FEATURES
• For Use in Range Guard® Commercial Cooking • Single or Dual Microswitches
Fire Suppression Systems • Easy to Install and Maintain
• Pneumatic Release of Up to 5 Agent Cylinders • Rugged, Cost-Effective Design
• Wall Mount in any Orientation • UL & ULC Listed
• Up to 200 ft. Mechanical Detection Cable
CABLE TENSION
BLOCK ASSEMBLY
LEVER (Part of
Valve Body
Subassembly)
DETECTION CABLE
(NOT SUPPLIED)
TUBING ELBOW
FITTING (Part of
Valve Body 1/4 in. O.D. (6 mm)
Subassembly) COPPER TUBING
TO SVA
(NOT SUPPLIED)
VALVE BODY
SUBASSEMBLY
GROMMET
MECHANICAL GAS
VALVE CABLE
3-1/4 in.
(83 mm)
11/16 in.
(19 mm)
GRAY BAND
Figure 2. CO2 Cartridge, P/N 06-235557-001
5/16-18 UNC
THROUGH HOLE (TYP)
(NOT SHOWN)
1/8 in.
NPT PORT
1-3/4 in.
(44 mm)
1/8 in. NPT PLUG
(IF APPLICABLE)
SPRING LOADED
SVA PISTON IN
PLUNGER
SET POSITION PISTON IN ACTUATED
POSITION (TOWARDS
CYLINDER VALVE)
CABLE TENSION
BLOCK ADJUSTING
SCREW
-2-
A+ DESIGN PARAMETERS
The following tables detail the mechanical operation and actuation design parameters for the Range Guard A+ Control
Box.
Badger Cable Line Max Cable Length Max Corner Pulleys Max Detectors
Operating Temperature Number of Extinguishing Minimum Length Copper Maximum Total Length
Range System Cylinders Actuation Tubing1 Copper Actuation Tubing1
1
High pressure 1/4-in. OD x 0.031 wall tubing with compression or flare fittings.
-3-
DIMENSIONS
The A+ Control Box (Figure 6) is mounted with four 3/8-inch diameter bolts or screws to a wall. The A+ Control Box
may be installed in any position, allowing the cable to enter from the top, bottom or either side.
The cover labels are applied to the outside of the cover after the A+ Control Box is mounted.
6-1/8 in.
(155 mm)
7 in. 5 in.
(178 mm) (127 mm)
1 in.
(25 mm)
5 in.
(127 mm)
1/2 in.
(12 mm)
ORDERING INFORMATION