Professional Documents
Culture Documents
1 REVISIONS
1.1 REV A
1. Updated version to use Word formatting of tables, figures and section control.
2. Updated Applications specification to ES1112 levels
3. Added details to document to include all communications fields, settings, and
limits.
4. Deleted Vendors, Third party spec, Pricing, and Cut sheet sections
5. Changed MCU section 10 to the Facility Control Integration section.
6. Added detail in Illustrated parts section.
1.2 REV B
Updated Section 3 to include more info on general cycle and electrical info.
Updated Section 4 to include more site economics analysis and more current
sites.
Updated numbered step format in all sections.
Updated Section 4 for fuels capability.
1.3 REV C
Added liquid fueled system info to document.
Updated engine removal section to include diffuser retention bolts.
Updated section 7.5 with complete register addresses per ES1096.
END OF SECTION
2 GENERAL INFORMATION
2.1 PURPOSE OF THIS MANUAL
The purpose of this manual is to provide safety information and instructions on the
installation and commissioning of the TA100 systems listed in the applicability on
the front page. This manual is intended to encompass all units in the TA100 line
except for offshore systems. This includes CHP or Monogen, gaseous fueled or
liquid fueled, indoor or outdoor, as well as units with and without Gas Boost
Compressors. The Manual is intended to provide a broad and detailed overview of
the information about the TA100 necessary to integrate, install, operate, and
maintain the TA100 system.
The latest revisions of all Capstone product documents are available on our
website, www.capstoneturbine.com. Select Document Library link under Quick
Links box on lower left side of home page.
WARNING
The exclamation point within an equilateral triangle is intended to alert the installer or operator to
the presence of important instructions in this manual.
The lightning flash, within an equilateral triangle, is intended to alert the user to the presence of
openly exposed, dangerous voltages. These voltages could cause serious injury or death.
The fire burst symbol within an equilateral triangle is intended to alert the user to the presence
of either a potentially explosive gas or liquid within the working apparatus or batteries associated with
the TA100.
The skull and cross bones within an equilateral triangle, is intended to alert the user to the
potential presence of airborne gases, fumes, or vapors which might produce dizziness,
unconsciousness, lung damage or death when adequate ventilation is not provided.
The human head symbol shown with fingers in ears, within an equilateral triangle, is intended to
alert the user to the potential presence of a noise hazard. Noise hazards can cause hearing loss.
The symbol shown with three equal lines representing heat and a thermometer, within an
equilateral triangle, is intended to alert the user to the potential presence of a burn hazard. When one
sees this symbol one should use special care to prevent burns.
The symbol shown with test tubes of substance dripped onto materials or a hand showing
corrosive effects is intended to alert the user to the potential presence of a corrosive material. When
one sees this symbol one should use special care to prevent contact with this substance.
Terminals for connection to the chassis grounding are labeled with this symbol.
Lethal voltages and currents exist within the TA100. All normal precautions must be taken
with electrical connections when any side panel is removed or side door is opened.
Ensure that there are no foreign objects in or lying around the TA100 before
starting.
Never attempt any maintenance or service without complete shutdown of electrical
components including commercial utility power or outside service voltage needed
for accessory items such as the battery charger.
After isolating the system electrically allow five minutes for PFC capacitors and the
DC bus capacitors to discharge. The PE area should not be entered without
allowing DC bus capacitors to discharge.
The PFC capacitors must be manually discharged before working in the area.
Never allow water to accumulate on the ground around the base of the TA100.
Proper precautions should be taken for maintenance of outdoor units to prevent
accidents.
Closing the doors of the unit prior to attempting to start the TA100 will prevent the
operator from being exposed to high levels of electrical power.
2.8 BURN PRECAUTIONS
For inside installations, the exhaust must be vented to the outside of the building.
Improper ventilation can cause toxic gas to accumulate, which can cause dizziness, nausea
or death.
The TA100 can be unstable when not permanently mounted. Crushing hazards exist
until the unit is correctly mounted.
2.12 NOTES
NOTE: Notes are used in this manual to draw attention to specific points of
importance.
END OF SECTION
FIGURE 3.2 TA100 SYSTEM MAJOR COMPONENTS (with optional HRU and GBC)
3.3.1 TURBINE
The turbine is a single shaft engine assembly. The main components are:
Centrifugal Compressor
Radial Turbine
High-speed alternator
Rotor Support System
Combustor
Recuperator
Control System
Rectifier
Inverter
Integrated Battery Charger
This HRU is usable in potable water systems and can be operated with flows from 20
gpm up to 80 gpm with water pressures up to 125 psig.
Exhaust G as
T I5
F M /F S T I1
103
106 106
W a te r
In le t
W a te r
H e a t R e c o v e ry O u tle t
U n it
T I2 PS
106 106
B ypass
Dam per
T I4
103
CHP
S
R e c u p e r a to r
T I2 & 3 T I1
103 103
Pow er E n c lo s u r e
E le c tr o n ic s C o m p re s s o r A ir In taTku er b in e
TI A lte r n a to r
104
PS
104
TI
102
O il C o o lin g
Fan
L u b e O il T a n k
C o m b u s to r
THS
O il FCV SV2 SV1
O il H e a te r 104
T h e r m o v a lv e 101 101 101
C o m b u s tio n
A ir In ta k e
Fuel G as
O il P u m p In le t
Fuel G as
C o a le s c e r
T I1 GD1 E n c lo s u r e GD2 C o m p re s s o r
A ir In ta k e
105 105 105
F ilte r
E n c lo s u r e F a n
E n c lo s u r e A ir
In t a k e
E n c lo s u r e -
P E A ir In ta k e C o m b u s tio n A ir
In ta k e
XXXZ
The TA100 microturbine is a single stage, single shaft turbine. It draws air into the
single stage centrifugal compressor section. The air is compressed and directed
through a diffuser into the combustion section where fuel is added and ignited.
The exhaust is directed through a nozzle and expanded through the radial turbine.
The microturbine alternator rotor spins inside the stator. The stator generates an
AC output signal. The signal is ~600 volts with a frequency of 2267 Hz. The
signal is converted from AC to DC then back to AC, 3 phase 50 or 60 Hz. As
electrical load is applied, more fuel is added to the combustor to maintain a
constant speed.
The TA100 system will automatically provide the correct power factor for the load
as long as the power demand is within the capability of the system. The system
can also drive “VARS” onto the grid to support tips of grids. This is field settable
and allows the customer to set a specific power factor when generating onto the
grid.
3.7.4 POWER
The maximum net output power of the TA100 system is 105 kW. The formula for
determining the power output of the system is voltage times the square root of the
number of phases () times the current times the power factor (PF).
SECTION 3 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
END OF SECTION
4 APPLICATION ENGINEERING
4.1 SYSTEM CHARACTERISTICS SUMMARY
This section summarizes the basic capabilities and characteristics of the TA100
system. The main features of the TA100 are depicted in Table 4.1 below. The
Performance capabilities of the system are shown in Table 4.2. Standard
capabilities of the TA100 include:
Remote Interface
Parallel Ready
Battery Charger
Digital Controller display
Integral Grid Protection
Compliant with IEEE1547 and UL1741
ELECTRICAL OUTPUT
Output 105 kW Net
FUEL CONSUMPTION
(ISO Rated Power)
- 21 SCFM (36 NM3/hr) @ 940 Btu/SCF LHV
Natural Gas - 350 kW @ 1,195,000 Btu/hr LHV
Heat Rate 11,950 Btu/kWH
THERMAL OUTPUT
(Optional Water HRU)
Output 180 kW / 614,000 Btu/hr
Rated water outlet temp 140 F (60 C)
Rated flow 60 gpm (3.8 l/s)
Total system efficiency > 80%
Nuclear energy plants, for example, produce enormous quantities of heated water
as a byproduct of creating steam to drive generator turbines, and prior to efficient
cogeneration this heat was expelled from the plant into local reservoirs and
habitats. Often, this hot water is cycled through housing or industrial facilities in
the surrounding area as a source of heat, or applied to agricultural purposes.
Some cogeneration systems produce cold water, not hot water, and the cold water
is used to supplement or replace cooling systems in areas where cooling is
desirable.
In the US, when a facility cogenerates a given quantity or type of usable energy,
the producer of that energy may become entitled to special benefits under the
Public Utility Regulatory Policies Act (PURPA) of 1978. These benefits include the
right to produce energy from cogeneration whether this energy is needed or not (a
right not guaranteed in other circumstances), and possibly the right to sell
cogenerated energy at favorable avoided-cost prices to utilities. To further
stimulate cogeneration, utilities may even be forced to purchase that energy at this
favorable price under the terms of PURPA.
There are two main types of cogeneration concepts: “Topping Cycle” plants and
“Bottoming Cycle” plants.
Topping Cycle
A topping cycle cogeneration plant generates electricity as its main energy
product. Facilities that operate a topping cycle produce the electricity for their own
use and may sell any excess power to a utility. That is, if they are a qualifying
facility (QF) as recognized by the Federal Energy Regulatory Commission (FERC).
Microturbine cogeneration is considered a topping cycle.
Bottoming Cycle
A bottoming cycle plant generates heat first in a furnace or a boiler. These
facilities are typically heavy industries such as glass or metals manufacturing
where very high temperature furnaces are used. The excess heat is used to
generate steam that is then used to operate a steam turbine that generates
electricity. The plant may sell any excess power to a utility, provided they are a
QF. Bottoming cycle plants are much less common than topping cycle plants.
160
140
120
100
80
60
40
20
0
22 23 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
The profile in Figure 4.1 depicts a factory that begins work at 6 AM operating two shifts
until midnight. The drop in usage at 3PM indicates that the second shift is a smaller
force than first shift. This customer’s usage is 98.75 kW per hour for a total of 2,370
kWh per day. At $0.08 per kWh this equates to $189.60 per day of an average of
$5706.96 per month. This is the usage charge that every customer sees.
The $0.08 per kWh used above is really an average cost per day. Most utilities have
three rates during a 24 hour period:
Example: If your utility charged the rates below, then your average cost would be $0.08
per kWh.
For a thorough site analysis, one should obtain the actual tariff rate structure for the site
utility provider.
Most large use customers are charged a demand charge. The demand charge is a flat
rate per kW. The rate can easily be up to $30 (or more) per kW depending on the
market. The number of kW’s is determined by the peak kW usage at any given time
during a certain period. In some markets the kW peak is determined once a year and in
other markets it is determined each billing cycle. Figure 4.2 below shows the peak
demand for a given facility through the year at $11 per kW.
Demand Charges
350 $3,500
300 $3,000
250 $2,500
200 $2,000
Cost
kW
150 $1,500
100 $1,000
50 $500
0 $-
em r
ne
Fe ary
il
O ber
t e st
M y
Au ly
em r
r
ay
ch
e
ec be
be
pr
r
ep gu
Ju
N t ob
ua
Ju
M
ar
nu
m
br
c
Ja
ov
D
S
If we assume that the above chart depicts the same factory charted in Figure 4.1 then
the bill for January is $5,706.96 plus $3,300 for a total of $9,006.96. Obviously, each
site analysis would require a detailed understanding of the specific tariff structure for the
site utility provider.
4.2.2.2 FUEL UTILITY CHARGES
Natural Gas (NG) is the fuel of choice for many applications since it is relatively
inexpensive and produces very low levels of emissions. Natural gas is sold at five
different price levels; Residential, Commercial, Industrial, Vehicle and Electric Utility.
Fuel for a genset would fall into the Commercial or Industrial category depending on how
the customer is classified by his natural gas provider.
Gas prices are quoted in therms and MMBtu. A therm is equal to 100,000 Btu. An
MMBtu is equal to 1,000,000 Btu. In almost every case the prices are quoted at the
higher heating value (HHV).
Manufacturers typically rate their engines using lower heating values (LHV) since the
exhaust is never taken to the lower exhaust temperatures of HHV assessments. Lower
heating values neglect the energy in the water vapor formed by the combustion of
hydrogen in the fuel. This water vapor typically represents about 10% of the energy
content. Therefore, the lower heating values for natural gas are typically 900 - 950 Btu
per cubic foot. The TA100 system LHV reference is 940 Btu/SCFM.
4.2.3 EVALUATION OF A POTENTIAL SALES PROJECT
Any possible sales project needs to be evaluated on both the electrical need of the
project as well as the thermal need of the site. An economic analysis is required
for each microturbine installation. The key factors to consider in the analysis are:
Cogeneration end users are typically looking for a 2 to 3 year payback periods on
a microturbine purchase. By adding a cogeneration aspect to the project
additional economics can be realized. In most cases the economics of a
microturbine are only realized when the thermal energy is used. In Europe, non-
cogeneration installations are almost never considered, unless the fuel is free.
Energy is expensive in Europe and most other places in the world. An exception
is France, where a large majority of the electricity is generated from nuclear
energy.
The application engineer must do a very detailed analysis of the site and take into
account the specific tariff structure of the local utility as well as other specific local
480V 400V
S26 outUnderVolt1Set Voltage RMS Low2 level V 240 240 200 200
S119 Under Voltage 1 Time Voltage RMS Low2 Fault time Sec 1 0.1 1 0.1
S28 outUnderVolt2Set Voltage RMS Low3 level V 384 408 320 340
S29 outUnderVoltTimeSet Voltage RMS Low3 Fault time Sec 2 0.5 2 0.5
S27 outOverVolt2Set Voltage RMS High1 level V 576 552 480 460
S29 outOverVoltTimeSet Voltage RMS High1 Fault time Sec 2 0.5 2 0.5
S25 outOverVolt1Set Voltage RMS High2 level V 624 576 520 480
S118 Over Voltage 1 Time Voltage RMS High2 Fault time Sec 1 0.1 1 0.1
S30 outOverFreqSet Frequency High Delta Hz 2.5 0.5 2.5 0.5
S32 outFreqTimeSet Frequency High Fault time Sec 2.5 0.1 2.5 0.1
S31 outUnderFreqSet Frequency Low 1 Delta Hz 3 1 3 1
S121 Under Frequency1 Delay Frequency Low 1 Fault time Sec 300 0.5 300 0.5
S120 Under Frequency2 Frequency Low 2 Delta Hz 5 3 5 3
S122 Under Frequency2 Delay Frequency Low 2 Fault time Sec 2 0.1 2 0.1
S33 outDcCurrLevelSet DC Current Limit (amps) % 0.5 0.5 0.5 0.5
S34 outDcCurrTimeSet DC Current Limit Fault time Sec 0.3 0.3 0.3 0.3
S37 gridLossPaDegSet Anti-Islanding detection deg 10 1 10 1
S36 gridLossPaTimeSet sec 0.5 0.2 0.5 0.2
S39 gridLossAcFreqSet Hz 2 2 2 2
S38 gridLossAcTimeSet sec 2 0.5 2 0.5
(disables
S26,S119,S25,S118,S37,S3
6,S39,S38 if set to 16795)
Start turbine
Start generating power
Stop generating power
Stop turbine (shut-down)
Power control command (utility mode only).
Mode change between voltage island mode and utility-tie current mode when
engine speed is zero.
Mode change between voltage island mode and utility-tie current mode while
engine remains running. PE shall “stop generate”, “change mode”, “generate
again in the other mode”.
4.4.2.1.27 Remote Monitoring
Remote monitoring shall be carried via RS485 MODBUS. The system controller also
provides “dry contact” status signals to indicate “READY, START, RUNNING, and
GENERATING” system status.
Start turbine
Start generating power
Stop generating power
Stop turbine (shut-down)
4.4.2.1.29 System controller authority
The power electronics also incorporates controllers to enable the accurate and
complete control of not only the power inverter but also the following:
Turbine
Oil pump
Liquid fuel pump
HRU damper (optional)
Gas Boost Compressor (optional)
4.5 FUEL TYPE CAPABLILITIES
The following section describes the properties and contaminants allowed in the
fuels that have been established and validated as usable with the TA100 system.
Before any project is substantially defined, a fuel sample analysis or the exact
characteristics and contaminants of the fuel should be provided to Capstone
engineering. If the fuel is within the bounds of the requirements described below
no further action will be required. If the fuel is found to not be within the
requirements below, then an engineering analysis will have to be completed and a
plan to validate the fuel would have to be completed before use in the TA100
would be allowed.
4.5.1 General Gaseous Fuel requirements
Table 4.7 below indicates the maximum and the minimum levels of constituents for
Carbon based gaseous fuels (HEC, NEC, and REC fuels). Table 4.8 provides
requirements for contaminant levels of all gaseous fuels. All gaseous fuels shall
require the supply facility to absolutely verify the fuel at the engine fuel system is
gaseous. This may be accomplished by providing an inline or wrap heater on the
fuel supply line to the unit to keep the fuel temperature above the vapor point. If
purchased with the optional cold weather kit, the TA100 will include fuel system
wrap heaters. Fuel composition shall be such that the gas fuel supply temperature
must be at least 10° F (5.6° C) above the dew point of the fuel at maximum engine
supply pressure.
4.5.2.1 Diesel
Diesel grades ASTM D975 No. 1-D, 2-D, Grade Low Sulfur No. 1-D and No. 2-D
shall be allowed. Use of a fuel stabilizer to prevent water absorption and microbial
effects is suggested. In some situations a additive to improve the cloud point may
be necessary as well.
4.5.2.2 Kerosene
Kerosene grades ASTM D3699 1-K and JIS K2209 shall be allowed. Use of a fuel
stabilizer to prevent water absorption and microbial effects is suggested. In some
situations a additive to improve the cloud point may be necessary as well.
1. Required fuel flow the same as high pressure feed requirements for the type of
fuel used.
2. Fuel temperature must be the highest of 0° C (32° F), or 10° C (18° F) above
the fuel dew point temperature at the Maximum Supply Pressure indicated in this
table.
105.0
100.0
95.0
Gross PE output (kW)
90.0
85.0
Current TA100
80.0
Advanced engine
75.0
Spec Requirement
70.0
65.0
60.0
-40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0
Ambient temperature (DegC)
#1 #5
PE Enclosure
Cooling Top Flow
Inlet Exhaust
#6
Enclosure
Bottom
Flow
Exhaust
For outdoor installations of the TA100, the inlets on top of the unit are covered with
a roof to protect the inlets from snow and rain entry. This inlet can be tilted up to
replace the two inlet filters for the engine intake and enclosure cooling. In addition
to the inlets on top of the unit, the PE cooling flow will be drawn into the PE on the
front door of the unit.
4.9.3 ENCLOSURE EXHAUST AND ROOM VENTILATION
When the TA100 is installed indoor, the room ventilation must be at least 5000
scfm per unit. A room exhaust fan near the rear of the unit is preferable since this
flow will entrain the exhaust energy from the rear enclosure exhaust ducts. These
ducts on the unit dump to the immediate vicinity of the unit.
If room ventilation is not possible as specified above, the enclosure cooling flow
exhausts on the back of the unit enclosure can be separately ducted to the
outdoors. If the enclosure cooling outlets are ducted, the upper and lower
outlets must be ducted separately for proper cooling of the enclosure. The
outlets are 0.56 m (22 inches) X 0.56 m (22 inches) and flanged. If ducting is
provided on the rear enclosure exhausts, it must be removable to disengage the
rear panel for access to the GBC. The clearance in the rear of the unit must be
maintained to provide the required space for the GBC rail to extend.
4.9.4 ENGINE EXHAUST
The exhaust from the microturbine exits the top of the enclosure at the rear of the
unit. Each application will have different exhaust requirements. The standard
indoor engine exhaust is simply a vertical pipe extending just out of the top of the
unit that is 25.4 cm (10 inches) in diameter.
When the TA100 is installed outdoors, the enclosure cooling will exhaust from the
rear enclosure exhaust ducts directly into the immediate vicinity.
NOTE: If the water quality does not comply with the requirements outlined in Table
4.21 it may alter Capstone performance specifications and void the warranty
The successful operation of the TA100 package is achieved with correct water
quality management. Inappropriate water quality may cause such problems such
as corrosion, scale deposition and slime formation on the system, lowering the
system performance, and possibly damage the flow meter installed inside the
package. This specification is intended to be a guideline for the water usage in the
Heat Recovery Unit (HRU) of the TA100 package. Follow best engineering
practices and local, state and federal regulations/codes for potable and non-
potable water standards. These requirements apply to any system whether it is
open, closed, water, or glycol. Typically systems with glycol currently use
propylene glycol for poisoning safety concerns.
4.10.1 Minimum water quality requirements
SECTION 4 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
5 INSTALLATION
5.1 SITE REQUIREMENTS
Good installation planning is the key to proper site selection. Inadequate site
planning may lead to future problems or potentially adverse operating conditions
for the TA100. Most installations require communication from the facility to
schedule the operation of the TA100 systems. This detail is included in Section 10
“Facility Control Integration”. The following guidelines should be followed when
selecting a site:
Free of debris
Not subject to flooding
Not subject to snow drifts in front of inlet or exhaust ducting on unit
Exhaust gases must be properly ducted away from the unit to prevent potential
recirculation into the microturbine and also to prevent exposure to people, animals
and heat sensitive equipment.
When located indoors, the exhaust gases always need to be ducted to the outside
and the air inlets need to be ducted from the outside. The site must allow for the
proper ducting to the enclosure / PE cooling air inlet as well as the engine
combustion air inlet. Proper sizing of the air inlet and exhaust ducts is critical to the
operation of the TA100. Sizing should be done per the requirements of
temperatures, flow rates, and pressure loss limits in Table 4.20.
Distance between the TA100, and any wall or permanent structure, should be
sufficient to allow maintenance and easy removal of components. This distance, in
the front and on each side of the TA100, should not be less than 1.1 meters. The
rear (exhaust end) of the turbine must have 1.3 meters of clearance and there
should be 1.8 meters between units. (See Figure 5.4)
Adequate noise isolation from any people or surrounding facilities.
Within a reasonable distance of an adequate supply of fuel.
5.1.1 If installation is being completed in the USA, the following information is
pertinent:
Information concerning fire and load protection standards, developed by the National
Fire Protection Association (NFPA), is available from NFPA. Their contact information
is:
5.1.2 The following standards are applicable depending on the TA100 system's fuel
supply and how the unit will be used:
When systems are mounted in arrays of more than 3 units grouped together, the
clearance between units should be doubled to prevent heat island effects.
CAUTION: Exhaust gases are extremely hot. Avoid contact with the
exhaust flow path. Serious burns can occur if the exhaust comes into contact
with skin.
Finned Tube
Heat
Exchanger
Water Outlet
Temperature Sensor
Damper Actuator
Water Inlet Line
Before proceeding with any fill process the following items should be verified.
1. Water Quality is acceptable per Table 4.21
2. Water treatment system is installed and ready for operation
3. No water leakage on facility piping
4. All water piping is well supported
5. Valves are in position ready for commissioning.
6. Circulation pump functions and provides flow
7. System design water temperature will not exceed limits
Complete the following purge procedure before commissioning of the HRU system
to provide verified clean water flow to the HRU system.
1. Close isolation valves and open the bypass valves.
2. Charge water from Flush Valve (A) and drain it from Flush Valve (B) to
remove contamination from water piping.
3. Close flush valves.
4. Close a bypass valve, open isolation valves, and charge water from
make-up water line and start the pump.
5. Clean the screen mesh strainer at the pump.
6. Clean the strainer filter at the inlet to the HRU system.
7. Turn on the pump and circulate water to catch dust and particles
existing in water system.
8. Check filter strainer at HRU system continue the purge process until
the filter does not catch any significant amount of particles during an
hour of operation.
9. Restart the pump (if required) and keep it running until air is fully
evacuated from the water system. (It may take up to a couple of
hours, depending on the application and plumbing.)
Once the system is purged, the HRU should be pressurized and filled with water
by the following procedure.
1. Turn the air vent cap on the HRU two (2) full turns counter-clockwise
for proper venting.
2. Fill the HRU with water until there is no more air trapped in the
system.
3. Close the air vent cap on the HRU by turning clockwise till seated.
4. At the completion of this procedure verify the system is leak free
before continuing with the Commissioning of the unit.
To prevent possible eye injuries from oil splatter when disconnecting oil
lines, safety goggles should be worn when servicing the oil system. Flexible
hoses may spray or splash oil during handling.
Use drip pans to prevent leaks or spills from collecting on the floor or
ground. Oil on the floor is a fire hazard and oil entering the ground could
contaminate the water table.
FIGURE 5.12 OIL TANK SIGHT GAUGE AND FILL LEVEL MARKINGS
NOTE: Verify this oil level remains within the acceptable range after the unit is
first started. When unit is first cycled the level will be lower due to filling of the
NOTE: Oil contamination can cause oil foaming, which may result in engine
failure. Use care not to contaminate the oil during the fill process.
NOTE: The TA100 lubrication system is designed to use only Mobil SHC 824. Do
not substitute oil brands or type.
5.13 GROUNDING
5.13.1 CHASSIS GROUNDING
NOTE: When multiple units are installed, all units must be grounded at a single
electrical point to prevent ground loop feedback between units.
The main ground, or building ground, must be certified to electrical building code,
or NEC code. The utility company or certified electrical contractor should install
this ground. Connect each microturbine ground terminal directly to the main
grounding point. It is important to keep the ground bonding resistance as small
as possible, especially from the power ground terminal to the main grounding
point because any major system noise will be conducted from this terminal to
ground. Grounding cable size must be 70mm2 (AWG 2/0) 90EC copper wire, the
same as all power output cables.
5.13.4 GROUND LEAKAGE PROTECTION
CAUTION: Never attempt to connect the output power cables while the
TA100 is operating or when the power cables are energized. Ensure all
output breakers are open before connecting the output power cables.
A A
B Delta B Utility
C or wye C
TA100 N
CHP Manual
Required
Protection Device Utility step-down
Switch Transformer
Any Load
Connection
G
Parameter Specification
Over-current (instantaneous) 150% of maximum rated current for five seconds
Automatically ensures that the system will not supply
more than maximum rated current by dropping
Thermal overload terminal voltage. Under normal circumstances, if
excessive load is placed on the generator, the
system will shut down on under voltage.
Ground leakage 60 – 130 mA for 3 milliseconds
Software settable up to 130% of nominal RMS rated
Over-voltage
voltage
Under-voltage (in voltage Software settable down to 50% of nominal RMS
mode) rated voltage
Software settable down to 50% of nominal RMS
Under-voltage (in utility mode)
rated voltage
Under/Over voltage time delay Software settable from 0.5 to 2.5 seconds
Over frequency Software settable from +0.5 to +2.5 Hz
Under frequency Software settable from -0.5 to -2.5 Hz
Under/Over Frequency time
Software settable from 0.1 to 2.5 seconds
delay
TABLE 5.1 POWER ELECTRONICS PROTECTION SETTINGS
A
B
C
TA100 N
CHP
Manual L1 L2 L3 L4 L5
Switch
A
B
C
TA100 N
CHP Auto
Transformer
L5 L4
L3
L1
G L2
NOTE: Extreme care is required when handling and routing the fiber optic cable. If
the cable is “kinked” or bent in any way it can be broken and will require
replacement. Connect one end of fiber optic cable to each TA100.
Fiber Optic
Cable
connections
PCB25 Location
Customer
Connections for
External power
(400-480 3
phase)
EXT
Two batteries should be placed into the battery storage area in the bottom of the
PE and connected as described below. The batteries are wired in series.
Turn the system ON/OFF switch SW1 to the off position.
Open 24 VDC breaker K5 (See Figures 5.24a and 5.24b). This breaker is on the
right hand side of the unit behind the front door of the power electronics.
Open the front door of the PE.
Install two 12VDC type batteries as shown in Figure 5.23
Connect the yellow lead to the negative terminal of the left hand battery.
Connect jumper from the positive terminal of the left hand battery to the negative
terminal of the right hand battery.
Before final connection of the batteries, an external charger can be connected to
the batteries to fully charge them before commissioning of the unit is started.
Leave the front door open to make sure it is obvious the batteries are still being
charged.
Connect the red lead to the positive terminal of the right hand battery.
Close the PE door making sure there is no interference with the battery cables.
Gaseous and liquid fuel is highly flammable and explosive. All fuel
supply connections should be made, tested, and inspected by fully trained
personnel. All local, state, federal, and international codes must be followed
to prevent injury to personnel or damage to facilities. Never install the fuel
lines near exhaust pipes. Failure to heed this warning could result in fire or
explosion that can cause severe personal injury, death, and/ or property
damage. The Capstone TA100 and associated natural gas compressor are
not designed for installation in hazardous areas. This equipment must be
located in well-ventilated areas to ensure that under no circumstances
flammable gases can collect.
For an install of the gaseous fueled TA100, it is recommended that a check valve
be installed between the fuel supply source and the TA100. This check valve will
prevent the possibility of any fuel in the TA100 fuel train from back flowing into any
other devices or lines in the facility feed system on startup. This situation is very
brief and primarily is a concern only with the low-pressure fuel system that
contains an optional integral GBC.
CAUTION: When making the fuel gas connections great care must be
taken to not damage the flexible portion of the fuel inlet piping. If the flexible
piping is over torqued and damaged it may rupture. It the flexible piping is
over torqued it will have to be replaced. Failure to do so could result in loss of
life, injury or property damage.
Note: Improperly sized piping could lead to insufficient pressure for the gas compressor.
Careful design of the feed system should be completed to guarantee the pressures
specified for use by the TA100 are not deviated from. Line losses at very low
pressures can become significant enough to drop the pressure below the specified
range if careful design is not completed.
The liquid fuel train allows the customer to feed fuel to the system with either a low
pressure feed pump or simple gravity feed. The main fuel tank will provide a
supply line to the unit and will have a return from the system that is bypass fuel
from the fuel pump. This bypass fuel will not be hot fuel and can simply be flowed
back into the main supply tank. The liquid fuel control system modulates both the
start fuel supply as well as the main fuel supply to the turbine as well as provides
the control to allow the fuel system to purge raw fuel out of the injectors and
manifold system after use to prevent coking of the fuel on hot metal parts in the
injector and manifold. This purge line will have to be directed to a “day” tank and
will have hot fuel in the line. There also is a mechanical purge that is a gravity
Connections to the TA100 liquid fueled unit are shown in Figure 5.26,5.27, and
5.28. Figure 5.27 shows the three connections to the main fuel tank (FUEL IN,
FUEL RETURN, and PRIMER RETURN). FUEL IN is the main supply line for
fuel to the TA100 from the main supply tank. FUEL RETURN is the connection to
return pump bypassed clean fuel back to the main fuel tank. PRIMER RETURN is
the clean fuel that is sent back to the main tank when the system hand valve is
being used to purge air from the fuel system after service. Figure 5.28 shows the
two connections to the “DAY” tank (MAIN PURGE and MECH PURGE). This tank
is a temporary holding tank that will have hot fuel flowed into it. MAIN PURGE
connection is for the hot fuel purged out of the TA100 after starting and after
shutdown. The fuel flowing out of this line can be very hot so this line should be a
metal line to the day tank. MECH PURGE is the mechanical purge valve flow that
will drain out of the engine after shutdown. This fuel line can have very hot fuel
and will return to the day tank. Both these lines have very small amounts of fuel
going through them (typically when flowing they will only flow about a pint at most
of fuel per purge period.
SECTION 5 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
6 COMMISSIONING
6.1 PRE-COMMISSIONING
NOTE: A Sample Pre-start check list and Commission Summary Report is provided in this
reference section at the end of the Section.
Verify the configuration is as intended and the following are set correctly for the
installation:
Verify that the correct configuration of load wiring (either 3 or 4 wires) is
connected.
Verify if a transformer is required that it is installed.
Verify the correct voltage and frequency settings.
Verify that the correct mode settings are loaded for the configuration installed (grid
/ current mode or island / voltage mode).
Verify the external grid protection hardware is installed if required.
Verify the system protection settings are correct for the hardware requirements.
Verify the HRU mode setting is loaded correctly for the installation requirements.
Verify the HRU damper position or temperature set points are loaded per the
installation requirements.
NOTE: Document any deviations and the action taken if necessary on the
Commissioning Summary Report. If anything in this section is
unacceptable, make note on the report and correct if possible. If the system
is not acceptable or corrections cannot be made, the Commissioning report
should indicate the situation and that commissioning could not be completed.
= ON = OFF
Unit Number
PE Version & CRC
EC Version & CRC
PLC Version
HMI Version
Heat Recovery Unit (HRU) (if installed)
Start Table (TBL) Version.
When the “Operation” button is selected the screen in Figure 6.3 will be displayed
Confirm that there are no alarm messages. If an alarm message is displayed then
it will have to be cleared before operating the TA100. Should the TA100 alarm for
any reason, the unit will shut down and will not allow restart until it is cleared. A
fault message will be displayed on the top middle right of the touch panel.
While machine is NOT operating, set fuel pump into TEST mode by doing the
following:
On the HMI, push the maintenance button to enter MAINTENANCE mode.
Enter the required password
Push CAL & TEST
Push DO TEST 2
Push TEST OUT
Select fuel pump ‘ON’ (turn pump off by selecting ‘off’ if needed)
Pressure
gauge
Spin-on
Fuel Pump Filter
Bleed Valve
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
NOTE: If the ambient temperature is below 15° C (59° F) follow the Cold Weather
Pre-Start outlined in Section 6.
7.2 CONTROLS
The TA100 system physical controls consist of the following three devices
Emergency Stop
Power On/Off Switch
Control Panel (HMI touch screen)]
All of these controls are on the right front door of the system as shown in Figure
7.1. The Control Panel touch screen has an extra weatherproof door over it to
provide easy access yet provide full sun / weather protection.
NOTE: If the ON/OFF switch is turned to the OFF position while the unit is running
then all systems will continue to operate. A shut down will only occur if the
emergency stop is pushed or if a normal shutdown is initiated. The switch
has either an on position or an off position as indicated in figure 7.2.
= ON = OFF
FIGURE 7.2 ON/OFF SWITCH
NOTE: Care should be taken to prevent rupturing the membrane on the touch
screen. Only use fingers to make selections. Never use pencils, pens or
other sharp objects. Rupturing the membrane will make the controller
NOTE: Only authorized personnel should change the settings in the maintenance
section.
Generate Start
Mode
There are user settable functions that determine the basic operational modes of the
TA100 system. The following describes how to configure these options on the system.
There are three control modes on the TA100 system. This selection determines how the
system accepts commands from the user. The user can provide local commands,
remote hardwired commands, and Modbus communicated commands to the system.
Refer to Section 7.5 for Modbus interface communication details.
To switch between control modes press the Control Mode button on the touch panel
screen (Figure 7.4). A small selection window will appear with the capability to select:
Local
Remote
Full Remote
Select the appropriate button per the descriptions below. After selecting the appropriate
button, confirm that the operation screen shows the selected option. The operation
mode can also be set using Modbus input per Section 7.5.
K5 Breaker
To clear a fault remotely, the correct register will be written to on the RS485 using
MODBUS per the register definition in 7.7 Communications in this section or a contact
closure made on the hardwired fault reset contacts.
7.3.3.9 MICROTURBINE START
Press the "START" selection and press enter (Figure 7.8) to confirm. This will initiate the
start sequence for the system. The engine will accelerate to 16,000 rpm to purge the
system for about 15 seconds and then will decelerate to 10,000 rpm (14,000 rpm liquid
fueled system). Once this speed has been reached, the fuel system will provide fuel and
spark to light off the turbine and then accelerate until running speed is achieved (68000
rpm). Thirty (30) seconds after reaching operating speed the unit will go into generate
mode. Table 7.1 details the start procedure that the system will perform.
If the unit is operating in Island mode, the TA100 will automatically adjust to supply
whatever load is on the output cables (unless it exceeds the system overload capabilities
or derate capability of the unit). When operated in Utility (or Grid) mode, the TA100
system will ramp over a period of a couple of minutes to full programmed load. If the
unit is in Auto Generate mode while Grid connected, the unit will warm up for about 30
seconds and then will ramp up to maximum load the system is capable of generating
considering the EGT limit and output power limit of the system or to the corresponding
load requested if in load following or load set point mode. If the unit is in Auto Generate
mode while in Island mode, the unit will warm up for about 30 seconds and then
automatically generate power to carry the load on the output lines. The maximum power
capability is dependent upon the maximum output of the unit (100kW net) and the
ambient temperature.
To monitor the start graphically, the user can press the “Next” button on the Operation
screen after the start has been requested and the next level of operation screen will
appear (Figure 7.9). From this screen press the Trend button to display the graphic
display (Figure 7.10) real time of the start.
NOTE: Only use the emergency stop button in the event of an actual emergency. After
activating the emergency shutdown DO NOT restart the unit until the trouble has
been diagnosed and resolved.
If the “Operation” screen is not displayed navigate using the touch pad control until
it is displayed. Once the “Operation” screen is displayed, use the following
instructions to shut down the unit:
Press the “Stop” selection on the “Operation” screen.
Press the “Enter” option on the verification screen (Figure 7.8).
Verify that the “Power” indicator has extinguished.
Verify that the power output value has decreased to zero 0.
When turbine speed has reached zero (0) then turn the ON/OFF switch to the OFF
position.
7.3.5 POST SHUTDOWN CHECKS
With the unit shut down and after the cooling period, check for oil, fuel, or water
leaks
7.4 STORAGE PREPARATION
If the unit will be place in storage and not operated for an extended period of time
perform the steps outlined in Section 5.18 on storage preparation.
7.5 SYSTEM COMMUNICATIONS
The communication method used on the TA100 is MODBUS single master/multi
slave method. Only the master can initiate a Query and/or Queries
(communication start). The slave responds by supplying the requested data to the
master, or by taking the action requested in the query. The master can address
individual slaves, or can initiate a broadcast query to all slaves. In case of a
broadcast query, each slave performs a specified function only and will not return
a response message. The slave returns a response message only when it is
The transmission format of the query consists of the Slave address or broadcast,
the function code of a specific request, and the data field and error-checking field.
Also, the transmission format of the response message consists of a field
confirming the requested contents and the error-checking field. MODBUS protocol
refers to registers as “coils” so these two terms will be used interchangeably in this
document. Communication Parameter settings are on the following pages.
7.5.1 COMMUNICATION PARAMETER SETTINGS
The communication parameters supported by the TA100 Engine Control Board are
listed in table 7.2.
*1: Bit rate accuracy 9600bps: 0.16% 19200bps: -1.36% 38400bps: 1.73% 57600bps: -
1.36%
*2: The Dip switch is located on the engine controller board, marked as SW1, at the right
side of connector Cne14. Dipswitch settings are listed below in TABLE 7.3.
Dip Switch 1 2 3 4 5 6 7 8
Comm Speed
9600 Off Off
19200 Off On
38400 On Off
57600 On On
CRC Low High Off
CRC High Low On
Modbus Addr
2 Off Off Off Off Off
3 Off Off Off Off On
4 Off Off Off On Off
Table 7.4 below indicates the MODBUS functions that allow communication to and
from the TA100 using MODBUS protocol. For instance, to write and send user
commands, use MODBUS Function 0x05.
Register
Address Value High (1) description Value Low (0) description
Name
Request shutdown of unit. No
impact if unit is shutdown and
command is resent. In Island
Request start of unit if
mode the unit will stop
system is not in Fault
generating power immediately
1 Engine Start condition. Continue
and shut down normally. In
running is this value is high
utility mode, the unit will ramp
and resent.
down power until NO Load
condition is achieved and then
will shut down.
Allow power generation if
system is running and Stop power generation. This
ready to generate. If set will cause an immediate
Generation
2 prior to start will go offload of the unit but the
Start
immediately into generation turbine will continue to
upon reaching system state operate.
that allows generation.
Immediately stop power
Emergency
3 generation and initiate Normal operation
Stop
shutdown.
4 Error Reset Clear active faults Normal operation
TABLE 7.6 WRITEABLE INPUT REGISTER LISTING
Error Limit
Code Name Description field Limit
EGT Spread Difference between EGT#1 and EGT#2
201 HH is too high. SP019 100° C
203 IC Comm FL Inverter Communication Fail
204 Oil I Temp HH Engine Oil inlet temperature high high SP007 90° C
MCU Comm
Modbus Communication Link Fail
205 FL
Oil inlet temperature Permit Fail. This
indicates the oil warming cycle timed
Oil I Temp out and could not achieve oil temp in
206 LLP time required. SP008 15° C
Error Limit
Code Name Description field Limit
101 E-Stop Emergency Stop
102 Overspeed Engine Overspeed SP001 73,500
103 Over Temp EGT Over Temperature SP015 665 deg C
105 Batt Volt LL Battery Voltage Low Low SP025 20 VDC
106 Speed Sen FL Engine Speed Pickup Failure
109 Oil SW Low oil pressure hdwr 45 psi
Combustion blowout during normal
112 Blowout running conditions SP031 -500° C/sec
113 Flameout EGT Flameout (EGT) during start-up SP030 -15° C/sec
SP229 1.2 sec
Chemical acceleration rate is too low
114 Low Energy during start SP026 200%
115 Purge FL Purge speed not held for required time SP034 16300 rpm
SP201 18 sec
116 IGN FL Ignite speed not held for required time SP013 10000 rpm
SP228 1.5 sec
Failure to obtain self sustain speed
117 Sustain FL during start in required time SP035 35000 rpm
SP213 120 sec
Unable to transition to steady state 2000 rpm
118 Rolling FL speed in required time from start SP036 below SS
SP214 200 sec
119 Idle FL Unable to reach idle speed in required SP038 68000 rpm
Error Limit
Code Name Description field Limit
624V (480 V
401 OVR Over Voltage S25 system)
520V (400 V
S25 system)
240V (480 V
402 UVR Under Voltage S26 system)
200V (400 V
S26 system)
403 OFR Over Frequency S30 1 Hz
404 UFR Under Frequency S31 1 Hz
405 Iso Detect Act Isolation Detect Active (grid loss) S36 0.3 sec
406 Iso Detect Pas Isolation Detect Passive (grid loss) S38 0.5 sec
DC component Current high - only for 0.5% of the
407 DC Cur Detect Utility mode S33 rated current
S34 0.3 sec
408 Phase Error Utility phase error
20% of rated
409 Voltage Error Inconsistent Voltage S14 voltage
410 Phase Rot Fail Utility phase error
Output over current - only for utility 115% of the
411 Out OCR mode S02 rated current
0.5 sec
150% of
Output current too high - only for island the rated current
412 Overload mode for 5 seconds
413 Inv Module Flt IGBT driver module fault
Inverter temperature high-as measured
414 Inv Temp Flt at the heat sink S103 90° C
415 INV Cur HH Inverter Current High High 500A
S Inv Module
416 Flt Start inverter module fault
417 Sub Inv C HH Start inverter current High High 60A
Power boost failure - detected by IGBT
418 Main Bst Fail driver 90° C
419 Bst Temp Fail Boost Temperature high at heat sink
SECTION 7 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
END OF SECTION
8 MAINTENANCE
NOTE: Maintenance should only be performed by factory trained and authorized personnel.
There are no user serviceable parts within the TA100 unit.
8.1 PRE MAINTENANCE CHECKS
Before performing any maintenance on the TA100 CHP, review the safety
precautions in the Sections 1-7 of this manual. Never attempt even simple
maintenance (air filter replacement, routine cleaning, etc.) without complete
shutdown of electrical components including commercial utility power or outside
service voltage needed for accessory items. Even after shutting off power to the
unit, the PFC capacitors and the DC bus capacitors will take a significant amount
of time to discharge. The PE should not be entered without allowing 5 minutes for
the DC bus capacitors to discharge and the PFC capacitors should be manually
discharged.
Additional warning signs or safety devices that are installation specific may be
required.
8.2 PERIODIC MAINTENANCE SCHEDULE
The periodic maintenance schedule for the TA100 gaseous fueled system is
shown in Table 8.1. The periodic maintenance schedule for the TA100 liquid
fueled system is shown in Table 8.2. A monthly visual inspection is required.
Maintenance is required every 4,000 hours of operation and every 24,000 hours a
major maintenance is required. Maintenance procedures are documented in
Section 8.5.
NOTE: Set points for Sensors and Safety Circuits are found in Section 7.5
NOTE: After replacing the fuel filter elements a leak check of the fuel train must be
performed.
NOTE: This filter is not used on units shipped after June 2006
Replace igniter
Replace oil temperature sensor
Replace oil pressure switch
Replace EGT thermocouples
Replace HRU water pressure switch
Replace HRU gas temperature sensors
Replace water flowmeter/switch
Replace engine inlet air temperature sensor
Replace fuel injectors
Inspect engine/oil tank assembly
CAUTION: Never remove any parts of the gas boost compressor while it
is in operation or while the fuel supply is on! Avoid unnecessary contact with
The gas boost compressor in the TA100 is a CompAir Hydrovane unit. Please
refer to CompAir manual ST15954-00 for information beyond what is included in
this manual.
NOTE: Panel weighs approximately 50 lbs. Use care when removing the screws.
Place the panel and screws away from the work area in a safe position.
The lower enclosure panel (Figure 8.1a) must also be removed to provide egress
clearance. This panel is secured with 2 bolts on each side of the panel. Store the
panel and bolts in a safe location.
Disconnect the gas supply union using two wrenches.
Remove the plastic cable tie on the electrical service loop (Figure 8.1b).
Disconnect the oil heater cable from the oil filler plug (Figure 8.1c).
Disconnect the high-pressure supply line at the GBC exit.
The GBC frame is retained in place with two bolts located under the front of the
GBC. Remove these bolts and nuts, and place in a safe location.
Pull the GBC assembly rearward on the rail 18 inches.
NOTE: The GBC should not be pulled back more than 18 inches because the
wheels will disengage from the rail. If the wheels should disengage from the
rail, lift the GBC back upon the rail after completing service.
Rear
Panel
Lower Enclosure
Panel and Bolts
Cable Tie
Oil Heater
GBC Trim
Panel GBC Air
Filter
Oil Drain
Plug
Oil Filler
Plug
Oil Screen
Filter cover
Lubricant
Return Plug
Assembly
Hydraulic
Hydraulic Service
Service Lines
Lines
Remove the GBC nameplate (if not removed already) and unscrew the 8 5-mm
socket head screws.
After removing the 8 screws, the separator cap can be lifted from the lubricant
chamber (Figures 8.4c and 8.4d). NOTE: GBC will have to be partially pulled back
on the rail to allow easier access in lifting off the separator cap. Follow the
procedure in section 8.5.2.2 for more information.
Gasket
Coalescer
Filter
Element
“O” Ring
Thoroughly clean the jointing surfaces of the separator cap and lubricant chamber
before fitting a new gasket.
Reinstall the separator cap onto the lubricant chamber by tightening the 8 screws
evenly to avoid distortion. Torque each screw to 15 ft-lbs.
Reconnect all five hydraulic lines.
Follow the steps in section 8.5.2.3 to reinstall the GBC in the microturbine
enclosure.
Note: Since the top mounted filters see similar airflow rates, replace both the
engine inlet filter and the enclosure air filter at the same time.
Remove the two bolts holding the weatherproof cover on the unit from the right
side of the unit (Figures 8.6, 8.7, and 8.8)
Tilt the cover up to allow access to the filters on top of the unit (Figure 8.9)
Remove the rear air filter
Position a new air filter in the rear air box
Lower the cover back down onto the system
Reinstall the two bolts holding the weatherproof cover on the unit from the right
side of the unit
Removable
Bolt
Hinge Pin
FIGURE 8.6 WEATHERPROOF TOP (FRONT)
Weatherproof
Top
Removable
Bolt Hinge Pin
Weatherproof Top
Lifted to Obtain
access to Air
Filters
Engine Inlet
Air Filter
Enclosure
Cooling Air
Filter
Power Electronics
Air Filter
CAUTION: Never remove any parts of the fuel system while the fuel train
is pressurized! A sudden escape of pressure may cause serious injuries.
Before carrying out any work on the filters, first depressurize the fuel train.
NOTE: This filter is not used in systems shipped after June 2006.
CAUTION: Never remove any parts of the fuel system while the fuel train
is pressurized! A sudden escape of pressure may cause serious injuries.
Before carrying out any work on the filters, first depressurize the fuel train.
Pressure
gauge
Spin-on
Fuel Pump Filter
Bleed Valve
CAUTION: Never remove any parts of the fuel system while the fuel train
is pressurized! A sudden escape of pressure may cause serious injuries.
Before carrying out any work on the filters, first depressurize the fuel train.
Pump
discharge
Pump inlet
CAUTION: Never remove any parts of the fuel system while the fuel train
is pressurized! A sudden escape of pressure may cause serious injuries.
Before carrying out any work on the filters, first depressurize the fuel train.
Shutoff
Valves
CE Unit
Shutoff
3/8” Bracket
Bolt
Valve Ground
wire and
attachment
Shutoff Valve
Molex
Metering Valve
Molex Connector
Metering Valve
Power Resistor
#3 Phillips Screws
7/8” Swagelock
7/8” Swagelock
Fitting
Fitting
Control Shutoff
Valve Valves
Fuel Control
Valve
8.5.12 IGNITER
CAUTION: Igniter removal will involve detaching the igniter cable from the
igniter and removing the igniter. There are high voltages present during
operation in this system; personnel should not attempt to service this system
until the unit has been completely de-energized.
NOTE: FOD - Foreign Object Damage - The term FOD is also used to refer to any
Foreign Object that could cause Damage.
To install an igniter:
Prepare igniter by coating the threads with Jet Lube 550 - Anti-Seize.
Place tab washer over igniter hole. Orient the tab washer so that the keyed tab fits
into the alignment hole (Figure 8.30). Never reuse tab washers.
Hand-thread the new igniter into the combustor housing.
Using an 11/16" deep well socket and torque wrench, tighten the igniter to 15.82 to
20.34 Nm (140 to 180 lb-in).
Igniter Cable
Igniter
Tab Washer in
Alignment Hole
EGT Thermocouple
EGT Thermocouple
Oil
Temperature
HRU Water
Pressure Switch
NOTE: The fuel injectors on the underside of the combustor have a tendency to fall
out when the fuel manifold is removed. To prevent this use a small amount of
anti-seize to hold the injector in place. Be very careful to not get any anti-
seize in the injector orifice.
To install the fuel injectors and fuel manifold with the combustion liner installed:
Insert injectors into the injector receiver holes on the right hand side of the
combustor. (Figures 8.40, 8.41, and 8.42)
Install the right hand fuel manifold, starting with the top most injector receiver and
moving in a clockwise direction.
Hand-tighten all injector receiver nuts into place.
Using a 5/8” wrench connect right hand fuel manifold to the fuel inlet tee.
Insert injectors into the injector receiver holes on the left hand side of the
combustor.
Install the left hand fuel manifold starting from the bottom and moving in a
clockwise direction towards the top.
Hand-tighten the injector receiver nuts into place.
Using a 5/8” wrench connect the left hand fuel manifold to the fuel inlet tee.
Using a 9/16” “crow’s foot” wrench and a torque wrench, tighten the injector
receiver nuts to 7.91 to 10.17 Nm (70 to 90 lb-in) of torque.
5/8” Wrench
7/8” Wrench
9/16” Wrench
Combustor
Retainer Bolt
(7/8” Wrench)
Borescope Procedure:
Be sure engine is off and cool enough to prevent injury to personnel and damage
to the borescope.
Remove Igniter cab, Igniter and Igniter tab washer using tools and procedures as
outlined in Section 8.5.5.
Prepare borescope and insert probe through Igniter hole.
Photograph or notate condition of Liner. Look for damage to the tips of the Primary
Tubes. Also, look for holes and cracks, or other damage, such as distortion of the
Liner walls near the Turbine Nozzle.
Send photos and data to Capstone for further evaluation.
8.5.18.3 REMOVAL
NOTE: If the liner is not going to be replaced immediately cover the combustor
housing with plastic wrap or another suitable covering.
8.5.18.4 INSTALLATION
NOTE: The outer edge of the combustion liner shrinks after operating within the
microturbine. This makes alignment on re-installation difficult. A special tool
( #T00135) has been developed to re-align the outer dimension of the liner
so it can be reinstalled in the microturbine. The tool is not required for
installing new liners. Figures 8.40 and 8.41 show this tool and how it is used.
Figure 8.45 shows the area of the tool, indicated in red, which should fit
snugly into the combustion liner.
Combustor Liner
Combustor Liner
Expander Tool
(Tool #T00135)
Combustor Liner
Expander Tool
Combustor Liner
Combustor Liner
Retainer Bolt
Injector Receiver
Reference mark
on Encoder Card
Reference mark
for encoder card screw
Measurement
on Phase 1
1. During starting, the current to drive the TA100 engine is a high frequency pulse
current, and the frequency is about 8 kHz.
2. To check that the timing of the engine is appropriate, connect an AC current
clamp meter on the first alternator output cable as shown in Figure 8.48b. A
clamp meter should be used which can measure an 8 kHz pulse current signal
accurately.
3. At the HMI, select “Crank Mode”, then select “start.”
4. Once the rpm reaches 16300 the current at the clamp meter should read in the
range of 16-20 amps.
8.5.20.2 REMOVAL
Open both front enclosure doors.
Disconnect the molex connector to the T2 probe on the front of the clamshell duct
(Figure 8.52a)
Unclamp the two fasteners on the front and back of the engine inlet plenum
clamshell covers (Figure 8.52a/c). Swing apart the two halves, swivel the entire
assembly around the engine axis and remove the hinge pin at the bottom of the
clamshell assembly. The two sides of the clamshell duct can then be removed
from the system for either side of the engine.
Front Engine
Inlet Clamshell
Engine Inlet
Temperature
probe (T2)
Rear Clamshell
Fastener
Clamp off oil supply and return lines using T00271 clamping pliers (Figure 8.54).
Tool T00271
NOTE: Mount the Engine Removal Tool with ½-13 hex bolts.
Engine Support
Bolts
Engine Removal
Tool Base
Bolt thru from the bottom with existing ½” hex bolts, using nuts as stops to allow
for length of bolt.
Install hoist onto carriage dovetail mount (Figure 8.57).
Attach engine hoist to engine case using supplied ½” hex bolt (Figure 8.58).
Engine Hoist
Engine Hoist
Dovetail Mount
Engine Hoist
Attachment to
Engine Case
Remove three (3) 10-32 SHCS bolts holding engine to combustor housing at 12, 5,
and 8 o’clock positions (forward looking aft) and install three screws in their place
(PN 302009) to hold the diffuser on the engineer assembly.
Remove the rest of the twenty-four (24) 10-32 SHCS bolts.
Install engine / combustor housing separating tools T00274 (2 required).
Alternate left to right tightening tool jackscrews to separate engine from combustor
housing. Hoist not shown in Figure 8.59 for visibility.
24 10-32
T00274 Tools SHCS bolts
Jack
Screws
Carefully swivel the engine assembly away from the combustor housing. Use
caution to prevent hard contact of the nozzle with the combustor housing (Figure
8.60).
Combustor
Housing
Turbine
Nozzle
After the engine is totally outside of enclosure, stabilize and guide the assembly
while carefully releasing the hoist brake to lower it to a transport platform or safe
location (Figure 8.62).
8.5.21 BATTERIES
The TA100 system uses internal power of 24 VDC that is provided by two 12 VDC
lead-acid batteries tied in series. The batteries are located in the bottom of the
Power electronics package on the front of the unit (Figure 8.63). See Section 5.16
for battery sizing and models.
NOTE: Before servicing the batteries review all safety precautions in Section 2
Safety information. Servicing of batteries should be performed or supervised
by personnel knowledgeable of batteries and the correct precautions. Keep
unauthorized personnel away from batteries. When replacing batteries,
always change the complete set of batteries, and replace only with the type
specified in Section 5.16. Lead-acid batteries destined for disposal are
considered a RCRA-regulated hazardous waste due to their lead content (US
EPA Hazardous Waste Number D008).
Two batteries should be placed into the battery storage area in the bottom of the
PE and connected as described below. The batteries are wired in series.
Shutdown and deactivate system per the normal shutdown procedures in Section
7.
Open the front door of the PE.
Install two 12VDC type batteries as shown in Figure 8.63
Connect the yellow lead to the negative terminal of the left hand battery.
Connect jumper from the positive terminal of the left hand battery to the negative
terminal of the right hand battery.
Before final connection of the batteries, an external charger can be connected to
the batteries to fully charge them before the unit is started. Leave the front door
open to make sure it is obvious the batteries are still being charged.
Connect the red lead to the positive terminal of the right hand battery.
Close the PE door making sure there is no interference with the battery cables.
SECTION 8 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
9 DIAGNOSTICS
The TA100 has embedded diagnostics and failure detection features in the control
system. The faults generated during failure allow the user to trace the root cause
of the failure on the system. The diagnostic tree in Section 9.4 has information to
allow high-level diagnostics to be performed on the system. When the diagnostics
become too involved for onsite evaluation, contact the Capstone Service
Department for assistance in resolving the situation.
9.1 DOCUMENTATION OF DIAGNOSTICS
Upon investigation of any issue requiring Capstone support, the inspecting
technician should fill out and deliver an Initial Failure Report (Form #39)
electronically to Capstone. This form should provide enough detail to allow
engineering to assist the operator in understanding and correcting any abnormal
operation, fault, or failure of the system.
9.2 DATA TRENDING ANALYSIS
Observing certain data over time on the TA100 system will provide insight into
required maintenance and service required. There are two pieces of data that can
provide significant insights into the continued health and output capability of the
system.
Oil temperature
Rated and referred Engine Exhaust Gas Temperature (EGTRATED).
The data for trending both of these items should be taken at a consistent operation
point to effectively trend the operation of the system (i.e. at 80 kW output after fully
stabilizing for 20 minutes). The system should be at a stable operating condition
for the same period of time before taking the data.
NOTE: Variations +or – 77° F (25° C) are normal, any variances outside this range are
abnormal and need to explored.
9.2.2.1 System Measurements:
9.2.2.2 Calculations:
0.5 sec
150% of
the rated
current
Output current too high - only for island for 5
1312 412 Overload mode seconds
1313 413 Inv Module Flt IGBT driver module fault
Inverter temperature high-as measured
1314 414 Inv Temp Flt at the heat sink S103 90° C
1315 415 INV Cur HH Inverter Current High High 500A
S Inv Module
1316 416 Flt Start inverter module fault
1317 417 Sub Inv C HH Start inverter current High High 60A
Power boost failure - detected by IGBT
1318 418 Main Bst Fail driver 90° C
1319 419 Bst Temp Fail Boost Temperature high at heat sink
1321 421 DC Link V HH DC Link Voltage High High S21 950 VDC
S22 0.5 sec
740 VDC
(480V
1322 422 DC Link V LL DC Link Voltage Low Low S19 system)
625 VDC
(408V
S19 system)
CT Sensor Current Transducer Failure detected by
1323 423 Fail inverter controller
(Potential) Voltage Sensor failure
1324 424 PT Sensor Fail detected by inverter controller
1325 425 Inv CPU Fail Inverter Controller CPU Failure
PROPRIETARY INFORMATION © 2011 Capstone Turbine Corporation
230 MG100 Rev C
TA100 MASTER GUIDE
Modbus Error Limit
Address Code Name Description field Limit
1326 426 Inv Mem Fail Inverter Memory Test Failure
External input failure – HRU or Safety
1328 428 Outside Fault board
1329 429 Starter Cur HH Start inverter current high high S51 40 amps
1330 430 Spin Dir Fail Starter rotation direction incorrect
1331 431 Starter Fail Hall effect sensor position incorrect
1332 432 INV Sys Fault Line voltage not present
Voltage from other unit not present -
Stand alone / utility start
Voltage mode before generate utility
detected
S Boost Sys Start Booster cannot maintain 90 VDC
1334 434 Fltl nominal 90 VDC
DC Buss voltage Low Low - output from
1335 435 DC BUS V LL rectifier after alternator S23 550V
S24 0.5 sec
S Boost Temp Start Boost module over temperature -
1336 436 Flt heat sink temperature 90° C
AC current leakage - difference
1337 437 Leak Current between output and return current 60mA
TABLE 9.3 INVERTER CONTROL FAULT CODES
Loop In
Control Loop Title Loop Description
(LIC) #
This loop is to complete safety
and pre checks on the system
1 Pre Start Loop
prior to energizing anything in the
system.
This loop is controlling the system
to spin the turbine as a motor to
2 Start Purge Loop push air through the system and
“purge” fuel vapors out of the
system prior to starting.
Fuel supply to
Check facility fuel Correct facility fuel
system limited or
supply supply
off
Check GBC in
diagnostic mode.
Check GBC has
GBC not providing Adjust pressure
GBC not providing power. Check GBC
fuel regulator. Change
fuel flow for output pressure
pressure or flow separator filter.
at or above 85 psi
even with fuel
valves open.
This fault occurs when Leaks discovered
the EGT has not risen Check for leaks on
>20°C with GBC operating high pressure
after ignition stage Fuel leak after GBC Repair leaks
manually and fuel output of
(10,000 rpm). No fuel getting to valves closed GBC or gas
116.1 X
combustor detector tripping
This fault will appear as Check in diagnostic
"Safety Fault" if Safety mode. Check for
system is operating opening of fuel
properly. shutoff valve by
audible indication
Repair / replace
Fuel shutoff valve and/or diagnostic
wiring harness or
failure opening. Check
Shutoff valve
wiring/connections
to Safety Board.
Check current in
the range of
500mA.
Remove FCV and
Moisture or Make sure heat
clean with alcohol,
sediments in FCV strips are powered
flush valve of any
causing valve seat and FCV is
sediments, attempt
to stick insulated
a restart
Check igniter in
diagnostic mode.
Listen for audible
Igniter failed indication of Replace Igniter
sparking. Check
116.2 No spark at igniter igniter tip for
corrosion. Check
cable connection.
Check harness
Exciter box not connection to PE /
Replace Exciter box
functioning EC board.
Replace igniter
Failed igniter cable
cable
Check alternator
wires for correct
Alternator wires
hookup and
misconnected Connect alternator
remove engine inlet
causing engine to wires correctly
No airflow in to verify rotation of
116.3 spin backwards
combustor engine in CCW
direction
Check combustion Change filters more
Inlet blocked or
air inlet, replace regularly dependent
extremely dirty filter
filter upon environment
Liner Deformed due
to improper Borescope liner or
116.4 Liner Failure installation without pull back engine to Replace liner
use of liner inspect
spreader tool
117 Sustain FL
At Ignition Stage.
This fault occurs No spark at Igniter See 116 IGN FL
121.3 when the EGT has
not risen >20°C
after ignition stage No fuel flow into
See 116 IGN FL
combustor
Connect Safety
Monitor Tool to
During Electrical
Fuel pressure too verify fault. Check Correct fuel
Acceleration (after
121.4 high or FCV fuel pressure or pressure and/or
ignition but less
leaking. check FCV for FOD clean FCV
than 35,000 rpm)
causing valve to
leak
Speed drops lower
During Chemical
than 3000 rpm
Acceleration
below the peak Combustor
121.5 (greater than 35,000 Attempt restart
level achieved flameout
rpm and less than
during this portion
68,000 rpm)
of the start
Gas detector
See 121.1 above
tripping
Connect Safety
Monitor Tool.
During Running Check all
Safety Loop
121.6 Mode (at 68,000 connections to
broken. Open
rpm) Safety Board and Wiring failure Repair wiring
circuit in the safety
safety system
loop wiring
according to
Interconnection
diagram.
Over Voltage
Facility or Grid Download HSD and
401.1 X 576V (480V System)
voltage too high analyze conditions
520V (400V System)
402 UVR
Under Voltage
Facility or Grid Download HSD and
402.1 X 240V (480V System)
voltage too low analyze conditions
200V (400V System)
403 OFR
Grid or genset Check sine wave of
403.1 quality is bad for voltage at grid or
connection to PE. genset when OFR
Over Frequency PE100 measures occurs.
X Suddenly inductive
1Hz time between 0V OFR sometimes
load was connected
403.2 and 0V of sine wave occurs by noisy
by contactor or
voltage as sine wave of
breaker.
frequency. voltage.
404 UFR
Grid or genset Check sine wave of
404.1 quality is bad for voltage at grid or
connection to PE. genset when OFR
Under Frequency PE100 measures occurs.
X Suddenly inductive
1Hz time between 0V OFR sometimes
load was connected
404.2 and 0V of sine wave occurs by noisy
by contactor or
voltage as sine wave of
breaker.
frequency. voltage.
Isolation Detect
Download HSD and
406.1 X Passive (grid loss)
analyze
0.5 sec
412 Overload
421 DC Link V HH
Unit not properly
Download HSD and
421.1 configured for
analyze.
utility start.
Incompatible Update software
421.2 DC Link Voltage High
software versions code
High
422 DC Link V LL
DC Link Voltage Low Unit not properly S57 is not set to Check S57.
422.1 X Low configured for utility start when Change to 1 for Setting corrupted
utility start. utility is present. utility start. 0 for
Voltage (Potential)
Download HSD and
424.1 X Sensor failure detected
analyze
by Inverter Controller
All of these faults, when encountered will generate a Safety Fault. In all cases, the
shutoff valves (SOV) will close when this level is exceeded or out of range.
Engine Speed
Speed Speed
increases drops to Alternator Transition to
to purge ignite Fuel Valve Ignition spin energy synchronous
speed speed opens Detected drops to Zero speed
Idle Ignite Electrical Chemical Running
state Purge Speed Ignition accelerate accelerate mode
Any S/D Any S/D faults Any S/D faults Any S/D faults Any S/D faults Any S/D faults Any S/D faults
faults detected detected detected detected detected detected
detected OR OR OR OR OR OR
Minimum Ignite speed EGTDOT < 10 EGTDOT < - 15 NG < Ngpeak – NG < NG
Purge speed outside limits DegC /sec for 9 DegC /sec 3000 synchronous –
not achieved OR seconds For 1.5 sec 8000 Rpm
OR EGT rise AND
Max Purge before ignition EGTDOT < - 15
speed exceeded command DegC /sec for 2
OR OR seconds
Minimum Purge Exceed time limit
time not achieved
System
put in wait
state till
Manual
reset
System
Start
Permission
state OK
TB9
CN1 CN2 CN1 CN21 CN9
+15V 1 +15V +15V S2+
1 1 1 1 1 1
S1 2 S1 S1 Inverter S2-
2
Speed 2 2 2 2 2
S2 3 S2 JB1 S2 Control S3+ Safety
3 3 3 3
Encoder S3 4 S3
3
S3
3
Board S3- Board
4 4 4 4 4
Card 0V 5 0V 0V
4
5 5 5 5 5 5 1 2 3
SHLD 6 SHLD CN4
6 6
CON2
RED + 7
EGT#3
BLK - 8
(For GSMS) SHD 9
The combination of both the EGT rate of decrease and the speed drop would
indicate a combustor blowout condition is existent. The Capstone engine control
logic has special blowout prevention logic during operation periods when the
system is marginal in combustion stability.
Flow switch will confirm if there is too low or no flow in the water system.
9.6.3.3.4 Bypass Damper Fault (from optional CHP control)
Bypass damper must be in full bypass mode for startup.
SECTION 9 GLOSSARY
Term Definition
AC Alternating current
Cogeneration (CG) Alternate name for Combined Heat and Power Systems
DC Direct current
I/O Input/Output
KW Kilowatt
The BMS and all TA100 units need to be connected to the same MODBUS cable,
a three conductor cable with the forth conductor as shield. The TA100 MODBUS
shield connection for each unit, TB9-pin10, should not be connected together via
the cable shielding conductor.
The BMS system can also communicate with each TA100 via the hardwire
connections described in Section 5.15.
10.2 POWER OUTPUT MODE SWITCHING
Dual mode operation of the TA100 microturbine systems provides the capability to
run both in utility-tie mode and voltage stand-alone mode. With commands
generated by a Building Management System (BMS), one unit or an array of units
has the capability to transfer from utility-tie mode to stand-alone mode during a
power failure or when isolated from the grid. This transfer of generating mode can
be completed in less than 15 seconds. After the utility power returns, the units can
be commanded to transfer back to utility-tie mode and start generation in current
mode. The BMS will have to be programmed to:
Send a command to the isolation switch(es) to isolate the TA100 units from the
utility service
Provide a signal to switch off all loads
Switch TA100 units into stand-alone voltage mode
Command the TA100 units to generate power in island mode
Provide commands to enable customer loads to be sequenced on
After the utility power returns, the BMS will have to determine if the utility is stable.
Once the utility is found to be stable, the BMS will:
Utility
MCU
K2
TA100
Unit
UPS
GBC
EXT POWER
CONNECT
Normal Load
ISOLATED
LOAD
N/L-1 N/L-n
Utility
PT Optical Fiber
K1 400/480V Power Bus
Sync. Signal
MCU
MCU
Neutral
MCU Neutral KN
KN
Breaker
Breaker
K2 MCU UPS
TA100 TA100
Unit #1 Unit #N
Normal Load
ISOLATED
LOAD
N/L-1 N/L-n
1. Utility protective relay KP. This relay is usually a utility provider required device to
protect the grid from the microturbine system back-feeding power to the utility
after a utility power failure. This relay is used to inform the BMS whether utility
power is normal or failed via a relay dry-contact output.
2. Isolation Relay K1. This relay is controlled by the BMS. It opens upon a utility
failure, and closes after the BMS is ready to connect all the TA100 units back to
the utility. If the BMS will be commanding the enabling of the protective relay, K1
can be eliminated.
3. Emergency Load Relay K2. This relay controls the load closure of the system
against the bus for the emergency load system. This load must be controlled by
the BMS to not overload the units with full step loads.
4. TA100 Neutral Relay KN. KN switches off the TA100 neutral lines in utility-tie
mode. The neutral line must be connected for the units to run in stand-alone
mode. This relay closes or opens the neutral line connection based upon
operating mode. (Note: Maximum neutral current is 200A for TA100 MT. KN
could be a 70A 3-phase relay with 3-phase shorting together or a 3-phase 200A
relay to handle 3 units together. The relay control coil should be powered by
external power supply.)
There will be a short interruption in power generation during the TA100 mode
transfer. This will be less than 15 seconds during the transition from utility-tie to
voltage stand-alone and less than 1 second during the transition from voltage
stand-alone back to utility-tie. During such a power gap, an external power supply
is necessary if the TA100 systems have optional internal Gas Boost Compressors
(GBC). NOTE: If the desire is to complete a non-shutdown transfer to the other
mode for all the units in a multiple unit installation, the external power must be
sized large enough to support the GBC’s for all the units and that supply will have
to be wired to each unit’s external power input connection. If the facility mode
transition can allow all but one unit to shutdown and restart, then at least one
TA100 unit in the array is required to have external power connected to the
external power connection on the TA100. This one unit will mode switch without
shutting down and then the remaining units in the array can use the power from
this unit to provide GBC and start power to bring them back online.
When the system is running in voltage island mode, and the utility returns, system
will switch into utility-tie mode automatically according following operation logic.
Figure 10.6 shows two arrays of TA100 systems that are operating in arrays.
These two arrays may be connected to load busses that are switched together and
the entire set of systems may operate as a single array or two independent arrays.
Tying the two controlling BMS systems together by linking their synchronization
boards provides this capability. This will allow for shutdown of systems for
maintenance while carrying near full loads and will also allow for higher loads on
one service to be carried by adding the other array to the system. The switch (S1)
may be opened at any time as long as the loads on the bus do not exceed the
capability of the TA100 systems operating on that bus. The facility is required to
monitor the voltage waveform of both sides of the S1 contactor. The facility is only
allowed to close the contactor (S1) if the waveforms are consistent between the
two busses. The reason for monitoring is to prevent the facility from closing the
contactor if that communication has a problem and the waveforms being out of
phase. This could damage the TA100 systems. If the two BMS systems are
connected with the required cable (Capstone P/N: 804374, Harness-Sync Board
Communication.) and there is no problem with this communication, the waveforms
will be the same. Note: The site needs to provide length information for cable
804374 in the specific installation and special order this cable from Capstone.
If one or more units are operating and generating in one array and the other array
is connected on the load bus, when units in the non-generating array are started,
they will not generate for 60 seconds. This is a safety feature for paralleling mode
on the same load bus.
The maximum fiber optical cable length from the BMS system to each TA100 is 50
meters. All cables from the BMS or SCADA system need to be installed inside
water resistant conduit.
MCU#1 MCU#2
Array #1 Array#1 Array#1 Array#1 Array#1 Array #2 Array#2 Array#2 Array#2 Array#2
MT#1 MT#2 MT#3 MT#4 MT#5 MT#1 MT#2 MT#3 MT#4 MT#5
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10
S1
LOAD 1 LOAD 2
Part
Item Number Qty Description
1 800508 1 ASSY-OIL TANK-WELDED
2 800819 1 ASSY-ENGINE
3 150049 1 PUMP-LUBE
4 316011 1 PIN-SPRING STEEL-3/32 DIA X 1/2
5 306058 2 O-RING-.739ID X .070CS-AS568-018
FERRULE-WIRE-14 AWG-INSULATED-
6 128038 3 BLUE
7 150005 1 FILTER-OIL-3 MICRON
8 800474 1 MANIFOLD-OIL FILTER-PIPING
9 120026 1 SWITCH-PRESSURE-ACTIVATES @ 45
PROPRIETARY INFORMATION © 2011 Capstone Turbine Corporation
285 MG100 Rev C
TA100 MASTER GUIDE 01/18/2011
PSI-OIL
10 326004 1 THERMOSTAT-110 DEG.
HEATER-IMMERSION-OIL-3/8 NPT-500W-
11 800753 1 230V
12 152010 1 HOLDER-FLAT CABLE TIE-1" x 1"-NYLON
13 210205 1 UNION-1/4 TUBE X 1/4 TUBE-SS
FITTING-MALE CONNECTOR-1/2 TUBE
14 210185 3 TO 3/4-16UNF
15 210032 4 CONNECTOR-HOSE END-PUSH ON
16 302016 6 SHCS-1/4-28-2B-ZINC PLATED
WASHER-1/4-VIBRATION RESISTANT
17 312013 12 LOCK
18 480003 2 HOSE-AEROQUIP-1/2 IN ID
19 136049 6 CONNECTOR-LUG-1/4" RING-6 AWG
20 132014 1 HEAT SHRINK TUBING-3/8"-KYNAR
21 132015 1 SPIRAL WRAP-3/8"-TEFLON
22 306065 1 O-RING-10.984 ID-.139 CS-VIT-75 DURO
23 144002 1 NAMEPLATE-MOBIL SHC 824
24 302009 3 SHCS-1/4-20 X 3/8
25 302032 4 SHCS-1/4-20 X 2-1/4 - ALLOY STEEL
26 209033 1 VALVE-OIL TEMP CONTROL-165-180 DEG
27 480296 1 MANIFOLD-OIL FILTER BYPASS-PIPING
28 210082 1 PLUG-PIPE-HEX HEAD-1/4NPT-BR
ELBOW-1/2T x 3/4-16-MALE-POSITIONAL-
29 210289 2 SS
THERMISTOR-1/4 MNPT-PROBE-0.8"
30 124027 1 LONG-SS
31 712007 1 NAME PLATE-OIL LEVEL
HEAT SHRINK TUBING-1/2"-ADHSV
32 132029 1 LINED-BLK
33 132016 1 HEAT SHRINK TUBING- 3/4 IN
DUCT-INTERFACE-DIFFUSER-
34 701157 1 COMBUSTOR
TABLE 11.1 PARTS LIST FOR ENGINE ASSEMBLY P/N 800820
Part
Item Number QTY Description
1 800454 1 WELDMENT- COMBUSTOR-ANNULAR-NG
2 800876 1 ASSY-LINER-COMBUSTOR-NG
3 312030 4 WASHER-TAB-RETAINER
4 700994 3 BOLT-COMBUSTOR RETAINER
5 480493 1 IGNITOR HAST-X TIP
6 700927 12 INJECTOR-3 HOLE-GASEOUS
7 800414 1 ASSY-FUEL MANIFOLD-ANNULAR-NG
TABLE 11.2 PARTS LIST FOR COMBUSTOR HOUSING ASSEMBLY P/N 800620
Part
Item Number QTY Description
ASSY-MANIFOLD-FUEL-RIGHT-ANN
1 800403 1
RECUP
ASSY-MANIFOLD-FUEL-LEFT-ANN
2 800404 1
RECUP
3 210230 1 TEE-1/2" TUBE-5/16" TUBE RUN-BT
TABLE 11.3 PARTS LIST FOR FUEL MANIFOLD (GAS) P/N 800414
Number
1 480400 1 HOSE-SS-TEFLON-LINED-24L-CE
2 480543 1 HOSE-SS-TEFLON-1/2" TUBE X 1/2" MNPT-55L-CE
3 312011 6 WASHER-FLAT-1/4-SS-18-8
4 304017 4 BOLT-1/4-20 x 1/2-HEX HD-SS
5 312010 6 WASHER-SPLIT LOCK- 1/4-SS
6 209039 2 VALVE-SHUT-OFF-CNG-1/2NPT
7 602045 1 TUBE STOCK-304SS-1/2OD X .049W
8 210308 4 FITTING-1/2 TUBE-MALE CONNECTOR-CE-SS316
9 312053 4 WASHER-1.06 OD-.83 ID-.060 TH-COPPER
10 210271 2 ADAPTER-1/2" OD MALE-1/2" MNPT-SS
11 800841 1 ASSY-SERVOID CONTROL VALVE-45 SCFM
12 300020 4 SCREW-#10-32 X 1/2 PPH
13 312008 4 WASHER-#10-LOCK
14 804224 2 HARNESS-FUEL SHUT OFF GROUND-CE
15 804223 1 HARNESS-FUEL SHUT OFF POWER JUMPER-CE
HARNESS-FUEL SHUT OFF CONTROL POWER-
16 804222 1 CE
17 210187 1 FITTING-MALE CONNECTOR-1/2 TUBE TO 1/2NPT
18 312002 2 WASHER-LOCK-#4
19 300002 2 SCREW-PHP-#4-40 X 1/4,SST
20 150090 1 FILTER-FUEL COALESCING-MANUEL DRAIN
21 480618 1 BRACKET-FUEL FILTER
22 300068 2 SCREW-1/4-20 X 4"-PAN HEAD-PHILLIPS-SS18-8
23 308013 2 NUT-HEX 1/4-20 SS-18-8
24 480582 1 BRACKET-VALVE SUPPORT
25 113013 1 RELAY- PCB-SPDT-24VDC
26 312004 2 WASHER-SPLIT LOCK-#6-SS
27 312023 2 WASHER-FLAT-#6-SS
28 300007 2 SCREW-PAN HD-#6-32 X 1/4-PH
TABLE 11.4 PARTS LIST FOR FUEL TRAIN (GAS) P/N 800803
Part
Item Number QTY Description
DEMISTER-PRE FILTER-INTEGRAL
1 150083 1 BRACKET-ANGLED
2 210055 1 CONNECTOR-MALE-1/4T-1/4NPT-BR
CONNECTOR-HOSE END-PUSH ON-1/2T-8
3 210032 2 HOSE-SS
CONNECTOR-3/4-16 FLARE-3/4-14 NPTF-
4 210210 2 BR
5 210213 2 FITTING-1/2 BARB-3/4-16 FLARE-BR
6 313008 1 CLAMP-HOSE-SAE #8-7/16 TO 1 INCH
7 480003 3 HOSE-AEROQUIP-1/2 INCH ID
8 602090 1 TUBE STOCK-TEFLON-1/4 OD X .030W
9 304030 2 BOLT-1/4-20 X 3/4-HEX HEAD SS 316
10 312011 4 WASHER-FLAT-1/4-SS-18-8
11 308029 2 NUT-1/4-20-TOOTH WASHER-SS 18-8
TABLE 11.5 PARTS LIST FOR OIL SYSTEM INTERCONNECT P/N 800466
11.5.1.1
11.6 OIL HEAT EXCHANGER ASSEMBLY
Part
Item Number QTY Description
1 800857 1 ASSY-EBM AXIAL FAN AND SHROUD
2 328005 1 HEAT-EXCHANGER
WASHER-#10 X 1/2 OD X .093 THICK
3 312033 8 RUBBER
4 312009 4 WASHER-FLAT- #10-SS-TYPE "A" PLAIN
5 312008 4 WASHER-#10-LOCK
6 300081 4 SCREW-10-24 X 1-HEX HEAD-SS18-8
7 113013 1 RELAY- PCB-SPDT-24VDC
8 300008 2 SCREW-PAN HD-#6-32 X 3/8-PH
9 128052 1 TERMINAL STRIP-6P-8-26 AWG-35A 600V-
UL
10 300011 2 SCREW-6-32 X 3/4-PAN HEAD-SS18-8
HARNESS-FAN-OIL COOLING RELAY-
11 804086 1 POS/NEG
12 804088 1 HARNESS-FAN-OIL COOLING-CONTROL 2
13 804087 1 HARNESS-FAN-OIL COOLING-CONTROL 1
HEAT SHRINK TUBING-1/2"-ADHSV LINED-
14 132029 1 BLK
TABLE 11.6 PARTS LIST FOR OIL HEAT EXCHANGER ASSEMBLY P/N 800808