FIRST EDITION
July- 1998
SAFETY REQUIREMENTS
ON
OF
PREPARED BY
FUNCTIONAL COMMITTEE
1
NOTE
OISD publications are prepared for use in the oil and gas industry under Ministry of Petroleum & Natural Gas.
These are the property of Ministry of Petroleum & Natural Gas and shall not be reproduced or copied and loaned or
exhibited to others without written consent from OISD.
Though every effort has been made to assure the accuracy and reliability of the data contained in these documents,
OISD hereby disclaims any liability or responsibility for loss or damage resulting from their use.
These documents are intended to supplement rather than replace the prevailing statutory requirements.
2
FOREWORD
The Oil Industry in India is more than 100 years old. As such, a variety of practices have been in vogue because
of collaboration/ association with different foreign companies and governments. Standardisation in design
philosophies , operating and maintenance practices was hardly in existence at a national level. This, coupled with
feed back from some serious accidents that occurred in the recent past in India and abroad, emphasised the need for
the industry to review the existing state of art in designing, operating and maintaining oil and gas installations.
With this in view, the Ministry of Petroleum & Natural Gas in 1986 constituted a Safety Council assisted by the
Oil Industry Safety Directorate (OISD) staffed from within the industry for formulating and implementing a series of
self regulatory measures aimed at removing obsolescence, standardising and upgrading the existing standards to
ensure safer operations. Accordingly, OISD constituted a number of functional committees comprising of experts
nominated from the industry to draw up standards and guidelines on various subjects.
The present document “Safety Requirements on Compression, Storage, Handling & Refuelling of Natural Gas
for Use in Automotive Sector” was prepared by the Functional Committee on “Safety Requirements on
Compression, Storage, Handling & Refuelling of Natural Gas for Use in Automotive Sector”. This document was
prepared based on the accumulated experience and knowledge of industry members, and various national and
international codes and practices.
This document will be reviewed periodically for improvements based on the new experiences and better
understanding. Suggestions from industry may be addressed to :
The Coordinator,
Committee on “Safety Requirements on Compression,
Storage, Handing & Refuelling of Natural Gas for Use
In Automotive Sector”
Oil Industry Safety Directorate,
2nd floor, Kailash Building,
26,Kasturba Gandhi Marg,
NEW DELHI – 110001.
3
FUNCTIONAL COMMITTEE
ON
“Safety Requirements on Compression,Storage, Handing & Refuelling of Natural
Gas for Use In Automotive Sector”
NAME ORGANISATION
LEADER
Sh. S.Singhal Indian Institute of Petroleum, Dehradun
MEMBERS
Sh. A.S.Ghoshal Chief Controller of Explosives, Nagpur
MEMBER COORDINATOR
Sh. S.Ghosh Oil Industry Safety Directorate, New Delhi
(Upto September, 1996)
4
1.0 INTRODUCTION 3.0 DEFINITIONS
Compressed Natural Gas (CNG) has been 3.1 ANSI B 31.3.
identified as one of the alternate fuels to liquid
petroleum fuels, which has added This code of American National Standards
environmental benefits. This fuel is being Institute on "Chemical Plant and Petroleum
used internationally with the proven success Refinery Piping" would be applicable for
as an automotive fuel. CNG Pipelines and tube work inside the
installation of CNG compression and retail
CNG is a mixture of hydrocarbon gases and outlets.
vapours consisting of principally methane in
gaseous form which are compressed to a 3.2 Statutory Authority.
pressure of 200 to 250 Kg/ Sq.cm.g. for use as
a vehicular fuel. Besides, installation of Govt. of India or its agency responsible for
conversion kit in an Automotive system, two particular aspect. “Chief Controller of
major installations need to be erected i.e. Explosives” is the statutory Authority for
administering the Gas Cylinder Rules 1981 &
1) Compressors station for either on- SMPV Rules 1981.
line operation or to serve as mother
station 3.3 Bulk Storage.
2) Refuelling station either with on-line
facility or with moveable cascade. Bulk storage is a facility for storing CNG in
stationary and mobile storages exceeding the
These facilities may be either co-located in the capacity of 1000 Lt. These pressure vessels
MS/HSD dispensing stations or at dedicated shall conform to the “Static & Mobile
stations. Pressure Vessels (Unfired) Rules, 1981 as
amended.
Safety at these installations is most important
factor in view of the operating conditions such 3.4 Capacity.
as pressure, storage of other flammable
materials etc. The provisions in this standard The gross capacity of a storage container in
shall provide a reasonable level of safety and water litres at 15 deg. C.
protection from loss of life and property from
fire and explosion. 3.5 Cascade (Gas Storage Unit)
1
Mixtures of hydrocarbon gases and vapours, The minimum period of time for which all
consisting mainly of Methane in gaseous form sides of an element of structure, any of which
which has been compressed for use as is subjected to a standard fire, continues to
automotive fuel. perform its structural function and does not
permit the spread of fire. Where a period of
3.8 Cylinder Appurtenances. time is used in conjunction with the
abbreviation FRR it is required that the
Devices connected to cylinder for safety, element of structure referred to shall have a
control or operating purposes. fire resistance rating of not less than the
period stated.
3.9 Cylinder.
3.12 CNG “On line” Station: The assembly of piping and fittings used for
interconnecting all cylinders/ vessels to a
CNG facility connected with natural gas common pipeline.
pipeline and having a compressor primarily to
fill stationary cascades for dispensing CNG to 3.19 Non Return Valve (NRV).
vehicles. In case the ‘on line’ station has
enough space to accommodate mobile This valve permits gas flow in one direction
cascades filling, it can be used to act as only.
mother compressor station.
3.20 Natural Gas.
3.13 CNG daughter station:
Mixture of gaseous hydrocarbons and vapours
CNG facility not connected to natural gas consisting primarily of Methane.
pipeline and dispensing CNG to the vehicles
(s) through mobile cascades.
A quick action shut off valve, which operates Material, in the form in which it is used and
from full open to full closed condition in less under the conditions anticipated, will not
than one complete turn. ignite, burn, support combustion, or release
flammable vapours when subjected to fire or
3.15 Fire Resistance Rating (FRR). heat.
2
3.30 Transport Vessel.
The point where the fuelling connection is
made, to vessel(s)/ vehicle (s). A cascade/ bulk storage mounted and installed
on a Light/ Heavy Commercial Vehicle,
3.23 Pressure Relief Device. trailer, or semi trailer for movement of CNG
on road and governed by statutory regulations.
Device designed to prevent rupture of vessel /
container by releasing excessive pressure
build-up as specified in clause 18 of SMPV 3.31 Working Pressure.
Rules, 1981. The systems and components of
CNG facilities are required to be certified for The pressure for which the equipment was
CNG use and marked accordingly. constructed or if conditions have changed, the
maximum pressure at specified temperatures,
3.24 Set Pressure. permitted at the most recent inspection.
The valve opening pressure in a relief valve 3.32 Vehicle Refuelling Probe.
which shall not exceed the marked service
pressure. This is a CNG refuelling device fitted at the
end of the refuelling hose at the dispenser
3.25 Shall. units suitable for insertion into the vehicle
refuelling valve receptacle.
Indicates mandatory requirement.
3.32 Vehicle Refuelling Shut Off Valve.
3.26 Should.
A quick action valve for stopping gas flow
Indicates recommendation or that which is and having the facility for venting residual
advised but not mandatory. high pressure gas in the refuelling line after
completion of the vehicle refuelling operation.
3.29 Sources of Ignition. 4.2 Any other device not specified above must be
constructed to provide safety equivalent to
Devices or equipment which, because of their that required for other parts of a system and
mode, use or operation, are capable of should have a similar certification/ approval
providing required thermal energy to ignite as detailed above.
flammable "CNG-Air mixtures" when
introduced to such a mixture or when such a 5. 0 NATURAL GAS QUALITY FOR
mixture comes into contact with them.
CNG FACILITIES
3
5.1 The principal constituent of CNG is methane 6.0 FACILITY PLANNING
alongwith some amounts of other elements.
Out of these, concentration of undesirable 6.1 The CNG Refuelling system shall comprise
constituents shall be restricted to the of a gas compression apparatus, static/ mobile
following: cascade/ pressure vessel and a gas dispenser
incorporating a measuring device. The system
shall be `ON-LINE' mother refuelling or
a) Carbon dioxide, daughter dispensing system attached to a
partial pressure 7 psi max mobile cascade.
b) Oxygen 0.5 vol. % max
c) Hydrogen Sulphide
and soluble sulphides 6.2 LAYOUT AND INTERDISTANCES
partial pressure .05 psi max
d) Moisture contain 7.0 lb. /MMCF. Max 6.2.1 Inter-distances between various equipment,
storage cylinders/ cascade etc. shall be as per
NB: when the dew point of the gas entering Table - I, II.
the cylinder is below the lowest anticipated
container temperature at the maximum 6.2.2 Safety distances not indicated above should be
anticipated container pressure, the above shall as approved by Chief Controller of Explosives
not apply. on case to case basis after due consideration
of all influencing factors.
5.2 ODOURISATION:
6.2.3 When inside a MS-HSD Service Station, the
5.2.1 Natural gas introduced into any system CNG storage and dispensing facilities shall be
covered by this standard should have a located in an isolated area not interfering in
distinctive odour strong enough to detect its the vehicular movement on the drive way and
presence down to a concentration (of CNG) in not coming within the hazardous areas of
air not exceeding 20% of the lower limit of petroleum facilities as prescribed in the Fourth
flammability. To achieve this, the injection of schedule of the Petroleum Rules, 1976. The
odorizing agent shall be done in a quantity to CNG facilities shall not be located beneath
ensure perception of CNG leakage by smell. electric power lines or where exposed by their
failure.
5.2.2 Suitable type of filters shall be used for
limiting liquid particulate as mentioned in the 6.2.4 The fencing may be limited up to the
clause 5.2.1. dispensing unit to avoid obstruction in the
driveway if the required clear space is
5.2.3 The odorisation and filtration system shall be available thereafter within the service station
located in a separate working area from the premises. The dispensing unit may also be
compressor or CNG storage unit but within located farther from the fence enclosure on a
the same fencing. There should be a clear separate pedestal observing the minimum
safety distance of 1.5 M around the safety clearance mentioned in Table II.
odorisation and filtration system to facilitate
easy maintenance and personnel movement.
TABLE -I
INTER DISTANCES
4
FROM BUILDINGS AND OUTER BOUNDARIES TO GAS STORAGE UNITS
NOTE: If on the side (s) towards the boundary of the installation, the clearance as above is not
available, the same may be reduced to 2 meters provided a 4 H-FRR RCC wall of adequate
height and length covering the cylinder cascades is constructed at the boundary and adequate
clear space is available on the other side of the wall.
TABLE - II
INTER DISTANCES
BETWEEN VARIOUS FACILITIES OF NATURAL GAS HANDLING AT
INSTALLATION
---------------------------------------------------------------------------------------------------------------------------------
5
Distance
From 1 2 3 4 5 6 7
(in meters)
---------------------------------------------------------------------------------------------------------------------------------
1. CNG - 3 2 3 6 6 T-1
Compressor (Min-3)
2. CNG 3 - 2 4 6 4 -Do-
Dispensing Unit
6. Vent of 6 4 T-1 4 6 - 6
MS/HSD u/g (Min-4)
storage tanks
6
shall be securely anchored to prevent may be considered after the establishment of
floating in case flooding is anticipated. its suitability and approval of the Chief
Controller of Explosives.
7.5 Gas storage facility shall be protected from
the effects of the weather by a roof or 9.4 The cylinders shall be re-examined and re-
canopy designed to facilitate the dispersion tested every five years and in accordance with
of free or escaped gas and shall not permit Gas Cylinder Rules, 1981 by a competent
gas to be trapped. person with due markings. No cylinder shall
be used which has not been duly re-tested as
7.6 Adequate means shall be provided to indicated.
prevent the flow or accumulation of
flammable or combustible liquids under 9.5 Cylinders shall be painted white to reduce
containers such as by grading, pads or solar heating effect and protect it from
diversion curbs. atmospheric corrosion.
9.1 The cylinders and their fittings for CNG use 10.5 All the piping and tubing shall withstand a
shall be designed, manufactured, tested pressure equal to that of safety relief device
including hydrostatic stretch test at a pressure and tested accordingly after assembly. The
in full conformity to IS:7285 and Gas testing to be done by inert gas, in case
Cylinder Rules, 1981, considering the natural gas is used the suitable safety
maximum allowable operating pressure of 250 measures to be adhered to.
kg/ Sq.cm.g.
10.6 VALVES
9.2 These cylinders are to be permanently and
clearly marked for “CNG only” and also 10.6.1 A minimum of four shut off valves shall be
labelled "CNG ONLY" in letter at least 25 fitted between the gas storage unit and vehicle
mm high in contrasting colour in a location refuelling filling nozzle as explained below:
which shall be visible after installation.
a) Each CNG storage unit to have quick
9.3 The cylinder shall be fabricated from steel. action isolation valve in the steel supply
However, cylinders with composite materials pipe immediately adjacent to such storage
7
unit to enable isolation of individual 11.4 Flexible hoses shall have permanent marking
storage unit. These valves shall be within indicating the manufacturer's name/
fencing of storage unit. identification, working pressure and suitability
for use with CNG.
b) Master shut off valve with locking
arrangement in close position, shall be 12. 0 PRESSURE GAUGES
installed in steel outlet pipe outside but
immediately adjacent to the gas storage 12.1 Every CNG storage unit including each
unit to isolate all downstream equipment cascade or bulk storage tank shall be provided
from the gas storage unit. This valve shall with a suitable pressure gauge directly in
be outside the fencing. communication with them.
c) A quick action emergency and isolation 12.2 The CNG storage unit shall have an opening
shut off valve shall be installed near not to exceed 1.4-mm diameter at the
dispensing unit with easy approach and to connection where pressure gauge is mounted.
remain closed when refuelling is not being
done. 12.3 The pressure gauge shall have dial graduated
to read approximately double the operating
d) A vehicle refuelling shut off valve shall be pressure but in no case less than 1.2 times the
installed for each flexible vehicle pressure at which pressure relief valve is set to
refuelling hose to control the refuelling function.
operation and shall have venting provision
to allow for the bleeding of the residual 12.4 All pressure gauges in the installation shall be
high pressure gas after refuelling is tested and calibrated atleast once a year and
complete. records maintained.
10.6.2 All these valves and other elements of piping
shall be suitable for the full range of pressure 13. 0 COMPRESSOR STATION
and temperature to which they may be
subjected. These valves are to have 13.1 The piping and its fittings upto the battery
permanent marking for service rating etc. limit of CNG installation shall conform to
ANSI B 31.8 or equivalent.
11. 0 CNG HOSES
13.2 Compressor shall be designed for use in CNG
11.1 Internally braided, electrically continuous, service and for the pressures and temperature
non-metallic and metallic hoses resistant to to which it may be subjected under normal
corrosion and suitable to the natural gas operating conditions conforming to API 618/
service may be used for CNG service in the API 813 or equivalent standard and Flame
downstream of emergency and isolation shut proof electric motor and associated fittings
off valve. should conform to IS:2148 suitable for class I
division I group II area.
11.2 These flexible hoses and their connections
shall be suitable for most severe pressure and 13..3 Compressor shall be fitted with the following
temperature service condition expected with a minimum devices :
burst pressure of at least four times the
maximum working pressure. a) Pressure relief valves on inlet and all stages
to prevent pressure build up above the
11.3 The flexible hoses with their connections shall predetermined set point.
be tested after assembly and prior to use to
atleast two times the working pressure and b) High discharge temperature shut down
also tested to a pneumatic pressure of atleast
400 bar under water. Thereafter, all the hoses c) High cooling water temperature switch fitted
shall be examined visually and tested for leaks to cooling water return line to shut the
with soapsuds or equivalent at an interval not compressor in the event of a fault.
exceeding one year. Hoses shall be rejected
and destroyed in the event of any leakage. d) High, inlet, inter stage & discharge
These tests are to be recorded and such pressures shut down.
records shall be available at installations at all
times. e) Low lube oil pressure shut down
8
f) Low cooling water flow switch fitted to the pressure setting, date of re-setting/ setting and
cooling water return line to shut the capacity.
compressor in the event of fault.
14.6 All safety relief devices shall be tested at least
g) A remote isolation switch for emergency once a year for proper operations and records
shut down to be provided with manual reset to be maintained.
at control panel.
14.7 All the safety relief devices shall have
13.4 Compressor shall be provided atleast the manufacturer's permanent marking indicating
following clear and permanent markings following :
readily accessible and easy to read in the
installed position : a) Set pressure to start discharge
b) Discharge capacity in CuM / min.
a) Manufacturer's name
b) Model 14.8 No shut off valves shall be installed between
c) Serial No./ month & year of the safety relief device and the gas storage
manufacture unit or bulk tank.
d) Certificate of approval no.
e) Rated capacity (cubic meter per hour) 14..9 All natural gas devices not otherwise
f) Operating speed (RPM) specifically mentioned shall be constructed
g) Required driving power( in kW) and installed to provide a safety equivalent
h) Maximum & minimum supply pressures to that other parts of the system.
i) Maximum outlet pressure
j) Certification for Natural Gas use 14.10 Gas detectors interlocked with compressor
cut out switch in the electrical system of the
13..5 A compressor and its all fittings shall be compressor are to be installed which would
tested for compliance of relevant standard automatically switch off the unit in case of
suitable for CNG use by a competent person/ major gas leak.
agency prior to installation.
15.0 ELECTRICAL EQUIPMENT
14. 0 PRESSURE RELIEF DEVICE
15.1 All electrical wiring and equipment, gas
14.1 Safety Relief Devices may consist of either storage dispensing unit located in hazardous
burst disc or safety relief valve and should area Division I and II shall be in accordance
conform to the requirements of OISD-STD- with the Indian Electricity Rules, Gas
132. Cylinder Rules, IS:5572 (Part 1), NFPA - 52.
14.2 Safety relief devices shall be installed with 15.2 The earthing at the installation, protection
unobstructed full size discharge to a safe place against ignition arising out of static, lightning
on bulk tanks and cylinders in the vertical and stray currents shall be as described in
position with suitable rain caps. These OISD-STD-110 and further maintained as per
devices should have their outlet arranged in a the guidelines given in OISD-STD-137.
manner so that in case of emergency a high-
pressure gas escapes from these should not 16.0 SAFETY AT VEHICLE FOR
directly hit on operators/ persons in the close REFUELLING
vicinity.
16.1 The vehicles shall have approved type of
14.3 Cylinder should have safety relief devices CNG kit fitted in accordance with the
fitted in conformity to the Gas Cylinder Rules. guidelines of Ministry of Surface Transport,
Govt. of India by an authorised workshop and
14.4 Piping shall be protected by safety relief such workshop should issue a fitness
devices in conformity to OISD-STD-132. certificate to the vehicle for its suitability for
CNG use. Such certificate should be always
14.5 Safety relief valves shall have a locking carried by the driver of the vehicle at all
arrangement to prevent tempering by times.
unauthorised persons. Any adjustments to the
safety relief valve shall be made by 16.2 Driver of the vehicle should also carry the
manufacturer or a competent person. These record showing the last examination of the
valves should have a permanent tag indicating vital parts of the system fitted in the vehicle
9
for CNG use and their next due date for such connection shall be tight without any
examination. The details must include the test leakage.
periodicity of cylinder, pressure relief devices,
pressure gauges, piping etc. e) The engine is switched off, hand brake is
firmly applied, the vehicle parked in gear or
16.3 The cylinder with valves and connected in " P " with automatic transmission.
facilities fitted in the vehicle shall be in
accordance with Gas Cylinder Rules. These f) No passenger remains inside the vehicle .
cylinders should be subjected to hydraulic test
at least once every five years. 18.3 Detailed precautions (refer 18.2) and
procedure of refuelling to be displayed near
16.4 Every vehicle using CNG fuel system should the dispensing unit and strictly followed by
display "CNG" labels prominently in the operator.
compliance to Central Motor Vehicle Rules .
18.4 The operator of the dispensing machine
17.0 DISPENSING UNIT should not leave the vehicle being refuelled.
17.1 Dispensers shall be installed on a suitable 18.5 The cylinder on the vehicle shall not be
foundation observing the minimum safety charged in excess of maximum allowable
distances etc. as given in 6.0 above. working pressure at normal temperature for
Dispensing unit to be protected against the cylinder.
possible damage by vehicular movement.
18.6 Before the refuelled vehicle is driven away
17.2 The flexible hoses fitted on the dispenser shall from the dispensing point the operator and
be mechanically and electrically continuous. driver should ensure that there are no
The design, material and construction of hoses apparent gas leaks either on the vehicle or on
shall be suitable for CNG and shall withstand the dispensing point that may have been
not less than four times the maximum working caused through faulty filling or the faulty
pressure of the system. action of connecting or disconnecting.
17..3 The dispensing unit shall be of a type 18.7 Warning signs with the words "STOP
approved by the Chief Controller of VEHICLE", "NO SMOKING", "NO OPEN
Explosives / Statutory Authorities . FLAME PERMITTED", "FLAMMABLE
GAS", shall be displayed at dispensing station
and compressor areas. The location of the
18. 0 CNG REFUELLING INTO signs shall be such that these are prominently
visible from each point of transfer/ operation.
VEHICLES
18.1 The vehicle refuelling shall be done by an
19. 0 FIRE PROTECTION
experienced operator duly certified by the oil /
gas company having control over the 19.1 Fire fighting facilities need to be carefully
refuelling station. planned after considering the availability of
municipal fire tenders etc. However, atleast
18.2 The operator of the CNG dispensing unit shall the following Portable fire extinguishers shall
check the following prior to refuelling the gas be positioned:
:
Location Type of Extinguishers
a) The driver of the vehicle is carrying updated
history record as given in clause 16. Dispensing Unit 1 x 10 kg. DCP
10
Installation { 25 Sq.M floor area e) Civil emergencies
f) Any other risk arising from the existence
19.2 Any other flammable materials not specified or use of the CNG refuelling station.
in this standard in the CNG installation shall
be stored in a non-flammable chamber with a 20.2 The above emergency plan shall be
minimum safety distance of 15 M from disseminated amongst all personnel involved
compressor station/ MCC/ electrical and ensured that they understand their roles
installation. and responsibilities in the event of an
emergency.
19.3 All approaches to machines, compressors,
storage facilities and work places shall be free 20.3 The operator of the refuelling station should
from obstacles, so that they are readily have close liaison with Fire Service, the
accessible in an emergency. Police, the Municipal Authorities and the
person supplying gas to CNG facility.
19.4 The electrical installations shall be inspected
by a competent Electrical Inspector as per IE 20.4 Important telephone numbers for emergency
Rules and compliance shall be made as use shall be displayed prominently.
pointed out in the inspection. Records shall
be maintained for all periodic inspections. 20.5 Means of communication shall be always at
the disposal of the Incharge of the installation
19.5 The flameproof characteristics of electrical on 24 hours basis.
equipment shall be checked through visual
checks, condition of gasket, completeness and 20.6 The emergency plan should be tested with
tightness of bolts, glands and as recommended drill atleast once a year.
by manufacturer's test certificates.
11
j) Fire fighting facilities ,methods of fire 1. New Zealand Standard no. NZS5425: Part 1:1980
fighting and its upkeep. i.e. Code of Practice for CNG Compressor and
k) Evacuation and safe egress of the vehicles. Refuelling Stations Part 1 On Site Storage and
l) Housekeeping Location of Equipment.
m) Safety in transportation of CNG.
n) First aid. 2. New Zealand Standard no. NZS5425: Part 2:1982
o) Emergency plan./drills i.e. Code of Practice for CNG Compressor and
Refuelling Stations Part 2 Compressor
21.3 Appropriate training techniques shall be Equipment.
adopted which will include :
3. NFPA 52 i.e. Compressed Natural Gas (CNG)
a) Classroom training Vehicular Fuel Systems, 1992
b) Hands on/ practical training
c) Demonstration 4. Gas Cylinder Rules, Govt. of India
d) Case studies
e) Training aids 5. Petroleum Rules, Govt. of India & Guidelines
issued by Chief Controller of Explosives, Govt. of
21.4 Proper records for the training and refresher India, for CNG Refuelling Stations.
courses shall be maintained at the installation.
6. BIS Standards as referred above
REFERENCES
7. OISD Standards
12