charging units possible
– Battery supply line has no EMI protection (battery cannot be removed)

35.1 Power supply to control panel


– CC11 Battery charging unit is integrated in the control panel module E3X10.
– CI11 Battery charging plug-in module E3C011 needed

– Battery charging unit contained in E3X10.


– Is one of the max. 16 I bus components
mains mains

CC11 Batteries
CI11 Batteries
TF* B2F020 B2F020 E3C011
FA... FA...

TF*
Battery charching
unit 29.6V
29.6V
AlgoPilot
E3X10. I-Bus I-Bus
B3Q...

* TF = temperature sensor for battery temperature monitoring

95
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Power supply

35.2 Additional power supply

Auxiliary batteries for the basic power supply:


CT11 max. 1x E3C011 with battery set as an addition

Additional batteries with auxiliary power supply:


:
max. 3 battery sets per B2F020 possible
mains mains

Basic emergency power supply 1st extension 2nd extension 3rd extension 4th extension

1 2 3 4 5
C-Bus
Batteries Batteries B2F020 Batteries Batteries Batteries
B2F020
TF* FA12... TF* FA12... B2F040 TF* FA12... TF* FA12... TF* FA12...

E3C011 E3C011 E3C011 E3C011


24V Battery charching unit

E3X10.
I-Bus

CC11

Monitoring via I-Bus or separate HW monitoring path


* TF = Temperature sensor for battery temperature monitoring
- separate battery charging unit
- as regards "battery charging" identical to E3X10.
- I-Bus module

Auxiliary power supply without battery e.g for door magnets


mains

CC11
TF* Batteries B1F120
FA12... B2F020
...140VA
max. 3A / 24VDC
Battery charging
unit Door magnets
29.6V

E3X10. I-Bus

 For details of structure of additional power supply –> also see pages 39 – 45

Components
B1F120 4952330001 Converter 115/230 V AC ->24 V DC, 3A Supply for door magnets etc. only
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
B2F040 5102990001 Converter 115/230 V AC ->29.6 V DC, 3.5 A
B2F060 5112850001 Converter 115/230 V AC ->24 V DC, 4.5 A Supply for door magnets etc. only
E3C011 5054790001 Plug-in battery charging module
E3X102 6290250001 Control panel module 1MBx8 bits RAM
E3X103 6290380001 Control panel module 2MBx8 bits RAM
FA2006-A1 A5Q00019356 12 V / 24 Ah battery
FA2007-A1 A5Q00022897 12 V / 38 Ah battery
FA2005-A1 A5Q00019677 12 V / 15 Ah battery
 Mains protection elements (surge arrester and mains filter) see page 104

96
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Power supply

35.3 Operating unit with power supply as of control panel


– As of CC11 –> operating unit is connected to E3X10.
– As of CI11 –> operating unit is connected to AlgoPilot B3Q…

CT11 CT11

+ / - / Earth + / - / Earth

Output 1 Output 2 CC11 Output 1 Output 2 CI11


24V / 2A 24V / 2A

E3X10. I-Bus AlgoPilot B3Q... I-Bus

Note:
Second supply output needed for operating units that have to satisfy EN54 only
(at least 1 operating unit per system).

35.4 Operating unit with autonomous power supply


– For AlgoPilot B3Q… operating units located far away
– Operating unit and power supply can be fitted in H38 housing –> see page 51

mains

CT11
B2F020 Batteries
C-Bus E3C011 FA...
B2F040

TF*

AlgoPilot B3Q...
29.6V

I-Bus

* TF = temperature sensor for battery temperature monitoring

97
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Power supply

35.5 Power supply for remote transmission devices and options


– With CC11 –> devices are connected to E3X10.
– With CI11 –> devices are connected to E3G070

CC11 CI11

E3X10. I-Bus
I-Bus AlgoPilot B3Q...

Res: 24V / 2A FÜ: 24V / 2A E3G070


0.63A
24V / 0,63A

Cable set Z3I390


required for RT: Cable set
Z3I390 required
RT

other equipment Remote transmission


(z.B. printer) or other equipment
(e.g. printer)

FÜ = Remote transmission

Components
B3Q... …... AlgoPilot operating units All AlgoPilot variants –> see page 47
E3X102 6290250001 Control panel module Flash ROM and 1MB RAM fitted
E3X103 6290380001 Control panel module Flash ROM and 2MB RAM fitted
E3G070 5466610001 'Universal' control plug-in module For alarm devices and control outputs
E3C011 5054790001 Plug-in battery charging module
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
B2F040 5102990001 Converter 115/230 V AC ->29.6 V DC, 3.5 A
FA2006-A1 A5Q00019356 12 V / 24 Ah battery
FA2007-A1 A5Q00022897 12 V / 38 Ah battery
FA2005-A1 A5Q00019677 12 V / 15 Ah battery

98
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Emergency power supply

36 Emergency power supply


36.1 Determining the battery capacity

Emergency current batteries available


 FA2006-A1 A5Q00019356 12 V/24 Ah battery1)
 FA2007-A1 A5Q00022897 12 V/38 Ah battery1)
 FA2005-A1 A5Q00019677 12 V/15 Ah battery1)
1) The battery capacities supplied may be slightly higher.

 The values 15 Ah, 24 Ah and 38 Ah should be taken into account when defining
the battery capacities needed.

Nominal battery capacity


 The nominal battery capacity is based on discharge over a period of 20 hours
 Faster discharge results in drops in capacity:
 With 12-hour discharge=: 9% drops (K = 1.1)

Battery aging
 As the battery ages, capacity is reduced
 A safety factor should be used for aging (total quiescent current × 1.25 or bat-
tery capacity × 0.8) > 24 h, according to DIN VDE 0833, Part 2 a safety factor
is no longer needed

Calculation
The battery capacity should be calculated individually!
Formula: Ah = A x h (with 72 h battery)
Ah = A x h x 1.25 (with 24 h battery)
Ah = A x h x 1.25 x 1.1 (with 12 h battery)

A = sum of quiescent current of all components (see chap. 36.2)


h = operating period needed in hours
1.25 = safety factor for aging with 12 h and 24 h batteries only
1.1 (K) = drops in capacity with 12 h battery only
Ah = battery capacity in Ah

99
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Emergency power supply

36.2 Quiescent current table


– Quiescent current during battery operation (24 V)
– As basis for individual emergency current calculation
– The current of the 5 V supply is included in these values

Component Quiescent current at 24 V DC (typical) Extra current during alarm


B1F120 / B2F020 / 0 0
B2F040 / B2F060
B2Q191/B1Q101 33 mA max. 1 A for duration of print process
B3Q321 17 mA + 5 mA
B3Q440 25 mA + 10 mA
B3Q6../566 100 mA with inactive lighting (active = + 200 mA) + 230 mA
B3Q580 20 mA + 160 mA
B3Q590/595 18 mA + 167 mA
B3R051 22 mA all LEDs inactive + 2 mA per activated LED
E3C011 50 mA 0
E3G050 10 mA all relays inactive + 11 mA per activated relay
E3G060 25 mA all control lines connected + 23 mA per activated control line, no ext. load
E3G070 25 mA 'Horn' control lines terminated + 34 mA without external load (horns, etc.)
E3G080 35 mA all lines terminated + 25 mA without external load (valves, horns, etc.)
E3G091 0 all channels inactive + 9 mA per activated channel
E3G110 0 during degraded mode and alarm active only + 15 mA per activated channel during degraded
mode
E3H021 85 mA 0
E3I020 25 mA 0
E3L020 22 mA + .. mA depending on what is activated
E3L030 18 mA + 40 mA no external load (FBF, HM, FSK)
E3M060 155 mA (=120 mA + 0.7 mA per MS9i element) 1) 0
E3M071 115 mA (=50 mA + 0.5 mA per D bus device) 1) 0
(no external 24 V loading)
E3M171 70 mA with 32 detectors (=50 mA without detectors + 0.5 mA 0
per D bus device) 1)
E3M080 85 mA 37 mA + 6 mA per terminated line + 10 mA per line in alarm
E3M111 210 mA (=50 mA + 0.31 mA per D bus device) 1) 0
(A+ no external 24 V loading)
E3M120 8.5 mA +1.3 mA for each detector address 0
E3M141 80 mA without devices (+0.47 mA per load factor) + .. mA depending on what is activated
E3X102/103 120 mA 'Horn' control line terminated + 50 mA without external load (horns, etc.)
K1D012 25 mA 0
K1D081 50 mA 0
K1D121 50 mA 0
K1D140 25 mA 0
K1H022 20 mA (all LEDs and optocouplers active) 0
K3G060 6 mA + 3 mA per relay
K3R072 22 mA + 2 mA per activated LED (-> F50F410)
0 per activated relay (-> K3G060)
NK823x 190 mA 0
Z3B171 0 + 27 mA per activated relay
E3I040 15 mA no external 24 V loading 0
K3I050 15 mA + 0 mA or 4 mA per activated LED
K3I090 50 mA 0
K3I110 24 mA max. 184 mA all rel. activated including service LED + 10 mA per activated relay
+ 0.5 mA per input with closed contact

1) only valid for devices with APMK = 1 / IMK = 1 (value for devices > 1 multiplied). DC1151 example: 0.5 mA x 12 = 6 mA

100
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Emergency power supply

36.3 Capacity values for standard configurations


CS1140 configuration Quiescent Battery capacity requirement for
current 12 h 24 h 72 h
CI with 128 detectors interactive 260 mA 4.2 Ah 7.8 Ah 18.7 Ah
(B3Q… + 1xE3M071 including detector + 1xE3G070 + 1xE3C011)
CI with 128 detectors AnalogPLUS 235 mA 3.8 Ah 7.0 Ah 16.9 Ah
(B3Q… + 1xE3M111 including detector + 1xE3G070 + 1xE3C011)
CI with 16 lines collective 315 mA 5.1 Ah 9.4 Ah 22.6 Ah
(B3Q… + 2xE3M080 including detector + 1xE3G070 + 1xE3C011)
TM
CI with 126 Sinteso detectors (calculated using a load factor of 1) 284 mA 4.7 Ah 8.5 Ah 20.4 Ah
5)
(B3Q… + 1xE3M141 including detector + 1xE3G070 + 1xE3C011)
CC with 512 detectors interactive (Example) 724 mA 11.9 Ah 21.7 Ah 52.1 Ah
(E3X102/103 + 1xB3Q… + 4xE3M071 including detectors + 2xE3L020) 1) 2) 3) 4)
CC with 512 detectors AnalogPLUS 474 mA 7.8 Ah 14.2 Ah 34.1 Ah
(E3X102/103 + 1xB3Q… + 1xE3M111 including detectors + 2xE3L020)
CC with 64 lines collective 944 mA 15.5 Ah 28.3 Ah 67.9 Ah
(E3X102/103 + 1xB3Q… + 8xE3M080 including detectors + 2xE3L020)
TM
CC with 252 Sinteso detectors (calculated using a load factor of 1) 462 mA 7.6 Ah 13.8 Ah 33.3 Ah
5)
(E3X102/103 + 1xB3Q… + 1xE3M141 including detectors + 2xE3L020)

Example:
1) E3X102/103 + 1x B3Q… + 4x E3M071 including detectors + 2x E3L020 (120 mA + 100 mA + 460 mA + 44 mA = 724 mA)
2) 724 mA x 12 h x 1.25 x 1.1 = 11.9 Ah
3) 724 mA x 24 h x 1.25 = 21.7 Ah
4) 724 mA x 72 h = 52.1 Ah
5) For an accurate calculation, use document 008478 (Excel sheet)

Notes:
– Fault signal acknowledged
– LCD backlighting inactive (timeout expired)
– Alarm devices, remote transmission devices etc. not considered
– Alarming duration:
Alarming duration not considered (in most countries an alarming duration of 10… 30 min. still has to be considered with effectively con-
nected alarm devices), see chap. 36.2
– Also consider quiescent current for extra battery charging plug-in module E3C011

101
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Alarming concept

37 Alarming concept
 The alarming concept must be defined individually for each system
 The rapid forwarding of alarm messages to the corresponding circle of recipients
is important
The requirements vary between
– "Discrete alarming" of the investigation crew, e.g. using human search system
– "Alarming / evacuation" for people familiar with location
– "Alarming / evacuation" for people not familiar with location
– "Area evacuation", e.g. floor

37.1 Cerberus alarm concept (CAC)


 The Cerberus alarm concept prevents the unnecessary calling-out of the fire bri-
gade for minor incidents
 The CAC is based on a "presence-dependent" form of alarm organization:
– Presence of operating staff, known as 'Manned'
– Absence of operating staff, known as 'Unmanned'
 The response of the operating staff is monitored by 2 independent time circuits
(V1 and V2)
 The CAC is an integrated part of the CC11/CI11 control panel, the parameters
needed can be entered via user functions

Principle of the Cerberus alarm concept


– During the "Manned" operating status, if an alarm is sounded the location of the
fire is first sought, and the decision on whether it is a "Serious/ minor incident"
taken locally
– During the "Manned" operating status, all alarms immediately activate "Remote
alarms"
– Activation of a manual call point always immediately triggers a "Remote alarm"

Operating personnel: present absent present


Alarm or
event absent

F
Alarm 
Confirm message V1
Reconnaissance countdown V1
no
acknowledged
?
Minor yes
Investigate fire Emergency incident
locationMonitoring time V2 V2
F

reset
?
no

Remote alarm Alarm 

102
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Alarming concept

37.2 Defining alarm organization


– The CS1140 fire detection system has up to 64 programmable organizational
levels (AREAS)
– Different "alarming variants" are possible (can be selected per OBJECT)
– The "V1" and "V2" time memories should be defined individually
– The "V2" time memory can be defined per OBJECT (if needed)
– Various country-specific special functions are available
– The alarm organization is programmed individually (via maintenance PC)

37.3 Designing the system operating unit


 The place from which the fire detection installation is operated must be defined
from an organizational standpoint
 If necessary, a double operation unit must be provided
 Particularly exposed operating units should be fitted with lockable plexi glass
doors (H26T... + Z3S...)
 The type of event and geographic location are displayed on the operating unit in
plain text
 The names of the geographic locations (rooms etc.) are defined individually us-
ing "user text" (via maintenance PC)
 If necessary, an extra event-related instruction, known as 'measures text' can
be assigned to certain rooms
 The fire detection installation may only be operated by instructed persons (ac-
cess to the operating unit is therefore protected by password or key switch)
 For details of the AlgoPilot operating console, see page 47

103
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Protective elements

38 Protective elements

Purpose
Protection from overvoltage and electromagnetic influences (EMI).

Normal usage

Control panel
 No extra protective measures needed. All plug-in modules have integrated pro-
tection from overvoltage and electromagnetic influence, but no protection from
lightning.

Installation
 As a rule use twisted cables, for detector lines, data lines, external supply
lines and lines to alarm devices.

Special measures
In systems at particular risk of lightning strikes, such as:
– Switchyards
– Alpine transmission installations
 Provide surge arrester for mains supply line
If extreme HF mains faults are expected
 Provide mains filter for mains supply line

If Z3I041 or B3P020 is used, and fitted near the


mains terminals, E3M060/071/171/120 + E3C011
are not possible on item 36!

For details –> see documents 001260 and 1683

Z3I041

B3P020

Components
B3P020 A5Q00008751 250 V AC / 6 A mains filter
Z3I041 4962900001 230 V AC surge arrester kit
Z3I121 4963000001 110 V AC surge arrester kit
– 5645750001 C mounting rail TS32 L=108 mm

104
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Commissioning

39 Commissioning
 For details, see document 004594

The CS1140 fire detection system is designed for a rational installation setup.
Connection to the control panel may be undertaken by experts without special
training (e.g. external electricians). Coordinated construction management is
however still indispensable. A specially trained person with a maintenance PC is
needed for commissioning (service technician).

Procedure

Preparatory work (by designer / construction manager)


 Plan system
 Produce connection diagram for control panel
 Supply control panel housing, component carrier and connection panel
 Instruct assembly staff

Assembly / connection of control panel (by electrician)


 Installation of component carrier at intended location
 Connect lines to detectors, alarm devices etc. on connection panel according to
diagram
 Check detector supply network up to and including connection panel in control
panel

Commissioning (by service technician)


 Fit board holder, connection cable, etc.
 Insert electronic plug-in modules and attach I bus
 Produce logical structure of system or adopt from designer
 Define system-specific functions
 Define user text
 Set parameters for detectors using special evaluation algorithms
 Detector localization
 Check control panel and detectors
 Download system data

105
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Flash programming, parameter setting

40 Flash programming, parameter setting


 The parameters for the CS1140 fire detection system are set via the mainte-
nance PC using the 'AlgoWorks' software tool kit.
 Online help text in various local languages
 2 user levels (service technician; national manager)
 Program new software using 'FlashTool' software. For the E3X102/103,
B3Q6../566 and E3H021 components, the application software is loaded to the
Flash-ROM via the maintenance PC using 'FlashTool' software.

 For details, see document 004282

40.1 Flash programming of new application software

AlgoPilot B3Q6..
CPU/ S5-4: 'ON' 1)
Operating unit ST2

Maintenance-PC
with ‘FlashTool’

A2 K2
Modembox
ST1
B3D021
A1 K1

ST2

CPU S5-2: 'ON' 1)


E3X102/103

Gateway E3H021 S5-1 Both set as 'external'


S5-2 (ON) for download
ST2
S6-2: 'ON' 1)

F14E320 Maintenance-PC
Red marking with ‘FlashTool’

A2 K2
Modembox
ST1
B3D021
A1 K1

1) For releasing the Flash programming. Press 'Reset' after changing.

106
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Flash programming, parameter setting

40.2 Download system data

40.2.1 61.2.1 B3Q4../B3Q6../E3X10./E3H02.


AlgoPilot B3Q6..
B3Q4..
CPU/
Operating unit ST2

Maintenance-PC
with ‘AlgoWorks’

A2 K2
Modembox
ST1
B3D021
A1 K1

ST2

CPU
E3X101/102/103

Gateway E3H021 S5-1 Both set as 'external'


S5-2 (ON) for download
E3H020
ST2

F14E320 Maintenance-PC
with ‘AlgoWorks’
Red marking

A2 K2
Modembox
ST1
B3D021
A1 K1

Functions at "Service technician" level


– If necessary, load new application software (Flash)
– Produce/add to logical structure for system
– Define user functions (system-specific)
– Define/correct user text
– Detector localization
– Data transfer of user functions

Components
B3D021 5052590001 Modem box for AlgoWorks (DUAL RS232 ITF) Complete with 20-pole flat cable, L=0.2 m
– 5053300001 Flat cable L=0.2 m As spare part
F14E320 4514390001 Y-flat cable, 14-wire, 0.5 m Options for programming E3H021

107
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CS1140 components in alphabetical order

41 CS1140 components in alphabetical order

B
B1F120 4952330001 Converter 115/230 V AC > 24 V DC, 3 A
B1Q101 5045800001 Tape printer 19”/3HU, 24 V DC
B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A
B2F040 5102990001 Converter 115/230 V AC ->29.6 V DC, 3.5 A
B2F060 5112850001 Converter 115/230 V AC > 24 V DC, 4.5 A
B2Q191 4848880001 Tape printer 19”/6HU, 24 V DC
B3D021 5052590001 Modem box DUAL RS232 ITF
B3P020 3926530001 Mains filter 250 V, 6 A
B3Q321 5656840001 'CH' fire brigade operating unit
B3Q440 4759520001 Standard 'Extinguishing' operating terminal
B3Q566 S54371-F13-A1 Standard 'China' operating terminal
B3Q661 A5Q00020708 'International' comfort operating terminal
B3Q681 S54371-F12-A1 'Nordic' comfort operating terminal
B3Q686 S54371-F11-A1 'CH' comfort operating terminal
B3Q580 4961770001 plain text display terminal
B3Q590 4961800001 Plain text operating terminal with Nordic lock
B3Q595 5341100001 Plain text operating terminal with KABA lock
B3R051 4905130001 '2x24 displays' parallel display
C
CAR00xxx (PSP) EPROM kit for 'CA11'
CAQT1xxx (PSP) 'China simple' EPROM kit
CAQTExxx (PSP) 'China traditional' EPROM kit
CAQTLxxx (PSP) 'Korea standard' EPROM kit
CAQT5xxx (PSP) 'Thailand' EPROM kit
CCQ00xxx (PSP) EPROM kit for E3X101
CCW00xxx (PSP) EPROM kit for E3X101 with K3N010

CAX00xxx (PSP) 'International' Flash program file for 'CA11'


CAYT1xxx (PSP) 'China simple' Flash program file
CAYTExxx (PSP) 'China traditional' Flash program file
CAYTLxxx (PSP) 'Korea standard' Flash program file
CAYT5xxx (PSP) 'Thailand' Flash program file
CCX00xxx (PSP) Flash program file for E3X102
CCY00xxx (PSP) Flash program file for E3X103
CKY00xxx (PSP) Flash program file for E3H021

CIX00xxx (PSP) 'International' Flash program file


CIYT1xxx (PSP) 'China simple' Flash program file
CIYT5xxx (PSP) 'Thailand' Flash program file
CIYTExxx (PSP) 'China traditional' Flash program file
CIYTLxxx (PSP) 'Korea standard' Flash program file

CTX00xxx (PSP) 'International' Flash program file


CTYT1xxx (PSP) 'China simple' Flash program file
CTYT5xxx (PSP) 'Thailand' Flash program file
CTYTExxx (PSP) 'China traditional' Flash program file
CTYTLxxx (PSP) 'Korea standard' Flash program file

CIQ00xxx (PSP) 'International' EPROM kit


CIQT1xxx (PSP) 'China simple' EPROM kit
CIQT5xxx (PSP) 'Thailand' EPROM kit
CIQTExxx (PSP) 'China traditional' EPROM kit
CIQTLxxx (PSP) 'Korea standard' EPROM kit

CIWT1xxx (PSP) 'China simple' EPROM kit


CIWT5xxx (PSP) 'Thailand' EPROM kit
CIWTExxx (PSP) 'China traditional' EPROM kit
CIWTLxxx (PSP) 'Korea standard' EPROM kit

CTQ00xxx (PSP) 'International' EPROM kit


CTQT1xxx (PSP) 'China simple' EPROM kit
CTQT5xxx (PSP) 'Thailand' EPROM kit
CTQTExxx (PSP) 'China traditional' EPROM kit
CTQTLxxx (PSP) 'Korea standard' EPROM kit

CKQ00xxx (PSP) EPROM kit for CK1142


CKW00xxx (PSP) EPROM kit for CK1143
E
E3C011 5054790001 Plug-in battery charging module
E3G050 4602550001 'Contacts' control plug-in module
E3G060 5425390001 'Monitored' control plug-in module
108
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CS1140 components in alphabetical order
E3G070 5466610001 'Universal' control plug-in module
E3G080 4759490001 'Extinguishing' control plug-in module
E3G091 4977070001 'CH' remote transmission interface
E3G110 5049910001 Degraded mode link
E3H021 A5Q00024660 Gateway plug-in module
E3I020 4602390001 RS232 plug-in module
E3I040 4993100001 LON plug-in module
E3L020 5466450001 'Driver' control plug-in module
E3L030 4759940001 'VdS' control plug-in module
E3M060 4602260001 'MS9i' line plug-in module
E3M071 4984050001 'Interactive' line plug-in module
E3M080 4602680001 'Collective' line plug-in module
E3M111 5115310001 'AnalogPLUS' line plug-in module
E3M120 5340130001 'CBA' line plug-in module
E3M141 S54405-A9-A1 'FD20' line plug-in module
E3M171 5286340001 'Interactive Ex' line plug-in module
E3X101 5466740001 EPROM control panel module and RAM kit separately
E3X102 6290250001 Flash ROM control panel module and 1MB RAM fitted
E3X103 6290380001 Flash ROM control panel module and 2MB RAM fitted
F
F12A100 4952750001 'Micro' 12-wire, 0.4 m flat cable
F12A470 4952880001 'Micro' 12-wire, 1.5 m flat cable
F14A230 4029670001 Flat cable, 14-wire, 0.25 m
F14A320 3196520001 Flat cable, 14-wire, 0.5 m
F14E320 4514390001 Y-flat cable, 14-wire, 0.5 m
F20A020 4763170001 'Micro' 20-wire, 0.165 m flat cable
F20A140 4968630001 'Micro' 20-wire, 0.650 m flat cable
F20A410 4953270001 'Micro' 20-wire, 1 m flat cable
F50F410 5291410001 LED flat cable for K3R072
FA2006-A1 A5Q00019356 12 V / 24 Ah battery
FA2007-A1 A5Q00022897 12 V / 38 Ah battery
FA2005-A1 A5Q00019677 12 V / 15 Ah battery
G
G1E010 3842760001 Universal carrier 3HU
G2A130 4750880001 19”/6HU adapter plate for AlgoPilot B3Q...
G2A140 4842280001 19”/6HU adapter plate for B3Q321/B3R051
G2F031 4092900001 19"/6HU front frame
H
H15Z200 4597160001 Folder pocket for H98T..
H15Z300 4761970001 Battery retaining plate for H47E110
H23B010 4762100001 Cover for H38T010 / H47T110
H23B020 4762780001 Cover for H28T110/130
H23B040 4845900001 Information module
H23G230 4750910001 Plastic housing for B3Q321/440 B3R051
H23U230 5328790001 Recess-mounted box for B3Q5xx
H23Z230 5328820001 Recessed mounted frame for B3Q5xx/B3R051
H26G220 4628000001 Plastic housing for AlgoPilot B3Q...
H26T030 5705300001 Plexi glass doors for AlgoPilot B3Q6../566
H28G200 4099440001 base of housing
H28T020 4105640001 Cover for H28G200 for B2Q191
H28T110 4749820001 Cover for H28G200 for AlgoPilot B3Q...
H28T120 4749950001 Cover for H28G200 for 4 x B3R051
H28T130 4759100001 Cover with plan compartment for H28G200
H28T150 4843670001 Cover with KABA locking cylinder
H28V000 3795820001 Beams for 19" 6HE adaptation
H28V010 3795660001 Hinges for G2F031 / G2A130
H28Z010 4105930001 Recess mounted frame for H28G200
H28Z020 4136000001 Recess mounted frame, intermediate piece
H37G410 5339590001 Housing for AlgoPilot B3Q... (flat doors)
H37G420 5341070001 Housing for AlgoPilot B3Q... (designer doors)
H37G430 5339620001 Housing for special applications (flat doors)
H37T000 5334670001 Inner doors for special applications
H37Z010 5339750001 Spacer for 2 or more housings next to one another
H38G210 4849010001 'Doors without cut-out' housing kit
H38G220 4849140001 'Doors with cut-out' housing kit
H38G230 4849270001 'Nordic plan compartment' housing kit
H38G310 4849300001 'Doors without cut-out' housing kit
H38G320 4849430001 'Doors with cut-out' housing kit
H47E100 4748850001 Component carrier for H47..
H47E110 4761840001 Component carrier for H47.. 'Empty'
H47G601 4953720001 'Doors without cut-out' housing kit
H47G611 4953850001 'Doors with cut-out' housing kit
H47T101 4953560001 Housing frame and 'doors without cut-out'
H47T111 4953690001 Housing frames and 'doors with cut-out'
H67E101 5097050001 Component carrier for H67..
H67G601 4955500001 'Doors without cut-out' housing kit

109
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CS1140 components in alphabetical order
H67G611 4956600001 'Doors with cut-out' housing kit
H67T101 4956150001 Housing frame and 'doors without cut-out'
H67T111 4956280001 Housing frame and 'doors with cut-out'
H67Z020 4969020001 Shielding hood for H67E...
H98G600 4161280001 Housing 42HE with base
H98T000 4161310001 42HE doors, hinged on right, no windows
H98T020 4594150001 42HE doors, hinged on left, no windows
H98Z010 4176060001 Pair of cover strips for H98G600
K
K1D012 4637600001 Modem board V28
K1D081 4637730001 Dual modem board V28
K1D121 4706010001 Dual modem board FSK/PSK
K1D140 4706140001 Modem board FSK/PSK
K1H022 A5Q00014427 Communications board for Cerloop application
K3G060 5287860001 Relay board
K3I050 4967660001 LON/mimic display board
K3I090 5108200001 PSA interface board
K3I110 5288120001 LON I/O board
K3N010 5228180001 RAM extension board 1024Kx8 bits for CC1143
K3R072 5286050001 Mimic display board
K5L020 4412320001 2-area extinguishing board
M
M3P030 3787740001 Modem filter module
N
NK823x.2 For order no., see document A6V10238669
NKA8011-A1 For order no., see document A6V10238669
NZ8201 For order no., see document A6V10238669
U
UPR28 4304340001 Recess-mounted box for 1 x H28G200
UPR29 4304470001 Recess-mounted box for 2 x H28G200
V
V2G040 4759230001 Cable for 9 V lithium battery
V2G050 5706110001 Bracket with cable for 9 V lithium battery
Y
YAH00 3305920001 Battery holder for G1E010 / 1x FA2006-A1
Z
Z1B020 4759070001 Installation options for E3I020 + B3Q...
Z1B030 4838920001 Installation options for TNA (P450)
Z1B060 5259830001 Installation kit for PSA interface board K3I090
Z1B070 A5Q00001720 Installation options for LON plug-in module E3I040 for use in H28G200
Z1I020 4754990001 Connection cable, 9-wire, 0.5 m
Z1I030 4755090001 Connection cable, 19-wire, 0.5 m
Z1I040 4755120001 Connection cable, 9-wire, 0.8 m
Z1I050 4755250001 Connection cable, 19-wire, 0.8 m
Z1I060 5258020001 Connection cable, 4-wire, 0.5 m
Z1I070 5258150001 Connection cable, 4-wire, 0.8 m
Z1I100 A5Q00007486 Connection cable, 10-wire, 0.5 m
Z1I110 A5Q00007487 Connection cable, 10-wire, 0.8 m
Z1K020 4754860001 Terminal block + board holder for H47/H67
Z1K030 4842310001 Terminal block + board holder for H38..
Z1K040 4906650001 Board holder for B1F120 for sep. supply B2Q191 in H28...
Z1K050 4952200001 Board holder for K1D...
Z2B040 4752530001 Installation options for TNA / AWG
Z2G030 3781980001 Hinges for 19" housings for G2F031
Z3B040 3792490001 Paper winding device for printer B1Q101
Z3B150 4518400001 Plug-in carrier for TA109
Z3B171 4843830001 1 x 250 V AC/10 A relay module
Z3B180 4762070001 19" adapter kit for H47E100/110
Z3G170 4762230001 Installation options for H47/H67/H98
Z3G220 5258440001 Marine kit
Z3G240 5329500001 Kit for increased vibrations
Z3I041 4962900001 230 V AC surge arrester kit
Z3I121 4963000001 110 V AC surge arrester kit
Z3I140 3803190001 'CH' mains socket for H38...
Z3I330 4751560001 Terminal block, 2x20 terminals for H47/67
Z3I331 5098800001 Terminal block, 2x20 terminals for H47/67 'Screwless'
Z3I350 4755380001 Cable set for H47/H67 with 'CC11'
Z3I380 4755670001 I bus flat cable + 'long' supply cable
Z3I390 4757290001 'Remote transmission CH' cable set
Z3I420 4838180001 Back-up terminal unit for H38/H47/H67
Z3I450 4842730001 'CH' mains socket for H47/67
Z3I460 4843120001 'CH' mains socket for H38...
Z3I470 4843410001 Cable kit for H38 with 'CI11'
Z3I481 4911850001 Flexible connection cable for 'CT11'
Z3I510 4848460001 Cable kit for H47 with 'CI11'
110
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
CS1140 components in alphabetical order
Z3I520 4849690001 Cable kit for K3R071/K3R072
Z3I530 4849720001 Adapter to B3R051 / K3R071/K3R072
Z3I570 4956440001 133 mm 'TS35' mounting rail with bracket
Z3I580 4956570001 291 mm 'TS35' mounting rail with bracket
Z3I870 4969440001 Cable kit for supply extension
Z3I1040 A5Q00004129 'CH' remote transmission kit
Z3S071 A5Q00025767 RAM kit 2x512Kx8 bits
Z3S090 4969570001 Key switch options (no locking cylinder)
Z3S100 5106130001 KABA key switch for B3Q590
Z3S200 5703490001 Key switch module for AlgoPilot B3Q6.. (KABA)
Z5B400 4757100001 'Empty' labeling kit
Z5B410 4755960001 'Portuguese' labeling kit
Z5B415 5706530001 'Portuguese' labeling kit
Z5B420 4756060001 'Flemish' labeling kit
Z5B430 4756190001 'Dutch' labeling kit
Z5B435 5706660001 'Dutch' labeling kit
Z5B440 4756220001 'Polish' labeling kit
Z5B450 4756350001 'Czech' labeling kit
Z5B460 4756510001 'Hungarian' labeling kit
Z5B470 4756640001 'Slovenian' labeling kit
Z5B480 4756770001 'Serbian' labeling kit
Z5B490 4756800001 'Croatian' labeling kit
Z5B500 4756930001 'Turkish' labeling kit
Z5B505 5706790001 'Turkish' labeling kit
Z5B510 4757030001 'Icelandic' labeling kit
Z5B520 4765240001 'German CH' labeling kit
Z5B525 5706820001 'German CH' labeling kit
Z5B530 4765370001 'German D' labeling kit
Z5B535 5706950001 'German D' labeling kit
Z5B540 4765400001 'Italian CH' labeling kit
Z5B545 A5Q00004396 'Italian CH' labeling kit
Z5B550 4765530001 'Italian I' labeling kit
Z5B555 5707050001 'Italian I' labeling kit
Z5B560 4765660001 'French CH' labeling kit
Z5B565 5707180001 'French CH' labeling kit
Z5B570 4765790001 'French B' labeling kit
Z5B580 4765820001 'French F' labeling kit
Z5B585 5707210001 'French F' labeling kit
Z5B590 4765950001 'Danish' labeling kit
Z5B595 5707340001 'Danish' labeling kit
Z5B600 4832030001 'Finnish' labeling kit
Z5B605 5707470001 'Finnish' labeling kit
Z5B610 4832160001 'Norwegian' labeling kit
Z5B615 5707500001 'Norwegian' labeling kit
Z5B620 4832290001 'Swedish' labeling kit
Z5B625 5707630001 'Swedish' labeling kit
Z5B630 4832320001 'English' labeling kit
Z5B635 5707760001 'English' labeling kit
Z5B640 4832450001 'English GB' labeling kit
Z5B645 5707890001 'English GB' labeling kit
Z5B650 4787950001 'Slovakian' labeling kit
Z5B660 4755830001 'Spanish' labeling kit
Z5B665 5707920001 'Spanish' labeling kit
Z5B680 4849560001 'Hebrew' labeling kit
Z5B685 5706400001 'Hebrew' labeling kit
Z5B700 5104220001 'CH' labeling kit for B3Q440
Z5B710 5104480001 'Nordic' labeling kit for B3Q580
Z5B720 5104510001 'European' labeling kit for B3Q580
Z5B730 5104640001 'Nordic' labeling kit for B3Q590/595
Z5B740 5104770001 'European' labeling kit for B3Q590/595
Z5B750 5105740001 'CH' labeling kit for B3Q590/595

– 4634980001 Solid state relay for K1D081

111
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Spare parts for CS1140 components

42 Spare parts for CS1140 components

A
4638090001 Cover frame (plastic) For B3Q321, B3Q440, B3R051
D
5646690001 DOM duplicate key in locking unit 2C 2500 For H28T/H47/H67
F
5053300001 Flat cable L=0.2 m For B3D021
4714510001 Flat cable for I bus + 'Short' supply line For I bus plug-in modules
L
EOL22 5162220001 End-of-line
P
3799770001 Rolls of paper, 4x For B2Q191, B1Q101
4757740001 PTC, 2 k 0.5 %, with cable For E3X10., E3C011
S
KABA100 1638370001 'KABA 8' key (#100) For B3Q321, Z3S010 (AlgoPilot), B3Q595
4843960001 'Nordic' key For B3Q480, B3Q590
T
4600510001 Transzorb diode bidirectional 20 V, 5 % 600 W/ms For E3M080 with DS11/MS9

112
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43 Configuration sheets
The following pages are intended as templates for copying or can be used as a
suggestion for a country-specific tool.
The system-specific configuration (use of installation space, number and type of
components, etc.) is entered on these sheets.

List of configuration sheets:


 Configurations with AlgoPilot B3Q... as main CPU
– CI1142 in housing H38... (flat) –> page 114
– CI1142 in housing H38... (deep) –> page 114
– CI1142 in housing H47... –> page 116
 Configurations with E3X10. as main CPU
– CC1142/43 in housing H47... –> page 117
– CC1142/43 in housing H47...(with extra power supply) –> page 118
– CC1142/43 in housing H67...(standard) –> page 119
– CC1142/43 in housing H67...(with 2 sets of batteries) –> page 120
– CC1142/43 in housing H67...(with extended connection panel) –> page 121
 Configurations with upright cabinet
– CS1140 in housing H98G600 –> page 122
 Configurations of AlgoPilot B3Q... operating units
– CT1142 –> page 123
 Configurations of display & operating device
– B3Q580/590/595, B3Q321, B3Q440, B3R051 etc. –> page 124
 Components positioned externally
– K3I110, K3I050, K3R072, K3G060 etc. –> page 124
 Printer configuration
– B2Q191, B1Q101 –> page 125

113
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.1 CI1142 in housing H38... (flat)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3M060 4602260001
21 23 ● E3M071 4984050001
AC/DC converter

● E3M171 5286340001
● E3M080 4602680001
B2F020

● E3M111 5115310001
● E3M120 5340130001
● E3M141 S54405-A9-A1
● E3L020 5466450001
31 ● E3G050 4602550001
● E3G060 5425390001
● E3G070 5466610001
FA2005-A1 B A ● E3G080 4759400001
● E3H021 A5Q00024660
● E3I020 4602390001
● E3I040 4993100001
● K3I090 5108200001
51
Cables, terminals, relays
2 1 Z1K030 4842310001
Z3I380 4755670001
FA2005-A1
Z3I470 4843410001
Z3B171 4843830001
Power supply, options
B2F020 A5Q00025281
E3C011 5054790001
28 FA2005- A5Q00019677
Battery (12 V / 15 Ah)
A1
Z3I450 4842730001

Note:
View B
View A

E3M60/071/171/120
38 Housing kit
and E3C011 are not
possible at positions <– for details see H38G220 4849140001
28+38 page 31 Operating console
All variants B3Q...
For AlgoPilot see Z5B…
Page 50 H26T…
47 48 45.1 .. 45.3 Z3S…
V2G…
1 2 3 Options
max. H23B010 4762100001
3xZ3B171 H23B040 4845900001
57 58 55.1 .. 55.3
EMC Precaution:
1 2 3
Position 57 must
max. not be fit with
3xZ3B171 either E3I040 or
E3G080 modules

<– for details see


H38G220 page 57

114
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.2 CI1142 in housing H38... (deep)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3M060 4602260001
● E3M071 4984050001
21 23 ● E3M171 5286340001
AC/DC converter

Mains
terminals ● E3M080 4602680001
● E3M111 5115310001
B2F020

● E3M120 5340130001
● E3M141 S54405-A9-A1
● E3L020 5466450001
● E3G050 4602550001
31
● E3G060 5425390001
● E3G070 5466610001
FA2006-A1 B A ● E3G080 4759400001
or
FA2005-A1 ● E3G110 5049910001
● E3H021 A5Q00024660
● E3I020 4602390001
● E3I040 4993100001
51
● K3I090 5108200001
Cables, terminals, relays
FA2006-A1
or 2 1 Z1K030 4842310001
FA2005-A1 Z3I380 4755670001
Z3I470 4843410001
Z3B171 4843830001
Power supply, options
B2F020 A5Q00025281
27 28 E3C011 5054790001
FA2006- A5Q00019356
Battery (12 V / 24 Ah)
A1
FA2005- A5Q00019677
View B

Note:
View A

Battery (12 V / 15 Ah)


E3M60/071/171/120 A1
37 38 and E3C011 are not Z3I450 4842730001
possible at positions <– for details see
27+37 page 33

Housing kit
46 47 48 1
2 H38G320 4849430001
45.1..45.3
8xZ3B171

3 Operating console
4
5 All variants B3Q...
max.

6
7
For AlgoPilot see Z5B…
8 Page 50 H26T…
56 57 58 1 EMC Precaution: Z3S…
2
8xZ3B171

Slot rows with V2G…


55.1..55.3

3
4 E3C011 module Options
max.

5
6
must not be fit B3R051 4905130001
7 with either E3I040
8 or E3G080 B3Q321 5656840001
modules! B3Q440 4759520001
H23B010 4762100001
H23B040 4845900001

H38G320
<– for details see
page 57

115
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.3 CI1142 in housing H47…


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3M060 4602260001
Cable duct 'CH' only ● ● E3M071 4984050001
21 22 23 24 25 1 ● E3M171 5286340001
AC/DC converter

2
● E3M080 4602680001

Connection
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

3
8xZ3B171

E3M111 5115310001

panel
4 ●
B2F020

Z3I330

Z3I330

Z3I330

5
6 ● E3M120 5340130001
max.
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

7
8 ● E3M141 S54405-A9-A1
● E3L020 5466450001
Cable duct
If Z3I041 or B3P020 ● E3L030 4759940001
31 32 33 34 35 36 37
Mains
is used, on Pos. 36 ● E3G050 4602550001
terminals
E3M060/071/171/120 ● E3G060 5425390001
and E3C011 is not
possible! ● E3G070 5466610001
<– for details ● E3G080 4759400001
see page 35 E3G110 5049910001
Modules


41 42 43 44 45 46 47 48 ● E3H021 A5Q00024660
● E3I020 4602390001
EMC Precaution: ● E3I040 4993100001
Relative to each ● K3I090 5108200001
E3C011 module Cables, terminals, relays
51 position, two
52 55
positions to the 1 Z1I020 4754990001
right and two 2 1 Z1I030 4755090001
positions to the 1 Z1I060
Batteries

FA2006-A1 FA2006-A1 5258020001


or or left must not be fit 1 Z1I100 A5Q00007486
with either E3I040
FA2007-A1 FA2007-A1 * 3 items inclu- 1/4 1/8 1 1/2 1/4 Z3I330 * 4751560001
or E3G080
modules! ded in Z3I380 4755670001
H47G601/611 Z3B171 4843830001
F20A140 4968630001
F20A410 4953270001
Power supply, options
H47G611 B2F020 A5Q00025281
E3C011 5054790001
FA2006- A5Q00019356
Battery (12 V / 24 Ah)
A1
FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
Z3I450 4842730001
<– for details see
page 58

Housing kit
H47G611 4953850001
Operating console
All variants B3Q...
For AlgoPilot see Z5B…
Page 50 H26T…
Z3S…
V2G…
Extra devices, options
B3R051 4905130001
B3Q321 5656840001
B3Q440 4759520001
H23B010 4762100001
H23B040 4845900001

116
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.4 CC1142/43 in housing H47…


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3X10.
Cable duct
● E3M060 4602260001
21 22 23 24 25 1 'CH' only ● ● E3M071 4984050001
AC/DC converter

2
● E3M171 5286340001

Connection
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

8xZ3B171 3

panel
4
● E3M080 4602680001
B2F020

Z3I330

Z3I330

Z3I330

5
6 ● E3M111 5115310001
max.
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

7
8 ● E3M120 5340130001
● E3M141 S54405-A9-A1
Cable duct
If Z3I041 or B3P020 is ● E3L020 5466450001
31 32 33 34 35 36 37 used, on Pos. 36 ● E3L030 4759940001
Mains
E3M060/071/171/120 E3G050 4602550001
terminals ●
and E3C011 is
not possible! ● E3G060 5425390001
● E3G070 5466610001
<– for details E3G080 4759400001
Modules


42 43 44 45 46 47 48
E3X10. + 2x Z1I030 + Z3I350

see page 37 ● E3G110 5049910001


● E3H021 A5Q00024660
● E3I020 4602390001
● E3I040 4993100001
● K3I090 5108200001
52 55 Cables, terminals, relays
1 Z1I020 4754990001
2 1 Z1I030
Batteries

FA2006-A1 FA2006-A1 4755090001


or or 1 Z1I060 5258020001
FA2007-A1 FA2007-A1
1 Z1I100 A5Q00007486
* 3 items inclu- 1/4 1/8 1 1/2 1/4 Z3I330 * 4751560001
ded in Z3I350 4755380001
H47G601/611 Z3I380 4755670001
H47G601 or H47G611 Z3B171 4843830001
F20A140 4968630001
F20A410 4953270001
<– for details see Power supply, options
page 58 B2F020 A5Q00025281
FA2006- A5Q00019356
Battery (12 V / 24 Ah)
A1
FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
Z3I450 4842730001
Housing kit
H47G601 4953720001
H47G611 4953850001
Component carrier
H47E100 474885
Operating console
All variants
B3Q...
For AlgoPilot see
Z5B…
Page 50
H26T…
Z3S…
V2G…

117
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.5 CC1142/43 in housing H47… (with extra power supply)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3X10.
Cable duct
● E3M060 4602260001
21 22 23 24 25 1 'CH' only ● ● E3M071 4984050001
AC/DC converter

2
● E3M171 5286340001

Connection
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

3
8xZ3B171

panel
4
● E3M080 4602680001
B2F020

Z3I330

Z3I330

Z3I330

5
6
● E3M111 5115310001
max.
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

7
8
● E3M120 5340130001
H47G611

Cable duct ● E3M141 S54405-A9-A1


If Z3I041 or B3P020 ● E3L020 5466450001
31 32 33 34 35 36 37 is used, on Pos. 36
Mains
E3M060/071/171/120 ● E3L030 4759940001
terminals
and E3C011 is not ● E3G050 4602550001
possible! ● E3G060 5425390001
● E3G070 5466610001
Modules

42 43 44 45 46 47 48 <– for details ● E3G080 4759400001


E3X10. + 2x Z1I030 + Z3I350

see page 39 ● E3G110 5049910001


H47G601

● E3H021 A5Q00024660
● E3I020 4602390001
● E3I040 4993100001
52 55 ● K3I090 5108200001
Cables, terminals, relays
1 Z1I020 4754990001
Batteries

FA2006-A1 FA2006-A1
or or 2 1 Z1I030 4755090001
FA2007-A1 FA2007-A1 1 Z1I060 5258020001
1 Z1I100 A5Q00007486
* 3 items inclu- 1/4 1/8 1 1/2 1/4 Z3I330 * 4751560001
ded in Z3I350 4755380001
H47G601/611 Z3I380 4755670001
21
AC/DC converter

22 25 Z3B171 4843830001
F20A140 4968630001
B2F020

FA2006-A1 FA2006-A1
or or F20A410 4953270001
FA2007-A1 FA2007-A1 Power supply, options
B2F020 A5Q00025281
H47T101

H15Z300 H15Z300 E3C011 5054790001


FA2006- A5Q00019356
Battery (12 V / 24 Ah)
31 A1
32 35 FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
E3C011
Z3I870

FA2006-A1 FA2006-A1
or or Z3I450 4842730001
FA2007-A1 FA2007-A1 Housing kit
41 H47G601 4953720001
H47E110

H15Z300 H15Z300 H47G611 4953850001


E3C011
Z3I870

Component carrier, opti-


ons
52 55 H47E100 4748850001
51
H47T101 4953560001
FA2006-A1 FA2006-A1
H15Z300 4761970001
E3C011

or or
Z3I870

FA2007-A1 FA2007-A1 Operating console


All variants B3Q...
H15Z300 H15Z300 For AlgoPilot see Z5B…
Page 50 H26T…
Z3S…
V2G…

118
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.6 CC1142/43 in housing H67... (Standard)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3X10.
Cable duct
● E3M060 4602260001
01 02 03 04 Mains 04 04 1 'CH' only ● ● E3M071 4984050001
2
● E3M171 5286340001

Pos.
Pos.
terminals
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

8xZ3B171
4
● E3M080 4602680001

Z3I330
Z3I330

Z3I330

Z3I330

Connection panel
6 ● E3M111 5115310001

max.
Pos.
Pos.
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

7
8 ● E3M120 5340130001
11 12 13 14 1 14 14 1 ● E3M141 S54405-A9-A1
Pos.31
Pos.31

2 2

Pos.
Pos.
E3L020
Pos.
Pos.

Pos.
Pos.

3 3 ● 5466450001

8xZ3B171
8xZ3B171

4 4
● E3L030 4759940001
Z3I330
Z3I330

Z3I330

Z3I330

5 5

max.
Pos.31
Pos.31

E3G050 4602550001
max.

6 6

Pos.
Pos.
Pos.
Pos.

Pos.
Pos.

7 7
8 8
● E3G060 5425390001
21 or ● E3G070 5466610001
AC/DC converter

<– for details ● E3G080 4759400001


Cable duct
B2F020

see page 43 ● E3G110 5049910001


● E3H021 A5Q00024660
● E3I020 4602390001
31 32 33 34 35 36 37 38 36 37
Mains ● E3I040 4993100001
terminals
● K3I090 5108200001
Cables, terminals, relays
If Z3I041 or 1 Z1I040 4755120001
B3P020 is 2 1 Z1I050 4755250001
E3X10. + 2x Z1I050 + Z3I350

42 43 44 45 46 47 48 46 47 48
used, 1 Z1I070 5258150001
E3M060/071/1 1 Z1I110 A5Q00007487
Modules

71/120 + 1/4 1/8 1 1/2 1/4 Z3I330 4751560001


E3C011 are Z3I350 4755380001
not possible on Z3I380 4755670001
52 53 54 55 56 57 58
item 36! Z3B171 4843830001
F20A140 4968630001
F20A410 4953270001
Power supply, options
61 62 65 B2F020 A5Q00025281
E3C011 5054790001
FA2006- A5Q00019356
Batteries

FA2006-A1 FA2006-A1 Battery (12 V / 24 Ah)


or or A1
FA2007-A1 FA2007-A1 FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
Z3I450 4842730001
Housing kit
H67G601 4955500001
H67G601 or H67G611 H67G611 4956600001
Attention: Component carrier, opti-
H67Z020 is only suitable for ons
H67E101 plug-in modules 38/48/58 H67E101 5097050001
cannot be used. H67Z020 4969020001
Operating console
<– for details All variants B3Q...
see page 59 For AlgoPilot see Z5B…
Page 50 H26T…
Z3S…
V2G…

119
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.7 CC1142/43 in housing H67... (with 2 sets of batteries)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3X10.
Cable duct
● E3M060 4602260001
01 02 03 04 04 1 'CH' only ● ● E3M071 4984050001
Mains 2
● E3M171 5286340001
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

terminals 3

8xZ3B171
4
● E3M080 4602680001
Z3I330

Z3I330

Z3I330

5
Connection panel 6 ● E3M111 5115310001

max.
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

7
8 ● E3M120 5340130001
11 12 13 14 1 14 1 ● E3M141 S54405-A9-A1
Pos.31
Pos.31

2 2
E3L020
Pos.
Pos.

Pos.
Pos.

3 3 ● 5466450001

8xZ3B171
8xZ3B171

4 4
● E3L030 4759940001
Z3I330

Z3I330

Z3I330

5 5
max.
Pos.31
Pos.31

E3G050 4602550001
max.

6 6

Pos.
Pos.

Pos.
Pos.

7 7
8 8
● E3G060 5425390001
21 ● E3G070 5466610001
AC/DC converter

<– for details ● E3G080 4759400001


Cable duct
B2F020

see page 43 ● E3G110 5049910001


● E3H021 A5Q00024660
● E3I020 4602390001
31 32 33 34 35 36 37 38 36 37
Mains ● E3I040 4993100001
terminals
● K3I090 5108200001
Cables, terminals, relays
If Z3I041 or 1 Z1I040 4755120001
Modules

B3P020 is 2 1 Z1I050 4755250001


E3X10. + 2x Z1I050 + Z3I350

42 43 44 45 46 47 48 46 47 48
used, 1 Z1I070 5258150001
E3M060/071/1 1 Z1I110 A5Q00007487
71/120 + 1/4 1/8 1 1/2 1/4 Z3I330 4751560001
E3C011 are Z3I350 4755380001
not possible on Z3I380 4755670001
52 55 item 36! Z3B171 4843830001
Z3I870 4969440001
FA2006-A1 FA2006-A1
F20A140 4968630001
Batteries

H15Z300 H15Z300 F20A410 4953270001


61 62 65 Power supply, options
B2F020 A5Q00025281
E3C011 5054790001
E3C011

FA2006-A1 FA2006-A1
Z3I870

or or FA2006- A5Q00019356
Battery (12 V / 24 Ah)
FA2007-A1 FA2007-A1 A1
FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
Z3I450 4842730001
Housing kit
H67G601 or H67G611 H67G601 4955500001
H67G611 4956600001
Component carrier, opti-
ons
H67E101 5097050001
H67Z020 4969020001
H15Z300 4761970001
<– for details Operating console
see page 59 All variants B3Q...
For AlgoPilot see Z5B…
Page 50 H26T…
Z3S…
V2G…

120
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.8 CC1142/43 in housing H67... (with extended connection panel)


System:
Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective
Number of detector addresses –
Number of detector lines
Fire controls For 30V For 250 V
Number of control outputs

Plug-in modules
● E3X10.
Cable duct ● E3M060 4602260001
'CH' only ● ● E3M071 4984050001
01 02 03 04
Mains ● E3M171 5286340001
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.
terminals ● E3M080 4602680001
● E3M111 5115310001
Z3I330

Z3I330

Z3I330

● E3M120 5340130001
Pos.
Pos.

Pos.
Pos.

Pos.
Pos.

● E3M141 S54405-A9-A1
11 12 13 14 1 ● E3L020 5466450001
Pos.31
Pos.31

2
Connection panel ● E3L030 4759940001
Pos.
Pos.

Pos.
Pos.

3
4 ● E3G050 4602550001
Z3I330

Z3I330

Z3I330

5 ● E3G060 5425390001
Pos.31
Pos.31

6
● E3G070 5466610001
Pos.
Pos.

Pos.
Pos.

7
8
<– for details ● E3G080 4759400001
9
21 22 23 10 see page 43 ● E3G110 5049910001
Pos.31
Pos.31

Pos.
Pos.

Pos.
Pos.

11
12
● E3H021 A5Q00024660
13 ● E3I020 4602390001
18xZ3B171
Z3I330

Z3I330

Z3I330

14
● E3I040 4993100001
Pos.31
Pos.31

15
Pos.
Pos.

Pos.
Pos.

16 ● K3I090 5108200001
max.

17
Cables, terminals, relays
31 18
AC/DC converter

1 Z1I040 4755120001
2 1 Z1I050 4755250001
Cable duct
B2F020

1 Z1I070 5258150001
1 Z1I110 A5Q00007487
1/4 1/8 1 1/2 1/4 Z3I330 4751560001
41 42 43 44 45 46 47 48 Z3I350 4755380001
Z3I380 4755670001
Z3B171 4843830001
Z3I870 4969440001
F20A140 4968630001
F20A410 4953270001
E3X10. + 2x Z1I050 + Z3I350

52 53 54 55 56 57 58
Modules

Power supply, options


B2F020 A5Q00025281
FA2006- A5Q00019356
Battery (12 V / 24 Ah)
A1
FA2007- A5Q00022897
Battery (12 V / 38 Ah)
A1
62 65 Z3I450 4842730001
Housing kit
Batteries

FA2006-A1 FA2006-A1 H67G601 4955500001


or or H67G611 4956600001
FA2007-A1 FA2007-A1 Component carrier, opti-
ons
H67E101 5097050001
H15Z300 4761970001
H67G601 or H67G611 Operating console
All variants B3Q...
For AlgoPilot see Z5B…
Page 50 H26T…
<– for details Z3S…
see page 59 V2G…

121
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.9 CS1140 in housing H98... or third-party housing


This configuration sheet is intended only to specify the mechanical components.
The 'CC1142/43 ...' configuration sheets can be used to specify the electronics.
Housings, doors, covers
Profile bar on
H98G600 4161280001
Cable duct rear panel
H98G600 H98T000 4161310001
04 Mains H98T020 4594150001
terminals H98Z010 4176060001

H67E100
Folder pocket
or H15Z200 4597160001
H67E110
Component carrier
H67E101 5097050001
Cable duct H67E111 5097180001
H67Z020 4969020001
H98Z010

H67Z020

H47E100 4748850001
H47E110 4761840001
G1E010 3842760001
H98T020

Retaining plate for batteries


H15Z300 4761970001

Options for installation on rear


wall
Z3G170 4762230001
H98T000

Options for 19" adaptation


H28V000 3795820001
H28V010 3795660001
Cover

Options for 19"


G2A130 4750880001
G2A140 4842280001
G2F031 4092900001
H98G600

Z3B180 4762070001
H47E110 G1E010
or
H47E110
or >>> G1E010

G1E010
Cabinet / door / side panel

G1E010

G1E010

122
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.10 AlgoPilot CT1142 operating unit


System:
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Station type CT11
Fitted in control panel housing CI/CC11

For details –> see pages 47 – 53 Operating terminal


B3Q...
Labeling kits
Z5B…

Operating unit options


B3Q661 B3Q681 B3Q686
’International’ ’Nordic’ ’CH’ Z3S200 5703490001
KABA lock is
Nordic lock is
included with included with
V2G…
Option Z3S200
the B3Q681 the B3Q686 PSA interface + options
K3I090 5108200001
H26T020 Z1B060 5259830001
F20A020 4763170001
H26T030 F20A410 4953270001
B3Q566
’China’ RS232 interface + options
E3I020 4602390001
Z1B020 4759070001
F20A140 4968630001
LON interface + options
E3I040 4993100001
Z1B070 A5Q00001720
For details –> see page 54 H23B020 4762780001
Housing H26…
H26G220 4628000001
UPR28 Housing H28…
UPR29
H28G200 4099440001
H28Z020
H28T110 4749820001
H28Z010 B3Q321 B3R051 B3Q440
H28T120 4749950001
H28G200 H28Z010 4105930001
H28Z020 4136000001
H28T110
UPR28 4304340001
UPR29 4304470001
H23B010 H23B040
Housing H37…
H23B020
H37G410 5339590001
H37G420 5341070001
Housing H38…
H38G220 4849140001
H26G220 H38G230 4849270001
Z3I470 4843410001
H28T120 H23B020 Z1B070 B2F020 A5Q00025281
E3C011 5054790001
FA2005-A1 A5Q00019677
Extra devices
B3Q321 5656840001
For details –> see page 56 For details –> see page 57 B3R051 4905130001
B3Q440 4759520001
H38G220 Covers
H23B010 4762100001
H23B020 4762780001
Information module
H37G410 H23B040 4845900001

H37G420

H38G230

For details of labeling kits (language-dependent) –> see page 50


For details of installation in the various housings –> see page 51

123
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.11 Display and operating devices


System:

For details –> see page 78 Display and operating unit


H23U230 B3Q580 4961770001
B3Q590 B3Q590 4961800001
B3Q595 5341100001
B3Q595
Labeling kit
B3Q580
Z5B…

Housing
H23G230 4750910001
Nordic lock
H23G230
Options for recessed mounting
H23Z230 KABA lock H23Z230 5328820001
H23U230 5328790001
H23G230
H23G230
K3I110 K3I050 LON mimic display board
K3I050 4967660001

Z3B230 LON I/O board


K3I110 5288120001
H23U220
Mounting plate
H23G230 Z3B230 5590010001

Extra devices
B3Q321 5656840001
B3R051 4905130001
B3Q440 4759520001

B3Q321 B3R051 B3Q440 H23Z230


For details –> see page 55

43.12 Externally positioned devices


System:

For details –> see page 78 – 80 Mimic display and options


K3R072 5286050001
F12A... Z3I530 K3G060 Z3I520 4849690001
K3R072
Z3I530 4849720001

Relay board
K3G060 5287860001

Flat cable, LED flat cable


Z3I520 F12A100 4952750001
F12A470 4952880001
F50F410 F50F410 5291410001

LON mimic display board


K3I050 4967660001
K3I050 K3I110
Z3I530
LON I/O board
K3I110 5288120001

Z3I520

124
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Configuration sheets

43.13 Printer B2Q191, B1Q101


System:
Fitted in H28... printer 1. 2.
B2Q191 4848880001
B1Q101 5045800001
H28Z010
UPR28
Housing H28…
H28G200 4099440001
H28T020 4105640001

Options for H28…


UPR28 4304340001
H28Z010 4105930001

Options for separate power supply


B1F120 4952330001
Z1K040 4906650001
B2Q191
H28G200
H28T020

B1Q101 options
Z3B040 3792490001

19" installation
G2F031 4092900001
Z2G030 3781980001

Installation in H98…
B1F120
H28V000 3795820001
Z1K040 H28V010 3795660001
G2F031 4092900001
Installation in H28... with own power supply
For details of connection options –> see page 90 RS232 plug-in module
E3I020 4602390001
19" installation
E3I020 options
Z1B020 4759070001
Z1K030 4842310001
G2F031 B1Q101 Z1I030 4755090001
Z1I050 4755250001

Modem boards
Z2G030 K1D012 4637600001
K1D121 4706010001

Board holder for K1D…


Z1K050 4952200001

B2Q191 flat cable


F14A230 4029670001
Installation in H98… F20A410 4953270001
F20A020 4763170001
H28V000 F20A140 4968630001

G2F031

H28V010

B2Q191

125
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
Siemens Switzerland Ltd © Siemens Switzerland Ltd 2005-2011
Industry Sector
Building Technologies Division Technical specifications and availability subject to change without notice.
International Headquarters
Gubelstrasse 22
6301 Zug, Switzerland
Tel. +41 41 - 724 24 24
www.siemens.com/buildingtechnologies

Document no. 008725_h_en_-- Manual CS11.1


Edition 06.2011 Register 3

You might also like